Definitions Of Terms:
Code References:
EN 02 - 2004
BS EN 1998-1:2004 (E)
General Data
Column No. : C1,C28
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 213
Critical Analysis Load : 218
Combination
[117] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +0.9 (LOAD 4: WL+X) +1.5
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 199.07 kN
Mux(top joint) = 271.34 kNm
Muy(top joint) = -141.72 kNm
Vux(top joint) = -94.51 kN
Vuy(top joint) = -180.94 kN
Ned(bottom joint) = 199.07 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -94.51 kN
Vuy(bottom joint) = -180.94 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 218
Combination
[117] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+0.9 (LOAD 4: WL+X) +1.5 (LOAD
12: TEL1)
Design shear force, Vuy = -180.9414 kN
Pu = 199.07
Design shear stress ,vEd = 1.1749 N/mm2
VRD,c = 159.59 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 1.1375
Along B
Critical Analysis Load : 218
Combination
[117] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+0.9 (LOAD 4: WL+X) +1.5 (LOAD
12: TEL1)
Design shear force, Vux = -94.508 kN
Pu = 199.07
Design shear stress ,vEd = 0.6518 N/mm2
VRD,c = 161.9785 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 290 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8305
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 1.1375
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C1,C28
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3650 mm
Clear Floor Height @ D,loD = 3650 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 212
Critical Analysis Load : 168
Combination
[67] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 6: WL+Z) +1.5
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 37.29 kN
Mux(top joint) = -13.11 kNm
Muy(top joint) = -22.56 kNm
Vux(top joint) = -15.93 kN
Vuy(top joint) = 32.02 kN
Ned(bottom joint) = 37.29 kN
Mux (bottom joint) = 119.72 kNm
Muy (bottom joint) = 43.55 kNm
Vux (bottom joint) = -15.93 kN
Vuy(bottom joint) = 32.02 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 168
Combination
[67] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 6: WL+Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = 32.0158 kN
Pu = 37.29
Design shear stress ,vEd = 0.207 N/mm2
VRD,c = 104.0303 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0081
k1 0.15
σcp = NEd / (B x D)
= 0.2131
Along B
Critical Analysis Load : 168
Combination
[67] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 6: WL+Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = -15.934 kN
Pu = 37.29
Design shear stress ,vEd = 0.1091 N/mm2
VRD,c = 108.8321 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0086
k1 = 0.15
σcp = NEd / (B x D)
= 0.2131
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
Provided spacing = 225 mm
General Data
Column No. : C2,C29
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1500 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 199
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 5: WL-X) +1.5
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 91.97 kN
Mux(top joint) = -19.34 kNm
Muy(top joint) = 193.27 kNm
Vux(top joint) = -128.88 kN
Vuy(top joint) = -12.9 kN
Ned(bottom joint) = 91.97 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -128.88 kN
Vuy(bottom joint) = -12.9 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3:
Critical Load Combination =
CL) +1.5 (LOAD 2: LL) +0.9
(LOAD 5: WL-X) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = -12.8999 kN
Pu = 91.97
Design shear stress ,vEd = 0.0838 N/mm2
VRD,c = 145.4537 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 0.5256
Along B
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 5: WL-X) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = -128.8809 kN
Pu = 91.97
Design shear stress ,vEd = 0.8888 N/mm2
VRD,c = 148.6683 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 290 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8305
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.5256
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C2,C29
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3650 mm
Clear Floor Height @ D,loD = 4150 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 198
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2 (LOAD 3: CL)
Load Combination = +0.6 (LOAD 2: LL) +(LOAD 9: LOAD CASE 9)
+1.2 (LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 73.95 kN
Mux(top joint) = 2.87 kNm
Muy(top joint) = 57.46 kNm
Vux(top joint) = -22.29 kN
Vuy(top joint) = 0.31 kN
Ned(bottom joint) = 73.95 kN
Mux (bottom joint) = 1.59 kNm
Muy (bottom joint) = -35.02 kNm
Vux (bottom joint) = -22.29 kN
Vuy(bottom joint) = 0.31 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Design Of Shear
Along D
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 9: LOAD CASE 9) +1.2
(LOAD 12: TEL1)
Design shear force, Vuy = 0.3082 kN
Pu = 73.95
Design shear stress ,vEd = 0.002 N/mm2
VRD,c = 121.0954 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.4226
Along B
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 9: LOAD CASE 9) +1.2
(LOAD 12: TEL1)
Design shear force, Vux = -22.2897 kN
Pu = 73.95
Design shear stress ,vEd = 0.1516 N/mm2
VRD,c = 126.372 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.4226
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C3,C30
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 450 mm
Column D = 700 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 28
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 5: WL-X) +1.5
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 492.77 kN
Mux(top joint) = 438.39 kNm
Muy(top joint) = 19.41 kNm
Vux(top joint) = 12.94 kN
Vuy(top joint) = -292.33 kN
Ned(bottom joint) = 503.91 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 12.94 kN
Vuy(bottom joint) = -292.33 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 5: WL-X) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = -292.3348 kN
Pu = 492.77
Design shear stress ,vEd = 1.0119 N/mm2
VRD,c = 235.4997 kN
As tension = 2161.44 sqmm
CRdc = 0.18/γc
= 0.12
deff = 642 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.5581
ρ1 = Asmain / (b x deff)
<> = 0.0075
k1 0.15
σcp = NEd / (B x D)
= 1.5643
Along B
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 5: WL-X) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = 12.9439 kN
Pu = 492.77
Design shear stress ,vEd = 0.0472 N/mm2
VRD,c = 242.6764 kN
As tension = 2161.44 sqmm
CRdc = 0.18/γc
= 0.12
beff = 392 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.7143
ρ1 = Asmain / (d x beff)
<> = 0.0079
k1 = 0.15
σcp = NEd / (B x D)
= 1.5643
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 450 mm
Max. 400 mm = 300 mm
Provided spacing = 225 mm
General Data
Column No. : C3,C30
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 450 mm
Column D = 700 mm
Clear Floor Height @ B,loB = 3650 mm
Clear Floor Height @ D,loD = 3650 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 2
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 258.21 kN
Mux(top joint) = 60.09 kNm
Muy(top joint) = 200.77 kNm
Vux(top joint) = 88.88 kN
Vuy(top joint) = 8.61 kN
Ned(bottom joint) = 292.11 kN
Mux (bottom joint) = 95.82 kNm
Muy (bottom joint) = -167.99 kNm
Vux (bottom joint) = 88.88 kN
Vuy(bottom joint) = 8.61 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Eccentricity ,(ei) (along both the
= 9.13 mm
directions)
MgeoD = 2.36 kNm
MgeoB = 2.36 kNm
Slenderness Check
Along D
slenderness ratio (λD) = 18.04 mm
Permissible limits (λDlim) = 57.81 mm
hence, Column is not slender
Along B
slenderness ratio (λB) = 28.06 mm
Permissible limits (λBlim) = 57.81 mm
hence, Column is not slender
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 8.6124 kN
Pu = 258.21
Design shear stress ,vEd = 0.0298 N/mm2
VRD,c = 183.4355 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
deff = 642 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.5581
ρ1 = Asmain / (b x deff)
<> = 0.0051
k1 0.15
σcp = NEd / (B x D)
= 0.8197
Along B
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 88.8809 kN
Pu = 258.21
Design shear stress ,vEd = 0.3239 N/mm2
VRD,c = 190.983 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
beff = 392 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.7143
ρ1 = Asmain / (d x beff)
<> = 0.0054
k1 = 0.15
σcp = NEd / (B x D)
= 0.8197
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 450 mm
Max. 400 mm = 300 mm
General Data
Column No. : C3,C30
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 450 mm
Column D = 700 mm
Clear Floor Height @ B,loB = 3050 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 30
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Bottom Joint
Ned(top joint) = 52.51 kN
Mux(top joint) = 6.75 kNm
Muy(top joint) = -24.66 kNm
Vux(top joint) = -31.05 kN
Vuy(top joint) = -4.67 kN
Ned(bottom joint) = 86.59 kN
Mux (bottom joint) = -9.11 kNm
Muy (bottom joint) = 80.88 kNm
Vux (bottom joint) = -31.05 kN
Vuy(bottom joint) = -4.67 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = -4.6662 kN
Pu = 52.51
Design shear stress ,vEd = 0.0161 N/mm2
VRD,c = 142.5953 kN
As tension = 1131 sqmm
CRdc = 0.18/γc
= 0.12
deff = 644 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.5573
ρ1 = Asmain / (b x deff)
<> = 0.0039
k1 0.15
σcp = NEd / (B x D)
= 0.1667
Along B
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -31.0485 kN
Pu = 52.51
Design shear stress ,vEd = 0.1126 N/mm2
VRD,c = 150.9006 kN
As tension = 1131 sqmm
CRdc = 0.18/γc
= 0.12
beff = 394 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.7125
ρ1 = Asmain / (d x beff)
<> = 0.0041
k1 = 0.15
σcp = NEd / (B x D)
= 0.1667
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 450 mm
Max. 400 mm = 300 mm
General Data
Column No. : C4
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1500 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 4
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 5: WL-X) +1.5
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 282.67 kN
Mux(top joint) = 177.02 kNm
Muy(top joint) = 14.39 kNm
Vux(top joint) = 9.6 kN
Vuy(top joint) = -118.05 kN
Ned(bottom joint) = 288.86 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 9.6 kN
Vuy(bottom joint) = -118.05 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 5: WL-X) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = -118.047 kN
Pu = 282.67
Design shear stress ,vEd = 0.7631 N/mm2
VRD,c = 136.5675 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0081
k1 0.15
σcp = NEd / (B x D)
= 1.6153
Shear check No Shear Reinforcement Required
Since VRD,C > Vuy
Along B
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 5: WL-X) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = 9.5987 kN
Pu = 282.67
Design shear stress ,vEd = 0.0657 N/mm2
VRD,c = 139.5395 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0086
k1 = 0.15
σcp = NEd / (B x D)
= 1.6153
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C4
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 4150 mm
Clear Floor Height @ D,loD = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 5
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2 (LOAD 3: CL)
Load Combination = +0.6 (LOAD 2: LL) +(LOAD 9: LOAD CASE 9)
+1.2 (LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 192.95 kN
Mux(top joint) = 86.86 kNm
Muy(top joint) = 2.09 kNm
Vux(top joint) = 0.86 kN
Vuy(top joint) = -36.19 kN
Ned(bottom joint) = 213.5 kN
Mux (bottom joint) = -63.3 kNm
Muy (bottom joint) = -1.5 kNm
Vux (bottom joint) = 0.86 kN
Vuy(bottom joint) = -36.19 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 9: LOAD CASE 9) +1.2
(LOAD 12: TEL1)
Design shear force, Vuy = -36.1911 kN
Pu = 192.95
Design shear stress ,vEd = 0.2329 N/mm2
VRD,c = 136.9463 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 1.1026
Along B
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 9: LOAD CASE 9) +1.2
(LOAD 12: TEL1)
Design shear force, Vux = 0.8643 kN
Pu = 192.95
Design shear stress ,vEd = 0.0059 N/mm2
VRD,c = 141.366 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 1.1026
General Data
Column No. : C4
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 6
Critical Analysis Load : 202
Combination
[101] : 1.2 (LOAD 1: DL) +1.2 (LOAD 3: CL)
Load Combination = +0.6 (LOAD 2: LL) +(LOAD 8: LOAD CASE 8)
