Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
http://biz.lgservice.com
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
TABLE OF CONTENTS
LG Model Name.................................................................................................................................3
Dimensions .....................................................................................................................................10
Installation.......................................................................................................................................12
Functions.........................................................................................................................................25
Operation ........................................................................................................................................28
Disassembly....................................................................................................................................38
LG Model Name
2003
1 2 - 3 4 5 6 7 8 9 10
Code Type Code of Model Meaning
2004~
1 2 - 3 4 5 6 7 8 9 10
Code Type Code of Model Meaning
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
■ Installation
Do not use damaged power cords, plugs, or a Always use the power plug and socket with the
loose socket. ground terminal.
Install the panel and the cover of control box Do not modify or extend the power cord.
securely.
• There is risk of fire of electric shock. • No grounding may cause electric shock.
For re-installation of the installed product, Do not install, remove, or re-install the unit by
always contact a dealer or an authorized ser- yourself.
vice center.
• There is risk of fire, electric shock, explosion, or • There is risk of fire, electric shock, explosion, or
injury. injury.
Be cautious when unpacking and installing the For installation, always contact the dealer or
product. an Authorized service center
• Sharp edges could cause injury. Be especially care- • There is risk of fire, electric shock, explosion, or injury.
ful of the case edges and the fins on the condenser
and evaporator.
Do not install the product on a defective instal- Be sure the installation area does not
lation stand. deteriorate with age.
• It may cause injury, accident, or damage to the • If the base collapses, the air conditioner could fall
product. with it, causing property damage, product failure,
and personal injury.
■ Operation
Do not turn the air-conditioner ON or OFF by Use a dedicated outlet for this appliance.
plugging or unplugging the power plug.
• There is risk of fire or electrical shock. • There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the Do not place a heater or other appliances near
outlet. Do not touch it with wet hands. the power cable.
• There is risk of fire or electrical shock. • There is risk of fire and electric shock.
Do not allow water to run into electrical parts. Do not store or use flammable gas or com-
bustibles near the air conditioner.
• There is risk of fire, failure of the product, or electric • There is risk of fire or failure of product.
shock.
x
Wa Thinner
Unplug the unit if strange sounds, odors, or Be cautious that water could not enter the
smoke comes from it. product.
• There is risk of electric shock or fire. • There is risk of fire, electric shock, or product dam-
age.
■ Installation
Always check for gas (refrigerant) leakage after Install the drain hose to ensure that water is
installation or repair of product. drained away properly.
• Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage.
Keep level even when installing the product. Use two or more people to lift and transport
the air conditioner.
• To avoid vibration or water leakage. • Avoid personal injury.
90˚
■ Operation
Use a soft cloth to clean. Do not use harsh Do not touch the metal parts of the product
detergents, solvents, etc. when removing the air filter. They are very
sharp!
• There is risk of fire, electric shock, or damage to the • There is risk of personal injury.
plastic parts of the product.
x
Wa
Do not step on or put anyting on the product. Do not insert hands or other objects through
(outdoor units) the air inlet or outlet while the air conditioner
is plugged in.
• There is risk of personal injury and failure of product. • There are sharp and moving parts that could cause
personal injury.
Dimensions
Symbols Used in this Manual
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the
air conditioner.
Indoor Unit
D
W
Installation plate
Model
24k Btu Series
Dimension
W mm 1090
H mm 300
D mm 178
Outdoor Unit
W
L2
L1
D
L3
L4
H
Liquid side
L7 L6 L8 L9
L5
MODEL
24k Btu Series
DIM
W mm 870
H mm 800
D mm 320
L1 mm 370
L2 mm 340
L3 mm 25
L4 mm 775
L5 mm 25
L6 mm 546
L7 mm 162
L8 mm 162
L9 mm 54
L10 mm 79
L11 mm 76.4
Installation
Selection of the Best Location
Indoor unit Rooftop Installations:
• Do not have any heat or steam near the unit. • If the outdoor unit is installed on a roof structure, be
• Select a place where there are no obstacles in front of the sure to level the unit. Ensure the roof structure and
unit. anchoring method are adequate for the unit location.
• Consult local codes regarding rooftop mounting.
• Make sure that condensation drainage can be conveniently
routed away.
Do not install near a doorway. Piping Length and Elevation
• Ensure that the space around the left and right of the unit is
more than "A". The unit should be installed as high on the Capacity Pipe Size Standard Max. Max. Additional
wall as possible, allowing a minimum of "B" from ceiling. Length Elevation Length Refrigerant
(Btu/h) GAS LIQUID (m) B (m) A (m) (g/m)
• Use a stud finder to locate studs to prevent unnecessary
damage to the wall. More than 24k 5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
More than
5cm A A
More
More than 70cm than 60cm
(3/16"~5/16")
Installation Plate
5-7mm
Chassis
Hook
• Open the Front Grille.
Type "A" screw
• Pass Telephone Control Cord Wire through the hole
which the power cord goes through.
2. Measure the wall and mark the centerline. It is • Connect Telephone Control Cord Wire to the phone jack
also important to use caution concerning the of telephone PCB of Control Box.
location of the installation plate-routing of the • Fix Telephone Control Cord Wire inside Control box so
wiring to power outlets is through the walls typi- as not to disconnect.
cally. Drilling the hole through the wall for pip- • Close the Front Grille.
ing connections must be done safely.
Adhesive
Only the
desired direction
Connecting
part
Drain
hose
Drain hose
Copper tube
Flaring work
• Firmly hold copper pipe in a die in the dimension shown in
the table above.
Handle When install, make sure that the
"A"
For right rear piping Connecting the pipings to the indoor unit and
drain hose to drain pipe.
