Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Voltage drop calculations using the DC-resistance formula are not always
accurate for AC circuits, especially for those with a less-than-unity power factor
or for those that use conductors larger than 2 AWG.
Voltage Drop Calculations For Engineers - Beginners (on photo: Low voltage
circuit breakers type NSX 250H, 600V)
If calculations with a different power factor are necessary, Table 1 also contains
the appropriate values of inductive reactance and AC resistance (see Example
2).
Calculation Example #1
A feeder has a 100 A continuous load. The system source is 240 volts, 3
phase, and the supplying circuit breaker is 125 A. The feeder is in a trade size
1¼ aluminum conduit with three 1 AWG THHN copper conductors operating
at their maximum temperature rating of 75°C. The circuit length is 150 ft, and
the power factor is 85 percent.
Calculation Example #2
If the power factor is 0.7 and the circuit length is 250 ft, is the voltage drop
excessive?
STEP-1 // Using the Table 1 column “XL(Reactance) for All Wires”, select PVC
conduit and the row for size 600 kcmil. A value of 0.039 ohm per 1000 ft is
given as this XL. Next, using the column “Alternating-Current Resistance for
Aluminum Wires”, select PVC conduit and the row for size 600 kcmil. A value
of 0.036 ohm per 1000 ft is given as this R.
STEP-2 // Find the angle representing a power factor of 0.7.
Using a calculator with trigonometric functions or a trigonometric function table,
find the arccosine (cos-1) θ of 0.7, which is 45.57 degrees. For this example,
call this angle.
STEP-7 // Find the voltage present at the load end of the circuit:
Alternating-Current Resistance and Reactance for 600-Volt Cables, 3-Phase, 60 Hz, 75°C
(167°F)
Premium Membership
Edvard Csanyi
Electrical engineer, programmer and founder of EEP. Highly specialized for design of
LV/MV switchgears and LV high power busbar trunking (<6300A) in power substations,
commercial buildings and industry facilities. Professional in AutoCAD programming.
11 Comments
1.
Salako Olakunle
JA N 1 1 , 2 0 1 7
Good work, it has been very educative. But please, at what percentage does
the voltage drop becomes excessive and what is the probable effect on the
circuit?
(reply)
2.
Manjunatha
NOV 23, 2015
Edvard
NOV 23, 2015
https://electrical-engineering-portal.com/mcb-miniature-circuit-breaker-construction
Regards
Edvard
(reply)
3.
Madhavanpillai
NOV 21, 2015
4.
Vishnu
OCT 11, 2015
5.
Doug McIntire, PE
SE P 2 5 , 2 0 1 5
Edvard,
I might point out that the last few steps are not needed. The L-L voltage drop is
the same as L-N in percentage the beauty of per unit type calculation. See in
step #4 of example #2 voltage drop is 3.584V. Divided into the line to neutral
voltage of 277V you get the same answer of .0129 or 1.29%. That is all that is
required to meet the code “noted” for feeders and branch circuits operating at
reasonable efficiency.
Be careful too as this defined as a feeder. I am led to assume that there are
branch circuits following on to this feeder load and that must be included in the
consideration. See NEC Article 100 definitions of branch circuit and feeder. I’m
possibly splitting hairs but we are making finer distinctions. Thanks for doing
this. Very useful.
(reply)
6.
S.D.Buddhisagar
SE P 2 5 , 2 0 1 5
R/s : I am , 64 , try to read your articles , through which I have benefited a lot , I
request you to guide me on how to do circuit analysis dependent sources,
Ialways get confused.
(reply)
7.
Ali C. Hussein
SE P 2 1 , 2 0 1 5
good work
(reply)
8.
SANJAY MAITRY
SE P 2 0 , 2 0 1 5
9.
Khalid Ur Rehman Shah
SE P 2 0 , 2 0 1 5
Good work
(reply)
10.
James M. Casallo, P.E.
SE P 1 9 , 2 0 1 5
Great article! I seem to always use the Line to Neutral value. Thanks for the
update and exercise. Keep up the great work and sharing of the knowledge.
(reply)
Leave a Comment
Tell us what you're thinking... we care about your opinion!
EMAIL ADDRESS *
© 2019 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | Terms of Service
×Get Notifications
The first consideration for voltage drop is that under the steady-state conditions
of normal load, the voltage at the utilization equipment must be adequate.
Fine-print notes in the NEC recommend sizing feeders and branch circuits so
that the maximum voltage drop in either does not exceed 3%, with the total
voltage drop for feedersand branch circuits not to exceed 5%, for
efficiency of operation.
In addition to steady-state conditions, voltage drop under transient conditions,
with sudden high-current, short-time loads, must be considered.
The most common loads of this type are motor inrush currents during starting.
These loads cause a voltage dip on the system as a result of the voltage drop in
conductors, transformers and generators under the high current. This voltage dip
can have numerous adverse effects on equipment in the system, and
equipment and conductors must be designed and sized to minimize these
problems.
