STANDART OPERATING PROCEDURE CONFIGURATION

FLOBOSS 103

Before configuring a Floboss using a PC/Laptop, make sure that you have equipments as follow:

1. Connecting FLOBOSS 103 to PC/Laptop


To make connection between PC/laptop and Floboss103 After connecting Hardware Floboss 103 to
PC/Laptop with USB Serial RS-232, Open ROCLINK 800 software.

User ID : LOI

Password : 1000

Alternatively, press Alt+Enter.


On directory tree or toolbar menu Click “ROC”  Direct connect

Make sure the connection status between the ROC and the FloBoss is ON-LINE (Green Color)

as indicated on the lower right hand of the display.

1. Meter Set Up

General
On toolbar menu Click “Meter”  Setup

Select General Tab

Write the Meter Tag and Meter Description for device identity

Set Meter Type  Orrifice

Calculation Standard 1992 AGA3 Parameter wil appear automatically

Set Flow Alarming  Disable

Input Pipe Diameter size value

Please input Pipe Inner Diameter size correctly refer to Piping Inner Diameter Chart

Input Orrifice Diameter size value

Set Low Flow Cut off  1,0 InH2O

Click “Apply”  “Update”


1.2 I/O Definition

Click Input Tab on Meter Setup Menu

Set Stacked DP Disable

Averaging Technique  Flow Dependent Linear

Click “Apply”  “Update”

Click the button bellow I/O Definition to select Pameter Preset for Static pressure, Static Pressure
and Temperature I/O Definition.

For Differential Pressure  Select AIN A1, EU


For Static Pressure  Select AIN A2, EU

For RTD  Select AIN A3, EU


1.3 Gas Quality

Click Gas Quality Tab On Meter Set Up Menu

Input data Gas Quality refer to Laboratory Analysis Result. Ensure Total Mole is 100%

Select Log Methane Adjust  Enable

Select Heating Value Basis  Wet

Select / Input Heating Value  Enter, enter heating value

Select / Input Specific Gravity  Enter, enter specific gravity

Select Gas Quality  Constant

Click “Apply”  “Update”  “OK”

2. Configure I/O (Input and Output)

2.1 Configurating I/O Differential Pressure.

On toolbar menu Click “Configure”  I/O  AI Point

Select Analog Input : “1-Diff Press”


Input the Low Reading EU and High Reading EU Value to set the Range of differential
pressure, Please refer to the floboss sensor data sheet or the Tag of specification.

Click “Apply”  “Update”

2.2 Setting I/O: Static Pressure

Select Analog Input : “2-Static”

Input the Low Reading EU and High Reading EU Value to set the Static pressure range,
Please refer to the floboss sensor data sheet or the Tag of specification.

Click “Apply”  “Update”

2.3 Setting I/O: RTD


Select Analog Input : “3-RTD”

Input the Low Reading EU and High Reading EU Value to set the Termperature range, Please
refer to the RTD specification.

Click “Apply”  “Update”  “OK”

4. Calculation Result

On toolbar menu Click “Meter”  Value

Click “Apply”  “Update”  “OK”

5. Configuration Display

On toolbar menu Click “Configure”  LCD User List

Click “Apply”  “Update”  “OK”


DP PRESS

STATIC
TEMP

FL RATE
FLTDAY

ENERGY
BATT

FLYEST