® Delayed Transition Manual

Cutler-Hammer Transfer Switches Open Transition Non-automatic


Product Focus Closed Transition Bypass Isolation

Contactor and Breaker-based


Transfer Switches

Av
ail
abl
efr
om

BRE
WSS
UPPL
Y.COM
Built with years of experience
Powered with innovation
Delivered with reliability

A History of Experience, Built With Experience Powered With Innovation Delivered With Reliability
Innovation and Reliability For over a century, Eaton has Eaton continues to meet Power outages due to bad
As a premier industrial focused on providing quality changing industry needs by weather or utility failure have
manufacturer, Eaton’s electrical power-centric products and providing a broad range of grown increasingly costly and
business is one of the world’s services. In today’s business automatic transfer switches. more disruptive to businesses
leading suppliers of electrical environment, customers like These switches may be and homeowners. A backup
control products and power you are driving our grouped into a basic, power system will keep your
distribution equipment with transformation from a leading enhanced or premium set of computers, security system,
yearly sales of over $2.5 billion. global electrical components features that will meet your heating or refrigeration
Eaton’s electrical products provider into a customer- application requirements. system, cash registers, home
include a complete line of low centric solutions partner who Eaton has used industry- health care equipment, or any
and medium voltage understands your business. leading breaker based designs system that uses electric
assemblies from substations, We do this through in-depth for years and now has a line of power, energized and
switchgear and panelboards to collaboration with customers contactor based designs. operational. The demands for
loadcentres, transformers and and subject matter experts These designs can be matched reliability have increased.
safety switches. These studying the issues inherent to a family of automatic Eaton meets those
products are used wherever to the electrical power transfer switch controllers that expectations by the stringent
there is a demand for electrical distribution and control will meet your specific needs. CSA C22.2 No. 178 and
power in residences, high-rise systems. Identify your application, UL1008 automatic transfer
apartment and office buildings, Eaton is one of the pioneering define your needs, and select switches with a world-class
commercial sites, hospitals electrical manufacturers and the solution from Eaton. product delivery system.
and factories. has been focused on providing Eaton will provide the
reliable backup power systems individual transfer switch built
with transfer switch to exacting standards or
equipment for over 75 years. supply the same transfer
switch in an integrated
lineup with other Eaton gear.
For startup service, application
support, and emergency
support, call Eaton Electrical
Services and Systems at
1-800-498-2678.

2
Solutions Overview

Eaton’s Cutler-Hammer® Basic Solution TRANSFER SWITCH STANDARDS


automatic transfer switches The Basic Solution offers a CSA C22.2 No. 178-1978 Canadian Standards Association
are designed to provide you transfer switch that meets the
with a full offering of transfer UL 991 UL Standards for Safety Tests for Safety-Related
most basic and cost-effective Controls Employing Solid-State Devices
switches to solve your industry requirement needs for an
and application needs. Eaton UL 1008 UL Standards for Transfer Switches
automatic, manual or
offers the industry’s most NEMA® ICS 109.21 Impulse Withstand Test
non-automatic transfer switch.
complete line of contactor- This solution set allows you IEEE® 472 (ANSI C37.90A) Ringing Wave Immunity/Voltage Surge Test
based, breaker-based, to choose from either a EN55022 (CISPR11): Conducted and Radiated Emissions
and Magnum “stored energy” contactor-based or a EN61000-4-2 Class B Level 4 ESD Immunity Test
based transfer switches. breaker based design and EN61000-4-3 (ENV50140) Radiated RF, Electromagnetic Field
This wide range of selections match that power-switching Immunity Test
enables you to identify your device with our basic transfer EN61000-4-4 Electrical Fast Transient/Burst Immunity Test
application needs and the switch controller.
benefits you expect to realize, EN61000-4-5 IEEE C62.41: Surge Immunity Test
and then choose the solution EN61000-4-6 (ENV50141) Conducted Immunity Test
Enhanced Solution
best for you. The corner stone EN61000-4-11 Voltage Dips and Interruption Immunity
of all of these offerings is the The Enhanced Solution meets
FCC Part 15 Conducted/Radiated Emissions (Class A)
proven design experience all of the basic automatic
transfer switch needs. CISPR 11 Conducted/Radiated Emissions (Class A)
and reliability built into all
In addition to meeting the IEC 1000-2 Electrostatic Discharge Test
Cutler-Hammer® transfer
switches. most basic transfer switch IEC 1000-3 Radiated Susceptibility Tests
requirement, the Enhanced IEC 1000-4 Fast Transient Tests
Solution allows for optimal IEC 1000-5 Surge Withstand Tests
control and improved flexibility.
CSA® Conformance C22.2 No. 178-1978 (Reaffirmed 1992)
This solution set allows you
to choose from either a UL 869A Reference Std for Service Equipment
contactor based or breaker- UL 50/508 Enclosures
based design. NEMA ICS 1 General Standards for Industrial Control Systems
NEMA ICS 2 Standards for Industrial Control Devices,Controllers
Premium Solution and Assemblies
The Premium Solution is NEMA ICS 6 Enclosures for Industrial Controls and Systems
offered for those applications NEMA ICS 10-1993 AC Automatic Transfer Switches
requiring continuity of power
ANSI C33.76 Enclosures
during the transfer and routine
test. This solution set offers NEC® 517, 700, 701 and 702 National Electrical Code
both contactor-based and NFPA 70 National Electrical Code
breaker-based designs with NFPA 99 Health Care Facilities
drawout capability. NFPA 101 Life Safety Code

Switch Types Available NFPA 110 Emergency and Standby Power Systems
EGSA 100S Standard for Transfer Switches
• Open Transition
• Closed Transition
• Delayed Transition
• Bypass Isolation
• Non-Automatic
• Manual

3
Make the right decision
• Identify Your Application
• Define Your Needs
• Determine Your Right Solution
• Select Eaton

ATS SOLUTION GUIDE: Highlighting Contactor-Based Designs

CUSTOMER BENEFITS KEY FEATURES AGRICULTURE

• Greater Reliability to Avoid Lost Revenue and Production Time • Soft Load Ramping —
• Continuity of Power Through Synchronization of Sources • 30 Cycle, 85 kA Short-Time Ratings
• Lower Energy Costs Realized through Managing Demand Charges • Integral Overcurrent Protection Available
• No Power Interruption During Switch Inspection or Testing • Drawout Design