Route the indoor tubing and the drain hose in the direction of
• Align the center of the pipes and sufficiently tighten
rear right.
the flare nut by hand.
Drain hose
Indoor unit tubing Flare nut Pipes
• Tighten the flare nut with a wrench.
Insert the connecting cable into the indoor unit from the out- Open-end wrench (fixed)
door unit through the piping hole.
Flare nut
• Do not connect the cable to the indoor unit.
Wrench Connection pipe
• Make a small loop with the cable for easy connection later.
Indoor unit tubing
Tape the tubing, drain hose, and the connecting cable. Be Outside diameter Torque
sure that the drain hose is located at the lowest side of the mm inch kg.m
bundle. Locating at the upper side can cause drain pan to Ø9.52 3/8 4.2
overflow inside the unit. Ø15.88 5/8 6.6
• When extending the drain hose at the indoor unit, install the
drain pipe.
Tape
Connecting
pipe Drain pipe
Drain hose
Connecting cable
Indoor unit drain hose
NOTE: If the drain hose is routed inside the room, insulate Adhesive
Vinyl tape(narrow)
the hose with an insulation material* so that dripping from Wrap the insulation material around the con-
"sweating"(condensation) will not damage furniture or floors.
necting portion.
*Foamed polyethylene or equivalent is recommended.
•Overlap the connection pipe insulation material and the
Indoor unit installation indoor unit pipe insulation material. Bind them together with
vinyl tape so that there is no gap.
• Hook the indoor unit onto the upper portion of the installa-
Plastic bands Insulation material
tion plate.(Engage the two hooks of the rear top of the
indoor unit with the upper edge of the installation plate.)
Ensure that the hooks are properly seated on the installa-
tion plate by moving it left and right.
• Wrap the area which accommodates the rear piping hous-
ing section with vinyl tape.
Connecting
cable
Connection Indoor
pipe unit pipe
Vinyl tape(narrow)
Vinyl tape(wide)
Drain hose Indoor unit tubing Flare nut Pipes
For left rear piping • Tighten the flare nut with a wrench.
Route the indoor tubing and the drain hose to
Open-end wrench (fixed)
the required piping hole position.
Flare nut
Drain pipe
• When extending the drain hose at the indoor unit, install the
drain pipe.
Insert the connecting cable into the indoor unit.
• Don't connect the cable to the indoor unit. Drain hose
• Make a small loop with the cable for easy connection later.
Tape the drain hose and the connecting cable.
Indoor unit drain hose
• Connecting cable
Vinyl tape (narrow)
Adhesive
Indoor unit
Spacer
Installation plate
8cm
• Wrap the area which accommodates the rear piping hous- Indoor unit installation
ing section with vinyl tape.
• Remove the spacer.
Connection Indoor
pipe unit piping • Ensure that the hooks are properly seated on the installa-
Vinyl tape
tion plate by moving it left and right.
Wrap with vinyl tape
(wide)
Pipe
Connecting
Vinyl tape(narrow) cable
Connecting cable
Drain hose
Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their
• Bundle the piping and drain hose together by wrapping slots(clicking sound).
them with cloth tape over the range within which they fit
into the rear piping housing section.
Pipe
Drain hose
Vinyl tape(narrow) Installation Information (For left piping)
• Good case
For left piping. Follow the instruction below.
Wrap with • Press on the upper side of clamp. ( )
vinyl tape(wide)
Piping for
passage through
piping hole
Set the pipings and the drain hose to the back
of the chassis with the tubing holder.
• Hook the edge of tubing holder to tap on chassis and push
the bottom of tubing holder to be engaged at the bottom of
chassis.
Tubing holder
Outdoor unit
Gas side piping
(Bigger diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench
The power cord connected to the "A" unit should be selected according to the following specifications(Type "B"
approved by HAR or SAA).
(mm2)
Grade
NORMAL CROSS
24k
-SECTIONAL AREA
2.5
Unit(A) Indoor
Cable Type(B) H05VV-F
The power connecting cable connecting the indoor and outdoor unit should be selected according to the following
specifications (Type "B" approved by HAR or SAA).
(mm2)
Grade
NORMAL CROSS
24k
-SECTIONAL AREA
2.5
Cable Type(B) H07RN-F
Cover control
Refix the control cover to the original position
with the screw.
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring,
be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations
to which the unit is subjected during the course of transportation. Check them and make sure that they are
all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness. (Refer to page 21))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func-
tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air
gap contact separation of at least 3mm in each active(phase) conductors.
Pipings
Connecting
cable
Air Purging
Air purging • Do a leak test of all joints of the tubing(both indoor and out-
door) and both gas and liquid side service valves.
Air and moisture remaining in the refrigerant system have Bubbles indicate a leak. Be sure to wipe off the soap with a
undesirable effects as indicated below. clean cloth.
• Pressure in the system rises. • After the system is found to be free of leaks, relieve the
• Operating current rises. nitrogen pressure by loosening the charge hose connector
at the nitrogen cylinder. When the system pressure is
• Cooling(or heating) efficiency drops.
reduced to normal, disconnect the hose from the cylinder.
• Moisture in the refrigerant circuit may freeze and block cap-
illary tubing.
• Water may lead to corrosion of parts in the refrigeration
system. Indoor unit
Therefore, the indoor unit and tubing between the indoor and
outdoor unit must be leak tested and evacuated to remove
any noncondensables and moisture from the system.
If tubing length is less than 10m (33 ft) if tubing length is longer than 10m (33 ft)
Test Running
1. Check that all tubing and wiring have been properly con- NOTE: If the actual pressure is higher than shown, the system is
nected. most likely over-charged, and charge should be removed.
