Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
CE 502
REINFORCED CONCRETE DESIGN
Entitled as
Submitted by
BAGSIK, MA. ANGELICA F.
DELA CRUZ, BEATRICE ANN O.
MONTON, KARYLL ANN A.
Submitted to
Engr. Mico Cruzado
This project is entitled as “Design of Four- storey Medical Facility” is presented by Ma. Angelica F.
Bagsik, Beatrice Ann O. Dela Cruz, and Karyll Ann A. Monton , as partial fulfillment for the requirements for
CE 502 (Reinforced Concrete Design).
The project was about structural analysis and design of identified parts of a four storey reinforced
concrete medical structure. Design specifications from NSCP 2010 and NBCP were utilized in the design
process. The parts analyzed and designed included: beams, columns, and slabs. The parts of the building
chosen were considered to be the most critical due to the highest result computed through STAAD pro
considering all load combinations. Design schedule and member details of the structure were then created
for the design proper.
Chapter 1: Project Background
Figure 1.1 Perspective View of the Proposed Four Storey Medical Facility
The project is a four (4) – storey medical facility, allotted as a special occupancy building. The
medical building is generally shaped as rectangular, having a total floor area of 396 m² with a length of 22m
and width of 18 m, and a total height of 14.5 m situated in a 500 m2 lot. The design of a four (4) – storey
medical facility aims for the capacity hold and sustain medical needs. The design project has one (1)
access stairs located at the west side of the building and two (2) fire exit and one (1) ramp located at the
end-right corner side of the building facing the east of the building and two (two) elevators located at the
middle of the building. The ground floor level contains the emergency room, pharmacy, outpatient
department, accounting, and radiology department. The next succeeding floors from second (2nd) to fourth
(4th) floor contains the special function rooms such as operating room, delivery room, wards, NICU, ICU,
storage room, sterilizing room, dining, pediatric are, dietarian, record room, lounges and offices. Each floors
has waiting area, female and male comfort room, and nurse station..
Figure 1.2 Proposed four (4)- storey residential building project is located at Camarin, Caloocan
City © Google Maps
It is intended to be built in Camarin, Caloocan City. As a place that experiences scarcity in medical facilities
that provides medical services that is needed in the city, making a medical facility is proper.
To design the most suitable and effective four (4) – storey medical facility while using the acquired
knowledge, concepts and principles in Structural Analysis, and Reinforced concrete design that will provide
Caloocan city a four (4) – storey medical facility that is beneficial to human needs.
To apply all acquired knowledge, concepts and principles in Reinforced concrete design to
solve the stated problem.
To design the most suitable and effective method that will provide medical facility to the said
barangay.
To design the four (4) – storey medical facility in submission to the necessary codes and
standards, in consideration of the trade-offs based on multiple constraints.
The client for this design project is the Municipal Health Office of Caloocan City, represented by Mayor
Angelo Benedict C. Miton. In the likes of their government to provide the peoples need, the client desires
an economical and fast method of construction.
The ballpark figure allotted for the project is P 120 million and 1-2 years for the duration.
1.4 Scope and Limitations
1.4.1 Scope
Design of (4) – storey medical facility considering three (3) design trade-offs.
The project was designed with the accordance to the National Building Code of the Philippines
and National structural Code of the Philippines.
Analyze the structure using STAAD Pro V8i program
Provide design drawings as well as structural member details; and
Provide initial cost estimates of the structural works.
1.4.2 Limitations
The project does not include the detailed computations of plumbing, mechanical and electrical
plans and their cost estimates.
The design of elements other than Reinforced Concrete is included.
The construction, operation, and maintenance are not covered.
The shearwall was excluded in analysis.
Medical care facility refers to an institution, place, building or agency that furnishes, conducts, and
operates health services for the prevention, diagnosis, or treatment of human disease, pain, injury,
deformity, or physical condition. The health service offered by a medical care facility can be either medical
or surgical. Such services may be provided to: a. two or more non-related mentally or physically sick or
injured persons; or b. two or more non-related persons requiring or receiving medical, surgical, or nursing
attention or services. Of all municipal services, provision of medical service is perhaps the most vital.