PREMIUM • Greater Reliability to Avoid Lost Revenue and Production Time • 30 Cycle, 85 kA Short-Time Ratings —
• Safe Preventative Maintenance without Power Interruption • Integral Overcurrent Protection Available
SOLUTION • No Power Interruption During Switch Inspection or Testing • Integrated Service Entrance Solution
• Interchangeable Bypass and Switch Devices
Continuity of Power • Drawout Design
During Retransfer

Critical Load Transfer • Greater Reliability to Avoid Lost Revenue and Production Time • Interchangeable Bypass and Switch Devices —
Applications • Safe Preventative Maintenance without Power Interruption • Drawout Design Standard
• No Power Interruption During Switch Inspection or Testing • Front Access Standard
Maximum Control and • Dual ATS
Ultimate Flexibility
• Greater Reliability to Avoid Lost Revenue and Production Time • 30 Cycle, 85 kA Short-Time Ratings —
Maximum Investment • Lower Energy Costs Realized from Managing Demand Charges • Integral Overcurrent Protection Available
• No Power Interruption During Generator Set Testing • Integrated Service Entrance Solution
• Drawout Design Available

• Greater Reliability to Avoid Lost Revenue and Production Time • Paralleled in Less than 100 ms —
• Lower Energy Costs Realized from Managing Demand Charges • Programmable Field Settings
• No Power Interruption During Generator Set Testing • Communication Capability

• Ability to Transfer Large Motor or Inductive Loads • 30 Cycle, 85 kA Short-Time Ratings on Power Circuit Breaker —
• Allows Loads to Re-Energize after Transfer at Normal Inrush Currents • Integral Overcurrent Protection Available
ENHANCED • Avoid Higher Starting Currents which Increase Energy Costs • Integrated Service Entrance Solution

SOLUTION • Ability to Transfer Large Motor or Inductive Loads • Multi Tap Transformer Voltage Selection Available —
• Allows Loads to Re-Energize after Transfer at Normal Inrush Currents • Easily Adjustable Time Delays for the Neutral Position
Momentary Loss of • Avoid Higher Starting Currents which Increase Energy Costs
Power Acceptable
During Retransfer • Ability to Transfer Large Motor or Inductive Loads • 30 Cycle, 85 kA Short-Time Ratings on Power Circuit Breaker —
• Allows Loads to Re-Energize after Transfer at Normal Inrush Currents • Integral Overcurrent Protection Available
Optimal Control and • Avoid Higher Starting Currents which Increase Energy Costs • Integrated Service Entrance Solution
Improved Flexibility
• Drawout Design Available
Moderate Investment
• Simplest of Transfer Switching Solution • Equal Withstand, Interrupting and Closing Ratings Open Transition
• Safe Manual Transfer Under Load • Integral Overcurrent Protection Available Breaker-Based
• Integrated Service Entrance Solution (100 – 1000 A)

BASIC SOLUTION • Most Simple Operation • Most Compact Offering Open Transition
• Most Cost-Effective • Multi Tap Transformer Voltage Selection Available Contactor-Based
Momentary Loss of • Application Flexibility (100 – 600 A)
Power Acceptable
During Retransfer • Permits Safe and Convenient Non-auto Transfer Under Load • 30 Cycle, 85 kA Short-Time Ratings on Power Circuit Breaker —
• Integral Overcurrent Protection Available
Least Critical Load • Drawout Design Available
Transfer Applications
• Permits Safe and Convenient Manual Transfer Under Load • Equal Withstand, Interrupting and Closing Ratings —
Basic Control • Most Cost-Effective Manual Transfer • Integral Overcurrent Protection Available
and Flexibility • Deadfront Design
Minimum Investment

• Continuity of Power for UPS Applications • Required UPS Bypass Signal Prevents Unauthorized Bypass —
SPECIAL SOLUTION • High Interrupting Ratings
• Reliable Manually Initiated Electrical Operation

4
COMMERCIAL INDUSTRIAL UTILITIES INSTITUTIONS GOVERNMENT COMMUNICATIONS DATA CENTRE

— — Soft Load Soft Load Soft Load Soft Load Soft Load
Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based
(600 – 5000 A) (600 – 5000 A) (600 – 5000 A) (600 – 5000 A) (600 – 5000 A)

Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition
Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation
Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based
(200 – 5000 A) (200 – 5000 A) (200 – 5000 A) (200 – 5000 A) (200 – 5000 A) (200 – 5000 A) (200 – 5000 A)

Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition
Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation
Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based
(100 – 1200 A) (100 – 1200 A) (100 – 1200 A) (100 – 1200 A) (100 – 1200 A) (100 – 1200 A) (100 – 1200 A)

Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition
Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based
(200 – 5000 A) (200 – 5000 A) (200 – 5000 A) (200 – 5000 A) (200 – 5000 A) (200 – 5000 A) (200 – 5000 A)

Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition
Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based
(40 – 1200 A) (40 – 1200 A) (40 – 1200 A) (40 – 1200 A) (40 – 1200 A) (40 – 1200 A) (40 – 1200 A)

Delayed Transition Delayed Transition Delayed Transition Delayed Transition Delayed Transition — —
Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based
(30 – 5000 A) (30 – 5000 A) (30 – 5000 A) (30 – 5000 A) (30 – 5000 A)

Delayed Transition Delayed Transition Delayed Transition Delayed Transition Delayed Transition — —
Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based
(40 – 1200 A) (40 – 1200 A) (40 – 1200 A) (40 – 1200 A) (40 – 1200 A)

Open Transition Open Transition Open Transition Open Transition Open Transition — —
Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based
(200 – 5000 A) (200 – 5000 A) (200 – 5000 A) (200 – 5000 A) (200 – 5000 A)

Open Transition Open Transition Open Transition Open Transition Open Transition — —
Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based
(30 – 1000 A) (30 – 1000 A) (30 – 1000 A) (30 – 1000 A) (30 – 1000 A)

Open Transition Open Transition Open Transition Open Transition Open Transition — —
Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based
(40 – 1200 A) (40 – 1200 A) (40 – 1200 A) (40 – 1200 A) (40 – 1200 A)

Non-Auto Non-Auto — — — — —
Magnum-Based Magnum-Based
(200 – 5000 A) (200 – 5000 A)

Manual or Non-Auto Manual or Non-Auto — — — — —


Breaker-Based Breaker-Based
(30 – 1000 A) (30 – 1000 A)

Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance Bypass
Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based
(100 – 1000 A) (100 – 1000 A) (100 – 1000 A) (100 – 1000 A) (100 – 1000 A) (100 – 1000 A) (100 – 1000 A)

5
Contactor-based Switch Type -
Transfer Switches Open Transition
Delayed Transition
Closed Transition

Standard Features (ATC-300)


• Switch position contacts:
• Source 1 Position 1NO and 1NC
• Source 2 Position 1NO and 1NC
• Source 1 and Source 2 sensing:
• Undervoltage/underfrequency
• Overvoltage/overfrequency
• 3-phase rotation protection
• 3-phase voltage unbalance/loss
• Pre-transfer signal contacts 1NO/1NC
• Go to Emergency (Source 2)
• Seven field-programmable time delays
1200 Ampere ATS with ATC-300 Controller • LCD-based display for programming, system diagnostics
and Help message display
• Mimic diagram with source available and connected
Product Description
LED indication
Eaton’s Cutler-Hammer® Automatic Transfer Switch is designed • Time-stamped history log
to provide unmatched performance, reliability and versatility for
• System test pushbutton
critical standby power applications. The switches can be
equipped with the ATC-300 or ATC-800 controllers to match your • Programmable plant exerciser — OFF, daily, 7, 14, 28-day
application needs. All the controllers offer rock-solid monitoring, interval selectable run time 0 – 600 minutes no load/load
status reporting and transfer control operation. Superior design with fail-safe
and robust construction make Eaton’s Cutler-Hammer® transfer
switch the industry benchmark for critical and distributed Optional Features
power systems. • Available surge suppression device for power/controller,
engine start circuit, phone and cable connections
Electrical Ratings • Space heater with thermostat
• Ratings 40, 100, 150, 200, 225, 260, 400, 600, 800, • Ammeter — load side
1000 and 1200 amperes • Power quality metering
• 2, 3 or 4-poles • 2 and 4 position switch
• Up to 600 Vac, 50/60 Hz. • Stainless steel cover for controller
• NEMA® 1, 3R, Open • Open in-phase transition or time delay neutral transition
• UL® 1008 listed
• CSA® C22.2 No. 178 certified Optional Features (ATC 800 only)
• Closed transition
Industrial Design Highlights • Remote communications
• Double-throw, mechanically interlocked transfer mechanism, • Load shed from emergency
preventing connection of both sources • Selected automatic or non-automatic operation
• Field-selectable multi-tap transformer panel permits operation
on a wide range of system voltages
• High withstand and closing ratings
• Compact design

6
AT C 3 C2 X 3 0400 X S C

Type Logic Number of poles Amperes Voltage Enclosure


AT = Automatic 3 = ATC-300 2 = 2-Pole 0040 = 40 A A = 120 V, 60 Hz K = Open
CT = Closed 8 = ATC-800 3 = 3-Pole 0080 = 80 A B = 208 V, 60 Hz S = NEMA 1
Transition 4 = 4-Pole 0100 = 100 A E = 600 V, 60 Hz J = NEMA 12
0150 = 150 A G = 220 V, 50 Hz R = NEMA 3R
0200 = 200 A H = 380 V, 50 Hz
0225 = 225 A K = 600 V, 50 Hz
Orientation Mechanism Mounting 0260 = 260 A M = 230 V, 50 Hz Certification
0400 = 400 A N = 401 V, 50 Hz
C = Contactor C2 = 2-Position X = Fix Mount U = UL Listed
0600 = 600 A O = 415 V, 50 Hz
C3 = 3-Position C = CSA certified
0800 = 800 A W = 240 V, 60 Hz
1000 = 1000 A X = 480 V, 60 Hz
1200 = 1200 A Z = 365 V, 50 Hz
Contactor-based Automatic Transfer Switch Catalogue Numbering System

CONTACTOR-BASED TRANSFER SWITCH 40 – 1200 AMPERES - DIMENSIONS IN INCHES (MM) AND APPROXIMATE SHIPPING IN LBS. (KG)

Enclosure Bolt Pattern Standard Terminals


A (Height) B (Width) C (Depth) G (Horizontal) H (Vertical) Load Side, Normal Neutral Weight
Amperes and Standby Source Connection Lbs. (kg)

40 – 100 @ 480 V 1 38.68 (982.5) 18.31 (465.1) 13.34 (338.8) 10.25 (260.4) 37.38 (949.5) (1) #14 – 2/0 (1) #14 – 1/0 164 (74)
40 – 100 @ 600 V 1 38.68 (982.5) 18.31 (465.1) 13.34 (338.8) 10.25 (260.4) 37.38 (949.5) (1) #14 – 2/0 (1) #14 – 1/0 164 (74)
150 – 200 @ 480 V 1 38.68 (982.5) 18.31 (465.1) 13.34 (338.8) 10.25 (260.4) 37.38 (949.5) (1) #6 – 300 kcmil (3) 1/0 – 250 kcmil 164 (74)
150 – 200 @ 600 V 1 48.74 (1238.0) 18.31 (465.1) 13.84 (351.5) 13.00 (330.2) 47.84 (1215.1) (1) #6 – 300 kcmil (3) 1/0 – 250 kcmil 260 (118)
225 – 400 @ 480 V 1 48.74 (1238.0) 18.31 (465.1) 13.84 (351.5) 13.00 (330.2) 47.84 (1215.1) (2) #3 /0 – 250 kcmil (6) 250 – 500 kcmil 260 (118)
225 – 1200 @ 600 V 2 79.41 (2017.0) 29.19 (741.4) 22.46 (570.5) N/A N/A (4) 1/0 – 750 kcmil (12) 1/0 – 750 kcmil 600 (272) 3-Pole
650 (295) 4-Pole
600 – 1200 @ 480 V 2 79.41 (2017.0) 25.25 (641.4) 3-Pole 22.46 (570.5) N/A N/A (4) 1/0 – 750 kcmil (12) 1/0 – 750 kcmil 600 (272)
29.19 (741.4) 4-Pole

1 Wall Mount 2 Floor Standing — Height Dimension Includes the Bottom Bracket

Automatic, Non-Automatic up to 400 Amps — Wall Mount. Automatic, Non-Automatic


600 to 1200 Amps Floor Standing (Height "A" Includes Bottom Bracket).

