Sei sulla pagina 1di 35

APPENDIX - X

MECHANICAL DESIGN CRITERIA,


EQUIPMENT/MATERIAL AND
TECHNICAL SPECIFICATIONS
fi." ~,~ 6l::.~.~! ~ .r~j
Saud: Electricity Company

APPENDIX

FOR

MECHANICAL DESIGN CRITERIA,


EQUIPMENTI MATERIAL AND
TECHNICAL SPECIFICATIONS
(REVISION NO.3)

ENGINEERING & DESIGN DIVISION -EAST


ENGINEERING & DESIGN DEPARTMENT
,.:
0:
'"
U
SAUDI ELECTRICITY COMPANY

::""
0

:J:
TABLE OF CONTENTS
'"
W

W
f-
0:«
0
cO
0
LLD..::;;
z::::l W
::;;
f- W
0--' (fJ f-
-« (fJ
f-O: >- >-
z
0
t)W eo
Wz
(fJ SECTION PAGE
Z 0:
t= f-W 0
e, 0(9 f= W
f-
e;: g::cO
t) «
u f-W
z(fJ Of- :s:
'"
t.> Of- 0:« 0
Cl
_z D..O W
(fJW WD.. --' INTRODUCTION 2
09: :!
O:::::l0:::>I
0:0 ---'
LL« t)
Ow 00: 0
t)t) WW W
0« OZ 0
0> OW 0
«I «(9 « 11 DESIGN CRITERIA
0 ..; N
...;
z
REVISIONS
2.01 GENERAL 3
2.02 HVAC DESIGN PARAMETERS 3
DEn, ;:;:[&;:;:DD_~

PREP. BY;
III EQUIPMENT/MATERIALS & TECHNICAL SPECIFICATIONS

DATE:
3.01 GENERAL 4
3.02 HVAC SYSTEM REQUIREMENTS 4
3.03 HVAC EQUIPMENT & MATERIALS 6
3.04 EXECUTION (HVAC) 21
3.05 PLUMBING SYSTEM MATERIAL REQUIREMENTS 28
3.06 FIRE DETECTION/ALARM, FIRE PROTECTION 31
SYSTEMS & GASEOUS PROTECTION SYSTEM

THIS DRAWING IS NOT


TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERiAlS UNTIL
CERTIFIEDAND DATED

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT / MATERIALS AND TECHNICAL 1
REFER TO REFER TO
JOB ORDERNO. SPECIFICATIONS VlAIN SOW/TS A OF 3
MAIN SOW/TS
33
..:
'"'"u SAUDI ELECTRICITY COMPANY
0
t.,
0
:.:
:t
u

W
I-
o::q:
0
06 SECTION I: INTRODUCTION
0
LLo.. ::;<
z=> ur ::;<
I- w
0-' (/)
I-
-q: (/)
1-0:: >- >-
z Ow (/)

0 Wz
I-W
Z
(/)

0:: This standard is intended to be used for substation and integral part of scope of work for
...
i= 0(9
0
i=
W
I- mechanical requirements. It covers mechanical, design criteria, equipment/materials &
02 g:06
0 -c
s:
U I-W
z(/) 01- technical specifications for substation projects.
'"""
Q
01-
_z o::q:
0..0
0
W
(/)W wo.. -'
00..
0::5 o::=>
-'
- -' I
0::0 LLq: 0
Ow 00:: 0
00 wW w
oq: oz 0
0> ow 0
q::I: q:(9 q:

0 ..; ...• ..; **** END OF SECTION I ****


z
REVISIONS

DEPT: .:.:£.&.:..:.0:..-0 _--I

PREP. BY:

DATE:

BY:

",r-:~':".. n;/
DATE:

THIS DRAWING IS NOT


TO BE USED FOR
CONSTRUCnON OR
FOR ORDERING
MATERIALS UNnL
CERnFIED AND DATED

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 2
REFER TO REFER TO
SPECIFICATIONS IIIAIN SOWITS A OF 3
JOB ORDER NO. MAINSOWITS
33
~ SAUDI ELECTRICITY COMPANY
U'"
Q

~
-e
SECTION 11:DESIGN CRITERIA
;.,
Q

G
w
2.01 GENERAL
t-
0::« o1l
00
LLo.. ::;;:
Z:::J W
::;;:
W
This Section outlines the PROJECT'S design criteria and shall be read in
t- t-
0-' en

t-o::>-
en
>- conjunction with the attached PROJECT drawings, the COMPANY Engineering,
z <.)W en en
Construction and Material Standard Specifications and the latest associated
..
0
~
Q2
wz
t-W 0
Ol') i=
:fo1l
z

<.)
0::
W
t-
« International Standards and Codes.
u zen t- w ~
<Jl
Ot- Ot- 0
'"
Q _z
enw
0::«
0..0
wo..
W
-'
O~ 0:::::J
O:::::J - -' I
-'
0::0
Ow
LL« <.)
Do:: 0
2.02 HVAC DESIGN PARAMETERS
<.)<.)wW W
0« OZ 0
0> OW 0
«I «l') « A. The following temperatures shall be the basis for design:
0
z
..; ..• ...;

REVISIONS

Design Ambient Conditions


DEFT:
--~
E&DD

PREP. BY: Outdoor:


Ambient Temperature Refer to TES-K-100.01
DATE:
Mean Daily Range Refer to TES-K-1 00.01

Indoor:
Room Temperature 25.0
Relative Humidity 50.0 %

Equipment Operation 24 hrs / day

B. Noise Level

In room: 45 dB(A) - ( 25-30 NC)


In open air at a distance of 2 meters: 60 dB(A) for overall area

C. Ambient Air Quality

The air conditioning system shall be designed for airborne dust


concentration of 1mg/m3 and sandstorm dust concentrations reaching
3
500mg/m near the ground. Dust particles sizes are as follows:

95% less than 20 micrometers (0.0008 inch)


50% less than 1.5 micrometers (0.00006 inch)

No continuous chemical air contamination is considered.

**** END OF SECTION 11****

THIS DRAWING IS NOT


TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERiAlS UNTIL
CERTIFIED AND DATED

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENTNO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 3
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN SOWITS MAIN SOWITS
33
,.:
'"w
U
SAUDI ELECTRICITY COMPANY
0

~
" SECTION Ill: TECHNICAL AND EQUIPMENT/MATERIALSSPECIFICATIONS
0

"
:!:
U

W
I-
0::«
OCl
06 3.01 GENERAL
LLCL :2 :2
z=>
0-' en
W
I- W
I-
i=c? >- en
>-
This Section outlines broadly the technical specifications of the major equipment!
z; Ow en en
0 Wz
I-W 0
Z 0:: materials required for the complete installation of the PROJECT. The specifications
...i= w
g:06 i=
00
~ 0
I- outlined herein shall be read in conjunction with the COMPANY Material Standard
u
<I>
I-W
zen 01- ~ Specifications and the associated International Standards and Codes. The ratings
01- Cl
'"
Q _z 0::« W
0..0
enw
00.. wo.. -'
-' and specific requirements of the various equipment shall be as indicated in Data
0::5 o::=>
- -' i'
0::0
Ow
LL« 0 Schedule of COMPANY Material Standard Specifications, and the CONTRACTOR
Cl 0::Cl
00
Cl«
ww
oz
w
Cl shall ensure full conformity with the same.
Cl> ClW Cl
«:r: «0 «
c
z;
..; ... -
REVISIONS
3.02 HVAC SYSTEM REQUIREMENTS

A. General
DEPT: E&OD

PREP. BY:
1. Heating, Ventilating and Air Conditioning System shall be provided to
maintain the desired indoor temperature and environmental condition for
DATE:
efficient equipment operation. HVAC System shall conform to the applicable
requirements of SEC Std. TES-P-119.19.

2. All units shall be mounted on the reinforced concrete pads with the necessary
vibration isolators.

3. Air distribution (supply and return) system shall be through factory insulated
double skinned spiral duct for indoor exposed ductwork, and externally
insulated factory made rectangular duct for covered and outdoor ductwork.
Airflow direction shall be marked-up on outdoor ducts for easy identification.
Exposed duct insulation shall be protected from all weather conditions and
provided with aluminum cladding that is resistant to ultraviolet radiation.

4. All fresh air make-up shall be through sand trap louver with air filtration,
volume control damper and removable 13mm wire mesh screen. Inertial Air
Filter with dedicated bleed fans is specified in area where high percentage of
sand or impurities is available in the air whole year round.

5. High building temperature alarm indication shall be provided for each HVAC
system to SCADA alarm.

6. Controls shall be Direct Digital Control (DDC). Interlock controls shall be


provided with SCADA and FACP to remotely monitor status of the HVAC
System, modification of set points and parameters, and to trip the duty Air
Conditioning Unit in case of smokelfire detection, respectively. This control
shall have provision to management stations and/or service terminal for
future connections.

7. Minimum amount of air shall be supplied to the basement (or cable entry
THIS DRAWING IS NOT
TO BE USED FOR
room) if any, to maintain the required room temperature.
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL 8. Except for toilet, temperature and humidity indicators (hygrometers) shall be
CERTIFIED AND DATED
conveniently installed in all rooms. Temperature and humidity sensors shall

HA(6/5/20 11)

PlANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 4
REFER TO REFER TO
SPECIFICATIONS \/lAIN SOWITS A OF 3
JOB ORDER NO. MAINSOWITS
33
.,"
0:
U
SAUDI ELECTRICITY COMPANY
0
~
-e be installed outside the building to send signal to HVAC control panel for
Q

:-
:I:
temperature and humidity indication.
u

w
~
0::« B. HVAC Control System
0<:1
0 0 :;;
u.CL :;;
Z=> w
0-' ~ ur
~

~o::
en
>- en
>-
1. The Direct Digital Control (DDC) system shall be compact module type 24V
z Ow en en
DC shall contain digital and analogue for input and output points as specified
..
0
~
WZ
~W
0(.9
Z
0
i=
g:o<:I 0
0::
W
~ below:
"'"
u
<JJ

Q
Zen O~
O~
_Z
~W
0::« w
CLO
~
0
OCL WCL -'
enw a. All alarms and indications (such as pre-filter, bag filter, exhaust fans,
0::5 o::=>I -'
0::0 u.«
Ow
- -' 0 etc.) shall be consider as input points in DDC system.
00:: 0
00 ww w
0« oz 0
0> ow 0 b. Compact module DDC shall be at least 16 points input and 16 points
«:I: «(.9 «
0 ...; ..• output.
z -'
REVISIONS
c. DDC shall be ready to communicate with computer system to building
B.M.S. in the future.
DEPT, =E&=DD~-I
d. DDC compact module shall be at least 20% free points spare.
PREP. BY:

DATE:
e. Portable operator's terminal shall be provided.

2. Control system shall also be provided with all the necessary pressure and
temperature control protective devices.

3. Provide duct smoke detectors complete with response indicator and shall be
connected to the fire alarm control panel under separate zone.

4. The wiring for proposed smoke detectors shall be either in conduits or MIC
type.

5. The DDC system shall also include all the necessary pressure and
temperature control protective devices as well as control relays, consisting of,
but not be limited to, the following, in addition to the requirements defined in
Section 4.3 ofTES-P-119.19:-

a. 7-day changeover switch from on-line to standby unit and vise versa.