+1.2 (LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 50.49 kN
Mux(top joint) = -31.48 kNm
Muy(top joint) = 3.48 kNm
Vux(top joint) = 1.01 kN
Vuy(top joint) = 19.31 kN
Ned(bottom joint) = 67.32 kN
Mux (bottom joint) = 34.15 kNm
Muy (bottom joint) = 0.04 kNm
Vux (bottom joint) = 1.01 kN
Vuy(bottom joint) = 19.31 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 202
Combination
[101] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 8: LOAD CASE 8) +1.2
(LOAD 12: TEL1)
Design shear force, Vuy = 19.3087 kN
Pu = 50.49
Design shear stress ,vEd = 0.1243 N/mm2
VRD,c = 117.9697 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.2885
Along B
Critical Analysis Load : 202
Combination
[101] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 8: LOAD CASE 8) +1.2
(LOAD 12: TEL1)
Design shear force, Vux = 1.0122 kN
Pu = 50.49
Design shear stress ,vEd = 0.0069 N/mm2
VRD,c = 123.4152 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.2885
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C5
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 7
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2 (LOAD 3: CL)
Load Combination = +0.6 (LOAD 2: LL) +(LOAD 9: LOAD CASE 9)
+1.2 (LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 452.28 kN
Mux(top joint) = 107.9 kNm
Muy(top joint) = 6.81 kNm
Vux(top joint) = 4.54 kN
Vuy(top joint) = -71.95 kN
Ned(bottom joint) = 459.7 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 4.54 kN
Vuy(bottom joint) = -71.95 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 9: LOAD CASE 9) +1.2
(LOAD 12: TEL1)
Design shear force, Vuy = -71.9532 kN
Pu = 452.28
Design shear stress ,vEd = 0.463 N/mm2
VRD,c = 180.0785 kN
As tension = 1131 sqmm
CRdc = 0.18/γc
= 0.15
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0073
k1 0.15
σcp = NEd / (B x D)
= 2.5845
Along B
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 9: LOAD CASE 9) +1.2
(LOAD 12: TEL1)
Design shear force, Vux = 4.5428 kN
Pu = 452.28
Design shear stress ,vEd = 0.0309 N/mm2
VRD,c = 183.0796 kN
As tension = 1131 sqmm
CRdc = 0.18/γc
= 0.15
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0077
k1 = 0.15
σcp = NEd / (B x D)
= 2.5845
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C5
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 8
Critical Analysis Load : 232
Combination
[131] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 228.61 kN
Mux(top joint) = 0.24 kNm
Muy(top joint) = 137.96 kNm
Vux(top joint) = 44.06 kN
Vuy(top joint) = 0.96 kN
Ned(bottom joint) = 242.22 kN
Mux (bottom joint) = 3.11 kNm
Muy (bottom joint) = 5.82 kNm
Vux (bottom joint) = 44.06 kN
Vuy(bottom joint) = 0.96 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 232
Combination
[131] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 0.9569 kN
Pu = 228.61
Design shear stress ,vEd = 0.0062 N/mm2
VRD,c = 146.2037 kN
As tension = 2010.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.013
k1 0.15
σcp = NEd / (B x D)
= 1.3063
Along B
Critical Analysis Load : 232
Combination
[131] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 44.0593 kN
Pu = 228.61
Design shear stress ,vEd = 0.3018 N/mm2
VRD,c = 150.4404 kN
As tension = 2010.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0138
k1 = 0.15
σcp = NEd / (B x D)
= 1.3063
General Data
Column No. : C5
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1150 mm
Clear Floor Height @ D,loD = 650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 163
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 13: TEL2)
Critical Location = Bottom Joint
Ned(top joint) = 182.03 kN
Mux(top joint) = 2.08 kNm
Muy(top joint) = 61.27 kNm
Vux(top joint) = -84.51 kN
Vuy(top joint) = -30.92 kN
Ned(bottom joint) = 187.25 kN
Mux (bottom joint) = -33.47 kNm
Muy (bottom joint) = 158.43 kNm
Vux (bottom joint) = -84.51 kN
Vuy(bottom joint) = -30.92 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = -30.919 kN
Pu = 182.03
Design shear stress ,vEd = 0.1999 N/mm2
VRD,c = 140.028 kN
As tension = 2010.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.013
k1 0.15
σcp = NEd / (B x D)
= 1.0402
Along B
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -84.5086 kN
Pu = 182.03
Design shear stress ,vEd = 0.5788 N/mm2
VRD,c = 144.612 kN
As tension = 2010.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0138
k1 = 0.15
σcp = NEd / (B x D)
= 1.0402
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 320 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C5
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 9
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 13: TEL2)
Critical Location = Bottom Joint
Ned(top joint) = 44.4 kN
Mux(top joint) = -2.16 kNm
Muy(top joint) = -17.44 kNm
Vux(top joint) = -26.97 kN
Vuy(top joint) = 1.84 kN
Ned(bottom joint) = 59.83 kN
Mux (bottom joint) = 4.08 kNm
Muy (bottom joint) = 74.22 kNm
Vux (bottom joint) = -26.97 kN
Vuy(bottom joint) = 1.84 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 1.8353 kN
Pu = 44.4
Design shear stress ,vEd = 0.0118 N/mm2
VRD,c = 94.9101 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.2537
Along B
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -26.9658 kN
Pu = 44.4
Design shear stress ,vEd = 0.1834 N/mm2
VRD,c = 99.2377 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.2537
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C6
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 10
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 507.5 kN
Mux(top joint) = 10.16 kNm
Muy(top joint) = 73.16 kNm
Vux(top joint) = 48.78 kN
Vuy(top joint) = -6.77 kN
Ned(bottom joint) = 514.31 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 48.78 kN
Vuy(bottom joint) = -6.77 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -6.7731 kN
Pu = 507.5
Design shear stress ,vEd = 0.0436 N/mm2
VRD,c = 163.4674 kN
As tension = 1131 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0073
k1 0.15
σcp = NEd / (B x D)
= 2.9
Along B
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 48.7835 kN
Pu = 507.5
Design shear stress ,vEd = 0.3319 N/mm2
VRD,c = 164.8194 kN
As tension = 1131 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0077
k1 = 0.15
σcp = NEd / (B x D)
= 2.9
General Data
Column No. : C6
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 11
Critical Analysis Load : 254
Combination
[153] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 4: WL+X) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 248.73 kN
Mux(top joint) = -16.83 kNm
Muy(top joint) = -179.71 kNm
Vux(top joint) = -81.24 kN
Vuy(top joint) = 9.4 kN
Ned(bottom joint) = 262.35 kN
Mux (bottom joint) = 11.35 kNm
Muy (bottom joint) = 63.94 kNm
Vux (bottom joint) = -81.24 kN
Vuy(bottom joint) = 9.4 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 254
Combination
[153] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 9.3964 kN
Pu = 248.73
Design shear stress ,vEd = 0.061 N/mm2
VRD,c = 156.5729 kN
As tension = 2463 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.016
k1 0.15
σcp = NEd / (B x D)
= 1.4213
Along B
Critical Analysis Load : 254
Combination
[153] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -81.2354 kN
Pu = 248.73
Design shear stress ,vEd = 0.5602 N/mm2
VRD,c = 160.8792 kN
As tension = 2463 sqmm
CRdc = 0.18/γc
= 0.12
beff = 290 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8305
ρ1 = Asmain / (d x beff)
<> = 0.017
k1 = 0.15
σcp = NEd / (B x D)
= 1.4213
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 320 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C6
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1150 mm
Clear Floor Height @ D,loD = 650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 164
Critical Analysis Load : 226
Combination
[125] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 4: WL+X) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 180.12 kN
Mux(top joint) = 3.69 kNm
Muy(top joint) = -77.15 kNm
Vux(top joint) = 134.17 kN
Vuy(top joint) = 13.2 kN
Ned(bottom joint) = 185.33 kN
Mux (bottom joint) = 18.87 kNm
Muy (bottom joint) = -231.41 kNm
Vux (bottom joint) = 134.17 kN
Vuy(bottom joint) = 13.2 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 226
Combination
[125] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 13.2039 kN
Pu = 180.12
Design shear stress ,vEd = 0.0857 N/mm2
VRD,c = 157.0883 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 1.0292
Along B
Critical Analysis Load : 226
Combination
[125] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 134.1715 kN
Pu = 180.12
Design shear stress ,vEd = 0.9253 N/mm2
VRD,c = 159.6229 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 290 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8305
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 1.0292
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C6
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 12
Critical Analysis Load : 226
Combination
[125] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 4: WL+X) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 44.52 kN
Mux(top joint) = -1.21 kNm
Muy(top joint) = 30.54 kNm
Vux(top joint) = 39.18 kN
Vuy(top joint) = 1.08 kN
Ned(bottom joint) = 59.94 kN
Mux (bottom joint) = 2.46 kNm
Muy (bottom joint) = -102.63 kNm
Vux (bottom joint) = 39.18 kN
Vuy(bottom joint) = 1.08 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 226
Combination
[125] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 1.0799 kN
Pu = 44.52
Design shear stress ,vEd = 0.007 N/mm2
VRD,c = 110.6086 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0096
k1 0.15
σcp = NEd / (B x D)
= 0.2544
Along B
Critical Analysis Load : 226
Combination
[125] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 39.1765 kN
Pu = 44.52
Design shear stress ,vEd = 0.2683 N/mm2
VRD,c = 115.6447 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0102
k1 = 0.15
σcp = NEd / (B x D)
= 0.2544
General Data
Column No. : C7,C8,C32,C34,C35
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1500 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 5
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 16
Critical Analysis Load : 202
Combination
[101] : 1.2 (LOAD 1: DL) +1.2 (LOAD 3: CL)
Load Combination = +0.6 (LOAD 2: LL) +(LOAD 8: LOAD CASE 8)
+1.2 (LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 363.27 kN
Mux(top joint) = -167.17 kNm
Muy(top joint) = 1.11 kNm
Vux(top joint) = 0.74 kN
Vuy(top joint) = 111.47 kN
Ned(bottom joint) = 370.69 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 0.74 kN
Vuy(bottom joint) = 111.47 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 202
Combination
[101] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 8: LOAD CASE 8) +1.2
(LOAD 12: TEL1)
Design shear force, Vuy = 111.4733 kN
Pu = 363.27
Design shear stress ,vEd = 0.7173 N/mm2
VRD,c = 159.632 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 2.0758
Along B
Critical Analysis Load : 202
Combination
[101] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 8: LOAD CASE 8) +1.2
(LOAD 12: TEL1)
Design shear force, Vux = 0.743 kN
Pu = 363.27
Design shear stress ,vEd = 0.0051 N/mm2
VRD,c = 162.8255 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 2.0758
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C7,C8,C32,C34,C35
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 4150 mm
Clear Floor Height @ D,loD = 3650 mm
No Of Floors = 1
No Of Columns In Group = 5
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 44
Critical Analysis Load : 202
Combination
[101] : 1.2 (LOAD 1: DL) +1.2 (LOAD 3: CL)
Load Combination = +0.6 (LOAD 2: LL) +(LOAD 8: LOAD CASE 8)
+1.2 (LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 200.42 kN
Mux(top joint) = -75.39 kNm
Muy(top joint) = -2.35 kNm
Vux(top joint) = -0.4 kN
Vuy(top joint) = 31.02 kN
Ned(bottom joint) = 220.96 kN
Mux (bottom joint) = 53.3 kNm
Muy (bottom joint) = -0.7 kNm
Vux (bottom joint) = -0.4 kN
Vuy(bottom joint) = 31.02 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 202
Combination
[101] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 8: LOAD CASE 8) +1.2
(LOAD 12: TEL1)
Design shear force, Vuy = 31.0181 kN
Pu = 200.42
Design shear stress ,vEd = 0.1996 N/mm2
VRD,c = 137.9402 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 1.1452
Along B
Critical Analysis Load : 202