People depend on medical facilities for treatment, surgery, recovery and so on.
Using the National Structural Code of the Philippines (NSCP) 2015, the designer was able to classify
the structure. With respect to the occupancy category, the building is classified as an Essential Facility.
With respect to the structural members, the building will have special moment resisting frames. These
data will help in designing the structure especially in the determination of the seismic forces acting on
the structure.
Is a composite material in which concrete's relatively low tensile strength and ductility are
counteracted by the inclusion of reinforcement having higher tensile strength or ductility. The reinforcement
is usually, though not necessarily, steel reinforcing bars (rebar) and is usually embedded passively in the
concrete before the concrete sets. Reinforcing schemes are generally designed to resist tensile stresses in
particular regions of the concrete that might cause unacceptable cracking and/or structural failure. Modern
reinforced concrete can contain varied reinforcing materials made of steel, polymers or alternate composite
material in conjunction with rebar or not. Reinforced concrete may also be permanently stressed (concrete
in compression, reinforcement in tension), so as to improve the behavior of the final structure under
working loads. In the United States, the most common methods of doing this are known as pre-tensioning
and post-tensioning.
For a strong, ductile and durable construction the reinforcement needs to have the following properties at
least:
As the name suggests this type of load does not change over time and acts permanently on the
building. In the euro code standards, dead loads are referred to as permanent actions. The definition states
that “the self-weight of construction works should be classified as a permanent fixed action.” (EN 1991-1-
1:2002, 12) Permanently fixed structure such as finishing that remains fixed is also classified as dead load.
The total weight of a structure might not be directly available in most cases. Also, redesigning theIstructure
leads to change in total weight. Material properties such as density and volume of the individual members
of the structure are used to calculate the weight.
As stated in Section 204 of the National Structural of the Philippines: “Dead loads consist
of the weight of all materials of construction incorporated into the building or other structure, including but
not limited to walls, floors, roofs, ceilings, stairways, built-in partitions, finishes, cladding and other similarly
incorporated architectural and structural items, and fixed equipment, including the weight of cranes.”
From Table 204-2 (Minimum Design Loads), the researchers determined the superimposed dead loads
incorporated in the structure.
PARAMETERS
Soil Profile Type Stiif Soil Profile, SD
Seismic Zone Zone 4
Seismic Source Type Type B
Near-Source Factor, Na 1
Near-Source Factor, Nv 1
Ct 0.0731
R (Special Reinforced
Concrete Moment-Resisting 8.5
Frame)
These loads change over time and are temporarily attached to a building. They result from using
and occupying the building. Environmental or human interactions are examples that cause live loads.
Design Parameters
LIVE LOADS
As stated in Section 205 of the National Structural Code of the Philippines: “Live loads shall be the
maximum loads expected by the intended use or occupancy but in no case shall be less than the loads
required be this section”.
From Table 205-1 (Minimum Uniform and Concentrated Live Loads), the group determined the
superimposed live loads into the structure.
The table below shows the live loads that will be acting on the structure once it was constructed.
The earthquake load induces dynamic loading on the foundation of a building leading to shear and
fatigue stresses and also causes deformation of a structure. Design of the building requires that the
structure can withstand some levels of displacement at the base (Murty, n.d, 1-5). The inertia force
experienced leads to the damaging of the structure. It happens so that the base of the building moves while
the upper part moves in the opposite direction leading to inertia force on the roof. This causes buckling on
the columns of the building. That is the basic way how the damage occurs due to the earthquake. It is
important that the columns are designed to withstand high buckling forces.
The study
utilized the static force procedure to get the earthquake loads acting on the structure.