2. Check that the gas and liquid side service valves are fully If the actual pressure are lower than shown, the system is
open. most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
Settlement of outdoor unit
PUMP DOWN
• Anchor the outdoor unit with a bolt and nut(ø10mm) tightly
This is performed when the unit is to be relocated or
and horizontally on a concrete or rigid mount. the refrigerant circuit is serviced.
• When installing on the wall, roof or rooftop, anchor the Pump Down means collecting all refrigerant in the outdoor
unit without loss in refrigerant gas.
mounting base securely with a nail or wire assuming the
influence of wind and earthquake. CAUTION:
• In the case when the vibration of the unit is conveyed to the Be sure to perform Pump Down procedure with the unit
hose, secure the unit with an anti-vibration bushing. cooling mode.
Tubing connection 4. Turn on the unit's operating switch and start the cooling
operation.
Evaluation of the performance 5. When the low-pressure gauge reading becomes 1 to
Operate unit for 15~20 minutes, then check the system 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side
refrigerant charge: valve stem and then quickly turn off the unit. At that time,
1. Measure the pressure of the gas side service valve. Pump Down has been completed and all refrigerant gas
will have been collected in the outdoor unit.
2. Measure the temperature of the intake and discharge of air.
Power-Failure Compensation Function User Selection ON/OFF
3. Ensure the difference between the intake temperature and
the discharge is more than 8°C(46°F) (Cooling) or 1) Operation Sequence
(Heating). Press the forced switch until BUZZER sounds 2 times
(beep~beep~).
Intake temperature
Release the forced switch if BUZZER sounds.
Discharge air
Check the function selection ON/OFF with the operation LED.
Power
button
Functions
Indoor Unit
Auto Changeover
Energy-Saving Control(Optional)
Auto Clean(Optional)
Plasma
• The function will be operated while in any operation mode with selecting the function.
• The function is to be stopped while it isoperating with selecting the function.
Heater (Optional)
Outdoor Unit
• High speed
- Although fan motor speed is middle, it will change high speed in case of below AC193V, over 45°C of
outdoor temp., and over fc, fh of comp. Freq.
• Low speed
- Although fan motor speed is middle, it will change Low speed in case of over AC 270V, over 21°C
(Heating Mode) of outdoor temp. below 24°C (Cooling Mode) of outdoor temp.
Low Ambient
Operation
Function of Controls
• DISPLAY
1) C/O Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
2) H/P Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
• OFF except when hot start during heating mode operation or while in defrost control.
Indoor pipe
Comp. free temp.
6˚C 7˚C
Comp. Step 4
3˚C Comp. Step 2
0˚C
Comp. off
Defrost Control(Heating)
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 35 minutes passed from
starting of heating operation and more than 4 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature
rises over 15°C even before 12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 35 minutes passed
from ending of the first defrost and more than 4 minutes operation of compressor.
On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
■ CT2 control
• If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the
compressor restart again.
• If CT2 occurs 5 times within 1hour, the appliance turn off and display ERROR CODE 22.
I1
Model Outdoor temp ≥ 38°C Outdoor temp < 38°C I2
Cooling Heating Cooling Heating
AS-W2465DH0 13.5 13.5 14 14 15.5
AS-W2465DH1 13.5 13.5 14 14 15.5
cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.
Swing mode
1. New Chaos swing mode
• By the Chaos swing key input, the upper/lower vane automatically operates with the Chaos swing or it is
fixed to the desired direction.
Cooling ON temp.
(Setting temp. +0.5˚C)
Forced operation
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch
is on the main unit of the appliance to operate the appliance in the standard conditions.
• The operation condition is set according to the outdoor temp. and intake air temperature as follows.
Setting speed of
Indoor temp. Operating Mode Setting temp.
indoor fan
T1 °C
T on °C
COMP
Freq. Free Fc-1 Fc-2 Fc-1 Fc-2 OFF Free
T1 °C
-13 °C
COMP Freq. Fh min Free Fc-1 Fc-2 OFF Fc-2 Fc-1 Free
Defrosting control
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing,
reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
• Defrosting control is available 50 minutes later since heating cycle started and the pipe temperature of out-
door unit reaches below -6°C.
Starting step
EEV Setting
Open step
ON ON
4-Way
Setting OFF Setting
Outdoor Speed Speed
FAN
Hi Speed
Setting
Speed
Indoor
Hot Hot
FAN Start
OFF Starting
Pre-Heat ON
OFF OFF
LED
Deice STEP 0 1 2 3 4 5 6
Auto Cleaning
• Function used to perform the Self Cleaning to prevent the Unit from Fungus and Bad Odors.
• Used after the Shut Down of Cooling Operation to Clean the Evaporator and keep it as fresh for the Next operation.
• During Self Cleaning the Outdoor Unit is Switched off.
• The function is easy to be operated as It is accessed through the Remote Controller.
Auto Changeover
Outdoor
• The air conditioner changes the operation temp.
mode automatically to keep indoor tempera-
Outdoor temp.
ture.
+2°C Indoor temp.
• When room temperature vary over ±2°C with 30°C
respect to setting temperature, air condition- +1°C
er keeps the room temperature in ±2°C with +0.5°C
respect to setting temperature by auto Set Temp.
-0.5°C 20°C
change mode.
-1°C
-2°C
Auto 10°C
Change COOLING HEATING
Mode.
Low Ambient
• If outdoor temperature drops below certain temperature,liquid back is prevented by reducing fan speed.
It can prevent frosting of evaporator and keep cooling operation
• No matter even if the outdoor temperature reaches -10°C.