Combination
[101] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 8: LOAD CASE 8) +1.2
(LOAD 12: TEL1)
Design shear force, Vux = -0.3975 kN
Pu = 200.42
Design shear stress ,vEd = 0.0027 N/mm2
VRD,c = 142.3062 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 1.1452
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C7,C8,C32,C34,C35
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 5
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 45
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2 (LOAD 3: CL)
Load Combination = +0.6 (LOAD 2: LL) +(LOAD 9: LOAD CASE 9)
+1.2 (LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 47.86 kN
Mux(top joint) = 39.7 kNm
Muy(top joint) = 0.46 kNm
Vux(top joint) = 0.13 kN
Vuy(top joint) = -26.63 kN
Ned(bottom joint) = 64.69 kN
Mux (bottom joint) = -50.8 kNm
Muy (bottom joint) = 0.01 kNm
Vux (bottom joint) = 0.13 kN
Vuy(bottom joint) = -26.63 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 9: LOAD CASE 9) +1.2
(LOAD 12: TEL1)
Design shear force, Vuy = -26.6253 kN
Pu = 47.86
Design shear stress ,vEd = 0.1713 N/mm2
VRD,c = 117.6193 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.2735
Along B
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 9: LOAD CASE 9) +1.2
(LOAD 12: TEL1)
Design shear force, Vux = 0.1322 kN
Pu = 47.86
Design shear stress ,vEd = 0.0009 N/mm2
VRD,c = 123.0838 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.2735
General Data
Column No. : C9
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 19
Critical Analysis Load : 168
Combination
[67] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 6: WL+Z) +1.5
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 272.89 kN
Mux(top joint) = -220.91 kNm
Muy(top joint) = -30.01 kNm
Vux(top joint) = -20.01 kN
Vuy(top joint) = 147.31 kN
Ned(bottom joint) = 279.08 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -20.01 kN
Vuy(bottom joint) = 147.31 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 168
Combination
[67] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 6: WL+Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = 147.3139 kN
Pu = 272.89
Design shear stress ,vEd = 0.9523 N/mm2
VRD,c = 152.0756 kN
As tension = 2010.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.013
k1 0.15
σcp = NEd / (B x D)
= 1.5594
Along B
Critical Analysis Load : 168
Combination
[67] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 6: WL+Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = -20.0141 kN
Pu = 272.89
Design shear stress ,vEd = 0.1371 N/mm2
VRD,c = 155.9821 kN
As tension = 2010.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0138
k1 = 0.15
σcp = NEd / (B x D)
= 1.5594
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 320 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C9
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 3000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 20
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 201.97 kN
Mux(top joint) = 8.22 kNm
Muy(top joint) = -230.76 kNm
Vux(top joint) = -102.71 kN
Vuy(top joint) = -19.6 kN
Ned(bottom joint) = 215.58 kN
Mux (bottom joint) = -50.56 kNm
Muy (bottom joint) = 77.3 kNm
Vux (bottom joint) = -102.71 kN
Vuy(bottom joint) = -19.6 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -19.6008 kN
Pu = 201.97
Design shear stress ,vEd = 0.1273 N/mm2
VRD,c = 159.9734 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 1.1541
Along B
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -102.7129 kN
Pu = 201.97
Design shear stress ,vEd = 0.7084 N/mm2
VRD,c = 162.3394 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 290 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8305
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 1.1541
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C9
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1150 mm
Clear Floor Height @ D,loD = 650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 165
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 180.46 kN
Mux(top joint) = 32.14 kNm
Muy(top joint) = -60.04 kNm
Vux(top joint) = 181.47 kN
Vuy(top joint) = -20.04 kN
Ned(bottom joint) = 185.68 kN
Mux (bottom joint) = 9.1 kNm
Muy (bottom joint) = -268.67 kNm
Vux (bottom joint) = 181.47 kN
Vuy(bottom joint) = -20.04 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -20.0358 kN
Pu = 180.46
Design shear stress ,vEd = 0.1308 N/mm2
VRD,c = 156.3935 kN
As tension = 3848.44 sqmm
CRdc = 0.18/γc
= 0.12
deff = 438 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6761
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 1.0312
Along B
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 181.4672 kN
Pu = 180.46
Design shear stress ,vEd = 1.2624 N/mm2
VRD,c = 158.5573 kN
As tension = 3848.44 sqmm
CRdc = 0.18/γc
= 0.12
beff = 288 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8341
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 1.0312
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C9
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 21
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 44.59 kN
Mux(top joint) = 23.34 kNm
Muy(top joint) = 46.87 kNm
Vux(top joint) = 46.04 kN
Vuy(top joint) = -13.84 kN
Ned(bottom joint) = 60.02 kN
Mux (bottom joint) = -23.69 kNm
Muy (bottom joint) = -109.63 kNm
Vux (bottom joint) = 46.04 kN
Vuy(bottom joint) = -13.84 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Final Critical Design Forces
Design Of Shear
Along D
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -13.8353 kN
Pu = 44.59
Design shear stress ,vEd = 0.0894 N/mm2
VRD,c = 110.6188 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0096
k1 0.15
σcp = NEd / (B x D)
= 0.2548
Along B
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 46.0421 kN
Pu = 44.59
Design shear stress ,vEd = 0.3154 N/mm2
VRD,c = 115.6542 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0102
k1 = 0.15
σcp = NEd / (B x D)
= 0.2548
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C10,C11
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 25
Critical Analysis Load : 166
Combination
[65] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 4: WL+X) +1.5
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 420.3 kN
Mux(top joint) = -346.38 kNm
Muy(top joint) = 22.45 kNm
Vux(top joint) = 14.97 kN
Vuy(top joint) = 230.98 kN
Ned(bottom joint) = 426.48 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 14.97 kN
Vuy(bottom joint) = 230.98 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 166
Combination
[65] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 4: WL+X) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = 230.9821 kN
Pu = 420.3
Design shear stress ,vEd = 1.4999 N/mm2
VRD,c = 188.792 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 2.4017
Along B
Critical Analysis Load : 166
Combination
[65] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 4: WL+X) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = 14.9699 kN
Pu = 420.3
Design shear stress ,vEd = 0.1032 N/mm2
VRD,c = 189.4738 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 290 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8305
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 2.4017
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C10,C11
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3650 mm
Clear Floor Height @ D,loD = 3650 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 26
Critical Analysis Load : 169
Combination
[68] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 7: WL-Z) +1.5
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 194.86 kN
Mux(top joint) = -8.12 kNm
Muy(top joint) = 72.14 kNm
Vux(top joint) = 35.78 kN
Vuy(top joint) = -21.88 kN
Ned(bottom joint) = 211.98 kN
Mux (bottom joint) = -98.89 kNm
Muy (bottom joint) = -76.31 kNm
Vux (bottom joint) = 35.78 kN
Vuy(bottom joint) = -21.88 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 169
Combination
[68] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 7: WL-Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = -21.8771 kN
Pu = 194.86
Design shear stress ,vEd = 0.1408 N/mm2
VRD,c = 114.9513 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 1.1135
Along B
Critical Analysis Load : 169
Combination
[68] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 7: WL-Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = 35.782 kN
Pu = 194.86
Design shear stress ,vEd = 0.2434 N/mm2
VRD,c = 118.1955 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 1.1135
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
Provided spacing = 225 mm
General Data
Column No. : C10,C11
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3200 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 27
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Bottom Joint
Ned(top joint) = 61.26 kN
Mux(top joint) = -21.86 kNm
Muy(top joint) = 33.63 kNm
Vux(top joint) = 31.72 kN
Vuy(top joint) = 13.57 kN
Ned(bottom joint) = 80.19 kN
Mux (bottom joint) = 24.27 kNm
Muy (bottom joint) = -74.2 kNm
Vux (bottom joint) = 31.72 kN
Vuy(bottom joint) = 13.57 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
Critical Load Combination =
(LOAD 3: CL) +1.5 (LOAD 2: LL)
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 13.5732 kN
Pu = 61.26
Design shear stress ,vEd = 0.0873 N/mm2
VRD,c = 97.1558 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.3501
Along B
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 31.7215 kN
Pu = 61.26
Design shear stress ,vEd = 0.2158 N/mm2
VRD,c = 101.362 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.3501
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C12,C21
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 85
Critical Analysis Load : 257
Combination
[156] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = -122.61 kN
Mux(top joint) = 62.85 kNm
Muy(top joint) = -6.55 kNm
Vux(top joint) = 4.36 kN
Vuy(top joint) = 41.91 kN
Ned(bottom joint) = -118.72 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 4.36 kN
Vuy(bottom joint) = 41.91 kN
Minimum Eccentricity,
Since Axial Force is tensile, Min. Eccentricity check not to be performed
Slenderness Check
Design Of Shear
Along D
Critical Analysis Load : 257
Combination
[156] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 41.9143 kN
Pu = 122.61
Design shear stress ,vEd = 0.4741 N/mm2
VRD,c = 80.1219 kN
As tension = 1030.44 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0117
k1 0.15
σcp = NEd / (B x D)
= 1.2261
Along B
Critical Analysis Load : 257
Combination
[156] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 4.3647 kN
Pu = 122.61
Design shear stress ,vEd = 0.0615 N/mm2
VRD,c = 79.0378 kN
As tension = 1030.44 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0145
k1 = 0.15
σcp = NEd / (B x D)
= 1.2261
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C12,C21
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 74
Critical Analysis Load : 101
Combination
[1] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination =
+1.5 (LOAD 2: LL)
Critical Location = Top Joint
Ned(top joint) = 138.04 kN
Mux(top joint) = -0.42 kNm
Muy(top joint) = 43.43 kNm
Vux(top joint) = -21.9 kN
Vuy(top joint) = -0.27 kN
Ned(bottom joint) = 147.59 kN
Mux (bottom joint) = 0.4 kNm
Muy (bottom joint) = -22.26 kNm
Vux (bottom joint) = -21.9 kN
Vuy(bottom joint) = -0.27 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Minimum Eccentricity Along D: = D / 30
Minecc (e0D) = 16.6667 mm
MM,Since <
= 20
20
Mmind = Ned x Minimum Eccentricity
= 2.95 kNm
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Along B
βB = 0.35 + fcd / 200 - λD / 150
= 0.1604
KφB = 1 + βD x ωef
= 1.19
MoeB (0.4 x Min(top, bottom) + 0.6
= 35.96 kNm
x Max(top, bottom))
M2B (e2D x ned) = 4.44 kNm
Mid Moment Along B
= 40.4 kNm
(MoeB+M2B)
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Along B
Critical Analysis Load : 101
Combination
[1] : 1.35 (LOAD 1: DL) +1.35
Critical Load Combination =
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Design shear force, Vux = -21.9033 kN
Pu = 138.04
Design shear stress ,vEd = 0.3085 N/mm2
VRD,c = 85.1934 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0177
k1 = 0.15
σcp = NEd / (B x D)
= 1.3804
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C13