Let’s see two most common methods for calculation of voltage drop –
approximate and exact methods:
1. Approximate method
2. Exact method #1
If the receiving end voltage, load current and power factor (PF) are known.
Go back to top ↑
2. Exact Method #2
If receiving or sending mVA and its power factor are known at a known sending
or receiving voltage.
or
where:
Tables for calculating voltage drop for copper and aluminum conductors , in either
magnetic (steel) or nonmagnetic (aluminum or non-metallic) conduit, are shown
below. These tables give voltage drop per ampere per 100 ft (30 m) of circuit
length.
The circuit length is from the beginning point to the end point of the circuit
regardless of the number of conductors.
Condition #1
Three or four single conductors in a conduit, random lay. For three-conductor
cable, actual voltage drop will be approximately the same for small conductor
sizes and high power factors. Actual voltage drop will be from 10 to 15% lower
for larger conductor sizes and lower power factors.
Condition #2
Voltage drops are phase-to-phase, for three-phase, three-wire or three-phase,
four-wire 60 Hz circuits. For other circuits, multiply voltage drop given in the
tables by the following correction factors:
Condition #3
Voltage drops are for a conductor temperature of 75 °C. They may be used
for conductor temperatures between 60 °C and 90 °C with reasonable accuracy
(within ±5%). However, correction factors in Table 1 can be applied if desired.
The values in the table are in percent of total voltage drop.
Go back to top ↑
Calculations
1. Multiply current in amperes by the length of the circuit in feet to get ampere-
feet. Circuit length is the distance from the point of origin to the load end of
the circuit.
2. Divide by 100.
3. Multiply by proper voltage drop value in tables. Result is voltage drop.
Example #1
A 460 V, 100 hp motor, running at 80% PF, draws 124 A full-load current. It
is fed by three 2/0 copper conductors in steel conduit. The feeder length is 150
ft (46 m).
What is the voltage drop in the feeder? What is the percentage voltage
drop?
Conclusion: 0.76% voltage drop is very acceptable. (See NEC Article 215,
which suggests that a voltage drop of 3% or less on a feeder is acceptable.)
Example #2
A three-phase, four-wire lighting feeder on a 208 V circuit is 250 ft (76.2 m)
long. The load is 175 A at 90% PF. It is desired to use aluminum 7
conductors in aluminum conduit.
Premium Membership
Edvard Csanyi
7 Comments
1.
Abiodun Sobayo
MAR 24, 2019
Nice to know this. Bit can we get a link to download all these calculations for
better understanding and to teach others.
(reply)
2.
Tariq
MAR 24, 2019
Dear Edvard:
Please Show The Mathematical Derive Of The Equation Of Exact Method #1
(And How Sending End Voltage (Vs) Appears In Voltage Drop Formula .
Best Regards ,
(reply)
3.
Mohamed Fadhil AL-Mukhtar
JA N 0 1 , 2 0 1 9
Hi everybody,
In fact I have a confussion for which power factor I use in determining voltage
drop of main cable (30m length) which supplies two motors (1st one 50HP ,
o.85 p.f, with 100m cable) and (2nd one 100HP , o.75 p.f,with 300m cable) .
Your answer is too much appreciated .
Thanks in advance
(reply)
4.
Chirantan Gupta
NOV 27, 2018
I saw the comments above and I guess what Gerald is referring to is the K
factor method which is popularly followed by NEC. However, NEC also supports
the IEEE 141-1993 formula. Refer to bottom of Table 9 Note 2 of NEC which
clearly says: Multiplying current by effective impedance gives good
approximation for line to neutral voltage drop. Thus, the approximate formula
(Sqrt(3)*I*(Rcosphi+Xsinphi) can be followed. For all practical purposes, I have
used this formula for last 25 years. The exact formula can also be used, and
there is a vectorial method to get the solution.
(reply)
5.
Eng. Abdolgabar Ahmed Mahmood
OCT 25, 2018
Dear Engineers,
GERALD NEWTON AND TOMMY RICE.
Please tell me your methods of voltage drop calculations I will be grateful for
you to let me know the best way of calculation because I am new in this field.
best regards
Eng. Abdolgabar Ahmed
(reply)
6.
Gerald Newton
MAR 08, 2017
Your voltage drop calculation article is off the wall. Sorry, but this is not how it is
done. Furthermore, the State of Washington specifically states in a news letter
how the inspectors want the calculation done. I have been in this business for
over 40 years and have never, ever seen anything like your method. I suggest
you do some research on how practical engineers and electricians do voltage
drop calculations.
(reply)
Tommy Rice
APR 01, 2017
could you e-mail me and tell me how Washington state wants their
calculations done. I use a different method for voltage drop calculations than
edvard csanyi
(reply)
Leave a Comment
Tell us what you're thinking... we care about your opinion!
YOUR REAL NAME *
EMAIL ADDRESS *
© 2019 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | Terms of Service
×Get Notifications