BY:
b. Provide the following safety controls and indicating lights or diagnostic
DATE, oCiJt..L.d d read-outs (as applicable) :

• Low chilled water temperature protection


• High refrigerant pressure
• Low oil flow protection
• Loss of chilled water flow
• Contact for remote emergency shutdown
• Loss of refrigerant charge protection.
• Motor current overload
• Phase reversal / unbalance / single phasing
THIS DRAWING IS NOT
TO BE USED FOR • Over or under voltage
CONSTRUCTION OR
FOR ORDERING • Failure of water temperature sensor used by controller.
MATERIALS UNTIL
CERTIFIEDAND DATED • Compressor operating status.

HA(6/5/20 11)

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 5
REFER TO REFER TO
SPECIFICATIONS ~AIN SOWITS A OF 3
JOB ORDER NO. MAINSOWITS
33
,..:
0:
'"
W
SAUDI ELECTRICITY COMPANY
Q

~
-e
Q
:.
:t
w
c. Provide the following additional operating controls as applicable: -
W
r
0::« cO
00
::;:
l.L.(L ::;: • Load limit thermostat to limit compressor loading on high return
z::> W W
0-' r r
-« U)

rO:: >-
U)
>- water temperature to prevent nuisance trip-out
z Uw U)
U)
0 wz Z 0::
;:::
•.. rw 0 w
O~ t= r
ii 8:06
U • High ambient unloader pressurestat that unloads compressor to
U rW
zu) Or ~
'"'" or
_z 0::« 0 keep head pressure under control and help prevent high Pressure
Q (LO W
U)W w(L
OQ, -'
-' nuisance trip-out during high ambient outdoor temperature.
0::::>
0::::>
0::0 -
l.L.«-' IU
Ow 00:: 0
Uu ww w
0« oz 0 • Condensing fan sequencing which automatically cycles fans in
0> ow 0
«I «~ « response to ambient, condensing pressure and expansion valve
0 ..;
z N
-' pressure differential thereby optimizing unit efficiency.
REVISIONS
Notes:

DEPT, .:::E&:.;;.;DD~-I 1. DDC Panel shall be located closer to the Outdoor HVAC unit, and not
PREP. BY;
more than 100m a way from the Outdoor HVAC units I Field Devices.

DATE:
2. For DX- Air Cooling system additional Control requirements, refer to TES-
P-119.19& 73-TMSS-1.

3.03 HVAC Equipment and Materials

1. Packaged Air Conditioning Units:

Manufactured Units: Self contained single packaged, pre-wired units


and pre- charged with refrigerant complying with 73- TMSS-1.

2. Air Cooled Condensing Units

a. Manufactured Unit

Self-contained, packaged, factory assembled and pre-wired units


complying with 73-TMSS-1.

b. Refrigerant Circuit

Provide each unit with independent refrigerant circuits, factory supplied


and piped.

3. Air Handling Unit - Direct Expansion (OX) Type

a. Configuration

THIS DRAWING IS NOT Fabricate with fan and coil section plus accessories, including filter section.
TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL b. Fabrication
CERTIFIEDAND DATED

HA(6/5/20 11 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 6
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN SOWITS MAIN SOWITS
33
~ SAUDI ELECTRICITY COMPANY
'"
I.J

t-e
Conform and certify by ARI 430 and 73-TMSS-1. Unit casing in contact
Q

:- with supply air shall be double wall construction consisting of 16 gauge


C
galvanized iron powder coated sheet exterior panel, 40mm thick, minimum
w
f- polyurethane injected panel insulation and an interior wall of aluminum
0:::« oil
00
u..Cl.::;;;
Z::::>W ::;;; material. Both skins are isolated through rubber-extruded gasket.
f- W
0--' en f-

f-O:::> en
Ow en >
en
Z
Install inspection light with door switch (micro switch) in the fan section of
..
0
i=
WZ
f-w 0
Z
0(.9 f=
0:::
W
f- AHU's and main electrical control panel board.
" g:oil 0 «
u Zen f-W 3:
Of-
'"'"
Q
Of-
_Z 0:::« 0
Cl.0 W
o Cl.WCl. --'
enw
--' 4. Air-Cooled Water Chillers
0:::3 0:::::::>
0:::0 ---'
I
u..« 0
Ow 00::: 0
00

ww
oz
w
0
Factory assembled and tested outdoor-type microprocessor controlled air-
0> ow 0
«I «(.9 « cooled liquid chillers consisting of screw compressors, condenser, evaporator,
cl
Z
..; ...• ...: electronic or thermostatic expansion valve, refrigeration accessories and control
panel. Construction and ratings shall be in accordance with SEC material
REVISIONS
specification for Packaged Air Cooled Water Chiller, 73-TMSS-02.

DEFT: [&00
5. Chilled Water Type Air Handling Unit
----I
PREP. BY:
Chilled Water Type Air Handling Unit shall be factory assembled consisting of
DATE: fan and coil section, filter section and mixing box for a complete and fully
operational system. Design, construction and ratings shall be in accordance
with 73-TMSS-03.

6. Chilled Water Pumps

Pumps shall be end suction type, single stage, horizontally split casing, direct
connected and in accordance with SEC standard material specification no. 73-
TMSS-4.

7. Fresh Air Fans (Option for High Static Pressure Loss in Fresh Air Intake):

Fan housing shall be of air-tight construction with scroll panel material formed
and embedded into the side panels. The housing and bearing supports shall
be constructed of welded structural steel members to prevent vibration and
rigidly support the shaft and bearing.

The fan wheel shall be of the non-overloading backward inclined or airfoil


centrifugal type. Wheel shall be statically and dynamically balanced. The wheel
cone and fan inlet cone shall be carefully matched and shall have precise
running tolerances for maximum performance and operating efficiency. Turned,
precision ground and polished steel shaft shall be sized so the first critical
speed is at least 25% over the maximum operating speed for each pressure
class. Close tolerances shall be maintained when the shaft passes through the
bearing.

Bearing shall be heavy duty grease lubricated, self-aligning or roller pillow


block type. Bearing shall be selected for basic rating fatigue life of 80,000 hours
at maximum operating speed for each pressure class.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR Each assembled fan shall be test run at the factory at the specified fan RPM
FOR ORDERING
MATERIALS UNTIL and vibration signatures shall be taken on each in the horizontal, vertical and
CERTIFIED AND DATED
axial direction. The unit shall be mounted on vibration isolators.

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 7
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. \/lAIN SOWITS MAlNSOWITS
33
"
0:
....
U
SAUDI ELECTRICITY COMPANY
0
t
"
0
:.
:t
8. Bleed Air Fans (Option for Inertial Air Filter System):
u

W
f-
0:::« 06 Centrifugal belt drive type designed primarily for continuous dust removal. Fan
0 0
LLQ.. :;;
z=> f-w w
:;; wheels shall be made of steel of side plate type with one- piece cast malleable
0-' en f-
>-
i=Ci en
en
>- iron or fabricated steel spider.
z UW en
0 wz Z 0:::
f= f-w 0 W
0<-,i= f-
e:""U g:06 U « 9. Air Cleaning
f-W ~
Z(f) Of-
on
Of- 0:::« 0
'"
Q _z
(f)W ,,-0 W
09, W"- ::!
o:::=>
-' a. Inertial Air Filter (For Make-up Air Intake System with high concentration
o:::=>
- -' U
I
0:::0 LL«
Ow
of Dust Particle)
00::: 0
Uu WW W
0« OZ 0
0> 0
«I ~~ « i. Components: All finished components shall be phosphatized and
ci
z
..; N ..; given a coat of zinc chromate primer and finished with a coat of gray
enamel.
REVISIONS

Housing: Shall be constructed of not less than 11 gage steel.


DEPT' ~£'&=DD'----1
The housing shall be of all welded construction and equipped
with continuous standing flanges around periphery of both air
PREP. BY:
entering and air exiting sides. Flanges shall have pre-drilled bolt
DATE: holes to facilitate field installation.

Bleed Air Manifold: Shall have continuous standing flange with


pre-drilled bolt holes to facilitate field connection. Manifolds shall
be sized to provide uniform airflow through each cells dust bin for
proper balance and dust removal.

Bull nose: Shall be aerodynamically formed of gage steel to


provide air entry.

Bleed Slot: Shall not be less than 16 gages steel. The bleed slot
shall be a rounded entry configuration to minimize destruction or
plugging under heavy dust concentrations.

Inlet Screen: Shall consist of 26 gages, four meshes, galvanized


hardware cloth integrally supported by a double layered 16 gage
galvanized steel frame. Inlet screen shall be bolted to the
housing.

ii Performance: Self-cleaning inertial air cleaner with a bleed rate of


11.1% of the clean airflow at ambient temperature and dust specific
gravity of 2.54 with minimum efficiency of 85% in accordance with
ASHRAE 52.1.

iii. Basic Configuration System: A small auxiliary bleed fan is the most
practical method of attaining the recommended 11.1% bleed airflow.

THIS DRAWING IS NOT b. High Efficiency Air Filters (Bag Filters)


TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL i. Media: Ultra-fine fiberglass.
CERTIFIEDAND DATED
- Holding Frame: Galvanized Steel.

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL REFER TO
8
REFER TO
SPECIFICATIONS IIIAlN SOWITS A OF 3
JOB ORDER NO. MAINSOWITS
33
'"' SAUDI ELECTRICITY COMPANY
''""
u

..•.
0

-e
0
:.
::
ii. Performance Rating:
u
W
I-
o::~ ASHRAE 52-76/EUROVENT 4/5 Test Method Average
00 ""
!.Lc..
z:::;'w
:2' :2'
W
Efficiency: 92.5%
I- I-
0-'
-<>:: U)
>- U)
1-0:: U) >-
z UW U)
Rated Air Flow Capacity at 152 Pa: 1180 Llsec.
..
0
i=
wz
I-w
0(9
0
Z

i=
g:""
0::
W
I-
«
"
'-''"
'"
Q
zU)
01-
_z
U
I-W
01-
o::~
c..O
:;:
0
w
Recommended Final Resistance: 250 Pa.
U)W
09:: wc.. :!
0:::::;'
-'
0:::::;,
-
0::0 !.L<>::
:r:
U -' c. Washable Permanent Panel Filters
Ow 00:: 0
Uu ww w
0<>:: oz 0
0>
<>:::r:
0
~~
<>:: i. Media: 14 mesh aluminum, alternate layers of flat and herringbone
cl ..; ..• -' crimp, four layers per inch (25mm), rod reinforced.
z
REVISIONS
- Frame: 16 gage (1.5mm) galvanized steel.

- Thickness: 50mm thick

PREP. BY; ii. Performance Rating:


DATE:
- Initial resistance at 2.54 m/sec.
Face velocity: 25 Pa w.g.

- Recommended final resistance at 2.54 m/sec.


Face velocity: 125 Pa w.g.

d. Filter Gages

i. Direct Reading Dial: 90mm diameter diaphragm actuated dial in


metal case, vent valves, black figures on white background, front
recalibration adjustment, range 0-125 Pa, 2% of full scale accuracy.

ii. Accessories: Static pressure probes with integral compression


fittings, 6mm aluminum or plastic tubing, 2-way or 3-way vent valves.

10. Power Ventilators

Exhaust fans shall be centrifugal type per 73- TMSS-05 requirements, except
for the following:

a. 8attery Room Application: Consists of non-corrosive parts with explosion


proof type motor with class 8 insulation ideal for 24 hours continuous
operation. Exhaust fan shall be 8elt Drive. Up-blast type, and ducted.

b. Toilet exhaust fan motor shall have NEMA design class 8 insulation. The
fan shall be Direct Drive sidewall centrifugal type.

THIS DRAWING IS NOT


TO BE USED FOR
11. Refrigerant Piping/Specialties
CONSTRUCTION OR
FOR ORDERING
MATERIAlS UNTIL a. Copper Tubing
CERTIFIEDAND DATED

ASTM 8280, type ACR hard drawn or annealed.


HA(6/5/20 11)

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 9
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN SOWfTS MAIN SOWfTS
33
,.:
'"'"
U
SAUDI ELECTRICITY COMPANY
Q
~
-c
Q
i, Fittings: ANSIIASME 816.22 wrought copper.
"
::
u
W
0:::« oil
~ ii. Joints: Braze, AWS A5.8 BC up silver/phosphorous/copper alloy
0 0
LLo.. ::2:
Z=> w
::2: with melting range 640 to 805°C.
0-' en
~
w
~
>- en
f=~ en >-
z Ow en
iii. Insulation: ASTM C534 flexible closed-cell elastomeric in tubular
..
0
i=
WZ
~W
0(9 f=
Z
0
0:::
W
~ form with 64 kg/cu.m density and 25mm thick.
" g:oIl 0 «
u Zen ~W
O~
5:
'"'"
Q
O~
_Z 0:::« 0
0..0 W
enw
O~
wo.. -'
::! b. Pipe Supports
o:::=>o:::=> I
0:::0 -
LL« -' 0
Ow 00::: 0
00

wW
OZ
w
0 i. Hanger for pipe sizes 13 to 40mm: Malleable iron, adjustable
0> OW 0
«I «(9 « swivel, and split ring.
c ..; N
..;
z
REVISIONS
ii. Wall Support for pipe sizes to 75mm: Cast iron hook.

iii. Vertical Support: Steel riser clamp.

iv. Floor Support: Cast iron adjustable pipe saddle, lock unit nipple
PREP. BY:
floor flange and concrete pier to steel support.
DATE:

v. Copper Pipe Support: Carbon steel ring, adjustable, copper plated.

c. Moisture and Liquid Indicators

Single or double port type, UL listed, with copper or brass body, solder or
flared ends, sight glass, color coded paper moisture indicator with
removable element cartridge and plastic cap; for maximum working
pressure of 3450 kPa, and maximum temperature of 93°C.

d. Valves

Diaphragm Packless Valves: UL listed, globe or angle pattern forged


brass body and bonnet, phosphor bronze and stainless steel diaphragms,
rising stern and handwheel, stainless steel spring, nylon seat disc, solder
or flared ends, with positive backseating for maximum working pressure
of 3450 kPa and maximum temperature of 135°C.

e. Service Valves

Forged brass body with copper stubs, brass caps, removable valve core,
(integral ball check valve) flared or solder ends, for maximum pressure of
3450 kPa.

f. Filter Driers

Replaceable Cartridge Angle Type:

Shell: ARI 710, UL listed, steel, removable cap for maximum working
THIS DRAWING IS NOT
TO BE USED FOR
pressure of 3450 kPa, outside diameter size connections:
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL i. Filter Cartridge: Pleated media with integral end rings, stainless
CERTIFIEDAND DATED
steel support.

HA(6/5/2011 )

PlANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 10
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDERNO. ~AIN SOWITS MAIN SOWITS
33
,.:
0:
'"
U
SAUDI ELECTRICITY COMPANY
C
~
-c ii. Filter/Dryer Cartridge: Pleated media with solid core sieve with
C
:.: activated alumina.
:I:
u

W
f-
CC« g. Solenoid Valves
00 ""
u.o. ::;; ::;;
z=> W W
0---'f- f-

f-CC
en
>- en
>-
Valve: ARI 760, pilot operated, copper, brass or steel body and
Z UW en en
0 wz
f-W 0
z CC internal parts, synthetic material seat, stainless steel stem and plunger
1= 0<.')i= W
0..
g:01l f- assembly, integral strainer, with flared, solder, or threaded ends; for
"
u
'"0'"'
zen
_z
U
f-W
Of-
Of- CC«
0.0
«
5:
0
W
---'
maximum working pressure of 3450 kPa. Stem shall permit manual
enw wo.
09= CC=> ::! operation case of coil failure.
cc=>
CCa u.« U -
---' I
Ow OCC 0
Uu

ww
oz
w
0
Coil Assembly: (UL 429), UL listed, replaceable with molded
0> ow 0
«I «<.') « electromagnetic coil, moisture and fungus proof, with surge protector and
0
z
..; ...• ..; color coded lead wires, integral junction box with pilot light.
REVISIONS
h. Thermal Expansion Valves

Angle or Straight Through Type: ARI 750: design suitable for refrigerant
DEPT: _E&_DD_~
brass body, internal or external equalizer, maximum operating pressure
PREP. BY:
(MOP) feature, adjustable superheat setting, replaceable inlet strainer,
DATE: with replaceable capillary tube and remote sensing bulb.

Selection: Evaluate refrigerant pressure drop through system to


determine available pressure drop across valve. Select valve for
maximum load at design operating pressure across valve. Select valve
for maximum load at design operating pressure and minimum 5.5°C
superheat. Select to avoid being undersized at full load and excessively
oversized at part load.
i. Flexible Connector

Corrugated stainless steel hose with single layer of stainless steel


braiding, minimum 230mm long with copper tube ends; for maximum
working pressure 3450 kPa.

12. Hydronic Piping

a. Chilled Water Piping, Above Grade

- Black Steel Pipe: ASTM A53, Schedule 40

i. Fittings: ANSI/ASTM B16.3 malleable iron or ASTM A234, forged


steel welding type.

ii. Joints: Threaded

Insulation: Refer to TES-K-100.01, Sect. 13.3. Above ground piping


shall be provided with Aluminum Cladding with 0.5 mm min. thick.

THIS DRAWING IS NOT


TO BE USED FOR
CONSTRUCTION
FOR
OR
ORDERING
b. Chilled Water Piping, Buried
MATERIALS UNTIL
CERTIFIED AND DATED
Pre-insulated chilled water pipes in unitized factory prefabricated
sections of approximately 3.0 meters in length.
HA(6/5/20 11)

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 11
REFER TO REFER TO
SPECIFICATIONS fAAIN SOWITS A OF 3
JOB ORDER NO. MAIN SOWITS
33
.""•
U
SAUDI ELECTRICITY COMPANY
Q

~
-e
Q
:. Materials
:t
u
W
f-
a:« 06 i. Core Pipe: Carrier pipe shall be black steel pipe per ASTM A53
0 0
LLCL ::;;: ::;;: Grade 8, schedule 40 with beveled ends.
Z::;:)W W
f-
0--' en f-
-« en
f-a: >- >-
Z Ow en en
ii. Insulation: Refer to TES-K-100.01, sect. 13.3.
..
0
f:
0:
WZ
f-W 0

8:06 ~
0(,9
0
Z a:
W
f-
u zen f-W
Of- ~ iii. Pre-insulated Fittings: All fittings shall be black steel, schedule
'"'"
Of- a:« 0
0 _Z W
en w CLO
OCL WCL --'
=' 40 conforming to ASTM A234 and dimensions as per ANSI/ANSI
a:5 a:::;:)
I
- --' 0
a:O LL« 816.9. All fittings shall have a 300 mm long steel pipe extension,
Ow Oa: 0
00

wW
OZ
W
0
factory welded each end. Insulation and casing shall be the same
0> 0
«I ~~ « materials as that for straight pipes.
0 ..; ...• ...;
z;
iv. Outer Casing: The casing shall be PVC, Class 3 as per ASTM
REVISIONS
01784

v. Field Joint Insulation: Filed joints shall be insulated with


DEPT: .::.:E&=DD~---I
polyurethane foam chemicals, applied into a galvanized sheet
PREP. BY:
metal mold around the pipe, fastened with stainless steel
DATE: bonding. Then silicon adhesive sealant is applied along the
seams to form a watertight joint.

c. Pipe Hangers and Supports

Conform to ANSI/ASME 831.9.

- Hangers for Pipe Sizes 13 to 40 mm: Malleable iron, adjustable


swivel, split ring.

- Hangers for Cold Pipe Sizes 50mm and over: Carbon steel,
adjustable, clevis.

- Multiple or Trapeze Hangers: Steel channels with welded spacers


and hanger rods.

- Wall Support for Pipe Sizes to 75mm: Cast iron hook.


~~
BY:

'" - Wall Support for Pipe Sizes 100mm and Over: Welded steel bracket
DATE:
rC~b20/1 and wrought steel clamp.

- Vertical Support: Steel riser clamp.

- Floor Support for Cold Pipe: Cast iron adjustable pipe saddle, lock
nut, nipple, floor flange and concrete pier or steel support.

- Hanger Rods: Mild steel threaded both ends, threaded one end or
continuous threaded.

THIS DRAWING IS NOT - Inserts: Malleable iron case of galvanized steel shell and expander
TO BE USED FOR
CONSTRUCTION OR plug for threaded connection with lateral adjustment, top slot for
FOR ORDERING
MATERIALS UNTIL reinforcing rods, lugs for attaching to forms, size inserts to suit
CERTIFIED AND DATED
threaded hanger rods.

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 12
REFER TO REFER TO
SPECIFICATIONS ~AIN SOWITS A OF 3
JOB ORDER NO. MAIN SOWITS
33
,.;
''"u" SAUDI ELECTRICITY COMPANY
0
~
-e d. Unions and Flanges
0

'"
X
U
- Unions for Pipe 50mm and Under:
W
I-
a:<>:
0 0 ""
LLa..
z;:} w ='! ='!
W
i. Ferrous Piping: 1034 kPa malleable iron, threaded.
I-
0---' U) I-
-<>: >- U)
I-a: U) >-
Z uw
0 wz
I-W 0 z
U)

a: ii. Copper Pipe: Bronze, soldered joints.


f:
•.. 0(9 W
i= I-
a: g:""
u
u
I-W ~
<>:
zU)
'"'" 01- 01-
a:<>: 0
- Flanges for Pipe Over 50mm:
Cl
_z Q.O W
U)W o a..Wa.. ---'
a:;:} a:;:} ='
- ---' :r:
a:a LL<>: U i. Ferrous Piping: 1034 kPa forged steel, slip on.
Ow oa: 0
Uu WW W
0<>: oz 0
0> OW 0
<>::r:<>:(9 <>: ii. Copper Piping: Bronze
c
z
,.; ... ..:

c. Gaskets: 1.59mm thick preformed neoprene


REVISIONS

- Dielectric Connections: Union with galvanized or plated steel


threaded end, copper solder end, water impervious isolation barrier.
DEPT, =E&:.:.:DD~4

PREP.8Y:
e. Gate Valves
DATE:

- Up to and Including 50mm: Bronze body, bronze trim, screwed


bonnet, non-rising stem, handwheel, inside screw with backseating
stem, solid wedge disc, alloy seat rings, threaded ends.

- Over 50mm: Iron body, bronze trim, bolted bonnet, non-rising stem,
handwheel, outside screw and yoke, solid wedge disc with bronze
seat rings, flanged ends.

f. Globe or Angle Valves

- Up to and Including 50mm: Bronze body, bronze trim, screwed


bonnet, rising stem and handwheel, inside screw with backseating
stem, renewable composition disc and bronze seat ring, threaded
ends.