The total design base shear in a given direction shall be determined from the following equation:
𝐶𝑣 𝐼
𝑉= 𝑊 𝐸𝑞𝑛. (208 − 4)
𝑅𝑇
The total design base shear need not exceed the following:
2.5𝐶𝑎 𝐼
𝑉= 𝑊 𝐸𝑞𝑛. (208 − 5)
𝑅
The total design base shear shall not be less than the following:
In addition, for Seismic Zone 4, the total base shear shall also not be less than the following:
0.8𝑍𝑁𝑣 𝐼
𝑉= 𝑊 𝐸𝑞𝑛. (208 − 7)
𝑅
For all buildings, the value of T may be approximated from the following equation:
3
𝑇 = 𝐶𝑡 (ℎ𝑛 )4 𝐸𝑞𝑛. (208 − 8)
Where:
The total force shall be distributed over the height of the structure in conformance with the
equation:
𝑛
The concentrated force, Ft at the top, which is in addition to Fn shall be determined from the
equation:
The value T used for the purpose of calculating Ft shall be the period that corresponds with the design base
shear as computed using Equation (208-4). Ft need not exceed 0.25V and may be considered as zero
where T is 0.7 second or less. The remaining portion of the base shear shall be distributed over the height
of the structure, including Level n, according to the following equation:
(𝑉 − 𝐹𝑡 )𝑤𝑥 ℎ𝑥
𝐹𝑥 = 𝐸𝑞𝑛. (208 − 15)
∑𝑛𝑖=1 𝑤𝑖 ℎ𝑖
At each level designated x, the force Fx shall be applied over the area of the building in accordance with the
mass distribution at that level. Structural displacements and design seismic forces shall be calculated as
𝑤𝑥 ℎ𝑥
the effect of forces Ft and Ft at the appropriate ∑𝑛 levels above the base.
𝑖=1 𝑤𝑖 ℎ𝑖
Once the magnitudes of the design loads for a structure have been estimated, an engineer must
consider all loads that might act simultaneously on the structure at a given time. In this case, we will
consider all the loads (dead load, live load, wind load, and earthquake load) in one analysis.
Various load combinations followed in designing this structure are specified in the NSCP 2015. The
structure must have adequate strength to resist the most unfavorable of all the load combinations. The
following equations show the load combinations that will be used.
1.2𝐷𝐿 + 1.6𝐿𝐿
This equation combines the vertical loads acting on the structure. For horizontal loads, we just sum
them up at each level of the structure.
𝐸+𝑊
These load combinations will then be computed in one analysis using the moment distribution
method.
Chapter 3: Design Constraints, Trade-offs, and Design Standards
Concrete made with a combination of expanded clay, shale, slag, or slate or sintered fly ash and natural
sand, with a density generally between 105 and120 lb/ft 3 (1680 and 1920 kg/m 3 ).
Lightweight concrete can be defined as a type of concrete which includes an expanding agent in that it
increases the volume of the mixture while giving additional qualities such as nailbility and lessened the
dead weight. It is lighter than the conventional concrete.
3.2.2 Beams
Beams can be described as members that are mainly subjected to flexure and it is essential to focus on the
analysis of bending moment, shear, and deflection. When the bending moment acts on the beam, bending
strain is produced. The resisting moment of is developed by internal stresses. Under positive moment,
compressive strains are produced in the top of beam and tensile strength and it is not suitable for flexure
member by itself.