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 75
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 182.81 kN
Mux(top joint) = 123.78 kNm
Muy(top joint) = -4.23 kNm
Vux(top joint) = 2.82 kN
Vuy(top joint) = 82.54 kN
Ned(bottom joint) = 186.7 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 2.82 kN
Vuy(bottom joint) = 82.54 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 82.5438 kN
Pu = 182.81
Design shear stress ,vEd = 0.9295 N/mm2
VRD,c = 85.6339 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0102
k1 0.15
σcp = NEd / (B x D)
= 1.8281
Along B
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 2.8191 kN
Pu = 182.81
Design shear stress ,vEd = 0.0392 N/mm2
VRD,c = 83.5165 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 144 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0126
k1 = 0.15
σcp = NEd / (B x D)
= 1.8281
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
Load Data
Analysis Reference No. = 76
Critical Analysis Load : 257
Combination
[156] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Bottom Joint
Ned(top joint) = 100.68 kN
Mux(top joint) = 109.99 kNm
Muy(top joint) = -36.24 kNm
Vux(top joint) = 19.11 kN
Vuy(top joint) = 100.15 kN
Ned(bottom joint) = 108.46 kN
Mux (bottom joint) = -190.37 kNm
Muy (bottom joint) = 21.08 kNm
Vux (bottom joint) = 19.11 kN
Vuy(bottom joint) = 100.15 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 257
Combination
[156] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 100.1471 kN
Pu = 100.68
Design shear stress ,vEd = 1.138 N/mm2
VRD,c = 89.4688 kN
As tension = 2060.88 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 1.0068
Along B
Critical Analysis Load : 257
Combination
[156] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 19.1102 kN
Pu = 100.68
Design shear stress ,vEd = 0.273 N/mm2
VRD,c = 82.9606 kN
As tension = 2060.88 sqmm
CRdc = 0.18/γc
= 0.12
beff = 140 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 1.0068
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 320 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
Provided spacing = 200 mm
General Data
Column No. : C14
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1500 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 77
Critical Analysis Load : 233
Combination
[132] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 77.83 kN
Mux(top joint) = 147.55 kNm
Muy(top joint) = 4.02 kNm
Vux(top joint) = -2.68 kN
Vuy(top joint) = 98.39 kN
Ned(bottom joint) = 81.72 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -2.68 kN
Vuy(bottom joint) = 98.39 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Eccentricity ,(ei) (along both the
= 2.5 mm
directions)
MgeoD = 0.19 kNm
MgeoB = 0.19 kNm
Slenderness Check
Along D
slenderness ratio (λD) = 6.92 mm
Permissible limits (λDlim) = 61.58 mm
hence, Column is not slender
Along B
slenderness ratio (λB) = 25.95 mm
Permissible limits (λBlim) = 61.58 mm
hence, Column is not slender
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 233
Combination
[132] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 98.3942 kN
Pu = 77.83
Design shear stress ,vEd = 1.1131 N/mm2
VRD,c = 84.4035 kN
As tension = 1608.48 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0182
k1 0.15
σcp = NEd / (B x D)
= 0.7783
Along B
Critical Analysis Load : 233
Combination
[132] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -2.684 kN
Pu = 77.83
Design shear stress ,vEd = 0.0378 N/mm2
VRD,c = 81.7121 kN
As tension = 1608.48 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.7783
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 320 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C14
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3000 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 78
Critical Analysis Load : 257
Combination
[156] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Bottom Joint
Ned(top joint) = 7.95 kN
Mux(top joint) = 114.05 kNm
Muy(top joint) = 3.27 kNm
Vux(top joint) = -1.27 kN
Vuy(top joint) = 105.12 kN
Ned(bottom joint) = 15.72 kN
Mux (bottom joint) = -201.23 kNm
Muy (bottom joint) = -0.53 kNm
Vux (bottom joint) = -1.27 kN
Vuy(bottom joint) = 105.12 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Along B
Critical Analysis Load : 257
Combination
[156] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -1.2664 kN
Pu = 7.95
Design shear stress ,vEd = 0.0181 N/mm2
VRD,c = 73.2234 kN
As tension = 2060.88 sqmm
CRdc = 0.18/γc
= 0.12
beff = 140 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.0795
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 320 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C15,C23
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1500 mm
No Of Floors = 1
No Of Columns In Group = 2
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 217
Critical Analysis Load : 228
Combination
[127] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 196.98 kN
Mux(top joint) = 76.64 kNm
Muy(top joint) = -87.34 kNm
Vux(top joint) = -58.24 kN
Vuy(top joint) = -51.11 kN
Ned(bottom joint) = 196.98 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -58.24 kN
Vuy(bottom joint) = -51.11 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 228
Combination
[127] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -51.1056 kN
Pu = 196.98
Design shear stress ,vEd = 0.3289 N/mm2
VRD,c = 115.233 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 1.1256
Along B
Critical Analysis Load : 228
Combination
[127] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -58.243 kN
Pu = 196.98
Design shear stress ,vEd = 0.3962 N/mm2
VRD,c = 118.4619 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 1.1256
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
Load Data
Analysis Reference No. = 218
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 97.2 kN
Mux(top joint) = 42.67 kNm
Muy(top joint) = -59.79 kNm
Vux(top joint) = -27.04 kN
Vuy(top joint) = -6.48 kN
Ned(bottom joint) = 97.2 kN
Mux (bottom joint) = 15.77 kNm
Muy (bottom joint) = 52.38 kNm
Vux (bottom joint) = -27.04 kN
Vuy(bottom joint) = -6.48 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = -6.4848 kN
Pu = 97.2
Design shear stress ,vEd = 0.0417 N/mm2
VRD,c = 101.9427 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.5554
Along B
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -27.0363 kN
Pu = 97.2
Design shear stress ,vEd = 0.1839 N/mm2
VRD,c = 105.8901 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.5554
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C16
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1500 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 55
Critical Analysis Load : 228
Combination
[127] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 440.56 kN
Mux(top joint) = -160.23 kNm
Muy(top joint) = 25.23 kNm
Vux(top joint) = -16.82 kN
Vuy(top joint) = -106.85 kN
Ned(bottom joint) = 447.37 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -16.82 kN
Vuy(bottom joint) = -106.85 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Final Critical Design Forces
Design Of Shear
Along D
Critical Analysis Load : 228
Combination
[127] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -106.8466 kN
Pu = 440.56
Design shear stress ,vEd = 0.6876 N/mm2
VRD,c = 147.6785 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 2.5175
Along B
Critical Analysis Load : 228
Combination
[127] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -16.8215 kN
Pu = 440.56
Design shear stress ,vEd = 0.1144 N/mm2
VRD,c = 149.1537 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 2.5175
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C16
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 4150 mm
Clear Floor Height @ D,loD = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 56
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 213.12 kN
Mux(top joint) = 161.75 kNm
Muy(top joint) = 38.38 kNm
Vux(top joint) = -11.11 kN
Vuy(top joint) = 72.66 kN
Ned(bottom joint) = 231.95 kN
Mux (bottom joint) = -139.72 kNm
Muy (bottom joint) = -7.7 kNm
Vux (bottom joint) = -11.11 kN
Vuy(bottom joint) = 72.66 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 72.662 kN
Pu = 213.12
Design shear stress ,vEd = 0.4697 N/mm2
VRD,c = 132.9654 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0096
k1 0.15
σcp = NEd / (B x D)
= 1.2178
Along B
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -11.1064 kN
Pu = 213.12
Design shear stress ,vEd = 0.0761 N/mm2
VRD,c = 136.7442 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0102
k1 = 0.15
σcp = NEd / (B x D)
= 1.2178
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
Load Data
Analysis Reference No. = 57
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 59.56 kN
Mux(top joint) = -83.64 kNm
Muy(top joint) = 14.7 kNm
Vux(top joint) = -2.74 kN
Vuy(top joint) = -44.42 kN
Ned(bottom joint) = 78.49 kN
Mux (bottom joint) = 67.33 kNm
Muy (bottom joint) = 5.4 kNm
Vux (bottom joint) = -2.74 kN
Vuy(bottom joint) = -44.42 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = -44.4156 kN
Pu = 59.56
Design shear stress ,vEd = 0.2858 N/mm2
VRD,c = 96.9289 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.3403
Along B
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -2.7356 kN
Pu = 59.56
Design shear stress ,vEd = 0.0186 N/mm2
VRD,c = 101.1473 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.3403
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C17
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1500 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 58
Critical Analysis Load : 255
Combination
[154] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 400.54 kN
Mux(top joint) = 6.15 kNm
Muy(top joint) = 65 kNm
Vux(top joint) = -43.35 kN
Vuy(top joint) = 4.1 kN
Ned(bottom joint) = 404.43 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -43.35 kN
Vuy(bottom joint) = 4.1 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Final Critical Design Forces
Design Of Shear
Along D
Critical Analysis Load : 255
Combination
[154] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 4.0997 kN
Pu = 400.54
Design shear stress ,vEd = 0.0464 N/mm2
VRD,c = 121.3425 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0142
k1 0.15
σcp = NEd / (B x D)
= 4.0054
Along B
Critical Analysis Load : 255
Combination
[154] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -43.3456 kN
Pu = 400.54
Design shear stress ,vEd = 0.6105 N/mm2
VRD,c = 113.1492 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0177
k1 = 0.15
σcp = NEd / (B x D)
= 4.0054
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C17
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 4150 mm
Clear Floor Height @ D,loD = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 59
Critical Analysis Load : 231
Combination
[130] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 207.66 kN
Mux(top joint) = 6.09 kNm
Muy(top joint) = 48.61 kNm
Vux(top joint) = -9.75 kN
Vuy(top joint) = 2.27 kN
Ned(bottom joint) = 218.42 kN
Mux (bottom joint) = -3.34 kNm
Muy (bottom joint) = 8.17 kNm
Vux (bottom joint) = -9.75 kN
Vuy(bottom joint) = 2.27 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Along B
βB = 0.35 + fcd / 200 - λD / 150
= 0.0047
KφB = 1 + βD x ωef
= 1.01
MoeB (0.4 x Min(top, bottom) + 0.6
= 26.24 kNm
x Max(top, bottom))
M2B (e2D x ned) = 12.18 kNm
Mid Moment Along B
= 38.42 kNm
(MoeB+M2B)
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 231
Combination
[130] : 1.1 (LOAD 1: DL) +1.1
Critical Load Combination =
(LOAD 3: CL) +1.5 (LOAD 2: LL)
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 2.2727 kN
Pu = 207.66
Design shear stress ,vEd = 0.0257 N/mm2
VRD,c = 95.7674 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0142
k1 0.15
σcp = NEd / (B x D)
= 2.0766
Along B
Critical Analysis Load : 231
Combination
[130] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -9.7475 kN
Pu = 207.66
Design shear stress ,vEd = 0.1373 N/mm2
VRD,c = 92.6081 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0177
k1 = 0.15
σcp = NEd / (B x D)
= 2.0766
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C17
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3200 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 60
Critical Analysis Load : 255
Combination