• You can Cool your room at your desired temperature all your around.
25
Comp Freq.
Cond . temp. Outdoor temp.:-10°C
20
Freq.
15
Temp.(°C)
Outdoor fan
10
On On Outdoor pipe temp. Outdoor fan On/Off control
° outdoor fan On/Off
0°C 5
Off Off control 0
0 50 100 150 200
°…
- 0°C Outdoor temp. -5
Time(Min.)
Disassembly
Indoor Unit
Earth
Conductor
Screw
Motor cover
Cross-flow fan
Troubleshooting Guide
Refrigeration Cycle Diagram
Cooling & Heating Models
INDOOR UNIT OUTDOOR UNIT
LIQUID SIDE
HEAT HEAT
EXCHANGE EXCHANGE
(EVAPORATOR) (CONDENSER)
GAS SIDE
REVERSING
3-WAY VALVE
ACCUMU VALVE
LATOR
COMPRESSOR COOLING
HEATING
Valve cap
Hexagonal wrench (4mm) Open position
Flare nut Flare nut Closed position
Open position
Closed position Pin
To To
piping piping Service Service
connection connection port cap port
To outdoor unit To outdoor unit
Air purging
Required tools : hexagonal wrench, adjustable wrench, The air in the indoor unit and in the piping must be
torque wrenches, wrench to hold the purged. If air remains in the refrigeration pipes, it will
joints, and gas leak detector. affect the compressor, reduce to cooling capacity,
and could lead to a malfunction.
The additional gas for air purging has been charged
in the outdoor unit.
However, if the flare connections have not be done
correctly and there gas leaks, a gas cylinder and the
charge set will be needed.
Gas side
Clsed
3-way
valve
CAUTION: Do not leak the gas in the air during Air purging.
• Procedure
(6) Set the 3-way valve to the back seat.
(1) Recheck the piping connections. (7) Mount the valve stem nuts to the 2-way and 3-
(2) Open the valve stem of the 2-way valve coun- way valves.
terclockwise approximately 90°, wait 10 sec- (8) Check for gas leakage.
onds, and then set it to closed position. – At this time, especially check for gas leakage
– Be sure to use a hexagonal wrench to operate from the 2-way and 3-way valve’s stem nuts,
the valve stem. and from the service port nut.
(3) Check for gas leakage.
– Check the flare connections for gas leakage.
CAUTION: If gas leakage are discovered
in step (3) above, take the following
(4) Purge the air from the system.
mesures :
– Set the 2-way valve to the open position and
If the gas leaks stop when the piping connections
remove the cap from the 3-way valve’s service
port. are tightened further, continue working from step (4).
– Using the hexagonal wrench to press the valve If the gas leaks do not stop when the connections
core pin, discharge for three seconds and then are retightened, repair the location of the leak, dis-
wait for one minute. Repeat this three times. charge all of the gas through the service port, and
(5) Use torque wrench to tighten the service port then recharge with the specified amount of gas from
nut to a torque of 1.8kg.cm. a gas cylinder.
Pumping Down
Gas side
Closed
3-Way
valve
Lo
CLOSE CLOSE
• Procedure
(6) Operate the air conditioner at the cooling
(1) Confirm that both the 2-way and 3-way valves cycle and stop it when the gauge indicates
are set to the open position. 1kg/cm2g.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position. (7) Immediately set the 3-way valve to the closed
– Be sure to use a hexagonal wrench to operate position.
the valve stems. – Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm2g.
(2) Operate the unit for 10 to 15 minutes.
(8) Disconnect the charge set, and mount the 2-
(3) Stop operation and wait for 3 minutes, then way and 3-way valve’s stem nuts and the ser-
connect the charge set to the service port of vice port nut.
the 3-way valve. – Use torque wrench to tighten the service port
– Connect the charge hose with the push pin to nut to a torque of 1.8 kg.m.
the service port. – Be sure to check for gas leakage.
Re-air Purging
(Re-installation)
Gas side
Closed
3-Way
valve
Gas cylinder
Lo
R22 OPEN CLOSE
• Procedure
(6) Disconnect the charge set and the gas cylin-
(1) Confirm that both the liquid side valve and the der, and set the Liquid side and Gas side
gas side valve are set to the closed position. valves to the open position.
– Be sure to use a hexagonal wrench to operate
(2) Connect the charge set and a gas cylinder to the valve stems.
the service port of the Gas side valve.
– Leave the valve on the gas cylinder closed. (7) Mount the valve stem nuts and the service
port nut.
(3) Air purging. – Use torque wrench to tighten the service port
– Open the valves on the gas cylinder and the nut to a torque of 1.8 kg.m.
charge set. Purge the air by loosening the flare – Be sure to check for gas leakage.
nut on the liquid side valve approximately 45°
for 3 seconds then closing it for 1 minute; CAUTION: Do not leak the gas in the air
repeat 3 times. during Air Purging.
– After purging the air, use a torque wrench to
tighten the flare nut on liquid side valve.
Gas side
3-Way
valve Open
Lo
OPEN CLOSE
• Procedure
(1) Confirm that both the 2-way and 3-way valves (3) Open the valve (Lo side) on the charge set and
are set to the back seat. discharge the refrigerant until the gauge indi-
cates 0 kg/cm2G.
(2) Connect the charge set to the 3-way valve’s – If there is no air in the refrigerant cycle (the
port. pressure when the air conditioner is not running
– Leave the valve on the charge set closed. is higher than 1 kg/cm2G), discharge the refrig-
– Connect the charge hose to the service port. erant until the gauge indicates 0.5 to 1
kg/cm2G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.