3.2.3 Columns
Table 2 Parameters of Girders used in the design
Figure 1
Figure 2 stress experienced by the structure
APPENDICES
APPENDIX A: SUPER IMPOSED DEAD LOADS (kPa)
CEILING
DELIVERY ROOM
(ACOUSTICAL FIBRE BOARD)--------------------0.05
FLOOR FINISHES
ULTRASOUND
(MARBLE AND MORTAR ON STONE
UTILITIES ------------------------------------------------0.30
CEILING
FLOOR FINISHES
FLOOR FILL
WALL COVERING
CEILING
FLOOR FINISHES
FLOOR FILL
WALL COVERING
CEILING
FLOOR FINISHES
FLOOR FILL
UTILITIES ------------------------------------------------0.30
WALL COVERING
CEILING
FLOOR FINISHES
FLOOR FILL
WALL COVERING
CEILING
FLOOR FINISHES
FLOOR FILL
HAND RAILS------------------------------------------200 N
WALL COVERING
CEILING
FLOOR FINISHES
(HARDWLINOLEUM OR ASPHALT
TILE 6mm)-----------------------------------------------0.05
FLOOR FILL
(LIGHTWEIGHT CONCRETE) --------------------0.015
HAND RAILS------------------------------------------200 N
COMPONENTS
FLOOR FINISHES
TREATMENT
(MARBLE AND MORTAR ON STONE
ROOM
CONCRETE FILL)-------------------------------------1.58
FLOOR FILL
UTILITIES ------------------------------------------------0.30
WALL COVERING
CEILING
FLOOR FINISHES
CEILING
FLOOR FINISHES
FLOOR FILL
WALL COVERING
CEILING
FLOOR FINISHES
FLOOR FILL
UTILITIES ------------------------------------------------0.30
WALL COVERING
STAIRS CEILING
FLOOR FINISHES
FLOOR FILL
WALL COVERING
CEILING
FLOOR FINISHES
FLOOR FILL
HAND RAILS------------------------------------------200 N
WALL COVERING
CEILING
FLOOR FINISHES
(HARDWLINOLEUM OR ASPHALT
TILE 6mm)-----------------------------------------------0.05
FLOOR FILL
(LIGHTWEIGHT CONCRETE) --------------------0.015
HAND RAILS------------------------------------------200 N
COMPONENTS
WALL COVERING
CEILING
FLOOR FINISHES
UTILITIES -----------------------------------------------0.30
WALL COVERING
FLOOR FINISHES
FLOOR FILL
UTILITIES ------------------------------------------------0.30
WALL COVERING
CEILING
FLOOR FINISHES
FLOOR FILL
UTILITIES ------------------------------------------------0.30
WALL COVERING
STAIRS CEILING
FLOOR FINISHES
FLOOR FILL
WALL COVERING
CEILING
FLOOR FINISHES
FLOOR FILL
HAND RAILS------------------------------------------200 N
WALL COVERING
CEILING
FLOOR FINISHES
(HARDWLINOLEUM OR ASPHALT
TILE 6mm)-----------------------------------------------0.05
FLOOR FILL
HAND RAILS------------------------------------------200 N
WALL COVERING
CEILING
FLOOR FINISHES
FLOOR FILL
UTILITIES ------------------------------------------------0.30
WALL COVERING
STAIRS CEILING
FLOOR FINISHES
FLOOR FILL
CEILING
FLOOR FINISHES
FLOOR FILL
HAND RAILS------------------------------------------200 N
The following are the sections and codes that are followed in conceptualizing and designing the structural
plan of the apartment building:
General. The construction of stairs and exits shall conform to the occupant load requirements of
buildings, reviewing stands, bleachers and grandstands:
a. Determinations of Occupant Loads. The Occupant load permitted in any building or portion thereof
shall be determined by dividing the floor area assigned to that use by the unit area allowed per
occupant as determined by the Secretary.
b. Exit Requirements. Exit requirements of a building or portion thereof used for different purposes
shall be determined by the occupant load which gives the largest number of persons. No
obstruction shall be placed in the required width of an exit except projections permitted by this
Code.
Notation
𝐴𝑠𝑡 = total area of nonprestressed longitudinal reinforcement (bars and steel shapes), mm 2.
𝑐𝑐 = clear cover from the nearest surface in tension to the surface of the flexural tension reinforcement,
mm.
𝑑𝑐 = thickness of concrete cover measure from extreme tension fiber to center of bar or wire located
closest thereto, mm.
𝐹 = loads due to weight and pressures of fluids with well defined densities and controllable maximum
heights, or related internal moments and forces.
𝐻 = loads due to weight and pressure of soil, water in soil, or other materials, or related internal moments
and forces.
𝐼𝑔 = moment of inertia of gross concrete section about centroidal axis, neglecting reinforcement, mm 4.
𝑤𝑢 = factored load per unit length of beam or per unit area of slab.
𝛼𝑓 = ratio of flexural stiffness of beam section to flexural stiffness of a width of slab bounded laterally by
center line of adjacent panle, if any on each side of beam.
𝛽1 = factor
𝛷 = strength-reduction factor.
The following are the sections and codes that are followed in conceptualizing and designing the structural
plan of the apartment building: