Sei sulla pagina 1di 2

Model AW-1

Abort Station for Extinguishing Systems & Main/Reserve


Selector Switch

Features

• Momentary Contact “Deadman”


Switch

• Manually Prevents SinorixTM System


Discharge

• Large Mushroom Button

• Listed and FM Approved

Introduction
The model AW-1 abort station is designed for use with push button, depending on system configuration and
Siemens Building Technologies, Inc., Fire Safety fire programming. The button must be kept pressed until the
detection systems which are listed/approved for release control panel is reset. If the control panel is not reset and
of SinorixTM Systems. the push button is released, provided that two zones
have alarmed, the releasing panel will enter a discharge
The abort station employs a momentary contact “dead- mode. This will result in immediate discharge, resump-
man type” push button switch which, while held in, tion of pre-discharge delay period, or beginning of pre-
prevents discharge of the clean agent. Upon release of discharge delay period, depending on the abort/delay
the push button, the SinorixTM system will be discharged configuration of the system. Pressing the button before a
either immediately or following a delay period, depending zone is in alarm will cause a trouble signal at the control
on the system configuration. panel.

Description Architect/Engineers Specification


The model AW-1 abort station consists of a momentary The abort station shall be a Fire Safety model AW-1
contact switch with large red “mushroom” head for ease with Underwriters Laboratories listing and Factory
of operation. It is mounted on a steel plate. Screw type Mutual approval.
terminals are provided for connection to the agent release
circuit. The entire assembly mounts on a standard 2½" It shall include a momentary contact “deadman” type
deep two gang electrical box. switch with push button which, while pressed, will
prevent the discharge of the clean agent. The switch shall
be mounted on a steel cover plate. Screw type terminals
Operation shall be provided. The entire assembly shall be capable
After one or both detection zones are in alarm, SinorixTM of being mounted on a standard 2½" deep two gang
system discharge can be withheld by pressing the switch electrical box.

CATALOG NUMBER
6605
Ordering and Electrical Information

Main Reserve Selector Switch


The main reserve selector switch is a means of transfer-
ring of the electrical supply from the main cylinder to the
reserve cylinder.

MainReserveSelectorSwitch

SelectorSwitch(MainReserve)
PartNumber SPY-MRS

Fire Safety Fire Safety


8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 1/06 Brampton, Ontario
Tel: (973) 593-2600 5M Canada L6T 5E4
Siemens Building Technologies FAX: (973) 593-6670 SFS-IG Tel: (905) 799-9937 January 2006
Fire Safety Website: www.sbt.siemens.com/fis Printed in U.S.A. FAX: (905) 799-9858 New Issue