WITHSTAND AND CLOSE-ON RATINGS (KA)

Ampere Rating 480 Volts 600 Volts


Any Specific Any Specific
100 Ampere ATS with ATC-300 Controller Breaker Breaker Breaker Breaker
100, 200 10,000 30,000 10,000 22,000
260, 320, 400 35,000 50,000 35,000 42,000
600, 800, 1000,1200 50,000 65,000 50,000 65,000

7
Contactor-based Switch Type -
Transfer Switches Bypass Isolation

Standard Features
• Draw-out cassette design on both ATS and Bypass
• No service interruption in Bypass to the same source
• Switch position contacts:
1200 Amp 3-Pole Bypass Isolation Switch • Source-1 Position 1-N.O. and 1-N.C.
• Source-2 Position 1-N.O. and 1-N.C.
• Source-1 and Source-2 sensing:
Product Description
• Undervoltage/underfrequency
Eaton’s Cutler-Hammer® Automatic Transfer Switch is designed • Overvoltage/overfrequency
to provide unmatched performance,reliability and versatility for • 3-phase rotation protection*
critical standby power applications. The switches can be • 3-phase voltage unbalance/loss*
equipped with the ATC-300 or ATC-800 controllers to match your • Pre-transfer signal contacts1-N.O. and 1-N.C.
application needs. A Bypass Isolation Transfer Switch may be • Go to Source-2 (EMERGENCY)
used to provide emergency power to life safety and other critical • Field-programmable time delays:
loads where maintenance of the main transfer switch, without • Time Delay Engine Start: 0 – 1200 seconds
interruption of power to the load, is either desirable or required. • Time Delay Normal to Emergency: 0 – 1800 seconds
• Time Delay Emergency to Normal: 0 – 1800 seconds
Electrical Ratings • Time Delay Engine Cooldown: 0 – 1800 seconds
• Ratings 100, 150, 225, 260, 400, 600, 800, 1000 • Time Delay Emergency Failure: 0 – 6 seconds
and 1200 amperes • LCD-based display for programming, system diagnostics
• 2, 3 or 4-poles and Help Menu display
• Up to 600 Vac, 50/60 Hz. • Mimic diagram with Source Available and Connected
LED indication
• NEMA® 1, 3R
• Time-stamped history log
• UL® 1008 listed • System TEST pushbutton
• CSA® C22.2 No. 178 certified • Programmable plant exerciser — OFF, daily, 7, 14*, 28-day*
interval selectable run time 0 – 600 minutes no load/load
Industrial Design Highlights with failsafe
• Front access is a standard feature on all ratings *Note: ATC-300 only.
• Entry:
• Top, bottom or both Optional Features
• Isolated compartments • Available Surge Protection Device (SPD) for power/controller,
• Improved safety: engine start circuit, phone and cable connections
• Isolated compartments with barriers • Automatic transfer operation with selectable (via programming)
• Single motion rack-out with doors closed non-automatic or automatic retransfer with failsafe
• Ability to test powerswitching elements during • Space heater with thermostat
draw-out process • Digital multi-function power quality metering
• Dual ATS capability — Bypass contactor can be controlled
• Stainless steel cover for controller
by the ATS controller in the bypass mode of operation
• Load sequencing contacts
• Installation flexibility:
• Field Entry/Exit locations can be modified in the field
• Interchangeable drawout contactors
• Field-selectable multi-tap transformer panel permits
operation on a wide range of system voltages
8
Bypass Isolation Switch Components

Front Access Draw-out Contactors Ease of Maintenance Dual ATS Capability


Front access is a standard The ATS and the Bypass Transfer to the Bypass power The controller on conventional
feature. Source-1 (NORMAL) draw-out cassette power contactor is easily initiated and Bypass Isolation Switches only
Source and Load connections contactor designs are identical controlled via door-mounted controls the ATS contactor.
are set up as standard top and interchangeable. This controls. Once the transfer to The Eaton design allows the
entry and Source-2 standard feature allows the the Bypass contactor is switch controller to remain
(EMERGENCY) Source user the ability to withdraw, complete, the ATS contactor active in both the ATS and
connections as bottom entry. maintain or swap contactor is easily racked out with the Bypass modes, thus providing
These connections are located assemblies, providing compartment door closed. control to either contactor.
in their own separate redundancy of ATS and Bypass The ATS contactor may then This ability of the controller to
compartments. These functions from one contactor be tested in the racked out remain active and control the
connections can be relocated assembly to the other. position. Bypass isolation contactor
in the field if necessary. provides "N+1" redundancy
Improved Safety Ease of Transfer of a second fully functioning
Multi-Tap Transformer The unique Eaton design The Eaton design allows the ATS, a feature unique to Eaton.
The industry-exclusive includes separation between operator to make a quick and
Multi-Tap system voltage control and power simple transfer from the ATS
selector allows the transfer components. The ATS and power contactor to the Bypass
switch to be applied on most Bypass isolation contactors are contactor by initiating the
system voltages by proper mounted in separate electrically operated transfer
insertion of the selector plug. compartments with protective via a 2-position switch. Door
barriers between them. This mounted indicating lights
design prevents the possibility confirm that a successful
of contact with the transfer has taken place.
rear-mounted power
connections to the contactors.
In addition, the top and bottom
entry have separate
compartment doors.
9
Bypass Isolation Contactor-Based Design NEMA 1

CONTACTOR-BASED TRANSFER SWITCH 100 – 1200 AMPERES — DIMENSIONS IN INCHES (MM) AND APPROXIMATE SHIPPING IN LBS. (KG)

Switch
Rating Enclosure Standard Terminals Weight
Amperes Height Width Depth Line Side (Normal Load Neutral Lbs. (kg)
and Standby Source) Connection Connection
100 – 200 90.00 (2286.0) 40.00 (1016.0) 28.97 (735.8) (1) #6 – 300 Cu/Al (1) #6 – 300 Cu/Al (3) #6 – 300 Cu/Al 1800 (817) NEMA 1
100 – 200 1 90.00 (2286.0) 40.00 (1016.0) 44.47 (1129.5) (1) #6 – 300 Cu/Al (1) #6 – 300 Cu/Al (3) #6 – 300 Cu/Al 1850 (840) NEMA 3R
400 – 1200 90.00 (2286.0) 40.00 (1016.0) 28.97 (735.8) (4) 3/0 – 750 Cu/Al (4) 3/0 – 750 Cu/Al (12) 3/0 – 750 Cu/Al 1800 (817) NEMA 1
400 – 1200 1 90.00 (2286.0) 40.00 (1016.0) 44.47 (1129.5) (4) 3/0 – 750 Cu/Al (4) 3/0 – 750 Cu/Al (12) 3/0 – 750 Cu/Al 1850 (840) NEMA 3R

1 NEMA 3R dimensions 2 If seismic mounting brackets are required, then the width will be 46.00 (1168.4)
10
BI C 3 C3 E 3 1200 W S C

Type Logic Number of poles Amperes Voltage Enclosure


BI = Bypass 3 = ATC-300 2 = 2-Pole 0100 = 100 A B = 208 V, 60 Hz S = NEMA 1
Isolation 8 = ATC-800 3 = 3-Pole 0150 = 150 A E = 600 V, 60 Hz R = NEMA 3R
Open 4 = 4-Pole 0225 = 225 A G = 220 V, 50 Hz
Transition 0260 = 260 A H = 380 V, 50 Hz
0400 = 400 A K = 600 V, 50 Hz
CB = Bypass
0600 = 600 A M = 230 V, 50 Hz
Isolation
Orientation Mechanism Mounting 0800 = 800 A N = 401 V, 50 Hz Certification
Closed
1000 = 1000 A O = 415 V, 50 Hz
Transition C = Contactor C3 = 3-Position E = Draw-out U = UL Listed
1200 = 1200 A W = 240 V, 60 Hz
X = Fixed Mount C = CSA certified
X = 480 V, 60 Hz
Z = 365 V, 50 Hz

Automatic Bypass Isolation Contactor-based Transfer Switch Catalogue Numbering System

WITHSTAND AND CLOSE-ON RATINGS (KA)

Ampere Rating 480 Volts 600 Volts


Any Specific Any Specific
Breaker Breaker Breaker Breaker
100 10,000 30,000 10,000 22,000
200 10,000 30,000 10,000 22,000
260 35,000 50,000 35,000 42,000
320 35,000 50,000 35,000 42,000
400 35,000 50,000 35,000 42,000
600 50,000 65,000 42,000 65,000
800 50,000 65,000 42,000 65,000
1000 50,000 65,000 42,000 65,000
1200 50,000 65,000 42,000 65,000

11
Breaker-based Switch Type -
Transfer Switches Automatic, Manual
and Electrically Operated
30A-1000A

Standard Features (ATC300)


• Switch position contacts:
• Source 1 Position 1NO and 1NC
• Source 2 Position 1NO and 1NC
• Programmable Micro-processor based control
• Normal/Standby source monitoring
• Plant Exerciser with Failsafe (programmable)
• High Withstand, Closing and Interrupting Ratings
ATHM Automatic Transfer Switch • Manual Transfer Under Load
• Engine Start Contacts
Product Description • Time Delay Normal to Emergency
An economical line of transfer switches with micro-processor • Time Delay Engine Start
based logic, offering a standard feature package, for basic • Time Delay Emergency to Normal
power applications on 30-1000 ampere systems up to 600 • Time Delay Engine Cooldown
volts, 2, 3 or 4 pole.
• LED indicators – switch position
• LED indicators – source available
Electrical Ratings
• Emergency source undervoltage/underfrequency sensing
• Ratings 40, 100, 150, 200, 225, 260, • Normal source undervoltage sensing
400, 600, 800 and 1000 amperes
• Time Delay Neutral
• 2, 3 or 4-poles
• Go to Emergency Contact (Area Protection)
• Up to 600 Vac, 50/60 Hz.
• Pre-Transfer Signal Contacts
• NEMA® 1, 3R, Open, 12, 4, 4x
• Pushbutton Bypass Time Delays
• UL® 1008 listed
• CSA C22.2 No. 178 certified
Optional Features
• Available surge suppression device for power/controller,
engine start circuit, phone and cable connections
• Space heater with thermostat
• Ammeter – load side
• Power quality metering
• Stainless steel cover for controller

Optional Features (ATC 600)


• Remote communications
• Load shed from emergency
• Selected automatic or non-automatic operation

12
TRANSFER SWITCH ENCLOSURE DIMENSIONS

Frame size Rating Figure Height Width Depth


30A - 150A, 600V
F 30A - 200A, 240V A 32.63” (829) 24” (610) 9” (229)
K, L, M 225A - 600A B 55” (1397) 32” (813) 15” (381)
N 800A - 1200A B 65” (1651) 38” (965) 16” (406)

AT H 3 FD A 3 0100 E S C

Type Logic Mounting Number of poles Amperes Voltage Enclosure


AT = Automatic 3 = ATC-300 A = Source1 (MCS), Source 2 (MCS) 2 = 2-Pole 0030 = 30 A A = 120 V, 60 Hz S = NEMA 1
MT = Non-Auto I = ATC-600 B = Source1 (MCCB), Source 2 (MCCB) 3 = 3-Pole 0070 = 70 A B = 208 V, 60 Hz R = NEMA 3R
Manual X = No logic C = Source1 (MCCB), Source 2 (MCS) 4 = 4-Pole 0100 = 100 A E = 600 V, 60 Hz J = NEMA 12
NT = Non-Auto D = Source1 (MCS), Source 2 (MCCB) 0150 = 150 A G = 220 V, 50 Hz L = NEMA 4
Electric 0200 = 200 A H = 380 V, 50 Hz D = NEMA 4X
0300 = 300 A K = 600 V, 50 Hz K = Open
0400 = 400 A M = 230 V, 50 Hz P = Sprinklerproof
0600 = 600 A N = 401 V, 50 Hz
Orientation Switch Frame 0800 = 800 A O = 415 V, 50 Hz
1000 = 1000 A W = 240 V, 60 Hz Certification
H = Horizontal Type 240Vac 480Vac 600Vac X = 480 V, 60 Hz
FD = F Frame 30-225A* 30-150A 30-150A Z = 365 V, 50 Hz U = UL Listed
KD = K Frame 400A 200-300A 200-300A C = CSA certified
LD = L Frame 600A 400A 400A
MD = M Frame 800A 600A** 600A**
NB = N Frame 800-1000A 800-1000A 800-1000A

Notes: *225A single phase applications only


**4 pole 600Vac 600A Use N Frame

Automatic Breaker-based Transfer Switch Catalogue Numbering System


13
Breaker-based Switch Type -
Transfer Switches Bypass Isolation

Transfer Switch Is Easy To Maintain And Test


The Cutler-Hammer® Bypass/Isolation Switch is designed to
require minimum maintenance even under the most strenuous
of operating conditions. Due to the use of moulded case
switches and their inherent self-protection capability, the contact
structure and mechanism is extremely long lived.
Our experience has shown that through normal operating
conditions, the moving and stationary contacts will maintain
Double Sided Bypass Isolation Switch
their integrity for the full expected life of the transfer switch.
When isolating and bypassing the transfer switch, a short term
Product Description (less than 3 second) power interruption results. However, this
The Cutler-Hammer® Bypass/Isolation Transfer Switch is designed is less than when transferring power after a power outage
for applications where preventative maintenance, inspection and using a standard transfer switch. Also, with a double-sided
testing must be accomplished while maintaining continuity bypass the transfer switch can be bypassed to either source
of power to the load. Proven Cutler-Hammer® switch designs quickly and easily regardless of the position or condition of
ensure reliable transfer from normal to auxiliary power sources – the transfer switch.
for rapid restoration of essential power in critical applications.
Now available in a compact 100 - 600A fully bussed design for Safety To Maintenance Personnel
both Single and Double Sided Applications. (800A to 4000A also In most instances, the Bypass/Isolation Switch will be in the
available. Contact your local Cutler-Hammer® sales representative Bypass Mode only during a maintenance or testing period.
for information). During this time, there could be operating personnel close to
the equipment. The self protection capability of the
Electrical Ratings Cutler-Hammer® switch would give these operators an extra
• Ratings 40, 100, 150, 200, 225, 260, measure of safety during a rare coincidental fault condition.
400, 600, 800 and 1000 amperes
Features
• 2, 3 or 4-poles
• Up to 600 Vac, 50/60 Hz. The Cutler-Hammer® Bypass Isolation Switch is available with
all the options and features of our standard Transfer Switch
• NEMA® 1, 3R
product line. Proven, microprocessor based programmable
• UL® 1008 listed controllers are supplied as standard on all Bypass Transfer
• CSA® C22.2 No. 178 certified Switches.

Superior Main Contact Structure


The Cutler-Hammer® Combination Bypass and Automatic
Transfer Switch is listed to CSA specifications C22.2 No. 178
and C22.2 No. 31.
As an added plus the switching devices are listed under CSA
C22.2 No. 5. Completely enclosed contacts provide both safety
and reliability. They also ensure the integrity of the contact
assemblies and minimize the need for periodic maintenance of
the contacts, reducing the need for downtime and
maintenance time.

14
BYPASS ISOLATION ATS (2 & 3 POLE) ENCLOSURE DIMENSIONS

Max Max Switch CSA Dimensions (inches/mm)


Amps Volts Frame Bypass Frame A H I J
150 480 F F 21/533 30/965 79.5/2019 18/457
150 600 F F 21/533 30/965 79.5/2019 18/457
200 240 F F 21/533 30/965 79.5/2019 18/457
225* 240 F F 21/533 30/965 79.5/2019 18/457
300 480 K K 21/533 38/965 79.5/2019 18/457
300 600 K K 21/533 38/965 79.5/2019 18/457
400 240 K K 21/533 38/965 79.5/2019 18/457
400 480 L K 21/533 38/965 79.5/2019 18/457
400 600 L K 21/533 38/965 79.5/2019 18/457
600 240 L L 21/533 38/965 79.5/2019 18/457
600 480 M L 21/533 38/965 79.5/2019 18/457
600 600 M L 21/533 38/965 79.5/2019 18/457
800 240 NB MD 27.12/689 38/965 91.5/2324 24/610
800 480 NB MD 27.12/689 38/965 91.5/2324 24/610
800 600 NB MD 27.12/689 38/965 91.5/2324 24/610
1000 240 NB ND 27.12/689 38/965 91.5/2324 24/610
1000 480 NB ND 27.12/689 38/965 91.5/2324 24/610
1000 600 NB ND 27.12/689 38/965 91.5/2324 24/610
* Single Phase Only
BYPASS ISOLATION ATS (4 POLE) ENCLOSURE DIMENSIONS

Max Max Switch CSA Dimensions (inches/mm)


Amps Volts Frame Bypass Frame A H I J
150 480 F F 21/533 30/965 79.5/2019 18/457
150 600 F F 21/533 30/965 79.5/2019 18/457
200 240 F F 21/533 30/965 79.5/2019 18/457
300 480 K K 21/533 38/965 79.5/2019 18/457
300 600 K K 21/533 38/965 79.5/2019 18/457
400 240 K K 21/533 38/965 79.5/2019 18/457
400 480 L K 21/533 38/965 79.5/2019 18/457
400 600 L K 21/533 38/965 79.5/2019 18/457
600 240 L L 21/533 48/1219 79.5/2019 18/457
600 480 NB ND 21/533 48/1219 91.5/2324 24/610
600 600 NB ND 21/533 48/1219 91.5/2324 24/610
800 240 NB ND 27.12/689 48/1219 91.5/2324 24/610
800 480 NB ND 27.12/689 48/1219 91.5/2324 24/610
800 600 NB ND 27.12/689 48/1219 91.5/2324 24/610
1000 240 NB ND 27.12/689 48/1219 91.5/2324 24/610
1000 480 NB ND 27.12/689 48/1219 91.5/2324 24/610
Typical Double Sided Bypass
Transfer Switch 1000 600 NB ND 27.12/689 48/1219 91.5/2324 24/610

4BI H 3 FD A 3 0100 E S C

Type Logic Mounting Number of poles Amperes Voltage Enclosure


4BI = Single 3 = ATC-300 A = Source1 (MCS), Source 2 (MCS) 2 = 2-Pole 0030 = 30 A A = 120 V, 60 Hz S = NEMA 1
Sided I = ATC-600 B = Source1 (MCCB), Source 2 (MCCB) 3 = 3-Pole 0070 = 70 A B = 208 V, 60 Hz R = NEMA 3R
Bypass X = No logic C = Source1 (MCCB), Source 2 (MCS) 4 = 4-Pole 0100 = 100 A E = 600 V, 60 Hz J = NEMA 12
5BI = Double D = Source1 (MCS), Source 2 (MCCB) 0150 = 150 A G = 220 V, 50 Hz L = NEMA 4
Sided 0200 = 200 A H = 380 V, 50 Hz D = NEMA 4X
Bypass 0300 = 300 A K = 600 V, 50 Hz K = Open
0400 = 400 A M = 230 V, 50 Hz P = Sprinklerproof
0600 = 600 A N = 401 V, 50 Hz
Orientation Switch Frame 0800 = 800 A O = 415 V, 50 Hz
1000 = 1000 A W = 240 V, 60 Hz Certification
H = Horizontal Type 240Vac 480Vac 600Vac
X = 480 V, 60 Hz
FD = F Frame 30-225A* 30-150A 30-150A Z = 365 V, 50 Hz U = UL Listed
KD = K Frame 400A 200-300A 200-300A C = CSA certified
LD = L Frame 600A 400A 400A
MD = M Frame 800A 600A** 600A** Notes: *225A single phase applications only
NB = N Frame 800-1000A 800-1000A 800-1000A **4 pole 600Vac 600A Use N Frame

Automatic Bypass Isolation Breaker-based Transfer Switch Catalogue Numbering System


15
BREAKER-BASED TRANSFER SWITCH WITHSTAND/CLOSING RATINGS
When protected by any manufacturers' breaker or Cutler-Hammer® circuit breaker upstream as shown, the transfer switch is rated for use on a circuit capable of
delivering not more than the RMS Symmetrical amps at the voltage shown below.
Voltage Transfer Switch Number of Poles Maximum fault level available at upstream device (kA symmetrical)
Ampere Rating Switched Upstream any manufacturers' breaker or Cutler-Hammer circuit breaker type

25kA 35kA 42kA 50kA 65kA 100kA 200kA


30 - 200 2,3,4 Any* Any* Any* Any* Any* Any* FDC,JDC,KDC
120/240
and 240, 225 2 Any* Any* Any* Any* Any* Any* FDC,JDC,KDC
208Y/120 300 2,3,4 Any* Any* Any* Any* Any* Any* KDC
400 2,3,4 Any* Any* Any* Any* Any* Any* KDC
600 2,3,4 Any* Any* Any* Any* Any* Any* LDC
800 - 1000 2,3,4 Any* Any* Any* Any* Any* Any* ---
30 - 150 2,3,4 Any* Any* Any* Any* Any* (FDB/FD)+LFD 150kA
FDC,JDC,KDC FCL***,LCL***
480Y/277 200 - 300 2,3,4 Any* Any* Any* Any* Any* KDC,NB-TP** LCL***
and 480
400 2,3,4 Any* Any* Any* Any* Any* --- ---
600 2,3 Any* Any* Any* Any* Any* NB-TP ---
800 2,3 Any* Any* Any* Any* --- NB-TP ---
600 - 1000 4 Any* Any* Any* Any* --- --- ---
1000 2,3 Any* Any* Any* Any* --- --- ---
30 - 150 2,3,4 Any* Any* (FD/FDB)+LFD (FD/FDB)+LFD (FD/FDB)+LFD (FD/FDB)+LFD ---
KDC KDC KDC LCL
600Y/347 200 - 300 2,3,4 Any* Any* Any* KDC KDC LCL ---
and 600
400 2,3,4 Any* Any* Any* KDC KDC --- ---
600 2,3 Any* Any* Any* LDC --- --- ---
600 4 Any* --- --- --- --- --- ---
800 - 1000 2,3,4 Any* --- --- --- --- --- ---

*Any manufacturers’ breaker **with P12 limiter *** 150kA maximum

BREAKER-BASED TRANSFER SWITCH WITHSTAND/CLOSING RATINGS


When protected by an upstream fuse type shown, the transfer switch is rated for use on a circuit capable of delivering not
more than the RMS Symmetrical amps at the voltage shown below.
Maximum fault level available at upstream device (kA symmetrical)
Voltage Transfer Switch Number of Poles
Ampere Rating Switched Upstream Fuse Type
Max. Fuse Amperes
100kA 200kA
30 - 225 2,3,4 --- J, T 200A
J,T --- 400A
120/240 R J,T 400A
300 2,3,4 J,T --- 600A
and 240,
208Y/120 J,T R 600A
400 2,3,4 L --- 1200A
L --- 800A
600 2,3,4 --- L 1600A

800 - 1000 2,3,4 --- L 1600A

--- J,T 200A


30 - 150 2,3,4 J,T --- 400A
480Y/277, R J,T 400A
200 - 300 2,3,4
480, J,T --- 600A
600Y/347 J,T R 600A
and 600 400 2,3,4 L --- 1200A
L --- 800A
600 2,3 --- L 1600A

600 4 --- L 1600A

800 - 1000 2,3,4 --- L 1600A

16
Automatic Transfer Controller Features
Switch Controllers

Design Highlights
• LCD-based display for programming, system diagnostic and
Help Message display
• Mimic diagram with source available and connected
LED indications
• Stores customer/factory established parameters in
nonvolatile memory
• Field programmable time delays
• Displays real time and historical information with a
time-stamped history log
• Permits system testing via a front screen test pushbutton
• Programmable plant exerciser — OFF, daily, 7, 14, 28-day
interval programmable run times
• Complies with UL 1008/CSA 22.2 No. 178

Contactor-Based Design ATS Showing Optional Controllers Available


General Description (ATC-600 and ATC-800 Controllers)
The ATC-600 and ATC-800 controllers were designed with
Product Description operational simplicity in mind. The user-friendly front panel
interface simplifies routine operation, programming, data
The automatic transfer switch controller is a key component
presentation and setting adjustments. An LCD-based display
within the automatic transfer switch. It provides the intelligence
provides the flexibility of a back-lit display for enhanced visibility.
to sense the proper conditions to initiate a transfer and a
retransfer of the contactor. Eaton’s Cutler-Hammer® automatic
Design Highlights
transfer switches come with the design flexibility of being
applied with one of three controllers. All three controllers provide • LCD-based display for programming, system diagnostic

the basic functions needed to perform an automatic transfer. and Help Message display
• Mimic diagram with source available and connected
LED indications
Design Highlights
• Stores customer/factory established parameters in
• Mimic diagram with source available and connected LED
nonvolatile memory
indications
• Field programmable time delays
• Field selectable fixed time delays
• Displays real time and historical information with a
• Permits system testing via a front screen test pushbutton
time-stamped history log
• Complies with UL 1008/CSA 22.2 No. 178
• Permits system testing via a front screen test pushbutton
• Generator Test Selectable — OFF, 7, 14, 28-day interval
• Programmable plant exerciser — OFF, daily, 7, 14, 28-day
interval selectable run times
General Description (ATC-300 Controller)
• Communicate via Modbus communication protocol
From installation to programming to usage, the ATC-300 open • Complies with UL 1008/CSA 22.2 No. 178
transition controller was designed with operational simplicity in
• Load monitoring, delayed, in-phase and closed transition
mind. The user friendly front panel interface simplifies routine
operation, programming, data presentation and setting
adjustments. An LCD-based display provides the flexibility
of a back-lit display for enhanced visibility.

17
AUTOMATIC TRANSFER SWITCH CONTROLLERS

Description ATC-300 ATC-600 / ATC-800


System Application Voltage Up to 600 Vac Up to 600 Vac
Voltage Specifications
Voltage Measurements of: Source 1 and 2 — VAB, VBC and VCA Source 1, 2 and Load — VAB, VBC and VCA
Voltage Measurement Range 0 – 790 Vac rms 0 – 700 Vac rms
Operating Power 65 Vac – 145 Vac 65 Vac – 145 Vac
Frequency Specifications
Frequency Measurements of: Source 1 and 2 Source 1 and 2
Frequency Measurement Range 40 – 70 Hz 40 – 80 Hz
Environmental Specifications
Operating Temperature Range -20 to +70ºC -20 to +70ºC
Storage Temperature Range -30 to +85ºC -30 to +85ºC
Operating Humidity 0 to 95% Relative Humidity (Non-condensing) 0 to 90% Relative Humidity (Non-condensing)
Operating Environment Resistant to Ammonia, Methane, Nitrogen, Resistant to Ammonia, Methane, Nitrogen, Hydrogen
Hydrogen and Hydrocarbons and Hydrocarbons
Front Panel Indication
Mimic Diagram with LED Indication Unit Status. Source 1 and 2 — Available and Automatic, Test and Program Mode.
Connected (5 Total) Source 1 and 2 —Available, Connected and Preferred.
Load Energized (10 Total) Preferred. Load Energized (10 Total)
Main Display LCD-Based Display LED Display
Display Language English, French English
Communications Capable N/A PONI/INCOM
Enclosure Compatibility NEMA 1, 12 and 3R, NEMA 1, 12, 3R and 4X UV
UV Resistant Faceplate Resistant Faceplate
Programming Selections
Time Delay Normal to Emergency 0 – 1800 Seconds 0 – 1800 Seconds
Time Delay Emergency to Normal 0 – 1800 Seconds 0 – 1800 Seconds
Time Delay Engine Cooldown 0 – 1800 Seconds 0 – 1800 Seconds
Time Delay Engine Start 0 – 120 Seconds 0 – 120 Seconds
Time Delay Neutral 0 – 120 Seconds 0 – 120 Seconds or Based on
Load Voltage Decay of 2% – 30% of Nominal
Time Delay Source 2 Fail 0 – 6 Seconds 0 – 6 Seconds
Time Delay Voltage Unbalance 10 – 30 Seconds N/A
Voltage Unbalance 3-Phase 0 or 1 (1 = Enabled) —
% of Unbalanced Voltage Dropout 5% – 20% (DO) Dropout -2% – 3% (PU) N/A
Phase Reversal 3-Phase OFF, ABC, CBA N/A
In-Phase 0 or 1 (1 = Enabled) N/A
Load Sequencing N/A Up to 10 Devices (via Sub-network)
Pre-Transfer Signal 1 – 120 Seconds (Form C Contact) 0 – 120 Seconds Up to 10 Devices (via Sub-network)
Plant Exerciser Selectable — Off, Daily or 7, 14, 28 Selectable — Disabled or 7
Day Intervals, 0 – 600 Minutes, Load or No Load Day Interval, 0 – 600 Minutes, Load or No Load
Preferred Source Selection N/A Source 1 or 2 or None
Commitment to Transfer in TDNE N/A Enabled or Disabled
Re-transfer Mode N/A Automatic or Manual
Auto Daylight Savings Time Adjustment 0 or 1 (1 = Enabled) —
System Selection Utility/Generator or Dual Utility Utility/Generator or Dual Utility or Dual Generator
Closed Transition Frequency Difference N/A 0.0 – 3.0 Hz
Closed Transition Voltage Difference N/A 1 – 5%

Note: Features are order specific. Not all features are supplied as standard.
18
Integrated Solutions

Automatic Transfer Switch Integrated Into a Switchboard Lineup

Integrated Solutions
Minimize initial equipment costs, reduce installation time, and
increase system reliability. These are goals of all involved in
placing electrical distribution equipment in service — from the
design engineer, to the electrical contractor, and especially with
the end user of the equipment.
Eaton believes the transfer switch equipment is an integral part
of the distribution equipment. This fundamental belief is why
Eaton offers various types of transfer switches for the design
engineer, electrical contractor and the user to choose from.
Eaton offers Contactor-Based, Moulded Case and Circuit Breaker
style switches.
All Eaton transfer switches are designed to meet the requirements
set forth by CSA C22.2 No.178, however, all transfer switches are
not created equal. You can be assured of safe and reliable operation
from all types of transfer switches that Eaton offers.

19
Eaton Corporation is a diversified PowerChain Management
power management company solutions help enterprises
ranked among the largest achieve sustainable and
Fortune 500 companies. The competitive advantages through
electrical sector is Eaton’s largest proactive management of the
division and is a global leader power system as a strategic,
in electrical control, power integrated asset throughout
distribution, power quality, its life cycle. With Eaton’s
automation, and monitoring distribution, generation and
products and services. power quality equipment;
Eaton’s global electrical product full-scale engineering services;
lines, including Cutler-Hammer®, and information management
MGE Office Protection systems, the power system
Systems™, Powerware®, is positioned to deliver
Holec®, MEM®, Santak and powerful results: greater
Moeller, provide customer-driven reliability, operating cost
PowerChain Management® efficiencies, effective use of
solutions to serve the power capital, enhanced safety, and
system needs of the industrial, risk mitigation.
institutional, government,
utility, commercial, residential,
IT, mission critical and OEM
markets worldwide.

Av
ail
abl
efr
om

BRE
WSS
UPPL
Y.COM
Eaton
5050 Mainway
Burlington, Ontario
L7L 5Z1
www.eatoncanada.ca
1-800-268-3578
fsc symbol
© 2009 Eaton Corporation
All Rights Reserved
Printed in Canada PowerChain Management is a registered
Publication No. BR01602001K trademark of Eaton Corporation.