- Over 50mm: Iron body, bronze trim, bolted bonnet, rising stem,
handwheel, outside screw and yoke, rotating plug type disc with
renewable seat ring and disc, flanged ends.

g. Swing Check Valves

Up to and Including 50mm: Bronze body, bronze trim, bronze rotating


swing disc, with composition disc, threaded ends.

Over 50mm: Iron body, bronze trim, bronze or bronze faced rotating
swing disc, renewable disc and seat, fJanged ends.

h. Spring Loaded Check Valves


THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR - Iron body, bronze trim, split plate, hinged with stainless steel spring,
FOR ORDERING
MATERIAlS UNTIL resilient seal bonded to body, water or threaded lug ends.
CERTIFIED AND DATED

j. Diaphragm Type Expansion Tanks


HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 13
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN SOWITS MAIN SOWITS
33
,.:
""'
w
SAUDI ELECTRICITY COMPANY
c
t-c
c
;.: - Construction: Welded steel, tested and stamped in accordance with
a ASME SEC 8-D, supplied with National Board Form U 1, rated for
W
I-
0::": 06 working pressure of 860 kPa, with flexible EPDM diaphragm sealed
0 0
LLCL ::;;: ::;;: into tank.
z~ w W
I- I-
0-' U)
U)
i=~ >- >-
z UW U)
0 WZ
I-w 0
Z
U)
0:: - Accessories: Pressure gage and air charging fitting, tank drain, pre-
...
f:
Ot!) i= W
I- charge to 83 kPa.
;;:
u
8:06U
I-W
-c
$:
tIl zU) 01-
01- 0
'"
Q _Z 0::":
U)W CLO W
OCL wCL -'
-' k. Air Vents
0::5 o::~ :r
0::0 - -'
"-..:
U
Ow 00:: 0
Uu
0..: oz
ww w
0
- Automatic Type: Short vertical sections of 50mm diameter pipe to
0> ow
..::r ..:t!) 0
..: form air chamber, with 3mm brass needle valve at top of chamber .
0 ..; ...• ,..;
z
- Brass or semi-steel body, copper, polypropylene or solid nonmetallic
REVISIONS
float, stainless steel valve and valve seat, suitable for system
operating temperature and pressure with isolating valve.
DEPT: ....;.E&.....;DD_--f
I. Strainers
PREP. BY:

DATE: - Size 50mm and Under: Screwed brass or iron body for 1206 kPa
working pressure, Y pattern with 0.8mm stainless steel perforated
screen.

- Size 65mm to 100mm: Flanged iron body for 1206 kPa working
pressure, Y pattern 1.2mm stainless steel perforated screen.

- Size 125mm and Larger: Flanged iron body for 1206 kPa working
pressure, basket pattern with 3.2mm stainless steel perforated
screen.

m. Relief Valves

- Bronze body, teflon seat, stainless steel stem and springs, automatic,
direct pressure actuated, capacities ASME certified and labeled .

n. Control Valves
. ~
- 3-way valve with integral magnetic actuator for modulating control of
chilled water. Screwed ends, cast iron valve body, chrome nickel steel
seat/inner rated at 16 bars nominal pressure horizontally mounted
with linear valve characteristics.

o. Balancing Valves

Bronze construction, screwed ends. Calibrated balancing valve


equipped with readout valves to facilitate connection of a differential
pressure meter. Each readout valve shall be fitted with an integral
valve designed to minimize system fluid loss during the monitoring
THIS DRAWING IS NOT process.
TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL Each valve shall have calibrated nameplate to indicate the degree of
CERTIFIEDAND DATED
closure of the precision machine orifice and to be constructed with
integral o-ring seals to prevent leakage around the rotating element.
HA(6/5/2011 )

PlANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 14
REFER TO REFER TO
SPECIFICATIONS \/lAIN SOWfTS A OF 3
JOB ORDER NO. MAIN SOWfTS
33
...'"
a:
w
SAUDI ELECTRICITY COMPANY
0
~
.,
0
:. Maximum operating pressure/temperature: 860 kPa / 121DC.
:t
u

W
f-
IY«
0 0
06
u...o..::;;; ::;;;
z:::>W
f- W
13. Ductwork
0-' eo f-
>- o:
i=~ >-
2: ()W (j) eo
0
f:
Wz
f-W 0
Z IY a. Galvanized Steel Ducts
0(') i= W
0- f-
a:u 8:06 () «
f-W
z(j) Of- ~ ASTM A653 hot dipped galvanized steel sheet, lock forming quality,
'"'" Of- IY«
_z 0
W
(j)W 0..0 -'
Q

OQ, wo.. :!
IY:::>
having G90 zinc coating in conformance with ASTM A90.
IY:::> r
- -' ()
IYo u...«
Ow OIY 0
()() WW
0« oz
W
0 b. Insulated Flexible Ducts
0> OW 0
«r «(') «

0
2:
..; N
...;
Two-ply vinyl film supported by helically wound spring steel wire, fiberglass
REVISIONS
insulation, polyethylene vapor barrier film.

i. Pressure Rating: 2.50 kPa positive and 250 Pa negative.


ii. Maximum Velocity: 2.03 m/sec.
DEPT, .:::E&:.:::DD~--I

PREP. BY:
iii. Temperature Range: -23DC to 71DC

DATE:

14. Ductwork Accessories

a. Air Turning Devices/Extractors

i. Fabricate in accordance with SMACNA HVAC Duct Construction


Standards.

ii. Multi-blade device with blades aligned in short dimension, steel


construction, with individually adjustable blades, mounting straps.

iii. Multi-blade device with radius blades attached to pivoting frame and
bracket, steel construction, with push/pull operator strap with 450
mm long removable key operator.

b. Motorized Volume Damper

i. Multi-Blade Damper: Fabricate of opposed blade pattern with


maximum blade sizes 200 x 1825mm. Assemble center and edge
crimped blades in prime coated or galvanized channel frame with
suitable hardware.

ii. End Bearings: Except in round ductwork 300mm and smaller,


provide end bearings. On multiple blade dampers, provide oil
impregnated nylon or sintered bronze bearings.

iii. Operators: UL listed and labeled spring return electric type suitable
for 220 volts, single phase, 60 Hz. Provide end switches to indicate
damper position. Locate damper operator on exterior of duct and
THIS DRAWING IS NOT
TO BE USED FOR
link to damper operating shaft.
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIEDAND DATED

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 15
REFER TO REFER TO
JOB ORDERNO. SPECIFICATIONS ~AIN SOWITS A OF 3
MAIN SOWITS
33
,.;
SAUDI ELECTRICITY COMPANY
"''"
u

c
t-e
c. Combination Fire and Smoke Dampers
c
:.:
:c
u

W
L Fabricate in accordance with NFPA 90A.
f-
a::«
LLa..""::;:
0 0
z::> W ::;:
W
ii. Provide factory sleeve and collar for each damper.
0-' f- en f-
en

f-a:: >- >-
Z ()w en en
0 Wz z a:: iii. Multiple Blade Dampers: Fabricate with 16 gage (1.5mm)
~ f-W 0
0(9 i= W
0-
a:u g:"" ()
f-
« galvanized steel frame and blades, oil impregnated bronze or
f- W 3;:
zen
'" Of- Of-
a::« 0 stainless sleeve bearings and plated steel axles, stainless steel jamb
'" en_z W
Q a..0 W
-' seals, 3.2 x 13 mm plated steel concealed linkage, stainless steel
O~ W~
a::::>
a::a - -'
LL« ()
=::!
a:: ::J: = closure spring, blade stops and lock, and 13 mm actuator shaft.
Ow o a:: 0
()() wW W
0« 02 0
0> OW 0
«::J:«(9 « iv. Operators: UL listed and labeled spring return electric type suitable
0 ..; ...• ...: for 220 volts, single phase, 60 Hz. Provide end switches to indicate
Z

REVISIONS
damper position. Locate damper operator on exterior of duct and
link to damper operating shaft.

v. Combination fire and smoke damper shall comply with the


DEPT: =E&.c...;DD_-I

requirements of UL 555 and UL 555S. The fire rating shall be 3


PREP. BY:
hours as per NFPA-90A.
DATE:

vi. Fusible Links: UL listed and labeled, UL 33, separate on 71 QCwith


adjustable link straps.

d. Duct Access Doors

i. Fabricate in accordance with SMACNA HVAC Duct Construction


APDlfl1VED
Standards - Metal and Flexible and UMC.

I By,VLhJ ii. Fabrication: Rigid and close fitting of galvanized steel with self
oiling hinges, sealing gaskets and quick fastening locking devices,
If~~2-0# For insulated ductwork, install minimum 25mm thick insulation with
sheet metal cover.

,/~T1Flm
a -

-
Less than 300mm square: Secure with sash locks.

Up to 450mm square: Provide two (2) hinges and two (2) sash
locks.
'BY

DATE:
~~

oS""d1..l)/
- J
- Up to 600 x 1200mm: Three (3) hinges and two (2)
compression latches with outside and inside handles.

- Larger sizes: Provide an additional hinge.

iii. Access doors with sheet metal screw fasteners are not acceptable.

e. Duct Test Holes

THIS DRAWINGIS NOT Drill test holes in accordance with TAB CONTRACTORs requirements:
TO BE USED FOR
CONSTRUCTION OR Cap with neat patches, neoprene plugs, threaded plugs, or threaded or
FOR ORDERING
MATERIALS UNTIL twist on metal caps.
CERTIFIEDANDDATED

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 16
REFER TO REFER TO
JOB ORDER NO. SPECIFICATIONS "'A1NSOWITS A OF 3
MAIN SOWITS
33
".'"..
u
SAUDI ELECTRICITY COMPANY

"~-c
f. Fire Dampers
;",
"
u
i. Fabricate in accordance with NFPA 90A. Fire rating shall be per
W
I--
o::~ O/l TES-P-119.21, Section 3.5.3.
0 0
u..~ ::;;; ::;;;
z=> W W
I-- I--
0-"
f=~
en
>- en
>-
ii. Enclosure: Galvanized Steel, 20 gage
z UW en en
0 wz z
..
;
0::
I--w 0
0(,9
g::0/l
f=
U
0::
W
I--
~ iii. Curtain Type Dampers: Galvanized Steel with interlocking blades.
v I--W 5:
'"t.>
zen 01--
01-- o::~ 0 Provide stainless steel closure springs and latches for closure under
Q _z W
~o
enW
o~ w~ -"
-" air flow conditions. Configure with blades out of air stream except
0::5 o::=> I
- -" u
0::0 u..~ for 250 Pa pressure class ducts up to 300mm in height.
Ow 00:: 0
Uu ww W
O~ oz 0
0> ClW Cl
~I ~(,9 ~ iv. Fusible links: UL 33, separate on 71°C with adjustable link straps
0
z
..; N ..; for combination fire/balancing dampers. UL listed and labeled.
REVISIONS
g. Flexible Duct Connections

i. Fabricate in accordance with SMACNA HVAC Duct Construction


DEPT: E&DD
----I
Standards - Metal and Flexible.
PREP. BY:

OATE: ii. Connector: Fabric crimped into metal edging strip.

- Fabric: UL listed fire retardant neoprene coated woven glass


fiber fabric to NFPA 90A, minimum density 1.0 kg/sq.m. Net
fabric width shall be approximately 75 mm.

iii. Materials: Flame spread/smoke developed rating of 25/50 or less in


accordance with NFPA 255 and UL 723.

h. Manual Volume Control Dampers

i. Fabricate in accordance with SMACNA HVAC Duct Construction


Standards - Metal and Flexible.

ii. Single Blade Dampers: Fabricate for duct sizes up to 150 x 760 mm.

iii. Multi-Blade Damper: Fabricate of opposed blade pattern with


BY:
maximum blade sizes 200 x 1825mm. Assemble center and edge
crimped blades in prime coated or galvanized channel frame with
suitable hardware.

iv. End Bearings: Except in round ductwork 300mm and smaller,


provide end bearings. On multiple blade dampers, provide oil
impregnated nylon or sintered bronze bearings.

v. Quadrants:

Provide locking, indicating quadrant regulators on single and


THIS DRAWING IS NOT multi-blade dampers.
TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING Where rod lengths exceed 750 mm provide regulator at both
MATERIALS UNTIL
CERTIFIEDAND DATED ends.

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 17
REFER TO REFER TO
SPECIFICATIONS IJIAlN SOWITS A OF 3
JOB ORDER NO. MAIN SOWITS
33
,..:
a:
SAUDI ELECTRICITY COMPANY
"'
u

::
c

" i. Back Draft Damper


c
;,
:t
U
i. Fabrication in accordance with SMACNA HVAC Duct Construction
W
I-
0:::<>: ~ Standards - Metal and Flexible.
0 0
LLa... ::;
z=> W ::;
I- W
I-
0-' (f)
>- (f) ii. Channel Frame: Galvanized steel gauge 16, 50mm width x 13mm
i=C2 (f) >-
z Uw (f)
height.
0 Wz Z 0:::
f= I-w 0
~ 0(9 W
a:u
z(f)
g:~ i=
U
I-W
01-
I-
<>:
~ iii. Shafting: 12.7mm dia. round rod, 1 continuous length per blade.
'"'" 01-
_z 0:::<>: 0
(f)W a... 0 W
Q

O~
Wa...
:! -'
0:::::::>
0:::::::>
0:::0 - -' U
LL<>:
:x: iv. Blades: motorized blades made of galvanized steel gauge 26 with
Ow
Uu
00::: 0
wW W sponge foam gasket on edges.
0<>: oz 0
0> OW 0
<>::x: <>:(9 <>:
cS ,.; ... ...: v. Blade Stopper: Made of gauge 18 galvanized steel.
z
REVISIONS vi. Type of Construction Duct mounted.

DEPT: .;..:.E&;.....:OO_-I 15. Air Outletsllnlets


PREP. BY:

a. Ceiling Diffusers
DATE;

i. Type: Square, adjustable pattern, stamped, multi-core to discharge


air in 360 degrees, four-way pattern with sectorizing baffles where
indicated. NC rating based on 35dB maximum.

ii. Fabrication: Aluminum with baked enamel off white finish.

iii. Accessories: Radial opposed blade damper and multi-Iouvered


equalizing grid with damper adjustable from diffuser face.

b. Supply Registers/Grilles

i. Type: Streamlined and individually adjustable blades, 19mm

BY,
/~
a ~\\
\.. ~
ii.
minimum depth, 19mm maximum spacing with spring or other device
to set blades, horizontal face, double deflection. NC rating based
on 35dB maximum.

Fabrication: Steel with gage 20 (0.90mm) minimum frames and


OATE'o.G,J.. 2c IJ gage 22 (0.76mm) minimum blades with factory off-white enamel
prime coat finish.

iii. Damper: Integral, gang operated opposed blade type with


removable key operator, operable from face.

c. Exhaust and Return Registers/Grilles

i. Type: Streamlined blades, 19mm minimum depth, 19 mm maximum


spacing, with spring or other device to set blades, horizontal face.
THIS DRAWING IS NOT
TO BE USED FOR
ii. Fabrication: Steel with gage 20 (0.90mm) minimum frames and
CONSTRUCTION OR
FOR ORDERING gage 22 (0.76mm) minimum blades, aluminum extrusions with
MATERIALS UNTIL
CERTIFIED AND DATED
factory off-white enamel prime coat finish.

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 18
REFER TO REFER TO
SPECIFICATIONS ~AIN SOWITS A OF 3
JOB ORDER NO. MAlNSOWITS
33
,..:
0:
SAUDI ELECTRICITY COMPANY
'"
U

....
C

-c iii. Damper: Integral, gang operated opposed blade type with


0
:.: removable key operator, operable from face.
:I:
u

W
I-
QC<{ O/S d. Sand Trap Louver
00
LLIl.:;: :;:
Z=> WI- W
0--'(/) I-
-<{
I-QC >- en
>-
i. Designed for intake application to separate sand from intake air.
z Ow en en
0 WZ Z QC Test dust distribution efficiency at 80% on 20 to 200 microns and
•..~ I-W
Oc>
0
i=
W
I- 50% on 1 to 70 microns.
0< g:0/S 0 <{
U I-W
Zen 01- s:
'"'"'
Q
01- QC<{
_Z 0
W
enW Il.O --' ii. Aluminum Construction: Frame 2mm thick, blades 4mm thick.
O~ WO- o=!
QC=> QC=> I
---'
QCO LL<{ 0 Provided with self-emptying sand drain holes from the base and
Ow OQC 0
00 WW
O<{ OZ
W
0
aluminum wire bird screen.
0> OW 0
<{I <{C> <{

0
z
..; ... ...: iii. Size: Designed at 1.52 m/s maximum face air velocity.
REVISIONS

16. Instrumentation
DEPT:
--~
E&DD

a. Pressure Gauge
PREp. BY:

DATE: Glacier filled, ASME B40.1, 65mm diameter drawn steel case, phosphor
bronze bourdon tube, rotary brass movement, brass socket, with front
recalibration adjustment, black scale on white background, 1% mid-scale
accuracy, scale calibrated in both psi and kPa.

b. Temperature and Humidity Indicators (Combination)

Wall mount, 300mm diameter dial, for indoor and outdoor service, bi-metal
sensing mechanism protected by weatherproof aluminum case,
temperature range -46 to 54°C relative humidity range 20 to 90%.

c. Thermostat

Low voltage, adjustable to control compressor stages and heating stages


in sequence with delay. Minimum two (2) stages for cooling and two (2)
stages for heating.

d. Humidistat

3-point, control heating or, in conjunction with an impulse relay, floating


step control. Low voltage.

e. Duct Type Thermometer (for Main Supply, Return & Fresh Air Ducted)

100 mm dial face with raised black numbers on silver face, with red
pointer. Scale ranges shall be -5 QCto 85 QC.

17. Ductwork Insulation

THIS DRAWING IS NOT


TO BE USED FOR
a. Materials
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL Flame spread/smoke developed rating of 25/50 or less in accordance with
CERTIFIEDAND DATED
NFPA 255 and UL 723.

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 19
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN SOWITS MAIN SOWITS
33
,.;
••'"
U
SAUDI ELECTRICITY COMPANY
Q

•.
;..
-e
b. ~
Q

='"
u

W
Glass fiber board, rigid for Rectangular Duct , and Roll Type for Spiral
I-
0:::« ~ Duct.
00 :::;;:
u...c.. :::;;:
z::> WI- W
0-' en I-
>- en
z
i=~
()w en >-
en
c. Insulation
0 wz z 0:::
f: I-w 0
e, 0(9 W
i= I-
ii
u
g:~
zen I-W
() «
$: ASTM C612, non-combustible.
01-
'"'"
Q
01-
_z 0:::« 0
c..O W
enw
oc.. wc.. -'
::!
0:::5 0:::::>
:I:
- -' ()
i. Thermal Conductivity: 0.33w/m DCat 24 DCmean temperature.
0:::0 u...«
Ow Do::: 0
()() WW w

0>
oz
OW
0
0 ii. Maximum Service Temperature: 121DC.
«:I: «(9 «
0 ..; ... ..:
z iii. Maximum Moisture Absorption: 0.20% by volume.
REVISIONS

iv. Thickness: 25mm.

DEn, .:::;E&.:::;OO_--I v. Density: 56 kg/m3 for Rectangular Duct


PREP. BY:

vi. Density: 48 kg/m3 for Spiral Duct


DATE:

d. Facing

Factory applied foil reinforced kraft (FRK) vapor barrier.

e. Adhesive

B..

f~~~-~--I
/2
~.• o,:~ Waterproof, fire retardant type
patches and joint sealing tape.
(apply vapor-seal pressure sensitive

oAm"l C-dn 20 11 f. Joint and Protrusion

75mm wide tape shall be used.

18. Vibration Isolators

a. Materials Composed of

i. Restrained spring mounting.

ii. Adjustment or cap screw.

iii. Neoprene vertical limit stops.

iv. Neoprene acoustical cup.

v. Non-skid neoprene friction isolation pad.


THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR b. A minimum clearance of 13mm shall be maintained around restraining
FOR ORDERING
MATERIALS UNTIL bolts and between the housing and the spring so as not to interfere with
CERTIFIEDAND DATED
the spring action.

HA(6/5/20 11)

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 20
REFER TO REFER TO
SPECIFICATIONS ~AIN SOWITS A OF 3
JOB ORDERNO. MAIN SOWITS
33
~ SAUDI ELECTRICITY COMPANY
'"
u

"~
-c
19. Painting I Coating
":.:
:I:
u
a. Refer to TES-H-107.01 and TES-H-107.02 requirements.
W
~ b. For substations located in marine, costal, agricultural, or industrial areas a
cr::« ~
00
u.0- ::;;:
z=> W
::;;:
W
corrosion resistive coating shall be factory or field applied on the unit
0--' I--
C/) I--
-« >-
I--cr::
C/)
>-
casing, condenser coils, evaporator coils, fins, panels, compressors, drain
z Ow C/) C/)
0 wz
I--w 0z cr:: pans, fans, grids, enclosures and pipes.
f:
e, Oc> f= W
0:
u
g:~
zC/) I--W
0
I--
«
5:
'"'" _z
01-- 01--
cr::« 0
Notes:
Q
cnW [1.0 --'
W
00- wO- =!
cr::=>cr::=>
---' 0I
cr::a u.«
Ow
1. The corrosion resistive coating for parts exposed to the direct sun shall be UV
Ocr:: 0
00

WW
OZ
W
0
resistant.
0> OW 0
«I «C> « 2. The corrosion resistive coating shall allow expansion and contraction for fins
0
z
..; N ...; and coils, and doesn't adversely affect heat transmission, rejection and
REVISIONS
reflection criteria in the heat exchanging surfaces.

DEPT: [&00

3.04 EXECUTION (HVAC)


PREP. BY:

DATE:

A. Submittals

1. Submit schematic diagrams indicating mechanical system refrigerant piping


(for split units), air balancing and HVAC control system components. Label
with settings, adjustable range of control and limits. Include written
description of control sequence of operation.

2. Include flow diagrams for each control system, graphically depicting control
logic.

3. Shop drawings indicating components, assembly, dimensions, weights and


loadings, required clearances, location and size of filed connections.

4. Submit product data indicating rated capacities, performance data/curves,


dimensions, weights specialties and accessories, electrical nameplate data
and wiring diagrams.

5. Submit test reports. Indicate pressure tests performed. Include data


section tested, test pressure and leakage rate following SMACNA HVAC Air
Duct Leakage Test Manual.

B. Installation

1. General

a. Install equipment in accordance with TCS-K-100.01, TES-P-119.19


and manufacturer's instructions.

THIS DRAWING IS NOT


TO BE USED FOR
b. Electric lights shall be installed in the mechanical room in front and
CONSTRUCTION OR behind the AHU compartment.
FOR ORDERING
MATERIALS uaru
CERnFIED AND DATED
c. Install AHU and ACCU units on vibration isolation as per TES-P-
119.19.
HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 21
REFER TO REFER TO
SPECIFICATIONS sowrrs A OF 3
JOB ORDER NO. ~AIN MAIN sowrrs
33
~ SAUDI ELECTRICITY COMPANY
'"
u

0
~
..,
0
:.::t d. Provide access around equipment for service, not less than the
u
manufacturer's minimum requirement, TES-K-100.01 and TCS-K-
W
I-
0:::« oI:l 100.01.
00
LLo.. ::;;
z:::> I-W
::;;
W
I-
0-' (f)

1-0::: >- (f)
>-
e. Sleeve duct passing through walls and floors.
z Uw (f) (f)
0 Wz Z 0:::
f: I-W 0
... 0(9 i= W
I- f. The opening of the Fresh air inlet in Mechanical Room shall min. 2.0m
0:u g::oI:l U «
3:
Z(f) I-W above the grade level / sidewalk way level
'"'" 01- 01- 0:::« 0
_Z
(f)W 0..0 W
Q
wo.. -'
OQ:
0::::::>
='
0::::::>
- -' UI
0:::0 LL« 2. Chilled Water System:
Ow 00::: 0
Uu WW W
0« OZ 0
0> OW 0
«I «(9 « a. Packaged Air-Cooled Water Chiller
0 ..; N ..;
z
- Include start-up instructions, operation & maintenance instructions,
REVISIONS
parts lists, recommended spare-parts list (RSPL), controls and
accessories. Include trouble-shooting guide.
OEPT: E&DD
---I
- Provide one (1) complete change of lubricating oil.
PREP. BY:

DATE: - Supply initial charge of refrigerant and oil for each refrigerant circuit.
Replace losses of refrigerant and oil.

b. Chilled Water Type Air Handling Unit (AHU)

- Include start-up instructions, operation and maintenance


instructions, parts lists, recommended spare-parts list (RSPL),
controls and accessories.

- Provide two (2) sets for each unit of fan belts and washable and bag
filters.

- Install in conformance with ARI 430.

c. Chilled Water Pump

- Include start-up instructions, operation and maintenance


instructions, parts lists, recommended spare-parts list (RSPL),and
accessories.

- Provide one (1) set for mechanical seals.

- Decrease from line sized with long radius reducing elbows or


reducers. Support piping adjacent to pump such that no weight is
carried on pump casing. For closed coupled or base mounted
pumps, provide supports under elbows on pump suction and
discharge line sizes 100mm and over.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR - Provide air cock and drain connection on horizontal pump casing.
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
- Provide drains for bases or seals, piped to and discharging into floor
drains.
HA(6f5f2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 22
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN sowrrs MAIN sowrrs
33
,.:
.,'"
U
SAUDI ELECTRICITY COMPANY
..
Q

e,
-e
Q
:. - Provide line sized shut off valve and strainer on pump suction and
'"
u
line sized check valve and balancing valve on pump discharge.
W
I-
o::<t:oI:S
00
LLCL
z:::> W
~ ~ d. Hydronic Piping
I- W
0-' I-
_<t: (I)
1-0:: >-
(I)
>-
Z Ow (I) (I)
- Provide necessary joining fittings. Ensure flanges, union and
..
0
i=
C2
WZ
I-W
Oc>
[oI:S
Z
0
f=:
0
0::
W
I-
<t: coupling for servicing are consistently provided.
U
CJ>
z(l) I-W01- S
01- o::<t: 0
'"
Q _z
(l)W CLO W
O~ WCL -'
::! - Use grooved mechanical coupling and fasteners in accessible
0:::::> 0:::::>:r:
- -' 0
0::0 LL<t: locations.
OW 00:: 0
00 WW W
O<t: OZ 0
0> OW 0
<t::r:<t:C> <t: - Use union, flanges and coupling downstream of valves and at
0
z;
..; N ...; equipment or apparatus connections. Do not use direct welded or
threaded connections to valves, equipment or other apparatus.
REVISIONS

- Use non-conducting dielectric connections whenever jointing


DEPT: E&DD
dissimilar metals.
PREP. BY;
- Provide hangers and supports in accordance with ASME 831.9.
DATE:

- Use gate valves for shut off and to isolate equipment, part of system
or vertical risers.

- Use graduated balancing valves or globe valves for throttling,


bypass or manual flow control services.

- Submit welder' certificate. Provide certificate of compliance from the


COMPANY indicating approval of welders. Also, Weld Procedure
Specification (WPS) shall be submitted for review and approval prior
to any welding work.

- Conform to ASME 831.9 code for installation of piping system.

- Welding materials and procedures as per ASME Code.

- Provide inserts for suspending hangers from reinforced concrete


slabs and sides of reinforced concrete beams.

- Provide hooked rod to concrete reinforcement section for inserts


carrying pipe over 100mm.

- Slope and arrange systems to drain at low points. Use eccentric


reducers to maintain bottom of pipe level.

e. Hydronic Specialties

- Provide air vents at system high points and as required.

THIS DRAWING IS NOT - Provide expansion tank and chemical feeding system on suction
TO BE USED FOR
CONSTRUCTION OR side of the system circulating pumps.
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
- Provide water make-up system.

HA(6/5/20 11 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 23
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ""AIN SOWITS MAIN SOWITS
33
,..:
0:
'"U SAUDI ELECTRICITY COMPANY
0
~
-e - Provide valved drain and hose connection on strainer blow-down
0
connection.
'"u'"
W
I-
0:::«
0 0 ""
LLc..
z:::>
:::::;:
W :::::;:
W
- Remove temporary strainers after cleaning the systems.
I- I-
0-' (f)
>- (f)
i=~ (f) >-
z <.)W (f)
0 Wz
I-W
Z 0::: - Provide relief valves on expansion tanks. Select system relief valve
•..
i= 0(9
0
i=
W
I- capacity so that it is greater than make-up pressure reducing valve
0: g:"" <.) «
3:
u
CJJ
Z(f) I-
01-
W
capacity. Select equipment relief valve capacity to exceed rating of
01- 0:::« 0
'"
Q _Z
(f)W c..O
Oc.. wc..
W
-' connected equipment.
0:::5 0:::::::> I
-'
-
0:::0 LL« -'
<.)
Ow
<.)<.)00::: 0

ww
oz
W
0
3. Refrigerant Piping Specialties
0> ow 0
«I «(9 «

0
z
,.; N ..; a. Provide pipe hangers and supports in accordance with ANSIIASME
831.5.
REVISIONS

b. Use solenoid valve in liquid line of systems operating with single pump
out or pump down compressor control.
DEPT: --,,£&_DD_--1

PREP. BY:
c. Dehydrate and change components such as piping and receivers, seal
DATE: prior to shipment until connected into the system.

d. Utilize flexible connectors at or near compressors where piping


configuration does not absorb vibration.

e. Provide refrigerant suction line with flexible closed-cell insulation tube


with aluminum jacketing.

f. Arrange piping to return oil to compressor. Provide traps and loops in


piping, and provide double risers as required. Slope horizontal piping
0.40% in direction of flow. Flood piping system with nitrogen when
brazing.

g. Follow ASHRAE 15 Procedures and TES-K-100.01 for charging and


purging of systems, and for disposal of refrigerant.

h. Provide replaceable cartridge filter driers, with isolation valves and


valved bypass for liquid line.

i. Install flexible connectors at right angles to axial movement of


compressor, parallel to crankshaft.

j. Provide two (2) refrigeration oil test kits each containing everything
required to conduct one test.

k. Provide two (2) filter - dryer cartridge of each type.

I. Pressure test system with dry Nitrogen to 1470 kPa. Perform final test
at 92 kPa vacuum and 1470 kPa using halide torch or electronic bale
THIS DRAWING IS NOT detector. Test to no bale.
TO BE USED FOR
CONSTRUCTION OR m. Test refrigeration piping system in accordance with ANSI/ASME 831.5
FOR ORDERING
MATERiAlS UNTIL
CERTIFIEDAND DATED

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL REFER TO
24
REFER TO
SPECIFICATIONS IiIAIN SOWITS A OF 3
JOB ORDER NO. MAINSOWITS
33
,.;
Cl!
U'" SAUDI ELECTRICITY COMPANY
C
~
-e 4. Ductwork and Duct Accessories
c
:.:c
u
a. Perform WORK in accordance with SMACNA HVAC Duct Construction
W
~
0::« Standards - Metal and Flexible, NFPA 90A Standards and TCS-K-
0 0 ""
lLn. ::;;
z::> W
::;; 100.01.
0---'(f)
W~ ~
-« >- (f)
~o:: (f) >-
z uw (f)
0 Wz z 0:: b. Fabricate and support in accordance with SMACNA HVAC Duct
•..
i= ~W 0
0(9 i= W
~ Construction Standards - Metal and Flexible.
02
u
[["" o
~W
«
:s:
Z(f) O~
'"'"
Q
O~
_Z 0::«
n.O
0
W
(f)W
09= Wn.
---' c. Provide motorized combination fire and smoke dampers in the main
0::::> =!
0::::>
0::0 lL« U---' I- supply and return duct penetrations through the walls/roof.
Ow 00:: 0
Uu WW W
0« OZ 0
0> OW 0
«I «(9 « d. Provide access doors for inspection and cleaning, before and after
0
z
..; ..• - filters, coils, fans, automatic dampers, fire dampers, combination fire
and smoke dampers, electric duct heater and elsewhere as required.
REVISIONS

e. Provide duct test holes where required for testing and balancing
purposes.
oEPT ;;;;;E&;;:.:oo_--I

PREP. BY:
f. Provide fusible link operated fire dampers in all other duct penetrations
DATE: and opening for louvers and grilles in fire rated walls and partitions.

g. Provide balancing dampers on duct take-off to diffusers, grilles and


registers regardless of whether dampers are specified as part of the
diffuser, grille or register assembly.

5. Air Inlet/Air Outlet

a. Paint ductwork visible behind air outlets and inlets back.

b. For exterior applications, provide vapor barrier jacket. Cover with


aluminum jacket with seams located on bottom side of horizontal
equipment.

c. Test and rate air outlet and inlet performance in accordance with ADC
Equipment Test Code 1062 and ASHRAE 70.

d. Install backdraft dampers on inlet to wall exhausters.

DATE,
o~ b '('191 I
-,=O';';;""';:'--'-..:........t
6. Ductwork Insulation

a. Verify that ductwork has been air leak and lighting tested before
applying insulation materials.

b. Provide ductwork with external insulation with vapor barrier jackets.


Use 25 mm thick insulation for ducts installed inside the building and
50 mm thk. Insulation with aluminum cladding (0.8mm thick) for
outside ducts.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR 7. Vibration Isolation:
FOR ORDERING
MATERIALS UNTIL
CERTIFIEDAND DATED
Provide vibration isolation on motor driven equipment over 0.35kW, plus
connected piping and ductwork.
HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT / MATERIALS AND TECHNICAL 25
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN SOWfTS MAIN SOWfTS
33
""'
0:
U
SAUDI ELECTRICITY COMPANY
Q

~
."
Q
:.
l:
8. Mechanical Identification
u

W
f-
0::« O/l AC units, ductworks, pipes, control panels and major control components
0 0
LL(1. :2
z:::> W :2
W
panels to be identified.
f- f-
0-' (J)
-« >- (J)
f-O:: (J)
<..:>W >-
Z (J)

•.
0
;::
02
Wz
f-W
0(9
[:O/l
z
0
i=
<..:> «
0::
W
f- c. Nameplates: For Outdoor equipments or panels, nameplate shall be an
u f-w
Z(J) Of- 5:
<JJ
of- 0::« 0
engraved Stainless Steel / Aluminum. However, for Indoor, nameplate shall
"'
c _Z (1.0
(J)W W(1. -' W
be plastic.
09:
0:::::>0:::::>=!
I
0::0 - LL«-' <..:>
Ow 00:: 0
<..:><..:>

WW
OZ
W
0
b. Plastic Tags: Laminated three layer plastic with engraved black letters on
0> OW 0
«I «(9 « light contrasting background color. Tag size minimum 40mm diameter.
0 ..; ...• ..;
z;
c. Stencils
REVISIONS

i. Stencils
DEPT, .:::E&:.:..::DD~--I
With clean cut symbols and letters of following size:
PREP. BY:

DATE: - 20 to 30mm Outside Diameter of Insulation or Pipe: 200mm long


color field, 13mm high letters.

- 40 to 50mm Outside Diameter of Insulation or Pipe: 200mm long


color filed, 20mm high letters.

- 65 to 150mm Outside Diameter of Insulation or Pipe: 300mm long


color field, 30mm high letters.

- 200 to 250mm Outside Diameter of Insulation or Pipe: 600mm long


color field, 65mm high letters.

- Over 250mm Outside Diameter of Insulation or Pipe: 800mm long


color field, 90mm high letters.

- Ductwork and Equipment: 65mm high letters.

- Stencil Paint: Semi-gloss enamel, colors conforming to ASME


A13.1.

ii. Color: Conform to ASME A 13.1

iii. Plastic Pipe Markers: Factory fabricated, flexible, semi- rigid plastic,
preformed to fit around pipe or pipe covering, minimum information
indicating flow direction arrow and identification of fluid being
conveyed.

iv. Plastic Tape Pipe Markers: Flexible, vinyl film tape with pressure
sensitive adhesive backing and printed markings.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR v. Underground Plastic Pipe Markers: Bright colored continuously
FOR ORDERING
MATERIALS UNTIL printed plastic ribbon tape, minimum 150mm wide by 4 mil (0.10mm)
CERTIFIED AND DATED
thick, manufactured for direct burial service.

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 26
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN SOWITS MAIN SOWITS
33
~
... SAUDI ELECTRICITY COMPANY
U

t-c
Q

9. Power Ventilator
"'
:t
U

w
I-
IY<C a. Provide power ventilator with sheaves (for belt drive fan) required for
0 ""
0
LLCL ~
w ~ final air balance.
z::> w
0-' I- I-
_<c (/)

I-IY >- (/)


>-
(/)
Z UW
0 Wz
I-W
Z
(/)

IY b. Install backdraft dampers on inlet to wall exhausters.


f: Oc.? 0 W
0- i= I-
0: g:"" U <C
U I-
z(/) 01- W s:
'" 01- IY<C 0
"'"" _z
(/)W CLO
WCL
W
-' 10. Air Cleaning
OQ, :!
IY::> IY::> I
IYO - -'
LL<c U
Ow OIY 0
Uu
O<C
WW
OZ
W
0 Install filter gage static pressure tips upstream and downstream of filters.
0> OW 0
<CI <Cc.? <C Mount filter gages on outside of filter housing or filter plenum, in accessible
cS
z
..; N
...; position. Adjust and level.
REVISIONS

C. Testing, Adjusting and Balancing


DEPT, .:::E&:.:.:DD~--I

PREP. BY:
1. Submit name of Testing, Adjusting and Balancing (TAB) agency for
approval within thirty (30) days after award of CONTRACT. Such agency
DATE: shall be company specializing in Testing, Adjusting and Balancing of
systems with minimum three- (3) years-documented experience. Perform
WORK under supervision of NEBB or any other Certified TAB Supervisor
acceptable to the COMPANY.

2. Total system balance shall be performed in accordance with TCS-K-100.01

3. Prior to commencing WORK, submit draft reports on NEBB form indicating


adjusting, balancing and equipment data required.

4. Submit draft copies of report for review prior to final acceptance of


PROJECT. Provide final copies to COMPANY REPRESENTATIVE and for
inclusion in operating and maintenance manuals.

5. Provide reports in soft cover, letter size, 3-ring binder manuals, complete
with index page and indexing tabs, with cover identification at front and
side. Include set of reduced drawings with air outlets and equipment
identified to correspond with data sheets and indicating thermostat
locations.

6. The WORK shall also include the following tests: Duct Leakage, Sound test,
Vibration Tests and commissioning for fire alarm system.

7. Include detailed procedures, agenda, sample report forms prior to


commencing any test.

8. Upon completion of installation and before the system is energized or


accepted, tests shall be carried out by the CONTRACTOR to demonstrate
that each installation is functioning in accordance with the specifications.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR 9. The CONTRACTOR shall test each circuit for grounds and shorts by means
FOR ORDERING
MATERIALS UNTIL of a megger insulation testing instrument which shall impress a voltage of
CERTIFIED AND DATED
not less than 500 Volts upon the circuit under test. Any circuit showing an
insulation resistance not less than the minimum values given in the NEC
HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 27
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN SOWITS MAIN SOWITS
33
'"<"''".J SAUDI ELECTRICITY COMPANY
Q

l:
-c
shall be investigated and weak points corrected. All circuits under megger
Q
;, insulation test shall be connected to respective final terminals with switches
=
<.J
or breakers in the "OFF" position.
W
I-
0:::«
00 ""
LLD-
W
~ ~ 10. The CONTRACTOR shall correct or replace any current carrying circuit
z=> W
0---' I- I-
i=~
U)
>- U)
>-
which is defective or grounded. The CONTRACTOR shall correct
z C>w U) U)
0 Wz
I-w
Z 0::: deficiencies encountered during the testing.
...
i= 0(.9 0i=
W
I-
c:u g:"" C> «
..,~ zU) I-w
01- ~ 11. Following established procedure, equipment will be energized upon
01- 0:::« 0
Q _z W
D-O ---'
U)W
090 wD- ---' certification that installation is satisfactory. Final operational tests shall
o:::=>o:::=> I
- ---' C>
0:::0 LL« determine that wiring connections are correct.
Ow 00::: 0
C>C> W W w
0« oz 0
0> 0
«I ~~
« 12. Pipe weld joints of chilled water lines (above grade and below grade) shall
0
z
..; N ..; not be covered with insulation until radiographed and/or hydrostatic tested
and found acceptable as per TCS-K-100.01.
REVISIONS

3.05 PLUMBING SYSTEM MATERIAL REQUIREMENTS


OEPT: E&DD
Plumbing system shall be in accordance with TES-P-119.19 requirements, except
PREP. BY:
items listed below:
DATE:

A. Plumbing Piping

Piping shall conform to the requirements of SEC Standard 75-TMSS-1.

B. Plumbing Fixtures

1. Western Water Closet

Vitreous china, floor-mounted, close-coupled, siphon-jet flush action water


closet with trims and complete insulated tank supply assembly per SEC
Standard 75-TMSS-02.

2. Eastern Water Closet

a. Manufacture: White Vitreous china, large standard rectangular shape with


E T1F1Ek
integral foot treads, designed to mount flush with the floor finish provided
BY, ~r with built-in or separate tar-coated or separate P-trap

DATE,OCnh 2..0 " d. Flush Tank: Wall-mounted high level plastic flush tank with side inlet
connection and stop valve, complete with float assembly, concealed
brackets or stainless fixing screws, pull chain, plastic flush pipe and
rubber connector.

3. Lavatory

a. Manufacture: White Vitreous china, counter top lavatory as per SEC


Standard 75-TMSS-2 complete with mounting kit, lavatory faucet with
spout with aerator, metal pop-up drain and handle stops. The fixture shall
THIS DRAWING IS NOT
TO BE USED FOR
be provided with supply assembly with 10mm diam. angle valve, inlet pipe
CONSTRUCTION OR male thread with escutcheon, flexible tube riser with reducing coupling,
FOR ORDERING
MATERiAlS UNTIL chrome finish.
CERTIFIED AND DATED

HA(6/5/20 11)

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 28
REFER TO REFER TO
SPECIFICATIONS I.1AIN SOWITS A OF 3
JOB ORDER NO. MAIN SOWITS
33
,..:
..
0:
W
SAUDI ELECTRICITY COMPANY
0
~
-c
It shall also be furnished with 32mm diam. adjustable P-trap made of
0
chrome plated cast brass with cleanout plug and arm with escutcheon.
'"
X
W

W
Strainer shall be made of copper alloy or corrosion resistant steel.
~
0::«
0 0
00
LLCl.::< ::< b. Trim: Two-handle center-set vandal-proof lavatory faucet made of
z=> w
0-' ~
w
(/) ~ durable cast brass, 1/4-turn washer-less ceramic disc valve cartridges
>-
i=~ (/)
(/)
>-
Z Uw en
0 Wz Z 0:: that are reversible for use with round or lever handles. All brass
~
•.. ~w 0 w
00
g:00 i= ~ components in contact with water shall contain no more than 3% lead
"
u
'"..,
Q
zen
O~
_z
U
!-w
O~
0::« 0
en w Cl. 0 w
«
~ content by weight. Meets ANSI /ASME A 112.18.1 M
o Cl.WCl. -'-'
0::5 o::=>r
0::0 -
Ow
LL« -' U c. Lavatory Counter material shall be Pink or Black colored artificial marble.
00:: 0
Uu ww w
0« oz 0
0> ow 0
«:I: «0 «
0
z
..; ...• ...; 4. Urinal
REVISIONS
a. Manufacture: Vitreous china, wall-hung siphon-jet action urinal per
SEC Standard 75- TMSS-2 without extended shields and complete
with mounting kit.
DEPT, -4
.:::[&::.::0::...0
PREP. BY:
b. Flush Valve: Exposed closet valve, chrome plated, metal oscillating
DATE: non-hold-open handle, 20mm diameter. IPS screw driver angle stop
with protective cap, adjustable tail piece, vacuum breaker flush
connection and spud coupling for 20mm diameter top spud, wall
and spud flanges. Valve shall be designed for a minimum working
pressure of 173 kPa.