[154] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 13: TEL2)
Critical Location = Bottom Joint
Ned(top joint) = 41.74 kN
Mux(top joint) = -4.99 kNm
Muy(top joint) = -13.65 kNm
Vux(top joint) = 18.37 kN
Vuy(top joint) = -0.48 kN
Ned(bottom joint) = 50.55 kN
Mux (bottom joint) = -3.35 kNm
Muy (bottom joint) = 48.77 kNm
Vux (bottom joint) = 18.37 kN
Vuy(bottom joint) = -0.48 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Design Of Shear
Along D
Critical Analysis Load : 255
Combination
[154] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = -0.4815 kN
Pu = 41.74
Design shear stress ,vEd = 0.0054 N/mm2
VRD,c = 73.7659 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0142
k1 0.15
σcp = NEd / (B x D)
= 0.4174
Along B
Critical Analysis Load : 255
Combination
[154] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 18.365 kN
Pu = 41.74
Design shear stress ,vEd = 0.2587 N/mm2
VRD,c = 74.9373 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0177
k1 = 0.15
σcp = NEd / (B x D)
= 0.4174
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C18
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 79
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = -17.73 kN
Mux(top joint) = -109 kNm
Muy(top joint) = -0.89 kNm
Vux(top joint) = 0.59 kN
Vuy(top joint) = -72.68 kN
Ned(bottom joint) = -13.84 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 0.59 kN
Vuy(bottom joint) = -72.68 kN
Minimum Eccentricity,
Since Axial Force is tensile, Min. Eccentricity check not to be performed
Slenderness Check
Design Of Shear
Along D
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = -72.6837 kN
Pu = 17.73
Design shear stress ,vEd = 0.8222 N/mm2
VRD,c = 70.5829 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0142
k1 0.15
σcp = NEd / (B x D)
= 0.1773
Shear check No Shear Reinforcement Required
Since VRD,C > Vuy
Along B
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 0.5936 kN
Pu = 17.73
Design shear stress ,vEd = 0.0084 N/mm2
VRD,c = 72.3808 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0177
k1 = 0.15
σcp = NEd / (B x D)
= 0.1773
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C18
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 80
Critical Analysis Load : 112
Combination
[12] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 64.8 kN
Mux(top joint) = -110.89 kNm
Muy(top joint) = 40.52 kNm
Vux(top joint) = -20.18 kN
Vuy(top joint) = -88.21 kN
Ned(bottom joint) = 74.35 kN
Mux (bottom joint) = 153.67 kNm
Muy (bottom joint) = -20 kNm
Vux (bottom joint) = -20.18 kN
Vuy(bottom joint) = -88.21 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Eccentricity ,(ei) (along both the
= 7 mm
directions)
MgeoD = 0.52 kNm
MgeoB = 0.52 kNm
Slenderness Check
Along D
slenderness ratio (λD) = 19.38 mm
Permissible limits (λDlim) = 64.56 mm
hence, Column is not slender
Along B
slenderness ratio (λB) = 48.44 mm
Permissible limits (λBlim) = 64.56 mm
hence, Column is not slender
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 112
Combination
[12] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -88.2097 kN
Pu = 64.8
Design shear stress ,vEd = 0.9978 N/mm2
VRD,c = 82.6759 kN
As tension = 1608.48 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0182
k1 0.15
σcp = NEd / (B x D)
= 0.648
Along B
Critical Analysis Load : 112
Combination
[12] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -20.1776 kN
Pu = 64.8
Design shear stress ,vEd = 0.2842 N/mm2
VRD,c = 80.3246 kN
As tension = 1608.48 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.648
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 320 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C19
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 81
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = -99.96 kN
Mux(top joint) = -161.78 kNm
Muy(top joint) = 6.89 kNm
Vux(top joint) = -4.59 kN
Vuy(top joint) = -107.88 kN
Ned(bottom joint) = -96.07 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -4.59 kN
Vuy(bottom joint) = -107.88 kN
Minimum Eccentricity,
Since Axial Force is tensile, Min. Eccentricity check not to be performed
Slenderness Check
Design Of Shear
Along D
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = -107.8821 kN
Pu = 99.96
Design shear stress ,vEd = 1.2259 N/mm2
VRD,c = 89.3736 kN
As tension = 2060.88 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 0.9996
Along B
Critical Analysis Load : 256
Combination
[155] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -4.5925 kN
Pu = 99.96
Design shear stress ,vEd = 0.0656 N/mm2
VRD,c = 82.8848 kN
As tension = 2060.88 sqmm
CRdc = 0.18/γc
= 0.12
beff = 140 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.9996
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 320 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C19
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 82
Critical Analysis Load : 112
Combination
[12] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 42.58 kN
Mux(top joint) = -162.81 kNm
Muy(top joint) = -34.24 kNm
Vux(top joint) = 15.21 kN
Vuy(top joint) = -132.28 kN
Ned(bottom joint) = 52.12 kN
Mux (bottom joint) = 233.93 kNm
Muy (bottom joint) = 11.37 kNm
Vux (bottom joint) = 15.21 kN
Vuy(bottom joint) = -132.28 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 112
Combination
[12] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -132.2815 kN
Pu = 42.58
Design shear stress ,vEd = 1.5032 N/mm2
VRD,c = 81.799 kN
As tension = 2513.28 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 0.4258
Along B
Critical Analysis Load : 112
Combination
[12] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 15.2068 kN
Pu = 42.58
Design shear stress ,vEd = 0.2172 N/mm2
VRD,c = 76.8596 kN
As tension = 2513.28 sqmm
CRdc = 0.18/γc
= 0.12
beff = 140 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.4258
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C20
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1500 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 83
Critical Analysis Load : 233
Combination
[132] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 88.48 kN
Mux(top joint) = 145.74 kNm
Muy(top joint) = -2.65 kNm
Vux(top joint) = 1.77 kN
Vuy(top joint) = 97.19 kN
Ned(bottom joint) = 92.37 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 1.77 kN
Vuy(bottom joint) = 97.19 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 233
Combination
[132] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 97.1856 kN
Pu = 88.48
Design shear stress ,vEd = 1.0994 N/mm2
VRD,c = 79.9634 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0142
k1 0.15
σcp = NEd / (B x D)
= 0.8848
Along B
Critical Analysis Load : 233
Combination
[132] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 1.7661 kN
Pu = 88.48
Design shear stress ,vEd = 0.0249 N/mm2
VRD,c = 79.9149 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0177
k1 = 0.15
σcp = NEd / (B x D)
= 0.8848
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C20
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3000 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 84
Critical Analysis Load : 233
Combination
[132] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Bottom Joint
Ned(top joint) = 12.03 kN
Mux(top joint) = 105.4 kNm
Muy(top joint) = -1.21 kNm
Vux(top joint) = 1.27 kN
Vuy(top joint) = 100.4 kN
Ned(bottom joint) = 19.81 kN
Mux (bottom joint) = -195.73 kNm
Muy (bottom joint) = 2.59 kNm
Vux (bottom joint) = 1.27 kN
Vuy(bottom joint) = 100.4 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Final Critical Design Forces
Design Of Shear
Along D
Critical Analysis Load : 233
Combination
[132] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 100.4042 kN
Pu = 12.03
Design shear stress ,vEd = 1.141 N/mm2
VRD,c = 77.7666 kN
As tension = 2060.88 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 0.1203
Along B
Critical Analysis Load : 233
Combination
[132] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 1.2684 kN
Pu = 12.03
Design shear stress ,vEd = 0.0181 N/mm2
VRD,c = 73.652 kN
As tension = 2060.88 sqmm
CRdc = 0.18/γc
= 0.12
beff = 140 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.1203
Shear check No Shear Reinforcement Required
Since VRD,C > Vux
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 320 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C22
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 87
Critical Analysis Load : 113
Combination
[13] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = -65.1 kN
Mux(top joint) = 176.8 kNm
Muy(top joint) = -14.86 kNm
Vux(top joint) = 9.91 kN
Vuy(top joint) = 117.89 kN
Ned(bottom joint) = -60.32 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 9.91 kN
Vuy(bottom joint) = 117.89 kN
Minimum Eccentricity,
Since Axial Force is tensile, Min. Eccentricity check not to be performed
Slenderness Check
Design Of Shear
Along D
Critical Analysis Load : 113
Combination
[13] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 117.8947 kN
Pu = 65.1
Design shear stress ,vEd = 1.3397 N/mm2
VRD,c = 84.7718 kN
As tension = 2060.88 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 0.651
Along B
Critical Analysis Load : 113
Combination
[13] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 9.9062 kN
Pu = 65.1
Design shear stress ,vEd = 0.1415 N/mm2
VRD,c = 79.2243 kN
As tension = 2060.88 sqmm
CRdc = 0.18/γc
= 0.12
beff = 140 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.651
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 320 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C22
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 88
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Bottom Joint
Ned(top joint) = -17.9 kN
Mux(top joint) = 153.3 kNm
Muy(top joint) = -33.04 kNm
Vux(top joint) = 19.43 kN
Vuy(top joint) = 131.85 kN
Ned(bottom joint) = -8.36 kN
Mux (bottom joint) = -242.15 kNm
Muy (bottom joint) = 25.23 kNm
Vux (bottom joint) = 19.43 kN
Vuy(bottom joint) = 131.85 kN
Minimum Eccentricity,
Since Axial Force is tensile, Min. Eccentricity check not to be performed
Slenderness Check
Design Of Shear
Along D
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 131.8529 kN
Pu = 17.9
Design shear stress ,vEd = 1.5069 N/mm2
VRD,c = 78.1829 kN
As tension = 3220.12 sqmm
CRdc = 0.18/γc
= 0.12
deff = 438 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6761
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 0.179
Along B
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 19.4296 kN
Pu = 17.9
Design shear stress ,vEd = 0.2826 N/mm2
VRD,c = 72.9427 kN
As tension = 3220.12 sqmm
CRdc = 0.18/γc
= 0.12
beff = 138 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.179
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C24
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1500 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 67
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 441.58 kN
Mux(top joint) = 163.1 kNm
Muy(top joint) = 34.99 kNm
Vux(top joint) = -23.33 kN
Vuy(top joint) = 108.76 kN
Ned(bottom joint) = 448.38 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -23.33 kN
Vuy(bottom joint) = 108.76 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Minimum Eccentricity Along D: = D / 30
Minecc (e0D) = 16.6667 mm
MM,Since <
= 20
20
Mmind = Ned x Minimum Eccentricity
= 8.97 kNm
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 108.7624 kN
Pu = 441.58
Design shear stress ,vEd = 0.6999 N/mm2
VRD,c = 147.8141 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 2.5233
Shear check No Shear Reinforcement Required
Since VRD,C > Vuy
Along B
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -23.3302 kN
Pu = 441.58
Design shear stress ,vEd = 0.1587 N/mm2
VRD,c = 149.2819 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 2.5233
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C24
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 4150 mm
Clear Floor Height @ D,loD = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 68
Critical Analysis Load : 228
Combination
[127] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 213.13 kN
Mux(top joint) = -160.31 kNm
Muy(top joint) = 29.39 kNm
Vux(top joint) = -8.79 kN
Vuy(top joint) = -72.06 kN
Ned(bottom joint) = 231.96 kN
Mux (bottom joint) = 138.66 kNm
Muy (bottom joint) = -7.09 kNm
Vux (bottom joint) = -8.79 kN
Vuy(bottom joint) = -72.06 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Eccentricity ,(ei) (along both the
= 9.13 mm
directions)
MgeoD = 1.95 kNm
MgeoB = 1.95 kNm
Slenderness Check
Along D
slenderness ratio (λD) = 25.26 mm
Permissible limits (λDlim) = 48.35 mm
hence, Column is not slender
Along B
slenderness ratio (λB) = 41.03 mm
Permissible limits (λBlim) = 48.35 mm
hence, Column is not slender
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 228
Combination
[127] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -72.0602 kN
Pu = 213.13
Design shear stress ,vEd = 0.4658 N/mm2
VRD,c = 127.3467 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0081
k1 0.15
σcp = NEd / (B x D)
= 1.2179
Along B
Critical Analysis Load : 228
Combination
[127] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -8.791 kN
Pu = 213.13
Design shear stress ,vEd = 0.0602 N/mm2
VRD,c = 130.8372 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0086
k1 = 0.15
σcp = NEd / (B x D)
= 1.2179
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C24
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 69
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 59.52 kN
Mux(top joint) = 85.19 kNm
Muy(top joint) = 18.93 kNm
Vux(top joint) = -3.32 kN
Vuy(top joint) = 45.32 kN
Ned(bottom joint) = 78.46 kN
Mux (bottom joint) = -68.84 kNm
Muy (bottom joint) = 7.64 kNm
Vux (bottom joint) = -3.32 kN
Vuy(bottom joint) = 45.32 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 45.316 kN
Pu = 59.52
Design shear stress ,vEd = 0.2916 N/mm2
VRD,c = 96.9245 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.3401
Along B
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -3.3222 kN
Pu = 59.52
Design shear stress ,vEd = 0.0226 N/mm2
VRD,c = 101.1431 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.3401
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C25
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1500 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 70
Critical Analysis Load : 232
Combination
[131] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 419.05 kN
Mux(top joint) = -89.23 kNm
Muy(top joint) = -24.06 kNm
Vux(top joint) = 16.04 kN
Vuy(top joint) = -59.5 kN
Ned(bottom joint) = 422.94 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 16.04 kN
Vuy(bottom joint) = -59.5 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 232
Combination
[131] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = -59.5035 kN
Pu = 419.05
Design shear stress ,vEd = 0.6701 N/mm2
VRD,c = 111.4971 kN
As tension = 678.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0076
k1 0.15
σcp = NEd / (B x D)
= 4.1905
Along B
Critical Analysis Load : 232
Combination
[131] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 16.0437 kN
Pu = 419.05
Design shear stress ,vEd = 0.2228 N/mm2
VRD,c = 103.1989 kN
As tension = 678.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 144 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0094
k1 = 0.15
σcp = NEd / (B x D)
= 4.1905
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
Provided spacing = 200 mm
General Data
Column No. : C25
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3000 mm
Clear Floor Height @ D,loD = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 71
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 271.42 kN
Mux(top joint) = 102.76 kNm
Muy(top joint) = 16.25 kNm
Vux(top joint) = -8.7 kN
Vuy(top joint) = 66.28 kN
Ned(bottom joint) = 280.96 kN
Mux (bottom joint) = -96.02 kNm
Muy (bottom joint) = -9.83 kNm
Vux (bottom joint) = -8.7 kN
Vuy(bottom joint) = 66.28 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Along B
βB = 0.35 + fcd / 200 - λD / 150
= 0.1373
KφB = 1 + βD x ωef
= 1.16
MoeB (0.4 x Min(top, bottom) + 0.6
= 15.4 kNm
x Max(top, bottom))
M2B (e2D x ned) = 9.49 kNm
Mid Moment Along B
= 24.89 kNm
(MoeB+M2B)
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 66.2799 kN
Pu = 271.42
Design shear stress ,vEd = 0.7464 N/mm2
VRD,c = 91.8324 kN
As tension = 678.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0076
k1 0.15
σcp = NEd / (B x D)
= 2.7142
Shear check No Shear Reinforcement Required
Since VRD,C > Vuy
Along B
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -8.6958 kN
Pu = 271.42
Design shear stress ,vEd = 0.1208 N/mm2
VRD,c = 87.2545 kN
As tension = 678.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 144 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0094
k1 = 0.15
σcp = NEd / (B x D)
= 2.7142
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C25
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1150 mm
Clear Floor Height @ D,loD = 650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 237
Critical Analysis Load : 113
Combination
[13] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 128.68 kN
Mux(top joint) = -45.13 kNm
Muy(top joint) = 0.12 kNm
Vux(top joint) = 51.45 kN
Vuy(top joint) = 54.75 kN
Ned(bottom joint) = 128.68 kN
Mux (bottom joint) = -108.07 kNm
Muy (bottom joint) = 59.28 kNm
Vux (bottom joint) = 51.45 kN
Vuy(bottom joint) = 54.75 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 113
Combination
[13] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 54.7459 kN
Pu = 128.68
Design shear stress ,vEd = 0.6193 N/mm2
VRD,c = 85.2937 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0142
k1 0.15
σcp = NEd / (B x D)
= 1.2868
Along B
Critical Analysis Load : 113
Combination
[13] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 51.4484 kN
Pu = 128.68
Design shear stress ,vEd = 0.7246 N/mm2
VRD,c = 84.196 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0177
k1 = 0.15
σcp = NEd / (B x D)
= 1.2868
General Data
Column No. : C25
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3200 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 72
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 13: TEL2)
Critical Location = Bottom Joint
Ned(top joint) = 51.67 kN
Mux(top joint) = -21.87 kNm
Muy(top joint) = -21.93 kNm
Vux(top joint) = 9.36 kN
Vuy(top joint) = -27.8 kN
Ned(bottom joint) = 62.49 kN
Mux (bottom joint) = 72.62 kNm
Muy (bottom joint) = 9.88 kNm
Vux (bottom joint) = 9.36 kN
Vuy(bottom joint) = -27.8 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = -27.796 kN
Pu = 51.67
Design shear stress ,vEd = 0.313 N/mm2
VRD,c = 62.5627 kN
As tension = 678.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0076
k1 0.15
σcp = NEd / (B x D)
= 0.5167
Along B
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 9.358 kN
Pu = 51.67
Design shear stress ,vEd = 0.13 N/mm2
VRD,c = 63.5224 kN
As tension = 678.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 144 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0094
k1 = 0.15
σcp = NEd / (B x D)
= 0.5167
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C26
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 89
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 124 kN
Mux(top joint) = 140.51 kNm
Muy(top joint) = -33.62 kNm
Vux(top joint) = 22.42 kN
Vuy(top joint) = 93.7 kN
Ned(bottom joint) = 127.89 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 22.42 kN
Vuy(bottom joint) = 93.7 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 93.698 kN
Pu = 124
Design shear stress ,vEd = 1.0599 N/mm2
VRD,c = 84.6738 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0142
k1 0.15
σcp = NEd / (B x D)
= 1.24
Along B
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 22.4199 kN
Pu = 124
Design shear stress ,vEd = 0.3158 N/mm2
VRD,c = 83.6982 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 142 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0177
k1 = 0.15
σcp = NEd / (B x D)
= 1.24
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
Load Data
Analysis Reference No. = 90
Critical Analysis Load : 113
Combination
[13] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 67.39 kN
Mux(top joint) = 150.97 kNm
Muy(top joint) = -11.74 kNm
Vux(top joint) = 12.15 kN
Vuy(top joint) = 122.71 kN
Ned(bottom joint) = 76.93 kN
Mux (bottom joint) = -217.07 kNm
Muy (bottom joint) = 24.68 kNm
Vux (bottom joint) = 12.15 kN
Vuy(bottom joint) = 122.71 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 113
Combination
[13] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 122.7116 kN
Pu = 67.39
Design shear stress ,vEd = 1.3944 N/mm2
VRD,c = 85.074 kN
As tension = 2513.28 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 0.6739
Along B
Critical Analysis Load : 113
Combination
[13] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 12.1461 kN
Pu = 67.39
Design shear stress ,vEd = 0.1735 N/mm2
VRD,c = 79.4646 kN
As tension = 2513.28 sqmm
CRdc = 0.18/γc
= 0.12
beff = 140 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.6739
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
Provided spacing = 200 mm
General Data
Column No. : C27
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 233
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 225.28 kN
Mux(top joint) = -90 kNm
Muy(top joint) = 37.37 kNm
Vux(top joint) = 24.92 kN
Vuy(top joint) = 60.01 kN
Ned(bottom joint) = 225.28 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 24.92 kN
Vuy(bottom joint) = 60.01 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Eccentricity ,(ei) (along both the
= 2.5 mm
directions)
MgeoD = 0.56 kNm
MgeoB = 0.56 kNm
Slenderness Check
Along D
slenderness ratio (λD) = 6.92 mm
Permissible limits (λDlim) = 37.09 mm
hence, Column is not slender
Along B
slenderness ratio (λB) = 17.3 mm
Permissible limits (λBlim) = 37.09 mm
hence, Column is not slender
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 60.0144 kN
Pu = 225.28
Design shear stress ,vEd = 0.6758 N/mm2
VRD,c = 91.2906 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0102
k1 0.15
σcp = NEd / (B x D)
= 2.2528
Along B
Critical Analysis Load : 253
Combination
[152] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 24.9177 kN
Pu = 225.28
Design shear stress ,vEd = 0.3461 N/mm2
VRD,c = 88.103 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 144 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.0126
k1 = 0.15
σcp = NEd / (B x D)
= 2.2528
Shear check No Shear Reinforcement Required
Since VRD,C > Vux
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 200 mm
Max. 400 mm = 300 mm
General Data
Column No. : C27
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 200 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 234
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Mid Joint
Ned(top joint) = 132.95 kN
Mux(top joint) = -43.02 kNm
Muy(top joint) = 75.68 kNm
Vux(top joint) = 47.81 kN
Vuy(top joint) = 36.85 kN
Ned(bottom joint) = 132.95 kN
Mux (bottom joint) = 67.5 kNm
Muy (bottom joint) = -67.71 kNm
Vux (bottom joint) = 47.81 kN
Vuy(bottom joint) = 36.85 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Along B
βB = 0.35 + fcd / 200 - λD / 150
= 0.1604
KφB = 1 + βD x ωef
= 1.19
MoeB (0.4 x Min(top, bottom) + 0.6
= 73.42 kNm
x Max(top, bottom))
M2B (e2D x ned) = 4 kNm
Mid Moment Along B
= 77.42 kNm
(MoeB+M2B)
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 36.8515 kN
Pu = 132.95
Design shear stress ,vEd = 0.4188 N/mm2
VRD,c = 93.7281 kN
As tension = 2513.28 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 1.3295
Along B
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 47.8084 kN
Pu = 132.95
Design shear stress ,vEd = 0.683 N/mm2
VRD,c = 86.3486 kN
As tension = 2513.28 sqmm
CRdc = 0.18/γc
= 0.12
beff = 140 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 2
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 1.3295
General Data
Column No. : C31
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1500 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 31
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 5: WL-X) +1.5
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 280.71 kN
Mux(top joint) = 180.02 kNm
Muy(top joint) = -24.74 kNm
Vux(top joint) = -16.5 kN
Vuy(top joint) = -120.05 kN
Ned(bottom joint) = 286.9 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -16.5 kN
Vuy(bottom joint) = -120.05 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 5: WL-X) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = -120.0474 kN
Pu = 280.71
Design shear stress ,vEd = 0.776 N/mm2
VRD,c = 141.9279 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0096
k1 0.15
σcp = NEd / (B x D)
= 1.6041
Along B
Critical Analysis Load : 167
Combination
[66] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 5: WL-X) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = -16.4958 kN
Pu = 280.71
Design shear stress ,vEd = 0.113 N/mm2
VRD,c = 145.2026 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0102
k1 = 0.15
σcp = NEd / (B x D)
= 1.6041
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C31
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 4150 mm
Clear Floor Height @ D,loD = 3650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 32
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2 (LOAD 3: CL)
Load Combination = +0.6 (LOAD 2: LL) +(LOAD 9: LOAD CASE 9)
+1.2 (LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 192.78 kN
Mux(top joint) = 75.38 kNm
Muy(top joint) = 0.62 kNm
Vux(top joint) = -0.46 kN
Vuy(top joint) = -31.3 kN
Ned(bottom joint) = 213.33 kN
Mux (bottom joint) = -54.47 kNm
Muy (bottom joint) = 2.51 kNm
Vux (bottom joint) = -0.46 kN
Vuy(bottom joint) = -31.3 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 9: LOAD CASE 9) +1.2
(LOAD 12: TEL1)
Design shear force, Vuy = -31.2989 kN
Pu = 192.78
Design shear stress ,vEd = 0.2014 N/mm2
VRD,c = 136.9237 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 1.1016
Along B
Critical Analysis Load : 203
Combination
[102] : 1.2 (LOAD 1: DL) +1.2
(LOAD 3: CL) +0.6 (LOAD 2: LL)
Critical Load Combination =
+(LOAD 9: LOAD CASE 9) +1.2
(LOAD 12: TEL1)
Design shear force, Vux = -0.4554 kN
Pu = 192.78
Design shear stress ,vEd = 0.0031 N/mm2
VRD,c = 141.3446 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.15
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 1.1016
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C31
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 33
Critical Analysis Load : 252
Combination
[151] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 44.89 kN
Mux(top joint) = 1.85 kNm
Muy(top joint) = 11.73 kNm
Vux(top joint) = 12.41 kN
Vuy(top joint) = 0.05 kN
Ned(bottom joint) = 60.32 kN
Mux (bottom joint) = 2.01 kNm
Muy (bottom joint) = -30.46 kNm
Vux (bottom joint) = 12.41 kN
Vuy(bottom joint) = 0.05 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 252
Combination
[151] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 0.0477 kN
Pu = 44.89
Design shear stress ,vEd = 0.0003 N/mm2
VRD,c = 94.9749 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.2565
Along B
Critical Analysis Load : 252
Combination
[151] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 12.4132 kN
Pu = 44.89
Design shear stress ,vEd = 0.0844 N/mm2
VRD,c = 99.2989 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.2565
General Data
Column No. : C33
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 37
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 541.32 kN
Mux(top joint) = -4.2 kNm
Muy(top joint) = -66.75 kNm
Vux(top joint) = -44.51 kN
Vuy(top joint) = 2.8 kN
Ned(bottom joint) = 549.67 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -44.51 kN
Vuy(bottom joint) = 2.8 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 2.8018 kN
Pu = 541.32
Design shear stress ,vEd = 0.018 N/mm2
VRD,c = 167.9711 kN
As tension = 1131 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0073
k1 0.15
σcp = NEd / (B x D)
= 3.0932
Along B
Critical Analysis Load : 116
Combination
[16] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -44.5117 kN
Pu = 541.32
Design shear stress ,vEd = 0.3028 N/mm2
VRD,c = 169.0797 kN
As tension = 1131 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0077
k1 = 0.15
σcp = NEd / (B x D)
= 3.0932
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C33
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 3000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 38
Critical Analysis Load : 250
Combination
[149] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 4: WL+X) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 200.76 kN
Mux(top joint) = 0.88 kNm
Muy(top joint) = 242.3 kNm
Vux(top joint) = 102.41 kN
Vuy(top joint) = -0.49 kN
Ned(bottom joint) = 214.37 kN
Mux (bottom joint) = -0.6 kNm
Muy (bottom joint) = -64.86 kNm
Vux (bottom joint) = 102.41 kN
Vuy(bottom joint) = -0.49 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 250
Combination
[149] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -0.4926 kN
Pu = 200.76
Design shear stress ,vEd = 0.0032 N/mm2
VRD,c = 159.0579 kN
As tension = 3848.44 sqmm
CRdc = 0.18/γc
= 0.12
deff = 438 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6761
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 1.1472
Along B
Critical Analysis Load : 250
Combination
[149] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = 102.4129 kN
Pu = 200.76
Design shear stress ,vEd = 0.7124 N/mm2
VRD,c = 161.0586 kN
As tension = 3848.44 sqmm
CRdc = 0.18/γc
= 0.12
beff = 288 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8341
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 1.1472
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C33
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1150 mm
Clear Floor Height @ D,loD = 650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 177
Critical Analysis Load : 250
Combination
[149] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 4: WL+X) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 180.56 kN
Mux(top joint) = -2.06 kNm
Muy(top joint) = 65.79 kNm
Vux(top joint) = -186.4 kN
Vuy(top joint) = 4.73 kN
Ned(bottom joint) = 185.78 kN
Mux (bottom joint) = 3.37 kNm
Muy (bottom joint) = 280.1 kNm
Vux (bottom joint) = -186.4 kN
Vuy(bottom joint) = 4.73 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 250
Combination
[149] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = 4.7284 kN
Pu = 180.56
Design shear stress ,vEd = 0.0309 N/mm2
VRD,c = 156.4061 kN
As tension = 4908.7 sqmm
CRdc = 0.18/γc
= 0.12
deff = 438 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6761
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 1.0318
Along B
Critical Analysis Load : 250
Combination
[149] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -186.4038 kN
Pu = 180.56
Design shear stress ,vEd = 1.2967 N/mm2
VRD,c = 158.5691 kN
As tension = 4908.7 sqmm
CRdc = 0.18/γc
= 0.12
beff = 288 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8341
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 1.0318
General Data
Column No. : C33
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 39
Critical Analysis Load : 250
Combination
[149] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 4: WL+X) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 44.64 kN
Mux(top joint) = 4.22 kNm
Muy(top joint) = -47.39 kNm
Vux(top joint) = -47.33 kN
Vuy(top joint) = -3.05 kN
Ned(bottom joint) = 60.06 kN
Mux (bottom joint) = -6.15 kNm
Muy (bottom joint) = 113.5 kNm
Vux (bottom joint) = -47.33 kN
Vuy(bottom joint) = -3.05 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 250
Combination
[149] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -3.0515 kN
Pu = 44.64
Design shear stress ,vEd = 0.0197 N/mm2
VRD,c = 110.6247 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0096
k1 0.15
σcp = NEd / (B x D)
= 0.2551
Along B
Critical Analysis Load : 250
Combination
[149] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 4: WL+X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -47.3345 kN
Pu = 44.64
Design shear stress ,vEd = 0.3242 N/mm2
VRD,c = 115.6598 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0102
k1 = 0.15
σcp = NEd / (B x D)
= 0.2551
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C36
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 46
Critical Analysis Load : 169
Combination
[68] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 7: WL-Z) +1.5
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 317.81 kN
Mux(top joint) = -189.03 kNm
Muy(top joint) = 40.03 kNm
Vux(top joint) = 26.7 kN
Vuy(top joint) = 126.05 kN
Ned(bottom joint) = 323.99 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 26.7 kN
Vuy(bottom joint) = 126.05 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 169
Combination
[68] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 7: WL-Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = 126.0522 kN
Pu = 317.81
Design shear stress ,vEd = 0.8148 N/mm2
VRD,c = 146.8467 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0096
k1 0.15
σcp = NEd / (B x D)
= 1.816
Along B
Critical Analysis Load : 169
Combination
[68] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 7: WL-Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = 26.6956 kN
Pu = 317.81
Design shear stress ,vEd = 0.1828 N/mm2
VRD,c = 149.8448 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0102
k1 = 0.15
σcp = NEd / (B x D)
= 1.816
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C36
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 47
Critical Analysis Load : 255
Combination
[154] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 234.73 kN
Mux(top joint) = 95.3 kNm
Muy(top joint) = 177.41 kNm
Vux(top joint) = 78.38 kN
Vuy(top joint) = -54.96 kN
Ned(bottom joint) = 248.34 kN
Mux (bottom joint) = -69.53 kNm
Muy (bottom joint) = -57.66 kNm
Vux (bottom joint) = 78.38 kN
Vuy(bottom joint) = -54.96 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 255
Combination
[154] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = -54.9577 kN
Pu = 234.73
Design shear stress ,vEd = 0.3569 N/mm2
VRD,c = 154.7247 kN
As tension = 2463 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.016
k1 0.15
σcp = NEd / (B x D)
= 1.3413
Along B
Critical Analysis Load : 255
Combination
[154] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = 78.3765 kN
Pu = 234.73
Design shear stress ,vEd = 0.5405 N/mm2
VRD,c = 159.139 kN
As tension = 2463 sqmm
CRdc = 0.18/γc
= 0.12
beff = 290 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8305
ρ1 = Asmain / (d x beff)
<> = 0.017
k1 = 0.15
σcp = NEd / (B x D)
= 1.3413
General Data
Column No. : C36
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1150 mm
Clear Floor Height @ D,loD = 650 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 166
Critical Analysis Load : 227
Combination
[126] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 98.99 kN
Mux(top joint) = -2.72 kNm
Muy(top joint) = 110.53 kNm
Vux(top joint) = -109.3 kN
Vuy(top joint) = -49.85 kN
Ned(bottom joint) = 104.21 kN
Mux (bottom joint) = -60.03 kNm
Muy (bottom joint) = 236.19 kNm
Vux (bottom joint) = -109.3 kN
Vuy(bottom joint) = -49.85 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 227
Combination
[126] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -49.8489 kN
Pu = 98.99
Design shear stress ,vEd = 0.3255 N/mm2
VRD,c = 145.7 kN
As tension = 3848.44 sqmm
CRdc = 0.18/γc
= 0.12
deff = 438 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6761
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 0.5656
Along B
Critical Analysis Load : 227
Combination
[126] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -109.2972 kN
Pu = 98.99
Design shear stress ,vEd = 0.7603 N/mm2
VRD,c = 148.5185 kN
As tension = 3848.44 sqmm
CRdc = 0.18/γc
= 0.12
beff = 288 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8341
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 0.5656
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C36
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3400 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 48
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +0.9 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 42.9 kN
Mux(top joint) = 27.73 kNm
Muy(top joint) = -41.28 kNm
Vux(top joint) = -45.38 kN
Vuy(top joint) = -10.84 kN
Ned(bottom joint) = 58.33 kN
Mux (bottom joint) = -9.11 kNm
Muy (bottom joint) = 112.98 kNm
Vux (bottom joint) = -45.38 kN
Vuy(bottom joint) = -10.84 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -10.8379 kN
Pu = 42.9
Design shear stress ,vEd = 0.0701 N/mm2
VRD,c = 110.3941 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0096
k1 0.15
σcp = NEd / (B x D)
= 0.2451
Along B
Critical Analysis Load : 251
Combination
[150] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +0.9 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -45.3805 kN
Pu = 42.9
Design shear stress ,vEd = 0.3108 N/mm2
VRD,c = 115.4422 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0102
k1 = 0.15
σcp = NEd / (B x D)
= 0.2451
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C37
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 49
Critical Analysis Load : 169
Combination
[68] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 7: WL-Z) +1.5
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 353.8 kN
Mux(top joint) = -312.02 kNm
Muy(top joint) = 37.13 kNm
Vux(top joint) = 24.76 kN
Vuy(top joint) = 208.07 kN
Ned(bottom joint) = 359.99 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = 24.76 kN
Vuy(bottom joint) = 208.07 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 169
Combination
[68] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 7: WL-Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = 208.0664 kN
Pu = 353.8
Design shear stress ,vEd = 1.3511 N/mm2
VRD,c = 180.0148 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
deff = 440 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6742
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 2.0217
Along B
Critical Analysis Load : 169
Combination
[68] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 7: WL-Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = 24.7612 kN
Pu = 353.8
Design shear stress ,vEd = 0.1708 N/mm2
VRD,c = 181.2096 kN
As tension = 3141.6 sqmm
CRdc = 0.18/γc
= 0.12
beff = 290 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8305
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 2.0217
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C37
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2800 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 50
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 340.37 kN
Mux(top joint) = -0.66 kNm
Muy(top joint) = -72.99 kNm
Vux(top joint) = -3.01 kN
Vuy(top joint) = 6.96 kN
Ned(bottom joint) = 357.07 kN
Mux (bottom joint) = 20.2 kNm
Muy (bottom joint) = -63.96 kNm
Vux (bottom joint) = -3.01 kN
Vuy(bottom joint) = 6.96 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Final Critical Design Forces
Design Of Shear
Along D
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 6.9583 kN
Pu = 340.37
Design shear stress ,vEd = 0.0448 N/mm2
VRD,c = 134.3326 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 1.9449
Along B
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -3.011 kN
Pu = 340.37
Design shear stress ,vEd = 0.0205 N/mm2
VRD,c = 136.5291 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 1.9449
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C37
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1150 mm
Clear Floor Height @ D,loD = 1150 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 244
Critical Analysis Load : 111
Combination
[11] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 69.56 kN
Mux(top joint) = 11.51 kNm
Muy(top joint) = 53.29 kNm
Vux(top joint) = -28.64 kN
Vuy(top joint) = -0.05 kN
Ned(bottom joint) = 69.56 kN
Mux (bottom joint) = 11.44 kNm
Muy (bottom joint) = 86.21 kNm
Vux (bottom joint) = -28.64 kN
Vuy(bottom joint) = -0.05 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 111
Combination
[11] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -0.0546 kN
Pu = 69.56
Design shear stress ,vEd = 0.0004 N/mm2
VRD,c = 108.3089 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0081
k1 0.15
σcp = NEd / (B x D)
= 0.3975
Along B
Critical Analysis Load : 111
Combination
[11] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -28.6392 kN
Pu = 69.56
Design shear stress ,vEd = 0.1962 N/mm2
VRD,c = 112.8701 kN
As tension = 1256.64 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0086
k1 = 0.15
σcp = NEd / (B x D)
= 0.3975
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
Load Data
Analysis Reference No. = 51
Critical Analysis Load : 111
Combination
[11] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 5: WL-X) +0.9
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 50.63 kN
Mux(top joint) = 11.69 kNm
Muy(top joint) = -0.54 kNm
Vux(top joint) = -15.84 kN
Vuy(top joint) = -0.05 kN
Ned(bottom joint) = 69.56 kN
Mux (bottom joint) = 11.51 kNm
Muy (bottom joint) = 53.29 kNm
Vux (bottom joint) = -15.84 kN
Vuy(bottom joint) = -0.05 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 111
Combination
[11] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -0.0546 kN
Pu = 50.63
Design shear stress ,vEd = 0.0004 N/mm2
VRD,c = 95.7392 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.2893
Along B
Critical Analysis Load : 111
Combination
[11] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 5: WL-X) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -15.8371 kN
Pu = 50.63
Design shear stress ,vEd = 0.1077 N/mm2
VRD,c = 100.0219 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.2893
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C38
Level : 0m To 1.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1000 mm
Clear Floor Height @ D,loD = 1000 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 52
Critical Analysis Load : 168
Combination
[67] : (LOAD 1: DL) +(LOAD 3: CL) +1.5
Load Combination = (LOAD 2: LL) +0.9 (LOAD 6: WL+Z) +1.5
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 491.09 kN
Mux(top joint) = -382.75 kNm
Muy(top joint) = -48.32 kNm
Vux(top joint) = -32.22 kN
Vuy(top joint) = 255.23 kN
Ned(bottom joint) = 497.28 kN
Mux (bottom joint) = 0 kNm
Muy (bottom joint) = 0 kNm
Vux (bottom joint) = -32.22 kN
Vuy(bottom joint) = 255.23 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Final Critical Design Forces
Design Of Shear
Along D
Critical Analysis Load : 168
Combination
[67] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 6: WL+Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vuy = 255.2339 kN
Pu = 491.09
Design shear stress ,vEd = 1.6668 N/mm2
VRD,c = 197.1634 kN
As tension = 3848.44 sqmm
CRdc = 0.18/γc
= 0.12
deff = 438 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6761
ρ1 = Asmain / (b x deff)
<> = 0.02
k1 0.15
σcp = NEd / (B x D)
= 2.8062
Along B
Critical Analysis Load : 168
Combination
[67] : (LOAD 1: DL) +(LOAD 3:
CL) +1.5 (LOAD 2: LL) +0.9
Critical Load Combination =
(LOAD 6: WL+Z) +1.5 (LOAD 12:
TEL1)
Design shear force, Vux = -32.2208 kN
Pu = 491.09
Design shear stress ,vEd = 0.2241 N/mm2
VRD,c = 196.8311 kN
As tension = 3848.44 sqmm
CRdc = 0.18/γc
= 0.12
beff = 288 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8341
ρ1 = Asmain / (d x beff)
<> = 0.02
k1 = 0.15
σcp = NEd / (B x D)
= 2.8062
Shear check No Shear Reinforcement Required
Since VRD,C > Vux
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 400 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C38
Level : 1.5m To 4.5m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 2500 mm
Clear Floor Height @ D,loD = 2800 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 53
Critical Analysis Load : 112
Combination
[12] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 6: WL+Z) +0.9
(LOAD 12: TEL1)
Critical Location = Top Joint
Ned(top joint) = 338.89 kN
Mux(top joint) = -27.14 kNm
Muy(top joint) = -144.97 kNm
Vux(top joint) = -88.67 kN
Vuy(top joint) = -14.25 kN
Ned(bottom joint) = 355.59 kN
Mux (bottom joint) = -69.87 kNm
Muy (bottom joint) = 120.98 kNm
Vux (bottom joint) = -88.67 kN
Vuy(bottom joint) = -14.25 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 112
Combination
[12] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vuy = -14.2466 kN
Pu = 338.89
Design shear stress ,vEd = 0.0921 N/mm2
VRD,c = 149.6422 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
deff = 442 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6727
ρ1 = Asmain / (b x deff)
<> = 0.0096
k1 0.15
σcp = NEd / (B x D)
= 1.9365
Along B
Critical Analysis Load : 112
Combination
[12] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 6: WL+Z) +0.9 (LOAD
12: TEL1)
Design shear force, Vux = -88.673 kN
Pu = 338.89
Design shear stress ,vEd = 0.6073 N/mm2
VRD,c = 152.483 kN
As tension = 1482.84 sqmm
CRdc = 0.18/γc
= 0.12
beff = 292 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8276
ρ1 = Asmain / (d x beff)
<> = 0.0102
k1 = 0.15
σcp = NEd / (B x D)
= 1.9365
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
General Data
Column No. : C38
Level : 4.5m To 5.65m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 1150 mm
Clear Floor Height @ D,loD = 1150 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 236
Critical Analysis Load : 219
Combination
[118] : 1.1 (LOAD 1: DL) +1.1 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +0.9 (LOAD 5: WL-X) +1.5
(LOAD 12: TEL1)
Critical Location = Bottom Joint
Ned(top joint) = 66.58 kN
Mux(top joint) = 68.25 kNm
Muy(top joint) = 23.91 kNm
Vux(top joint) = -14.35 kN
Vuy(top joint) = 26.35 kN
Ned(bottom joint) = 66.58 kN
Mux (bottom joint) = 98.55 kNm
Muy (bottom joint) = 40.4 kNm
Vux (bottom joint) = -14.35 kN
Vuy(bottom joint) = 26.35 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 219
Combination
[118] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+0.9 (LOAD 5: WL-X) +1.5 (LOAD
12: TEL1)
Design shear force, Vuy = 26.3542 kN
Pu = 66.58
Design shear stress ,vEd = 0.1696 N/mm2
VRD,c = 97.8637 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.3804
Along B
Critical Analysis Load : 219
Combination
[118] : 1.1 (LOAD 1: DL) +1.1
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+0.9 (LOAD 5: WL-X) +1.5 (LOAD
12: TEL1)
Design shear force, Vux = -14.3499 kN
Pu = 66.58
Design shear stress ,vEd = 0.0976 N/mm2
VRD,c = 102.0315 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.3804
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm
Provided spacing = 225 mm
General Data
Column No. : C38
Level : 5.65m To 9.05m
Design Code = EN 02 - 2004
Grade Of Concrete (fck)
= C40/50 N/sqmm
(Cylindrical)
Partial Factor for Concrete ( γc) = 1.5
Partial Factor for Concrete ( γcd) = 1.2
Grade Of Steel (fyk) = Fy500 N/sqmm
Partial Factor for Reinforcement (
= 1.15
γ s)
Partial Factor for Reinforcement (
= 1
γsd)
Column B = 350 mm
Column D = 500 mm
Clear Floor Height @ B,loB = 3200 mm
Clear Floor Height @ D,loD = 3050 mm
No Of Floors = 1
No Of Columns In Group = 1
Minimum eccentricity check = Simultaneously (Both Axis)
Effective Length Along D = 1
Effective Length Along B = 1
Load Data
Analysis Reference No. = 54
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35 (LOAD 3: CL)
Load Combination = +1.5 (LOAD 2: LL) +1.5 (LOAD 7: WL-Z) +0.9
(LOAD 13: TEL2)
Critical Location = Top Joint
Ned(top joint) = 49.39 kN
Mux(top joint) = -3.37 kNm
Muy(top joint) = -49.04 kNm
Vux(top joint) = -16.54 kN
Vuy(top joint) = 1.09 kN
Ned(bottom joint) = 68.32 kN
Mux (bottom joint) = 0.34 kNm
Muy (bottom joint) = 7.17 kNm
Vux (bottom joint) = -16.54 kN
Vuy(bottom joint) = 1.09 kN
Minimum Eccentricity,
Since Axial Force is compressive, Min. Eccentricity check to be performed
Check,e0
Geometric imperfection, ei
θ0 = 0.005
αn = 1
αm = 1
θ1 = 0.005 Radian
Where
A = Moments directly from analysis
B = Moments due to minimum eccentricity
C = Moments due to geometrical imperfection
D = Max of (Manalysis+MGeo) , Mmin
E = Moment due to slenderness effect
F
= Mdesign+ M2 /2
Top.Bottom
F Mid = Moe+M2
Design Of Shear
Along D
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
Critical Load Combination =
(LOAD 3: CL) +1.5 (LOAD 2: LL)
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vuy = 1.093 kN
Pu = 49.39
Design shear stress ,vEd = 0.007 N/mm2
VRD,c = 95.5746 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
deff = 444 mm
k = MIN(1 + SQRT(200 / deff),2)
= 1.6712
ρ1 = Asmain / (b x deff)
<> = 0.0058
k1 0.15
σcp = NEd / (B x D)
= 0.2822
Along B
Critical Analysis Load : 117
Combination
[17] : 1.35 (LOAD 1: DL) +1.35
(LOAD 3: CL) +1.5 (LOAD 2: LL)
Critical Load Combination =
+1.5 (LOAD 7: WL-Z) +0.9 (LOAD
13: TEL2)
Design shear force, Vux = -16.5358 kN
Pu = 49.39
Design shear stress ,vEd = 0.1125 N/mm2
VRD,c = 99.8662 kN
As tension = 904.8 sqmm
CRdc = 0.18/γc
= 0.12
beff = 294 mm
k = MIN((1 + SQRT(200 / beff)),2)
= 1.8248
ρ1 = Asmain / (d x beff)
<> = 0.0062
k1 = 0.15
σcp = NEd / (B x D)
= 0.2822
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 8 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 20 = 240 mm
Min. dimension of column = 350 mm
Max. 400 mm = 300 mm