Evacuation
(All amount of refrigerant leaked)
Gas side
3-Way
valve Open
Vacuum pump
Lo
OPEN CLOSE
• Procedure
(1) Connect the vacuum pump to the center hose (3) Close the valve (Lo side) on the charge set,
of charge set center hose turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
(2) Evacuation for approximately one hour. tely 5 minutes after turning off the vacuum
– Confirm that the gauge needle has moved pump).
toward -76 cmHg (vacuum of 4 mmHg or less).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
Gas Charging
(After Evacuation)
Gas side
Open
3-Way
Check valve valve
Charging
cylinder
Lo
(1) OPEN CLOSE
• Procedure
\
(1) Connect the charge hose to the charging This is different from previous procedures.
cylinder. Because you are charging with liquid refrigerant
– Connect the charge hose which you dis-con- from the gas side, absolutely do not attempt to
nected from the vacuum pump to the valve at charge with larger amounts of liquid refrigerant
the bottom of the cylinder. while operating the air conditioner.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys-
tem can be charged with liquid. (4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
(2) Purge the air from the charge hose. – Stopping partway will allow the gas to be dis-
– Open the valve at the bottom of the cylinder charged.
and press the check valve on the charge set to – If the system has been charged with liquid
purge the air. (Be careful of the liquid refriger- refrigerant while operating the air conditioner
ant). The procedure is the same if using a gas turn off the air conditioner before disconnecting
cylinder. the hose.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant. (5) Mount the valve stem nuts and the service
– If the system can not be charged with the spec- port nut.
ified amount of refrigerant, it can be charged – Use torque wrench to tighten the service port
with a little at a time (approximately 150g each nut to a torque of 1.8 kg.m.
time) while operating the air conditioner in the – Be sure to check for gas leakage.
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure (pumping down-pin).
Self-diagnosis Function
■ Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.
Indoor Error
LED 1 LED 2 Indoor
Error code Description INV TPS
(Red) (Green) Status
00 No Error ON
01 Indoor Room themistor error 1time OFF
02 Indoor in-piping sensor error 2times OFF
05 Communcation error between in and out 5times OFF
06 Indoor Out-Piping sensor error 6times OFF
Outdoor Error
LED 1 LED 2 Indoor
Error Code Description INV TPS
(Red) (Green) Status
21 DC Peak (IPM Fault) 2times 1time OFF
22 CT 2(Max CT) 2times 2times OFF
23 DC Link Low Volt. 2times 3times OFF
24 L_P/Heater Sink 2times 4times OFF
25 Low voltage / Over voltage 2times 5times OFF
26 DC Comp Position Error 2times 6times OFF
27 PSC Fault Error 2times 7times OFF
28 DC Link High Volt 2times 8times OFF
32 D-Pipe High (INV) 3times 2times OFF
33 D-Pipe High (Normal) 3times 3times OFF
40 CT Sensor (Open/Short) 4times O OFF
41 INV. D-PipeTh Error(Open/Short) 4times 1time OFF
44 Outdoor air Th Error(Open/Short) 4times 4times OFF
45 Cond. Pipe Th Error(Open/Short) 4times 5times OFF
46 Suction Pipe Error(Open/Short) 4times 6times OFF
47 Const D-pipe Th Error(Open/Short) 4times 7times OFF
51 Capacity over 5times 1time OFF
53 Signal error (Indoor ↔ Outdoor) 5times 3times OFF
60 EEPROM Check Sum Error 6times O OFF
61 Cond. Pipe High 6times 1time OFF
62 Heatsink High 6times 2times OFF
63 Cond. Pipe Low 6times 3times OFF
65 Heatsoml Th error (Open/Short) 6times 5times OFF
Trouble analysis
1. Check temperature difference between intake and discharge air, and operating current.
Temp. Difference
Temp. difference : approx. 8°C Refrigerant leakage
Current : less than 80% of Clog of refrigeration cycle
rated current Defective compressor
Operating Current
Temp. difference : less than 8°C
Excessive amount of refrigerant
Current : near the rated
current
NOTICE
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
Higher
Normal Excessive amount of High pressure does not quickly
refrigerant rise at the beginning of operation.
NOTICE
1. The suction pressure is usually 4.5~6.0 kg/cm G at normal condition.
2
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
Electronic Parts
❇ Refer to electronic contorol device drawing & schematic diagram.
NO YES
While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 2 minutes after stopped.
When the mark ( ) is displayed in LCD Check the contact of CN-DISP 1, 2 connector
screen, replace battery.
Check point
• Check the connecting circuit between
MICOM PIN and CN-DISP1 PIN
• Check receiver ass'y
LED01G
(RED)
1 Sec. 1 Sec. 1 Sec.
1 Time 1 Time 1 Time
LED02G
(GREEN)
2 Sec. 2 Sec.
24 Low / High press 2 times 4 times Low / High press switch OPEN Off
41 D-pipe sensor INV. (open/ short) 4 times 1 time Open / Short Off
45 Cond. Pipe sensor (open/ short) 4 times 5 times Open / Short Off
46 Suction pipe sensor (open/ short) 4 times 6 times Open / Short Off
47 D-pipe sensor Cons. (open/ short) 4 times 7 times Open / Short Off
61 Cond. Pipe sensor temp. high 6 times 1 time Cond. Temp. high Off
62 Heat sink sensor temp. high 6 times 2 times Heat sink temp. high Off
65 Heat sink sensor (open/ short) 6 times 5 times Open / Short Off
Display
Title Cause of error Check point & Normal condition
code
• Open / Short
Indoor air sensor • Soldered poorly Normal resistor : 10KΩ/ at 25°C (Unplugged)
01
• Internal circuit error Normal voltage : 2.5Vdc / at 25°C (plugged)
• Open / Short
Normal resistor : 5KΩ/ at 25°C (Unplugged)
02 Indoor inlet pipe sensor • Soldered poorly
Normal voltage : 2.5Vdc / at 25°C (plugged)
• Internal circuit error
• Open / Short
Normal resistor : 5KΩ/ at 25°C (Unplugged)
06 Indoor outlet pipe sensor • Soldered poorly
Normal voltage : 2.5Vdc / at 25°C (plugged)
• Internal circuit error
10kΩ 2.5Vdc
Ω V
Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor.
3. If the resistance of the sensor is 10KΩ/ 5KΩ at 25°C, then sensor is normal.
4. If the resistance of the sensor is 0 KΩ or ∞, then sensor is abnormal. → Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc at 25°C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. → Repair or Change the PCB.
2) Troubleshooting CH21
Display
Title Cause of error Check point & Normal condition
code
• An instant over current in the U,V,W phase
- Comp lock
• Instant over current - The abnormal connection of U,V,W
21 DC Peak • Over Rated current • Over load condition
• Poor insulation of IPM - Overcharging of refrigerant
- Pipe length.
• Poor insulation of compressor
Comp
U Resistance(Ω) at 20°C
Inverter Constant
Ω Terminal
comp. comp.
V W U-V 0.64 0.8
V-W 0.64 0.8
W-U 0.64 0.8
Copper
Comp pipe Resistance(Ω) at 20°C
Inverter Constant
Terminal
Ω comp. comp.
U-GND 2MΩ 2MΩ
V-GND 2MΩ 2MΩ
W-GND 2MΩ 2MΩ
Check Point
1. Check the wire connection. (U,V,W)
2. Check the load condition. (Refrigerant, Pipe length, …) → Adjust the load condition
3. Check the electricity leakage of the compressor. → Normal : Over 2MΩ.
4. Check the resistance of compressor. → Normal : 0.65Ω(INV), 0.8Ω(Cons.) → No difference at each terminal.
5. Check the insulation from water at IPM part. → Check the trace of water.
6. Check the IPM circuit.
3) Troubleshooting CH22
Display
Title Cause of error Check point & Normal condition
code
Malfunction of current detection circuit.
C/T (Open / Short)
22 Initial current error
Internal circuit The voltage of “C01N” Is 4.0Vdc(25A) .
Check Point - +
1. Check the power source. + -
2. Check the fan operation is right.
+ -
3. Check the current.
4. Check the install condition.
5. Check the internal circuit. (C/T, Diode, Resistor)
Display
Title Cause of error Check point & Normal condition
code
Check Point
1. Check the power source.
2. Check the components
(B/Diode, Reactor, PSC Parts )
Display
Title Cause of error Check point & Normal condition
code
TRANS1
50Hz, DC12V
CN PRESS
CN TRNAS1
Check Point
• CH 24 • CH 25
1. Check the connection of “CN_PRESS” 1. Check the power source.
2. Check the install condition for over load. 2. Check the components
3. Check the SVC V/V open. (Trans1, B/Diode, Diode, Resistance)
Display
Title Cause of error Check point & Normal condition
code
B
E
Check Point
• CH 26 • CH 27
1. Check the connection of “U,V,W” 1. Check the component of “IGBT”
2. Check the insulation of IPM part. 2. Check the components
3. Check the compressor. (same with CH21) (IGBT, R04S, NF1, BD02S)
Display
Title Cause of error Check point & Normal condition
code
Check Point
• CH 51 • CH 60
1. Check the indoor unit capacity. 1. Check the insertion condition of EEPROM.
2. Check the poor soldering
Display
Title Cause of error Check point & Normal condition
code
Toff °C
T2 °C
T1 °C
COMP Frequency
Normal Normal OFF Normal
(Hz)
Check Point
• CH 61 • CH 62
1. Check the install condition for over load. 1. Check the fan is locked.
(Refrigerant, Pipe length, Blocked, …) 2. Check the Outdoor temp. is very high.
