Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
iPASOLINK 100/200
SECTION III MAINTENANCE
CONTENTS
CONTENTS ............................................................................................................................- 1 -
1. General..........................................................................................................................1-1
2. Precaution ....................................................................................................................2-1
2.1 Maintenance and Operation Manual....................................................................................... 2-4
2.1.1 Wrist Strap Connection.................................................................................................... 2-4
2.1.2 Maintenance Mode Setting (for the LCT Operation) ........................................................ 2-4
2.1.3 Manual Switch Operation ................................................................................................ 2-5
2.1.4 XPIC Configuration........................................................................................................ 2-18
3. Test Sets and Accessories .........................................................................................3-1
4. Current Status ..............................................................................................................4-1
4.1 Current Status......................................................................................................................... 4-1
5. Routine Maintenance...................................................................................................5-1
5.1 Meter Reading ........................................................................................................................ 5-1
5.2 Performance Monitoring ......................................................................................................... 5-3
5.2.1 PM Parameters ............................................................................................................... 5-3
6. Corrective Maintenance ..............................................................................................6-1
6.1 Alarm/Status ........................................................................................................................... 6-2
6.1.1 Alarm Management ......................................................................................................... 6-4
6.1.2 Alarm and Status Indication Detail .................................................................................. 6-4
7. Control Items................................................................................................................7-1
7.1 Loopback ................................................................................................................................ 7-2
7.1.1 IF Loopback..................................................................................................................... 7-2
7.1.2 TDM Loopback Control.................................................................................................... 7-9
7.2 Equipment Maintenance ....................................................................................................... 7-22
7.2.1 Equipment Utility ........................................................................................................... 7-22
7.2.2 Equipment Reset........................................................................................................... 7-67
7.2.3 Radio Control ................................................................................................................ 7-74
7.2.4 Laser Management ....................................................................................................... 7-86
7.2.5 Cluster Alarm Setting .................................................................................................... 7-91
7.2.6 Inventory........................................................................................................................ 7-95
Maintenance NWD-107462-05E
October, 2011
- 2 -/END
NWD-107462-05E Maintenance
General 1-1
1. GENERAL
This section provides information on routine and corrective maintenance for the
iPASOLINK used for 6 to 42 GHz PDH/SDH/Packet digital radio system.
Maintenance NWD-107462-05E
1-2/END General
NWD-107462-05E Maintenance
Precaution 2-1
2. PRECAUTION
The maintenance personnel should report arrival and departure from a station to the
relevant station. The following precaution must be carefully observed during
maintenance.
Warning
1. The -48V DC power is superimposed on the centre conductor of the coaxial
cable between the IDU and the ODU. Connecting test equipment directly to
this terminal may damage it and touching the coaxial cable core may cause
electrical shock.
Caution
1. In a system using the OPTICAL STM-1 interface, do not stare at the laser
beam or look at it directly with optical instruments. Otherwise, it may hurt
your eyes (Class 1 laser product)
2. The top surface of the IDU above MODEM is hot in operation.
3. When replacing the IDU, turn off the “ODU PWR” switch and disconnected
all cables.
4. During maintenance, the IDU should be set to maintenance ON by the LCT.
5. To prevent traffic interruption, under the maintenance, perform TX/RX SW
manual switching in 1+1 system.
Maintenance NWD-107462-05E
2-2 Precaution
6. While the CPU is initialized by the CPU RESET switch, alarm(s) status is
reset to normal. After initialized, the alarm information is properly provided
through relay contacts.
7. Information on the maintenance and the control such as Mute, CW, LB etc.
is released if the power is turned off.
NWD-107462-05E Maintenance
Precaution 2-3
Straight Type
Tighten the TNC-male connector of IF cable to the IDU with engage connector nut
only using fingers and holding the cable with another hand.
L-angle Type
Tighten the engage connector nut only for the L-angle connector also.
(Tightening Torque: 0.3 to 0.5 N-m (3 to 5kg. Cm))
If rotate other parts of the L-angle connector as illustrated left, it can cause connector
damage.
Maintenance NWD-107462-05E
2-4 Precaution
Procedure 2-1
Procedure 2-2
2. Confirm that the MAINT on the top of the LCT window becomes yellow.
Maintenance Button
NWD-107462-05E Maintenance
Precaution 2-5
3. And also confirm that the MAINT LED at the front of the equipment becomes
yellow.
Note: This item is supported when the configuration is set to 1+1 Hot Standby
mode only.
Ex: MODEM No.1 and No.2 constructed as 1+1 Hot Standby mode and
MODEM No.1 act as working side. MODEM No.2 is act as standby side.
Procedure 2-3
1. Click the Maintenance button on the top of the LCT window to turn on the
maintenance mode.
Maintenance NWD-107462-05E
2-6 Precaution
7. Click OK button.
NWD-107462-05E Maintenance
Precaution 2-7
10. The MODEM TX / RX Switch Control window appears again. Confirm the
parameters displayed.
11. Click Maintenance button on the top of the LCT window to exit the
maintenance mode.
Note: This item is supported when the configuration is set to 1+1 Twin
Path/Hot Standby mode only.
Ex: MODEM No.1 and No.2 constructed as 1+1 Twin Path mode and
MODEM No.1 act as working side. MODEM No.2 is act as standby side.
Procedure 2-4
Maintenance NWD-107462-05E
2-8 Precaution
7. Click OK button.
NWD-107462-05E Maintenance
Precaution 2-9
10. The MODEM TX / RX Switch Control window appears again. Confirm the
parameters displayed.
11. Click Maintenance button on the top of the LCT window to exit maintenance
mode.
Procedure 2-5
Maintenance NWD-107462-05E
2-10 Precaution
8. The RSTP Control window appears again. Confirm the parameters displayed.
NWD-107462-05E Maintenance
Precaution 2-11
9. After finishing RSTP Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
Procedure 2-6
4. Select SNCP Switch Control from the Protection Control sub menu.
5. The SNCP Switch Control window appears. Click the desired number to
configure.
Maintenance NWD-107462-05E
2-12 Precaution
7. Click OK button.
NWD-107462-05E Maintenance
Precaution 2-13
10. The SNCP Switch Control window appears again. Confirm the parameters
displayed.
11. Click Maintenance button on the top of the LCT window to exit maintenance
mode.
Maintenance NWD-107462-05E
2-14 Precaution
(5) Timing Source Switch Control (This mode available when the Lock
Out is Off only)
In case that Lock Out Status is set to On, follow the Procedure 2-7 to change the
setting to Off and then follow the Procedure 2-8 to configure Timing Source
Switching.
Procedure 2-7
4. Select Timing Source Switch Control from the Protection Control sub
menu.
5. The Timing Source Switch Control window appears. Click desired Lock
Out to configure.
6. The Timing Source Switch Control box appears. Select Off from Lock Out.
NWD-107462-05E Maintenance
Precaution 2-15
7. Click OK button.
9. The Timing Source Switch Control window appears again. Confirm the
parameters displayed.
10. After finishing Lock Out Setting, click Maintenance button on the top of the
LCT window to exit maintenance mode.
Maintenance NWD-107462-05E
2-16 Precaution
Procedure 2-8
4. Select Timing Source Switch Control from the Protection Control sub
menu.
5. The Timing Source Switch Control window appears. Click the desired
Timing Source Switch Control to configure.
Click.
6. The Timing Source Switch Control box appears. Select specify switching
mode (Manual SW or Forced SW).
7. Click OK button.
NWD-107462-05E Maintenance
Precaution 2-17
10. The Timing Source Switch Control window appears again. Confirm the
parameters displayed.
11. Click Maintenance button on the top of the LCT window to exit maintenance
mode.
Maintenance NWD-107462-05E
2-18/END Precaution
When the cable length difference between Master and Slave MODEMs is eight
meters or more, adjust length by LCT operation, Maintenance Æ Offline
Maintenance Control.
Default: -8 m to +8 m
When executing Mute or CW, perform after executing XPIC Reset (for both
local and remote stations). For this, select Forced Reset of the XPIC Reset
radio button.
NWD-107462-05E Maintenance
Test Sets and Accessories 3-1
The test sets and special accessories listed in Table 3-1 are required for maintenance.
If recommended test sets and accessories are not available, equivalents may be used.
Maintenance NWD-107462-05E
3-2/END Test Sets and Accessories
NWD-107462-05E Maintenance
Current Status 4-1
4. CURRENT STATUS
But it is just for viewing system status only you can not make any changes of all
items displayed on this window. (Such as modify, adding, masking alarms or items)
The Active Alarm tab displays all current alarms detected on the equipment
side.
You can download the current alarm list to LCT PC by clicking Save button
on the top left of the Active Alarm tab.
The Event Log tab displays all alarms and status detected when there is any
changed on the line card and configuration on equipment.
Maintenance NWD-107462-05E
4-2 Current Status
You can download the Event Status list to the LCT PC by clicking Save
button on the top left of the Event Log tab.
1. Click Save button of the Active Alarm tab or the Event Log tab.
NWD-107462-05E Maintenance
Current Status 4-3
3. The Save As window appears. Select the proper folder of the Local PC, and
then click Save button.
4. After finishing the export of log file, the Download Complete window
appears. Click Close button.
Maintenance NWD-107462-05E
4-4 Current Status
NWD-107462-05E Maintenance
Current Status 4-5
The ODU tab displays all alarm and status detected on ODU.
Maintenance NWD-107462-05E
4-6 Current Status
The IDU tab displays all alarms and status detected on IDU.
NWD-107462-05E Maintenance
Current Status 4-7
Maintenance NWD-107462-05E
4-8/END Current Status
NWD-107462-05E Maintenance
Routine Maintenance 5-1
5. ROUTINE MAINTENANCE
This chapter provides the routine (annually) maintenance procedures to ensure the
satisfactory operation of the equipment. During routine maintenance, carefully
observe the precautions given in Chapter 2.
Procedure 5-1
Maintenance NWD-107462-05E
5-2 Routine Maintenance
Notes
1. If an abnormal indication appears, check Alarm/Status, performance monitor
and perform loopback test to distinguish sections of normal and alarmed.
2. RX LEVEL varies depending on received RF signal level.
3. Power Supply voltage at ODU varies depending of IF cable length between
the IDU and ODU.
NWD-107462-05E Maintenance
Routine Maintenance 5-3
5.2.1 PM Parameters
Performance Monitor Parameters can be measured from iPASOLINK.
Maintenance NWD-107462-05E
5-4 Routine Maintenance
NWD-107462-05E Maintenance
Routine Maintenance 5-5
Maintenance NWD-107462-05E
5-6 Routine Maintenance
NWD-107462-05E Maintenance
Routine Maintenance 5-7
Maintenance NWD-107462-05E
5-8 Routine Maintenance
NWD-107462-05E Maintenance
Routine Maintenance 5-9
Maintenance NWD-107462-05E
5-10 Routine Maintenance
NWD-107462-05E Maintenance
Routine Maintenance 5-11
Maintenance NWD-107462-05E
5-12/END Routine Maintenance
NWD-107462-05E Maintenance
Corrective Maintenance 6-1
6. CORRECTIVE MAINTENANCE
Faults can be classified in to those that cause deterioration of the transmission quality
and those that interrupt the traffic due to a malfunction of the equipment. This
chapter explains the troubleshooting procedures for equipment faults and the
corresponding remedial methods. The purpose of troubleshooting malfunctioning
equipment is to restart the service by locating the faulty part and replacing it with a
spare.
The faults that cause deterioration quality are primarily originated by changes
occurred in the state of propagation. Therefore, if a decline in the transmission
quality or similar fakes place frequently, the link design will have to be reviewed.
Maintenance NWD-107462-05E
6-2 Corrective Maintenance
6.1 Alarm/Status
When an alarm event has occurred, at first, check alarm indication on the front of the
IDU. Continuously, connect the PC to the LOCAL jack on the LCT port mounted on
the IDU and check alarm/status indication.
A faulty part can be located by checking the ALARM LED indications and LCT
Alarm indications.
Alarm Report
When an alarm is detected, alarm notification is made to the user by lighting
up the LEDs on the rack, and reporting the alarm to user interface. The alarm
notification is also made to the user by an Office alarm, such as the station
alarm bell and lamps.
Web-LCT indication
The alarm LED indications faulty part can be located by checking the ALM
LED indicators and Web-LCT Alarm indications.
NWD-107462-05E Maintenance
Corrective Maintenance 6-3
Meter Reading
Loopback
Maintenance NWD-107462-05E
6-4 Corrective Maintenance
Critical (CR) :
The Critical severity level indicates that a service affecting condition has occurred
and an immediate corrective action is required. Such a severity can be reported, for
example, when a managed object becomes totally out of service and its capability
must be restored.
Major (MJ):
The Major severity level indicates that a service affecting condition has developed
and an urgent corrective action is required. Such a severity can be reported, for
example, when there is a severe degradation in the capability of the managed object
and its full capability must be restored.
Minor (MN):
The Minor severity level indicates the existence of a non-service affecting fault
condition and that corrective action should be taken in order to prevent a more
serious (for example, service affecting) fault. Such a severity can be reported, for
example, when the detected alarm condition is not currently degrading the capacity
of the managed object.
Warning (WR):
The Warning severity level indicates the detection of a potential or impending
service affecting fault, before any significant effects have been felt. Action should be
taken to further diagnose (if necessary) and correct the problem in order to prevent it
from becoming a more serious service affecting fault.
NWD-107462-05E Maintenance
Corrective Maintenance 6-5
Maintenance NWD-107462-05E
6-6 Corrective Maintenance
NWD-107462-05E Maintenance
Corrective Maintenance 6-7
Maintenance NWD-107462-05E
6-8 Corrective Maintenance
NWD-107462-05E Maintenance
Corrective Maintenance 6-9
Maintenance NWD-107462-05E
6-10 Corrective Maintenance
NWD-107462-05E Maintenance
Corrective Maintenance 6-11
Maintenance NWD-107462-05E
6-12/END Corrective Maintenance
NWD-107462-05E Maintenance
Control Items 7-1
7. CONTROL ITEMS
Following control items is available when the maintenance mode is on only. And be
careful during the operation on these control items. Because there is possibility to be
traffic affected during operation.
z Loopback Control
- IF Loopback Control
- TDM Loopback Control (E1 LB1/LB2)
- TDM Loopback Control (STM1 LB1/LB2)
z Database Upload/Download
- HW Reset Control
- FW Reset Control
z Radio Control
z License Management
Maintenance NWD-107462-05E
7-2 Control Items
z Inventory Information
z Performance Monitor
z Offline Maintenance
- Data Adjust
- RF Sub Band Select
7.1 Loopback
When there is an interruption of signals, use the SDH/SONET/PDH analyzers and
isolate the faulty section by checking the traffic signal by loopback. Setup the test
equipment according to the following diagrams for PDH or SDH configuration.
The facility loopback is toward the baseband interface direction and terminal
loopback is toward the CS card direction. They are performed at the STM-1/4 (SDH)
or E1 (PDH) interfaces. (Note 1, 2)
When executing the loopback control, set Maintenance Mode to ON and do not
release Maintenance Modes while controlling loopback.