5. Eyewash With Auxiliary Body Spray

a. Unit shall meet ANSI Standard and OSHA rules and regulations.

b. Eyewash: Easy cleaning, non-clogging eyewash with stainless steel


receptor, twin soft PVC covered ABS plastic anti surge heads,
stainless steel spray rings, dual automatic pressure compensating
devices, chrome plated brass ball valve easily activated by either
flag and or foot treadle, universal emergency sign, stainless steel
dust cover, supply and waste pipe fittings.

c. Drench Hose: Eye/face and body spray with ABS plastic spray head,
squeeze lever handle valve and 2.4 meters heavy duty yellow rubber
hose.

d. The unit shall be protected against corrosive atmosphere.

e. A 533mm long self-adhesive, barber pole stripe in green and bright


yellow shall be provided to improve visibility.

c. Plumbing Equipment

THIS DRAWING IS NOT


TO BE USED FOR
1. Booster Pump
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL The pump shall be close-coupled and designed for horizontal installation.
CERTIFIEDAND DATED
Pump parts material specifications shall be as follows:

HA(6/5/2011 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL REFER TO
29
REFER TO
JOB ORDER NO. SPECIFICATIONS ~AINsowrrs A MAINsowrrs OF 3
33
"''""
u
SAUDI ELECTRICITY COMPANY

~
-e Casing: Cast Iron
Q
:.: Case Wearing Ring: Bronze
x
u
Impeller: Bronze
W
I-
0:::« o/l Shaft: Stainless Steel
00
u..a..~ ~ Mechanical Seal: Buna N Bellows, Stainless Steel Metal
z=> W W
0""" I- I-

1-0::
(/)
>- (/)
>-
Parts, Ni-Resist Seat and Carbon Washer
z uw (/)
(/)
0 Wz Z 0::
~ I-w
0(9
0 W
0-
Q: g:o/lU
i=
«
l-
Painting/Coating: Refer to TES-H-107.01 and TES-H-107.02
01- :s:
z(/) I-
u W
en
01- 0:::« 0 requirements.
_z
'"
c (/)W
a..0 .....•
W
09: Wa.. =o!
- .....• I
o:::=>
o:::=>
0::0 u..« U The pump shall be designed to deliver water as required by the system,
Ow DO::: 0
Uu

WW
OZ
W
0
including the emergency eyewash and hand spray equipment with an inlet
0> OW 0
«I «(9 « supply pressure of 138 kPa. Pump motor shall have a TEFC enclosure and
0
z;
..; ...• ..; operable at 220 volts/ 1-phase / 60 Hz. , and 3500 rpm.
REVISIONS
The booster system shall be skid mounted and provided with shed when
installed outside the building. The skid shall include control panel, pressure
DEPT: E&DD
tank, pressure gauge and pressure switch.
---i
PREP. BY:
2. Sump Pump
DA.TE:

The pump shall conform to the requirements of a dewatering pump on SEC


Standard 83- TMSS-1. Discharge rate and discharge pipe diameter shall be 4
liters per second (63.41 gpm) and 50 mm respectively. The pump motor
shall operate on a 220V, 60 Hz, single phase power supply, and 3500 rpm.

3. Water Transfer Pump

The pump shall be close-coupled and designed for horizontal installation.


Pump parts material specifications shall be as follows:

Casing: Cast Iron


Case Wearing Ring: Bronze
Impeller: Bronze
Shaft: Stainless Steel
Mechanical Seal: Buna N Bellows, Stainless Steel Metal
Parts, Ni-Resist Seat and Carbon
Washer

The pump shall be designed to deliver 1.58 liters per second (25 Gpm) of
water. Pump motor shall have a TEFC enclosure and operable at 220 volts/
1-phase / 60 Hz. , and 3500 rpm.

The pump shall be provided with shed when installed outside the building. It
shall be manually operated with auto stop to avoid dry running (No water
flow).

4. Transformer Pit Pump

THIS DRAWING IS NOT


TO BE USED FOR
The pump shall be self priming type and designed for horizontal installation.
CONSTRUCTION OR Pump parts material specifications shall be as follows:
FOR ORDERING
MATERIALS UNTil
CERTIFIEDAND DATED
Casing: Ductile Iron
Impeller: Ductile Iron
HA(6/5/20 11)

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 30
REFER TO REFER TO
SPECIFICATIONS ~AIN SOWITS A OF 3
JOB ORDER NO. MAIN SOWITS
33
,.;
''""
u
SAUDI ELECTRICITY COMPANY
0
~
-e Shaft: SAE 4140
0
Mechanical Seal: Silicon/Silicon
'"
'"
u
Painting/Coating: Refer to TES-H-107.01 and TES-H-107.02
W

0:::«
I-
~ requirements.
0 0
u...a.:;; :;;
z=> W
I- W
I-
0-'
t=~
(f)
>- (f) The pump shall have a discharge capacity of 4.0 LPS. Pump motor shall
(f) >-
z <..>w (f)
have a TEFC enclosure, and operable at 220 volts /1-phase/ 60Hz., and
..0: g:~t=
0
1=
wz
I-w
0(9
Z
0
<..>
«
0:::
W
I-
1750 rpm.
u z(f)
01-
3:
I- W

'"'"
Q
01-
_Z 0
0:::« W
0.0
(f) W
00. wo.
od -' The pump shall be provided with galvanized steel sun shade. It shall be
0:::5 o:::=> I
-
0:::0 u...« <..> -' manually operated with auto stop to avoid dry running (No water flow).
Ow 00::: 0
<..><..> wW w
0« oz 0
0> ow 0
«I «(9 «
c
z
..; ..• ,..; 5. Electric Water Heater
REVISIONS
The water heater shall conform to the requirements of SEC Standard 94-
TMSS-1. Minimum capacity shall be 57 liters Minimum (15 gallons Min.).
DEPT: E&OD

PREP. BY:
6. Water Storage Tank
DATE:

Constructed of polyethylene and provided with insulation. The thermal


conductivity of the tank shall be 0.112 W/M-deg K. The inside surface of the
tank shall be clean, smooth, uninterrupted and free of foreign material.
Shape shall be cylindrical-horizontal type. Capacity shall be 1895 liter
(500 gallons).

Tank Nozzle and Manhole: Tank nozzles shall be provided with steel pipe
couplings, threaded steel flanges or standard pipe nipples. Manhole shall
also be provided for cleaning and maintenance. Nozzles shall be for inlet,
outlet, drain, level switch and sight glass.

7. Pump Control Panel

For Pumps control system, refer to 83- TMSS-01 items 5.3.1.a ; except that
for Outdoor Installation, Panel Classification shall be NEMA 4X.

3.06 FIRE DETECTION/ALARM. FIRE PROTECTION SYSTEMS & GASEOUS


PROTECTION SYSTEM

Provide and install a complete fire detection/alarm and fire protection systems
for the complete building which shall include the following major devices:

1. Fire Protective Signaling Panel (FPSP)

Fire protective signaling panel shall be in accordance with the requirements of


90-TMSS-01.
THIS DRAWING IS NOT
TO BE USED FOR 2. Automatic Fire Detectors
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIEDAND DATED
Automatic fire detectors shall be in accordance with the requirements of SES-8-
001, TES-8-106.01 and TES-P-119.21.

HA(6/5/20 11 )

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL REFER TO
31
REFER TO
SPECIFICATIONS IIIAIN SOWITS A OF 3
JOB ORDERNO. MAIN SOWITS
33
,..:
0:
'"
U
SAUDI ELECTRICITY COMPANY
C
~
"
c
x
3. Manual Alarm Stations
'"
u

W
I-
0::« Manual alarm stations shall be in accordance with the requirements of SES-8-
0 0
LLo..
""::;;:
z::::>W
::;;:
W
001, TES-8-106.01 and TES-P-119.21.
I- I-
O~ U)
-« U)
1-0:: >-
U) >-
z Clw U)
0
;:::
Wz
I-W
z 0:: 4. Audible and Visual Alarm Devices
... 0(9
0
i=
W
I-
02 ["" Cl «
u I-W :s:
'"Q
l.>
zU)
01-
_z
OI-
0::« 0 Audible and visual alarm devices shall be in accordance with the requirements of
0..0 W
U)W wo.. ~ SES-8-001, TES-8-106.01 and TES-P-119.21.
O~ 0::::::> ~
0::::::>
-
0::0 LL«
I
Cl ~
Ow 00:: 0
Cl Cl ww w
0« 02 0
0> ow 0
«I «(9 « 5. Data Printer
0 ..; N ..:
z
REVISIONS
Data printer shall be in accordance with the requirements of TES-P-119.21.

DEPT, =E&::::DD~-I
6. Fire Fighting Equipment
PREP. BY:
Firefighting equipment shall be provided in accordance with the requirements
DATE: outlined in 90-TMSS-3, TES-P-119.21 and hereunder:

a. Workshop and Record Room - 20 Ibs., C02 type Portable Fire Extinguisher.

b. Control Room, Communication Room, 13.8kV Switchgear Room and GIS


room - 20 Ibs., C02 type Portable Fire Extinguisher.

c. Cable basement, 8attery Room, HVAC units area and Station Service
Transformer area - 17 Ibs., Class A8C (Multi purpose dry chemical)
Cartridge Operated type Portable Fire Extinguisher. For 8attery Room the
portable fire extinguishers to be located outside beside the room door and
shall be provided with protective cover.
/

d. At each Power Transformers - 125 Ibs capacity, steel dry chemical type,
class A8C (Multi purpose dry chemical), External cartridge operated.

7. Gaseous Fire Protection System FK-5-1-12

a. Design, provide and install automatic gaseous fire protection system for the
protected area as per Scope of work in accordance with TES-8-106.06
and NFPA 2001 Standard.

b. Design Requirements are as follows:

i. Provide adequate amount of extinguishing agent based on the


minimum design concentration of 4.2% for the protected area.

ii. Locate extinguishing and back-up supply inside the Tank Room which
THIS DRAWING IS NOT
TO BE USED FOR
shall be located inside the Control Room. (if applicable).
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL iv. Interface gaseous fire protection system with building fire alarm and
CERTIFIED AND DATED
detection system, fire/smoke dampers, door holders and HVAC
system.
HA(6/5/20 11)

PLANT NO. INDEX DOCUMENT NO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL 32
REFER TO REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN SOWITS MAIN SOWITS
33
..."
a:
U
SAUDI ELECTRICITY COMPANY
"t.,
":t
'"
U

W
8. Equipment Warning Signs
o::<{
~
0 ""
0
u...D-
W
~ ~ Equipment warning signs shall be provided in accordance with the requirements
z=>
0-' ~ W
~
-<{ en
~o:: >-
en
>-
of TES-P-119.21.
z UW en en
0 wz z 0::
f: ~w 0 ui
e,
0:
0(') i=
-c ~ 9. CONTRACTOR shall provide a programming kit (Iaptop accessories) and other
V
["" ~wU
3:
'"'"
zen
o~
_z
o~
o::<{ 0 related items, along with two (2) sets of programming manuals, programming
Q 0-0 w
enw
O~ WO- :! -' software, alarm system down load programming for computerized/addressable
o::=> o::=> I
0::0 -u...<{U -' fire alarm system.
Ow 00:: 0
Uu WW W
O<{ OZ 0
0> OW 0
<{I <{(') <{ 10. CONTRACTOR shall provide an auto dialer telephone as per TES-P-119.21.
0
z M ..• .;

REVISIONS
11. Fire Alarm system shall be integrated with SAS.

DEPT: [&OD
----f
PREP. BY:

DATE:
**** END OF SECTION III ****

THIS DRAWING IS NOT


TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTil
CERTIFIEDAND DATED

HA{6/5/20 11)

PLANT NO. INDEX DOCUMENTNO. PAGE NO. REV.


MECHANICAL DESIGN CRITERIA,
EQUIPMENT I MATERIALS AND TECHNICAL REFER TO
33
REFER TO
SPECIFICATIONS A OF 3
JOB ORDER NO. ~AIN SOWITS MAIN SOWITS
33