Schematic Diagram
Wiring Diagram
Indoor Unit
Models: AS-W2465DH0, AS-W2465DH1
Outdoor Unit
Models: AS-W2465DH0, AS-W2465DH1
Components Location
Indoor Unit
Models: AS-W2465DH0, AS-W2465DH1
• TOP VIEW
• BOTTOM VIEW
BD02S
CN_OIL/S
CN_PRESS
BD01S
PTC
C08J
C10J
CN_FAN(A) CN_FAN(B)
CN_HEATER2 CN_4WAY CN_HOT GAS CN_HEATER CN_P/ICE
C07J
CN_C/COMP2 CN_C/FAN TRANS1
C09J
R05J
3 1
CN-COIL1
+
J26
J29
J27
4
J28
J30
J32
3
R01V
J31
J21
J23
J25
J24
J22
RY_PWR
~
+
~
-
C04S
R05V
CN-COIL2
R04S
C01K
RY_C/COMP
ZD02K
D02K
R04V
R05K
IGBT
R06V
R02J
R03J
ZD01K
D01V
CT
BD01C
C05J C06J
C06S
R05S R04C
IC01V
R01S
C03C
4 3
R02S D01C
C02K
NTC01K R04J
D01S IC01S CN_GND2
D01K
C09S
(BK)
R02C
D02C
D02N
D01N
R02N
R05C
R01N
R08V
R03C
R01C
R06C
BD01N
C01C
ZNR01J ZNR02J
DISP_B
SURGE
CN_TH5/D3
IC11K
ZD05K
CN_CT/SUB
C19Z
C01F
R03K
IC02S
R01K
R12K
IC02K
LED01G
CN_JIG_S
C01S SW1 -
LED02G
ZD04K
+
IC01K
R01Y
R03S
R02Y NOMAL
Q01C
LONG R13K
IC04K
C01N
PIPE LENGTH C04J
C08Z
(DISP_C)
CN_TH4
CN_MOTOR JIG ZD03K
C06H
IC03K
ADDR_S/W
R04K
C02F
R02K
- +
CN_ADDR1
R26K
IC06K
C05H
D01Z
R13Z
D01Y
R07C
R03Y
C01Y
ZD06K
C02C
(SUC/DISP_I)
22
IC05K
CN_TH3
C08D
C04H
CN_ADDR2
R14Z R27K
IC08K
20 32(P)
C05D SUC/DISP_A
R07M
R08M
R06M
ZD01F
R05M
R01M
R04M
R03M
R02M
D02Z
R04F
C10Z ZD08K
J60
J59
J34
CN_TH1
C01H
J53
J54
J55
J52
J33
J51
18
IC07K
J57
J56
J58
(H/SINK)
L02D
R15Z EEPROM
R04P
NF01J
C10D R02D ZD07K
OSC01B
31(W)
W
IC09K
15
C03H
(YL) R06F
R28K
D03Z
C04D
(AIR/PIPE)
CN_TH2
IC10K
30(V)
13 V
13
12
L03D R29K
(BL)
CN_ADDR3
D01D
C02H
C12Z
PWB:6870A90154A
IC12K
C01D
C01A
29(U)
U
IC01A
10
ASM:6871A10117
(RD)
R31K
R17K
R16K
R30K
R36K
R35K
R32K
R33K
R37K
R34K
R15K
R14K
28(NW)
CN_FLASH
CN_WRITER
L01D
27(NV)
R01J
+
5
R21P
26(NU)
ASM:6871A20679
-
R17Z
R16Z
R17P
R16P
R15P
1
25
C02D
1 24 CN_GND1
C02J C03J
(BK)
SMPS C06D
CN_LEV3 CN_LEV5
C07D
D08K
D07K
D03K
D06K
D05K
D04K
C01J
C03D
CN_CP(N)
CN_CP(L)
R02P IC04D WCN_P(L)
R12P CN_COM1
CN_COM
CN_LEV1 CN_LEV2 CN_LEV4 CN_LEV6
L
R01P R11P
(BR)
R14P CN_CENTRAL
CN_JIG_PC 2004.10.24. lab2
WCN_GND3 FUSE 15A
20A
• BOTTOM VIEW
J80C
SSERP_NC
S/LIO_NC
J01C
S10DB
)A(NAF_NC
J90C
CTP
J70C
62J
72J
92J
03J
23J
82J
J50R
J20FN
12J
13J
32J
22J
42J
52J
CN-COIL1 1SNART
RWP_YR
CN-COIL2
V50R
V30R
TC
V20R
V40R
S40R
TBGI
V60R
J20R
J30R
S40C
K10C
V10D
K10DZ
C10DB
K20DZ
K50R
K20D
S90C
J50C J60C
S30C S20C
PMOC/C_YR
S50R
S10R
C30C
S10D S20R
J40R 2DNG_NC
S90C
C10D
K10D
C30R
C10R
C50R
C20D
C60R
N20D
N10D
N10R
V80R
C20R
N20R
EGRUS
C10C
S50C
K11CI
K30R
G20R
K10R
T60C
G10R
K21R
F10C V70R
K01R
K20CI
S_GIJ_NC
G10DEL
K40DZ
K60R
G20DEL
S70C
Y10R Y20R
T22R
1WS
S70R
S60R
K10CI
N10C
H61R
H51R
T40R
S30R
1RO
K11R
T02R
T30C
Z81C
Y10D
K40CI
H80R
C70R
S80C
M10C
H21C
V10C
Y30R
H01C
H60R
ADDR_S/W
K70R
Y10C
N20C
M20C
Z80C
4HT_NC
T41R
H41R
H70C
K30CI
H60C
K40R
N30R
K20R
F20C
K81R
K62R
F30R
Z10D
F10Q
SPM2
F20R
T20C
M50R
M40R
M60R
M70R
M80R
Z70C
M30R
1RDDA_NC
M20R
M10R
K60CI
K22R
H50R H31R
H80C
H90C
H11C
H50C
A2
H70R K60DZ
F10R
23
0C
S10C
I
K83R
22 Z31R
3HT_NC
K50CI
MORPEE
F50R
Z41R K32R
H40R
K72R
K91R
H40C
21
D80C
Z80R
20 Z20D
P
K80CI
L10R
L20R
D90C
H21R
2RDDA_NC
K80DZ
Z20C
F40R
F10DZ
19 D50C 1
Z01C
K93R
K80R
M60CI
B10CSO
18
H90R
1HT_NC
45J
15J
25J
35J
55J
06J
43J
95J
33J
85J
75J
65J
H10C
K70CI
D20L
Z90C W K70DZ
A20C
A30R
K61C
K90R
Z51R
T81R
F30C
K71C
W
K04R
17
Z40C
T51R
J10FN
D01C
H10R
16 D20R
K90CI
15
K70C
K60C
B10R
K02R
M11R
M50C
P40R
K82R
V F60R
H30R
H30C
Z01R
T61R
K11C
14 V
Z30D
K01CI
Z21C
2HT_NC
K80C
K42R
A10C
K90C
D10D
L10C
D40C
13
A10R
F70R
K92R
K21C
A20R
K41C
H11R
T71R
K01C
13
12
7
Z11C
H20C
U D30L
12
M01C
M01R
M40C
K21CI
Z60C
Z50R
T01R
11 U
Z21R
Z71R
Z31C
10
A10CI
Z02R
K52R
K12R
T10R
A30C
3RDDA_NC
H01R
SPMS
H20R
P12R
9
D10C
Z81R
8 Nw 28 M50CI
RETIRW_NC
Z61R
Z91R
7
T10C
Z90R
T90R
Z60R
K31C
K51C
M40CI
Z41C
M90CI
6 Nv 27
D10L
J10R
5
Z71C
4 2MPS Nu 26
P81R
M80CI
K43R
K41R
HSALF_NC
K73R
K71R
K61R
K51R
Z30C Z50C
K53R
K63R
K23R
K03R
K13R
K33R
3
D20C
1
M90R
2
3
P91R
25
P70C
P02R
P60C
Z10R
P80C
Z20R
Z40R
Z30R
Z10C
1 24 1DNG_NC
J20C J30C
Z11R
M30C
Z70R
D60C
Z51C
P51R
P71R
P61R
M70C
)N(PC_NC
M70CI N
P90R
P30C
T10Q
K70D
K60D
K40D
K30D
K80D
K50D
P30R P31R
T11R
D40CI
Z61C
T31R
P10CI 3VEL_NC
D30C
5VEL_NC
P50C
D70C
C08K J10C
M90C
T21R
P20R P21R
T60R
T50R
P20C
P70R
1MOC_NC
)L(PC_NC
T20R
P10R P11R L
P40C
ESUF
M11C
P50R
P10C
2VEL_NC 4VEL_NC
M60C
CP_GIJ_NC
P60R
P80R
P01R
P41R LARTNEC_NC
WCN_GND3
DISPLAY ASSEMBLY
– 6871A20624A
Product Specifications
Table-1
Model Name
AS-W2465DH0 AS-W2465DH1
Item Unit
W 3,867 3,867
MIN kcal/h.(W) 3,326 3,326
Btu/h. 13,200 13,200
W 7,030 7,030
Cooling Capacity Type kcal/h.(W) 6,048 6,048
Btu/h. 24,000 24,000
W 7,736 7,736
Max kcal/h.(W) 6,653 6,653
Btu/h. 26,400 26,400
W 3,369 3,369
MIN kcal/h.(W) 2,898 2,898
Btu/h. 11,500 11,500
W 8,440 8,440
Heating Capacity Type kcal/h.(W) 7,258 7,258
Btu/h. 28,800 28,800
W 8,879 8,879
Max kcal/h.(W) 7,636 7,636
Btu/h. 30,300 30,300
IN:20°C,Out: -10°C(Heater ON) Btu/h. - -
IN:20°C,Out: -10°C(Heater OFF) Btu/h. - -
Power Input Cooling W 2,500 2,500
Heating W 2,980 3,100
Heating(-10°C,Heater ON) W - -
Heating(-10°C,Heater OFF) W - -
Running Current Cooling A 11.5 11
Heating A 13 13.5
Heating(-10°C,Heater ON) A - -
Heating(-10°C,Heater OFF) A - -
Starting Current Cooling A 11 11
Heating A 13 13.5
Cooling kcal/hW 2.42 2.42
EER Btu/h.W 9.6 9.6
Heating kcal/hW 2.43 2.34
Btu/h.W 9.66 9.3
COP Cooling W/W 2.82 2.81
Heating W/W 2.83 2.72
Power Supply Ø,V,Hz 1,220-240,50 1,220-240,50
Power Factor % 97 97
Air Circulation Indoor,Max m3/min(CFM) 18.0(636) 18.0(636)
Outdoor,Max m3/min(CFM)
Moisture Removal l/h.(pts/h.) 3.2(6.7) 3.2(6.7)
Noise Level Indoor,High dB(A)±3 44 44
(Sound Med. dB(A)±3 - -
Pressure,1m) Low dB(A)±3 37 37
Outdoor,Max dB(A)±3 58 58
Refrigerant(R410A)Charge 1800 1800
Power Cord AWG#:P*mm2 3*2.5 3*2.5
Connecting Cable AWG#:P*mm2
Connecting Tube Liquid Side mm(in) 9.52(3/8) 9.52(3/8)
(Ø. Socket Flare) Gas Side mm(in) 15.8(5/8) 15.8(5/8)
Length,std m(in) 7.5(295) 7.5(295)
Drain Hose (O.D , I.D) mm(in) 21.5,16(0.85,0.63) 21.5,16(0.85,0.63)
Indoor mm 1090*300*178 1090*300*178
Dimension inch 42.9*11.8*7 42.9*11.8*7
(W*H*D) Outdoor mm 870*800*320 870*800*320
inch 34.25*31.5*12.6 34.25*31.5*12.6
Net Weight Indoor kg(lbs) 13(28.7) 13(28.7)
Outdoor kg(lbs) 60(132.3) 60(132.3)
Exploded View
Indoor Unit
Models: AS-W2465DH0, AS-W2465DH1
135316
152302
159830
135314
131410 733010
149304
342800
359011
135311
354210
147581
352115
346810
35211B
268711A 135516
352150
266090
263230B
W6640
264110
146811
263230A
Outdoor Unit
Models: AS-W2465DH0, AS-W2465DH1 (UE1 Chassis)
435512
137213A
435300
137213B
554031
549610
546810
552113
559010
649950
268711F
552116 435511
437211
263230D
447910
552202
561410
W0CZZ
554160
261704
550140 552203B
437210
435301 430411
349480 552203A