7.1.1 IF Loopback
Execute the MODEM Loopback control for checking the incoming of traffic signal
inside MODEM interface (The traffic signal from E1 interfaces to wireless
direction).
NWD-107462-05E Maintenance
Control Items 7-3
Notes
1. Turn on the TX Mute Control before executing IF Loopback. While IF
Loopback is being executed, the TX INPUT ALM of ODU will occur because
the MOD output is determinate. So, the MOD ALM and TX INPUT ALM will
be masked while IF Loopback is executed.
2. The MOD ALM and TX INPUT ALM will be un-masked as soon as the IF
Loopback is off.
3. If the remote control connected at opposite side, the remote control will be
disconnect while the IF Loopback is executed and does not restore in default.
So, it is necessary to set the IF Loopback Release Time to release IF
Loopback automatically before executing the IF Loopback.
Importance:
1. Turn ON the TX Mute control before executing IF Loopback.
Procedure 7-1
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the MODEM Loopback Control from the Loopback Control sub
menu.
5. The MODEM Loopback Control window appears. Click Off at the specify
MODEM No. (or SW GRP) of IF Loopback field.
Maintenance NWD-107462-05E
7-4 Control Items
7. Click OK button.
NWD-107462-05E Maintenance
Control Items 7-5
10. The MODEM Loopback Control window appears again. Confirm that the
status of IF Loopback of specified MODEM is displayed On.
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
Maintenance NWD-107462-05E
7-6 Control Items
Importance:
1. Turn ON the TX Mute control before executes IF Loopback.
2. When executing the Loopback control, set Maintenance Mode to ON and do
not release Maintenance Modes during controlling loopback.
Procedure 7-2
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the MODEM Loopback Control from the Loopback Control sub
menu.
5. The MODEM Loopback Control window appears. Click Off at the specify
MODEM (No.1/No.2) of IF Loopback field.
NWD-107462-05E Maintenance
Control Items 7-7
7. Click OK button.
Maintenance NWD-107462-05E
7-8 Control Items
10. The MODEM Loopback Control window appears again. Confirm that the
status of IF Loopback of specified MODEM is displayed On.
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
NWD-107462-05E Maintenance
Control Items 7-9
Execute the TDM Loopback Control (E1 Loopback1) for checking the incoming of
E1 traffic signal inside E1 interfaces. (The traffic signal from outside to E1 interfaces
direction).
Note: During executing Loopback, the AIS will be detected at down stream of
the specified channel (Loopback channel).
Importance:
1. When executing the Loopback control, set Maintenance Mode to ON and do
not release Maintenance Modes while controlling loopback.
Procedure 7-3
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the TDM Loopback Control (E1 Loopback1) from the Loopback
Control sub menu.
5. The TDM Loopback Control (E1 Loopback1) window appears. Click Off
at the specified E1 Loopback1 channel from the Main Board field.
Maintenance NWD-107462-05E
7-10 Control Items
6. The TDM Loopback Control (E1 Loopback) box appears. Click On for
specified E1 Loopback1 CH**.
NWD-107462-05E Maintenance
Control Items 7-11
7. Click OK button.
10. The TDM Loopback Control (E1 Loopback1) window appears again.
Confirm that the status of specified CH is displayed On.
Maintenance NWD-107462-05E
7-12 Control Items
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
NWD-107462-05E Maintenance
Control Items 7-13
Execute the TDM Loopback Control (E1 Loopback2) for checking the incoming of
E1 traffic signal through MODEM IF. (The traffic signal from wireless to E1
interfaces direction).
Remote login to the opposite site NE and execute LB2 at opposite site NE.
Note: During executing Loopback, the AIS alarm will be detected at down
stream of the specified channel (Loopback channel).
Importance:
1. When executing the Loopback control, set Maintenance Mode to ON and do
not release Maintenance Modes during controlling loopback.
Procedure 7-4
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the TDM Loopback Control (E1 Loopback2) from the Loopback
Control sub menu.
5. The TDM Loopback Control (E1 Loopback2) window appears. Click Off
at the specified E1 Loopback2 Channel from the Main Board field.
Maintenance NWD-107462-05E
7-14 Control Items
6. The TDM Loopback Control (E1 Loopback2) box appears. Click On for
specified E1 Loopback2 CH**.
NWD-107462-05E Maintenance
Control Items 7-15
7. Click OK button.
10. The TDM Loopback Control (E1 Loopback2) window appears again.
Confirm that the status of specified CH is displayed On.
Maintenance NWD-107462-05E
7-16 Control Items
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
Execute the TDM Loopback Control (STM-1 Loopback1) for checking the incoming
of TDM traffic signal inside STM-1 interfaces. (The traffic signal from outside to
STM-1 interfaces direction).
Note: During executing Loopback, the AIS will be detected at down stream of
the specified channel (Loopback channel).
NWD-107462-05E Maintenance
Control Items 7-17
Importance:
1. When executing the Loopback control, set Maintenance Mode to on and do
not release Maintenance Modes while controlling loopback.
Procedure 7-5
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
Maintenance NWD-107462-05E
7-18 Control Items
7. Click OK button.
10. The TDM Loopback Control (STM-1 Loopback1) window appears again.
Confirm that the status of STM-1 Loopback1 Port** is displayed On.
NWD-107462-05E Maintenance
Control Items 7-19
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
Execute the TDM Loopback Control (STM-1 Loopback2) for checking the incoming
of TDM traffic signal through MODEM IF. (The traffic signal from wireless to
STM-1 interfaces direction).
Remote login to the opposite site NE and execute STM-1 Loopback2 at opposite site
NE.
Note: During executing Loopback, the AIS will be detected at down stream of
the specified channel (Loopback channel).
Importance:
1. When executing the Loopback control, set Maintenance Mode to ON and do
not release Maintenance Modes during controlling loopback.
Maintenance NWD-107462-05E
7-20 Control Items
Procedure 7-6
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
NWD-107462-05E Maintenance
Control Items 7-21
7. Click OK button.
10. The TDM Loopback Control (STM-1 Loopback2) window appears again.
Confirm that the status of STM-1 Loopback2 Port** is displayed On.
Maintenance NWD-107462-05E
7-22 Control Items
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
NWD-107462-05E Maintenance
Control Items 7-23
• Provisioning Clear
Use this function to clear Provisioning setting from Main Board and STM-1
(option).
Procedure 7-7
2. Select the Export (NE->Storage) Utility from the Equipment Utility sub
menu.
Maintenance NWD-107462-05E
7-24 Control Items
5. The Save As window appears. Select the specified directory on the specified
device (local PC/USB memory) and then click Save button.
NWD-107462-05E Maintenance
Control Items 7-25
Connect USB memory to the USB port at the front of iPASOLINK and the
operation is on LCT.
Maintenance NWD-107462-05E
7-26 Control Items
This function is used for downloading F/Ws from Local PC or USB Memory to
the targets. (Main Board, ODU)
This function is used for downloading FPGA from Local PC or USB Memory to
the target cards.
This function is used to update the MODEM parameter file on the MODEM
module.
Importance:
1. Confirm that you have IDU Main Board Program File that is provided from
NEC.
2. Confirm the current version of IDU Main Board Program File from the IDU
tab of Equipment Inventory Information window.
Procedure 7-8
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
NWD-107462-05E Maintenance
Control Items 7-27
4. The Update (Storage->NE) Utility window appears. Click the Program File
radio button and then click Execute button.
5. The Update (Storage->NE) Utility box appears. Select the Main Board
from drop-down list and then click Next button.
Maintenance NWD-107462-05E
7-28 Control Items
7. The file selection window appears. Select the Main Board firmware file and then
click Open (or OK) button.
• Local PC
• USB Memory
NWD-107462-05E Maintenance
Control Items 7-29
11. After the download is completed, the Update Complete! window appears.
Check the Program ROM Switching check box and then click OK button.
Maintenance NWD-107462-05E
7-30 Control Items
Note: If the check box of Program ROM Switching is not checked, you have to
execute Program ROM Switching later by manually. (For more detail
refer to 7.2.1.3 Program ROM Switching)
And use in the following case.
3. When suppose to continue downloads another data and then executes the
update one time.
4. Program ROM will be switched to new version after equipment restart. You
can confirm running version in Equipment Inventory Information Window.
12. The Warning box appears. Click OK button. iPASOLINK will be restarted
automatically.
13. The Information box appears. Click OK button. The WebLCT will shutdown
automatically.
NWD-107462-05E Maintenance
Control Items 7-31
15. Select the Inventory (Equipment Inventory Information) from the LCT
menu.
16. The Equipment Inventory Information (IDU) window appears. Confirm the
Current version (new program running version) of Main Board.
Maintenance NWD-107462-05E
7-32 Control Items
17. After finishing Program File download, click Maintenance button on the top of
the LCT window to exit maintenance mode.
NWD-107462-05E Maintenance
Control Items 7-33
(b) ODU
Importance:
1. Confirm that you have ODU Program File that is provided from NEC.
2. Confirm the current version of ODU Program File from the ODU tab of the
Equipment Inventory Information window.
3. Turn on the Maintenance Mode before download ODU Program File. And do
not release Maintenance Mode while downloading.
Procedure 7-9
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode ON.
3. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
5. The Update (Storage->NE) Utility box (1/2) appears. Select the ODU from
drop-down list and then click Next button.
Maintenance NWD-107462-05E
7-34 Control Items
6. The Update (Storage->NE) Utility box (2/2) appears. Select the MODEM
from drop-down list and then click Next button.
NWD-107462-05E Maintenance
Control Items 7-35
8. The file selection window appears. Select the ODU firmware file and then click
Open (or OK) button.
• Local PC
• USB Memory
Maintenance NWD-107462-05E
7-36 Control Items
12. After the download is completed, the Update Complete! window appears.
Check the Program ROM Switching check box and then click OK button.
NWD-107462-05E Maintenance
Control Items 7-37
Note: If the checkbox of Program ROM Switching is not checked you have to
execute Program ROM Switching later by manually. (For more detail
refer to 7.2.1.3 Program ROM Switching)
13. The Warning box appears. Click OK button. iPASOLINK will be restarted
automatically.
Maintenance NWD-107462-05E
7-38 Control Items
14. The Information box appears. Click OK button. The WebLCT will shutdown
automatically.
16. Select the Inventory (Equipment Inventory Information) from the LCT
menu.
NWD-107462-05E Maintenance
Control Items 7-39
18. After finishing Program File download, click Maintenance button on the top of
the LCT window to exit maintenance mode.
Importance:
1. Confirm data file of FPGA was already acquired from NEC.
2. Confirm the F/W versions on the IDU tab of the Equipment Inventory
Information window.
3. When executing the FPGA data download, set Maintenance Mode to on and
do not release Maintenance Modes while controlling download.
Procedure 7-10
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
4. The Update (Storage->NE) Utility window appears. Select the FPGA Data.
Maintenance NWD-107462-05E
7-40 Control Items
5. The FPGA Data window appears. Select the specific Card (Main Board or
STM1-S) / FPGA from drop-down lists for download then click Next button.
• When selecting the Main Board from drop-down list of Card type
NWD-107462-05E Maintenance
Control Items 7-41
7. The file selection window appears. Select the FPGA Data file and then click
Open (or OK) button.
• Local PC
• USB Memory
Maintenance NWD-107462-05E
7-42 Control Items
NWD-107462-05E Maintenance
Control Items 7-43
11. The Update Complete! window appears after downloading. Then auto-revert
should be executed by clicking the OK button.
12. The Information box appears. Click OK button. The WebLCT will shutdown
automatically.
14. Select the Inventory (Equipment Inventory Information) from the LCT
menu.
15. After restarting, confirm the new program running on the Equipment
Inventory Information (IDU) window.
Maintenance NWD-107462-05E
7-44 Control Items
16. After finishing FPGA Data download, click Maintenance button on the top of
the LCT window to exit maintenance mode.
NWD-107462-05E Maintenance
Control Items 7-45
Importance:
Upload existing Configuration Data File.
Note:
1. Do not use the same folder between Exist Configuration Data File and Data
for Download that allows comparison of each Data.
2. When executing the Configuration Data download, set Maintenance Mode to
on and do not release Maintenance Modes while controlling download.
Procedure 7-11
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
4. The Update (Storage->NE) Utility window appears. Check the Config Data
radio button then click Execute button.
5. The source selection window appears. Select the specific Config Data Type
(Network Config, Equipment Config, Partial Equipment Config, User Config).
Maintenance NWD-107462-05E
7-46 Control Items
6. Select destination storage (Local PC/USB Memory) from the Import File
field and then click File icon button.
7. The file selection window appears. Select the Config Data file and then click
Open (or OK) button.
• Local PC
NWD-107462-05E Maintenance
Control Items 7-47
• USB Memory
8. The source selection window appears again. When selected source is other than
Partial Equipment Config, click OK button, and proceed to step 11.
Maintenance NWD-107462-05E
7-48 Control Items
10. Configuration item selection window appears. Select a target configuration and
then click OK button.
NWD-107462-05E Maintenance
Control Items 7-49
13. The Update Complete! window appears after downloading. Then auto-revert
should be executed by clicking OK button.
14. The Information box appears. Click OK button. The WebLCT will shutdown
automatically.
Maintenance NWD-107462-05E
7-50 Control Items
16. Upload the Configuration Data File again and then acquire the Configuration
Data.
17. Confirm the latest Configuration Data running by comparing the newly acquired
Configuration Data to that acquired before download.
18. After finishing Configuration Data download, click Maintenance button on the
top of the LCT window to exit maintenance mode.
Importance:
1. Confirm specific Parameter File for MODEM was already acquired from
NEC.
2. Confirm specific Parameter File for MODEM.
3. When executing the MODEM Parameter Download, set Maintenance Mode
to ON and do not release Maintenance Modes while controlling Download.
Procedure 7-12
20. Click Maintenance button on the top of the LCT window to turn maintenance
mode ON.
22. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
NWD-107462-05E Maintenance
Control Items 7-51
24. The Update (Storage->NE) Utility box appears. Select a desired MODEM
and then click Next> button.
25. The source selection window appears. Select the destination storage (Local
PC/USB Memory) from the Import File field and then click File icon button.
Maintenance NWD-107462-05E
7-52 Control Items
26. The file selection window appears. Select the MODEM Parameter file and then
click Open (or OK) button.
• Local PC
NWD-107462-05E Maintenance
Control Items 7-53
• USB Memory
Maintenance NWD-107462-05E
7-54 Control Items
30. The Update Complete! window appears after downloading. Then auto-revert
should be executed by clicking the OK button.
31. After restarting, open the window of specific MODEM and then confirm the
latest MODEM Parameter Data running by comparing the confirmed parameter
of specific MODEM.
An SSL server certificate file that is supported in the iPASOLINK is a zip file.
This file must include public key and secret key as follows:
iPASOLINK-serverAAA.zip
|
+---- BBB.crt
+---- BBB.key
NWD-107462-05E Maintenance
Control Items 7-55
Procedure 7-13
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode ON.
5. The source selection window appears. Select the destination storage (Local
PC/USB Memory) from the Import File field and then click File icon button.
Maintenance NWD-107462-05E
7-56 Control Items
6. The file selection window appears. Select the SSL Server Certificate file and
then click Open (or OK) button.
• Local PC
• USB Memory
NWD-107462-05E Maintenance
Control Items 7-57
Maintenance NWD-107462-05E
7-58 Control Items
10. The Information window appears after downloading. Click OK button. The
WebLCT will shut down automatically.
12. After finishing SSL Server Certificate download, click Maintenance button on
the top of the LCT window to exit maintenance mode.
Importance:
1. When executing the Program ROM Switching, set Maintenance Mode to ON
and do not release Maintenance Modes while controlling Switching.
NWD-107462-05E Maintenance
Control Items 7-59
Procedure 7-14
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Select the Program ROM Switching from the Equipment Utility sub menu.
4. The Program ROM Switching window appears. Click the Main Board in the
Item field.
5. The Program ROM Switching (Main Board) box appears. Confirm the
information then click OK button.
Maintenance NWD-107462-05E
7-60 Control Items
7. The Information box appears. Click OK button. The WebLCT window will
shutdown automatically.
9. Select the Equipment Utility (Program ROM Switching) from the LCT
menu.
10. Confirm the Current version of the Main Board in the Program ROM
Switching window.
11. After finishing Program ROM Switching, click Maintenance button on the top
of the LCT window to exit maintenance mode.
Importance:
When executing the Program ROM Switching, set Maintenance Mode to ON and
do not release Maintenance Modes while controlling Switching.
Procedure 7-15
1. Click Maintenance button on the top of the LCT window to turn maintenance
NWD-107462-05E Maintenance
Control Items 7-61
mode on.
3. Select the Program ROM Switching from the Equipment Utility sub menu.
4. The Program ROM Switching window appears. Click the ODU No. in the
Item field.
5. The Program ROM Switching (ODU) box appears. Confirm the information
then click OK button.
Maintenance NWD-107462-05E
7-62 Control Items
8. After restarting, confirm the Current version of ODU in the Program ROM
Switching window.
9. After finishing Program ROM Switching, click Maintenance button on the top
of the LCT window to exit maintenance mode.
Procedure 7-16
2. Select the USB Memory Utility from the Equipment Utility sub menu.
NWD-107462-05E Maintenance
Control Items 7-63
4. After confirming that the necessary data does not exist in USB Memory, click
Format button.
5. After formatting, the USB Memory Utility window appears again. Confirm
that the USB memory was formatted.
Procedure 7-17
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
5. The Shipment box appears. Select the Provisioning Clear from the
Maintenance NWD-107462-05E
7-64 Control Items
8. The Information box appears. Click OK button The WebLCT will shutdown
automatically.
NWD-107462-05E Maintenance
Control Items 7-65
Procedure 7-18
2. Select the Date / Time setting from the Equipment Utility sub menu.
4. The Date / Time Setting box appears. Refer to the table below to assign a
proper value for each parameter accordingly.
Maintenance NWD-107462-05E
7-66 Control Items
7. The Date/Time Setting window appears again. Confirm the modified date and
time of the information displayed.
NWD-107462-05E Maintenance
Control Items 7-67
Reset control available only when Maintenance Mode is On. If Maintenance Mode is
Off, Reset control will return the error response.
• Card Reset
Available to control each option card individually. Main ETH signal will be
downed during the resetting. After Card Reset finished, option card need to be
resetting the configuration information that retains by IDU (MB/CTRL). Card
Reset replies NG response and does not execute if option card was not registered,
not mounted and mounted different place.
Maintenance NWD-107462-05E
7-68 Control Items
Procedure 7-19
2. Expand the H/W / F/W Reset Control from the Maintenance Control sub
menu.
3. Select the H/W Reset Control from the H/W / F/W Reset Control sub
menu.
4. The H/W Reset Control window appears. Click Main Board (L2SW) in the
Item field.
5. The H/W Reset Control box appears. Confirm the information then click OK
button.
NWD-107462-05E Maintenance
Control Items 7-69
9. After finishing Reset Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
Procedure 7-20
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Select the H/W / F/W Reset Control from the Maintenance Control sub
menu.
4. Select the H/W Reset Control from the H/W / F/W Reset Control sub
menu.
5. The H/W Reset Control window appears. Click Option in the Item field.
Maintenance NWD-107462-05E
7-70 Control Items
6. The H/W Reset Control box appears. Confirm the information then click OK
button.
NWD-107462-05E Maintenance
Control Items 7-71
10. After finishing Reset Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
Procedure 7-21
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Expand the H/W / F/W Reset Control from the Maintenance Control sub
menu.
4. Select the F/W Reset Control from the H/W / F/W Reset Control sub menu.
5. The F/W Reset Control window appears. Click Main Board in the Item
field.
Main Board
6. The F/W Reset Control box appears. Confirm the information then click OK
button.
Maintenance NWD-107462-05E
7-72 Control Items
8. The Information box appears. Click OK button. The WebLCT window will
shutdown automatically.
11. After finishing Reset Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
NWD-107462-05E Maintenance
Control Items 7-73
Procedure 7-22
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Select the H/W / F/W Reset Control from the Maintenance Control sub
menu.
4. Select the F/W Reset Control from the H/W / F/W Reset Control sub
menu.
5. The F/W Reset Control window appears. Click specific ODU No. in the Item
field.
ODU (No.1)
6. The F/W Reset Control box appears. Confirm the information then click OK
button.
Maintenance NWD-107462-05E
7-74 Control Items
9. The CPU Reset (ODU) starts automatically. Confirm the current status on the
ODU tab.
10. After finishing Reset Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
The function of each control is as follows (These windows are not available when
MAINT is OFF. Switch to Maintenance mode first is displayed).
If TX Power Control Mode selects ATPC Mode, execute temporally fix control
to transmit POWER. Select the value range described in ( ) of ATPC Range that
located in the Provisioning Menu (MODEM Function setting -> TX Power
Setting) for Transmit POWER. ATPC Manual Control available to select the
either Auto or Manual. If transmit POWER is required to fix control temporarily,
select Manual then select fixed value and it will be fixed until selecting Auto.
NWD-107462-05E Maintenance
Control Items 7-75
z TX Mute Control
Despite the equipment configuration setting, forcing the “TX Mute Control” to
ON, the transmit power of the ODU will stop.
Notes
1. IF Mute Control is set to OFF and due to uncontrollable factors Mute OFF
does not work, Mute status will remain on.
2. In case of 1+1 Hot Standby configuration, the Mute OFF control does not
mute both lines. Moreover, when force Mute is controlled in No.1/No.2,
Maintenance Mode can not set to Off.
3. When TX Mute is controlled by a remote control, it is possible to set the
automatic restoration time. Therefore, TX Mute Release Time is set.
4. TX Mute Release Time is set together with TX Mute Control by the item that
becomes effective only when TX Mute Control is done from a higher-level
device.
z CW Control
The flat rate of the transmission modulation method of the control station in the
AMR mode is temporarily managed.
The modulation method can be set according to the target device regardless of
the AMR Range setting.
Under the 1+0 configuration, each Slot#/Slot# is individually controlled.
This control is done by exchanging request/answer of the control between
local/remote stations as well as LB2.
When the TX Modulation Manual Control setting is returned from Manual to
Auto, the fixed modulation method is returned to QPSK.
Maintenance NWD-107462-05E
7-76 Control Items
Performing this function (Manual Control), the Maintenance Mode becomes On.
However, in case of Auto setting and if Maintenance Mode is set to Off it will cancel
the “auto setting”.
Procedure 7-23
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode ON.
4. The MODEM Maintenance Control window appears. Click Off in the ATPC
Manual Control field.
Click.
5. The MODEM Maintenance Control box appears. Assign a proper value for
each parameter.
NWD-107462-05E Maintenance
Control Items 7-77
Maintenance NWD-107462-05E
7-78 Control Items
10. After finishing Radio Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
Procedure 7-24
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode ON.
Click.
5. The MODEM Maintenance Control box appears. Assign a proper value for
each parameter.
NWD-107462-05E Maintenance
Control Items 7-79
Maintenance NWD-107462-05E
7-80 Control Items
10. After finishing Radio Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
7.2.3.3 CW Control
Procedure 7-25
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode ON.
NWD-107462-05E Maintenance
Control Items 7-81
5. The MODEM Maintenance Control box appears. Assign a proper value for
each parameter.
Maintenance NWD-107462-05E
7-82 Control Items
NWD-107462-05E Maintenance
Control Items 7-83
10. After finishing CW Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
Procedure 7-26
12. Click Maintenance button on the top of the LCT window to turn maintenance
mode ON.
14. Select the MODEM Maintenance Control from the Maintenance Control
sub menu.
15. The MODEM Maintenance Control window appears. Click QPSK in the TX
Modulation Manual Control field.
Maintenance NWD-107462-05E
7-84 Control Items
16. The MODEM Maintenance Control box appears. Assign a proper value for
each parameter.
NWD-107462-05E Maintenance
Control Items 7-85
20. The MODEM Maintenance Control window appears again. Confirm the
parameters displayed.
Maintenance NWD-107462-05E
7-86 Control Items
The following Laser management Items are available to execute from the LCT.
For SDH optical interface, the ALS (Automatic Laser Shutdown) control
performs the resumption of optical power for a definite period of time.
In addition, this function operates under ALS control execution (optical power
shutdown). If ALS is not activated, the control is not carried out.
Procedure 7-27
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Select the Laser Shutdown Control from the Maintenance Control sub
menu.
4. The Laser Shutdown Control window appears. Select Off in the Forced
Laser Shutdown Control field.
NWD-107462-05E Maintenance
Control Items 7-87
Click
5. The Laser Shutdown Control box appears. Select the parameter radio button.
Maintenance NWD-107462-05E
7-88 Control Items
9. The Laser Shutdown Control window appears again. Confirm the parameters
displayed.
10. After finishing Laser Shutdown Control, click Maintenance button on the top
of the LCT window to exit maintenance mode.
Procedure 7-28
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode ON.
3. Select the Laser Shutdown Control from the Maintenance Control sub
menu.
4. The Laser Shutdown Control window appears. Select Control in the ALS
Restart field.
NWD-107462-05E Maintenance
Control Items 7-89
5. The Laser Shutdown Control box appears. Click the parameter radio button.
Maintenance NWD-107462-05E
7-90 Control Items
9. The Laser Shutdown Control window appears again. Confirm the parameters
displayed.
10. After finishing ALS Manual Switch Control, click Maintenance button on the
top of the LCT window to exit maintenance mode.
NWD-107462-05E Maintenance
Control Items 7-91
In case of detect House Keeping input at own station, Cluster Alarm will transmit to
the opposite station by set up the bit of Cluster ALM input (output toward to
wireless)
In case of detect any changes for Cluster ALM output (input toward to wireless) after
Cluster Alarm signal was received by equipment in the opposite station. The
equipment in the opposite station will be set-up bit for House Keeping output control
then Relay output (RL) will be executing.
After receiving a Cluster Alarm signal from the opposite station and another Cluster
ALM is input (output to the direction of the radio) a setup is performed, Cluster
Alarm signal is sent out to an opposite office. It is possible to transmit the Cluster
Alarm signal.
House Keeping external input port owns six port, four of six ports are used
by both Cluster Alarm and House Keeping and each port is required to select
Alarm function.
In case of 1 to 4 external input ports are selected to Cluster Alarm input, F/W
execute to change the signal of HKIN1-4 into Cluster Alarm signal in
wireless frame then output the signal toward to opposite side of wireless. In
addition, any Modems are available to output the Cluster Alarm input signal.
House Keeping output port owns 6 port, 4 of 6 port are using by both Cluster
Alarm and House Keeping and each port (HK1-4) require to set up
Maintenance NWD-107462-05E
7-92 Control Items
Set up to OK or not OK for each item (parallel alarm require to set up for
each alarm items), execute port output if detect over one alarm at specific
item.
H/W control output port for other 2 port. (RL1, RL2 port will be fixed for
parallel alarm out put by H/W.)
Cluster Alarm output 1 to 4 signals are selected after the incoming signals of
a MODEM under redundant system, and the arbitrary Cluster Alarm is
output to the radio port of CH unit.
Cluster alarm input and output and a through function are separately
controllable between different ports.
NWD-107462-05E Maintenance
Control Items 7-93
Table 7-19
No. Item Detection Conditions House Keeping
- - OUT4 OUT3 OUT2 OUT1
RL 1 RL 2 RL 3 RL 4 RL 5 RL 6
Alarm (Parallel)
1 MAINT MAINTENANCE • - Mask Mask Mask Mask
2 IDU ALM IDU Total Alarm - - O O • O
3 IDU CPU ALM ODU CPU Alarm - • - - - -
4 PS ALM Power supply failure - • - - - -
5 ODU LAM IDU Alarm - - • O O O
6 ODU CPU ALM IDU CPU Alarm - - O • O O
7 HIGH BER ALM High BER Error - - O O O •
8 Other - - O O O O
House Keeping Alarm
1 OUT 1 House Keeping Out 1 - - - - - O
2 OUT 2 House Keeping Out 2 - - - - O -
3 OUT 3 House Keeping Out 3 - - - O - -
4 OUT 4 House Keeping Out 4 - - O - - -
Cluster Alarm
1 OUT 1 Cluster Alarm Out 1 - - - - - O
2 OUT 2 Cluster Alarm Out 2 - - - - O -
3 OUT 3 Cluster Alarm Out 3 - - - O - -
4 OUT 4 Cluster Alarm Out 4 - - O - - -
•: Initial setting
O: Changeable
Procedure 7-29
3. Select Cluster Alarm Setting from the Relay-Alarm Mapping Setting sub
menu.
Maintenance NWD-107462-05E
7-94 Control Items
Modify
NWD-107462-05E Maintenance
Control Items 7-95
8. The Cluster Alarm Setting window appears again. Confirm the parameters
displayed.
7.2.6 Inventory
Inventory will display the iPASOLINK, information of H/W, FW in mounted
MODEM, Network information and Software License Key information.
Procedure 7-30
10. Select the Equipment Inventory Information from the Inventory sub
menu.
11. The Equipment Inventory Information window appears. Select the IDU tab.
Maintenance NWD-107462-05E
7-96 Control Items
NWD-107462-05E Maintenance
Control Items 7-97
13. It is available to save the Inventory Information if you click the Export IDU
Inventory Information button.
15. The Save As window appears. Select the proper folder of local PC and then
click Save button.
Maintenance NWD-107462-05E
7-98 Control Items
16. After finishing the export of inventory file, the Download Complete window
appears. Click Close button.
17. Confirm that the Inventory Information File was saved in the selected folder.
Procedure 7-31
NWD-107462-05E Maintenance
Control Items 7-99
Maintenance NWD-107462-05E
7-100 Control Items
5. It is available to save the Inventory Information if you click the Export ODU
Inventory Information button.
NWD-107462-05E Maintenance
Control Items 7-101
7. The Save As window appears. Select the proper folder of local PC and then
click Save button.
8. After finishing the export of inventory file, the Download Complete window
appears. Click Close button.
Maintenance NWD-107462-05E
7-102 Control Items
9. Confirm that the Inventory Information File was saved in the selected folder.
Procedure 7-32
2. Select the S/W License Information from the Inventory sub menu.
NWD-107462-05E Maintenance
Control Items 7-103
Maintenance NWD-107462-05E
7-104 Control Items
6. The Save As window appears. Select the proper folder of local PC and then
click Save button.
7. After finishing the export of license information file, the Download Complete
window appears. Click Close button.
NWD-107462-05E Maintenance
Control Items 7-105
8. Confirm that the License Information file is saved in the selected folder.
Maintenance NWD-107462-05E
7-106 Control Items
The PM Register retains all monitoring data of 7-days and current monitoring data
will be transferred to the PM Register according to the timing of 0:00 minute
- E1 PMON Report
- PMON/RMON/FDB Clear
Procedure 7-33
2. Select the MODEM PMON Report from the PMON / RMON Report sub
menu.
NWD-107462-05E Maintenance
Control Items 7-107
Click.
5. The MODEM PMON Report (1-day) window appears. Confirm the detail of
MODEM PMON Report.
7. The MODEM PMON Report (15-min) window appears. Confirm the 15-min
Data (all data of 7 days) that saved in NE.
Maintenance NWD-107462-05E
7-108 Control Items
NWD-107462-05E Maintenance
Control Items 7-109
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
11. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
12. Confirm that the MODEM PMON Report File was saved in the selected folder.
Maintenance NWD-107462-05E
7-110 Control Items
Procedure 7-34
2. Select the E1 PMON Report from the PMON / RMON Report sub menu.
Click
NWD-107462-05E Maintenance
Control Items 7-111
Maintenance NWD-107462-05E
7-112 Control Items
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
E1 1-day: 1day-E1-s1p1-YYYYMMDD.pmon
E1 15-min: 15min-E1-s1p1-YYYYMMDD.pmon
11. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
NWD-107462-05E Maintenance
Control Items 7-113
12. Confirm that the E1 PMON Report File was saved in the selected folder.
(1) RS Tab
Procedure 7-35
2. Select the STM-1 PMON Report from the PMON / RMON Report sub menu.
3. The STM-1 PMON Report window appears. Click RS tab and confirm the
Performance Monitor value that monitored for 15-minute and 1-day will be
displayed.
Maintenance NWD-107462-05E
7-114 Control Items
Click
5. The STM-1 PMON Report (1-day) window appears. Confirm the detail of
STM-1 PMON Report.
NWD-107462-05E Maintenance
Control Items 7-115
Maintenance NWD-107462-05E
7-116 Control Items
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
11. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
NWD-107462-05E Maintenance
Control Items 7-117
12. Confirm that the STM-1 PMON Report File was saved in the selected folder.
(2) MS Tab
Procedure 7-36
2. Select the STM-1 PMON Report from the PMON / RMON Report sub menu.
3. The STM-1 PMON Report window appears. Click MS tab and confirm the
Performance Monitor value that monitored for 15-minute and 1-day will be
displayed.
Click
4. Click STM-1.
5. The STM-1 PMON Report (1-day) window appears. Confirm the detail of
STM-1 PMON Report.
Maintenance NWD-107462-05E
7-118 Control Items
NWD-107462-05E Maintenance
Control Items 7-119
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
Maintenance NWD-107462-05E
7-120 Control Items
11. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
12. Confirm that the STM-1 PMON Report File was saved in the selected folder.
Procedure 7-37
2. Select the ETH RMON Report from the PMON / RMON Report sub menu.
3. The ETH RMON Report window appears. Confirm the Remote Network
Monitoring value that monitored for 15-minute and 1-day will be displayed.
NWD-107462-05E Maintenance
Control Items 7-121
Click
5. The ETH RMON Report (1-day) window appears. Confirm the detail of
RMON Report.
Click
Maintenance NWD-107462-05E
7-122 Control Items
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
NWD-107462-05E Maintenance
Control Items 7-123
11. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
12. Confirm that the ETH RMON Report File was saved in the selected folder.
Procedure 7-38
2. Select the VLAN Counter Report from the PMON / RMON Report sub
menu.
Maintenance NWD-107462-05E
7-124 Control Items
3. The VLAN Counter Report window appears. Confirm the VLAN Counter
Report value that monitored for 15-minute and 1-day will be displayed.
Procedure 7-39
2. Select the PMON / RMON / FDB Clear from the Maintenance Control sub
menu.
3. The PMON / RMON / FDB Clear window appears. Select the PMON /
RMON Clear radio button and then click Execute button.
NWD-107462-05E Maintenance
Control Items 7-125
7. Select the each PMON or ETH RMON Report sub menu from the PMON /
RMON Report of the LCT menu.
Maintenance NWD-107462-05E
7-126 Control Items
Procedure 7-40
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Select the PMON / RMON / FDB Clear from the Maintenance Control sub
menu.
4. The PMON / RMON / FDB Clear window appears. Select the FDB Table
Clear radio button and then click Execute button.
5. The FDB Table Clear box appears. Select the All radio button and then click
OK button.
NWD-107462-05E Maintenance
Control Items 7-127
Procedure 7-41
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Select the PMON / RMON / FDB Clear from the Maintenance Control sub
menu.
4. The PMON / RMON / FDB Clear window appears. Select the FDB Table
Clear radio button and then click Execute button.
Maintenance NWD-107462-05E
7-128 Control Items
5. The FDB Table Clear box appears. Select the VLAN ID radio button and input
the VLAN ID No., and then click OK button.
NWD-107462-05E Maintenance
Control Items 7-129
Procedure 7-42
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
3. Select the PMON / RMON / FDB Clear from the Maintenance Control sub
menu.
4. The PMON / RMON / FDB Clear window appears. Select the FDB Table
Clear radio button and then click Execute button.
5. The FDB Table Clear box appears. Select the Port radio button and select card
name and Port No. from each drop-down list, and then click OK button.
Maintenance NWD-107462-05E
7-130 Control Items
NWD-107462-05E Maintenance
Control Items 7-131
Procedure 7-43
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode ON.
5. The Offline Maintenance Control box appears. Select specific status from
the DADE Adjust drop-down list, click OK button.
Maintenance NWD-107462-05E
7-132 Control Items
NWD-107462-05E Maintenance
Control Items 7-133
10. After finishing DADE adjustment, click Maintenance button on the top of the
LCT window to exit maintenance mode.
It can set up individually each ODU, the Sub Band which can be set up is according
to the alphabet "A-H, J-N, P and R, X".
Notes
1. Before changing the Sub Band setting, it is required to set TX Mute to ON,
and also prevent any rewriting data in the ODU Flash ROM.
2. In case of ODU which does not support a Sub Band change and from a
higher order Sub Band. If a change setup is carried out, an ODU
classification is judged and a Sub Band change setup is not performed.
Procedure 7-44
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
Maintenance NWD-107462-05E
7-134 Control Items
5. The Offline Maintenance Control box appears. Select the RF Sub Band
Select drop-down list and click the OK button.
NWD-107462-05E Maintenance
Control Items 7-135
8. The Offline Maintenance Control window appears again. Confirm that the
Status was modified as same as the selection in the DADE Adjust field.
9. After finishing RF Sub Band Select, click Maintenance button on the top of the
LCT window to exit maintenance mode.
Maintenance NWD-107462-05E
7-136 Control Items
Procedure 7-45
1. Click Maintenance button on the top of the LCT window to turn maintenance
mode on.
NWD-107462-05E Maintenance
Control Items 7-137
8. After finishing Maintenance Test, the LB (LT, DM, or LM) Result window
appears. Confirm the parameters displayed.
