ETAP
The best things in life are free. This is what I felt when I am doing this exercise, comparing results from InterPSS with ETAP.
To verify on how an open source software match up to an expensive commercial software like ETAP, I tried comparing the
results side by side. I used ETAP 5.5.6 and InterPSS 1.4.04 in my comparison.
Utility:
Voltage: 132KV
Fault Capacity: 2000 MVA (3 phase), 2000 MVA (1 phase)
X/R: 7 (3 phase), 7 (1 phase)
Transmission Line:
Impedance
Positive: 0.243 + j0.143 ohms per km
Zero 0.39 + j0.36 ohms per km
Length: 15km
Transformer:
Capacity: 30 MVA
Voltage: 132/33KV
Z: 12.5%
X/R: 23.7
I did an ANSI 1/2 cycle fault calculation. The results are as follows:
If you analyze the results, the InterPSS has the same results as ETAP on the ANSI 1/2 cycle fault, except for a slight difference
on the L-L-G fault.
These results proves that InterPSS can be used for fault calculation without worrying about erroneous results. Please note
however, that in any automated calculation, the results is as good as the inputs. Try to be careful on the parameter values you
input into your fault calculation softwares.
Login Form
" Username
# Password
Remember Me
Log in
https://eeame.com/portal/tutorials/88-interpss-vs-etap.html 2/4
7/23/2019
A Visitor From eeame.com Electrical Engineers and Master Electricians (EEAME) Portal - InterPSS vs. ETAP
(https://eeame.com)
visited This Link
(https://eeame.com/portal/tutorials/1
15-earth-fault-loop-impedance-part-
1.html) From Gharyan,Jabal al Gharbi
00 Days, 00 Hours, 15 Minutes, and 31
Seconds Ago
Live DashBoard
(https://alivestats.com/live/stats/?
web=eeamecom) - Get Widget
(https://alivestats.com/install.php)
© 2019 Electrical Engineers and Master Electricians (EEAME) Portal Back to Top
https://eeame.com/portal/tutorials/88-interpss-vs-etap.html 4/4