Maintenance NWD-107462-05E
7-138 Control Items
Click Export CSV File button on the top of the ETH OAM LB / LT / DM
/ LM Control window.
NWD-107462-05E Maintenance
Control Items 7-139
Click Export CSV File button in the LB (LT, DM, or LM) Result
window.
11. The Save As window appears. Select the proper folder of local PC and then
click Save button.
History Information:
HistoryInfoExport-YYYYMMDDhhmmss.csv
Test Result:
TestResultInfoExport-LB(LT, DM, or LM)-YYYYMMDDhhmmss.csv
Maintenance NWD-107462-05E
7-140 Control Items
12. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
13. Confirm that the CSV File was saved in the selected folder.
NWD-107462-05E Maintenance
Control Items 7-141
Procedure 7-46
2. Select the Import License key from the S/W License Setup sub menu.
3. The Import License key window appears. Click the Setup button.
Maintenance NWD-107462-05E
7-142 Control Items
NWD-107462-05E Maintenance
Control Items 7-143
4. The Import License Key window appears then click File icon button.
5. Select the license key(s) to be applied in the Dialog box for file selection where
license key is located.
Procedure 7-47
Maintenance NWD-107462-05E
7-144 Control Items
2. Select the Radio Capacity Setting from the S/W License Setup sub menu.
3. The Radio Capacity Setting window appears. Click the Setup button.
4. The Radio Capacity Setting box appears. Specify the Radio Capacity License
and then selected the desired MODEM (Slot**) from the New State drop-down
list.
5. Click OK button.
7. The Radio Capacity Setting window appears again. Confirm the parameters
NWD-107462-05E Maintenance
Control Items 7-145
displayed.
Maintenance NWD-107462-05E
7-146/END Control Items
NWD-107462-05E Maintenance
Trouble Shooting 8-1
8. TROUBLE SHOOTING
Maintenance NWD-107462-05E
8-2 Trouble Shooting
START
YES
Connect the LCT to the IDU and
Is ALM NO
check ALARM/STATUS menu.
indicator on the IDU
Check every items whether
solid red ?
indicated status is alarm or normal.
YES
Is ALM NO
indicator
The IF cable
on the MODEM Card Is TX Input NO
type, Cable length and
blinking red? indicated normal? cable loss are used
standard NO
YES YES
Check the IF cable YES
connection and connectors Replace the Change the
whether the cable is open or ODU with IF cable to
short circuit. Is TX power of NO
a spare. standard.
the ODU indicated
normal?
YES
Is ODU
NO CPU/Cable Open ALM
indicated
normal?
YES
Reset CPU of the ODU.
YES YES
Is TX power NO
Is ODU
vary with ATPC manual
ALM indicated
control?
normal?
YES
YES
Replace the ODU END Check the RX Replace the ODU with Replace
with a spare. section of the ODU. a spare, if TX power alarm the ODU
continues when temperature with a spare.
is improved.
NWD-107462-05E Maintenance
Trouble Shooting 8-3
START
YES
Connect the LCT to the IDU and
Is ALM NO check Current Status menu.
indicator on the IDU Check every items whether
solid red ? indicated status is Alarm or Normal.
YES
NO
Is ALM
indicator
on the MODEM Card
blinking red ? NO
Is RX Level
indicated Normal?
YES
YES
Check the IF cable connection
and connectors whether the Is RX LEVEL by
cable is open or short circuit. RSL monitor vary ath random
NO interval?
YES
NO Check fading or
Is ODUCPU
/Cable Open ALM indicated interference.
Reset CPU of the ODU.
Normal?
YES
YES NO YES
Replace the END Check the TX Replace the Check Antenna system
Set proper
ODU section of the ODU or Replace the ODU
frequency.
with a spare. ODU. with a spare. with a spare.
Maintenance NWD-107462-05E
8-4 Trouble Shooting
START
NO Is PWR LED on
the IDU solid green?
YES
Replace Fuse
in the IDU Connect the LCT to the IDU
Is ALM and check Current Status
NO NO
indicator on the IDU menu. Check every items
solid red ? whether indicated status is
Alarm or Normal
YES
NO
Is ALM indicator
blinking red ?
YES
NO
Is AIS Generated
indicated Normal?
Check associated
YES
DTE.
Check associated
DTE at local site. YES
NO Is CH Usage
indicated Normal ?
NWD-107462-05E Maintenance
Trouble Shooting 8-5
Is ODU indicated NO
Normal?
YES
Check the section
of the ODU.
NO Is Module ALM NO
Is IDU indicated
Normal? of Main Board Indicated
Normal?
YES YES
Replace the IDU
with a spare.
NO
Is Module ALM
of Option Card Indicated
Normal?
YES
Replace the Option Card
with a spare.
NO
Is RDI indicated
Normal?
YES
Check the opposite
Equipment.
Select IF Loopback from
MODEM Loopback Control menu in the
Maintenance Control menu on the LCT.
NO
Check the section
of the ODU.
Is Input LOS NO
indicated Normal?
YES
Check associated DTE
and cable connection.
Check associated DTE and cable
connection at opposite site.
Maintenance NWD-107462-05E
8-6 Trouble Shooting
Check the name plate of the spare ODU. When the indicated items are coincided, the
ODU can be replaced.
Caution:
1. Do not remove/connect the IF cable with the IDU power ON. Turn the IDU
power OFF before connecting/disconnecting the IF cable, or equipment
may be damaged.
2. To avoid microfonic properties, occurrence of bit errors, when installing
the ODU on the HYB or OMT, protect the ODU from mechanical knocks
which is not replaced.
6 to 11 GHz 13 to 42 GHz
Caution: Be careful that the surface of the ODU is hot during operation.
The mounting and demounting the ODU from/to antenna, refer to Installation in
Section II.
NWD-107462-05E Maintenance
Trouble Shooting 8-7
Procedure 8-1
(1) Removing
2. Turn off the power switch on the MODEM which is connected to the ODU is to
be replaced.
6. Loosen the four bolts fixing the ODU with a T type hexagonal driver.
(2) Mounting
1. When the ODU is used for vertical polarization, rotate the ODU so that the plate
marked V is on the top.
Maintenance NWD-107462-05E
8-8 Trouble Shooting
2. When the ODU is used for horizontal polarization, remove the guide pin fixed on
the plate marked V.
3. Insert the guide pin removed in step 2 behind of the plate marked H.
NWD-107462-05E Maintenance
Trouble Shooting 8-9
Note:
1. Be careful not to damage the flange and O-ring.
2. Be careful to tighten the four screws alternately and gradually.
6. Mount the spare ODU onto the bracket and tighten the four screws on the ODU.
8. Wrap twice the IF IN/OUT connector with self-bonding tape for waterproofing.
Maintenance NWD-107462-05E
8-10 Trouble Shooting
NWD-107462-05E Maintenance
Trouble Shooting 8-11
Maintenance NWD-107462-05E
8-12 Trouble Shooting
Caution:
1. Persons performing maintenance must take necessary steps to avoid
electro-static discharge which may damage the cards or cause error. Wear
a conductive wrist strap connected to the grounded (G) jack on the front of
the equipment shelf. This will minimize static build-up during maintenance
(see Figure 2-1 in Chapter 2).
2. Do not remove/connect the IF cable with the IDU power ON. Turn the IDU
power OFF before connecting/disconnecting the IF cable, or equipment
may be damaged.
(a) Removing
Procedure 8-2
1. Disconnect power supply cable from power supply connector. Disconnect the IF
cable, signal cables and the power cable, etc. in the following order.
1-1. Disconnect E1, STM-1, LAN, AUX. signal cables from connector.
1-2. Disconnect IF cable from IF IN/OUT connector.
1-3. Disconnect ground cable from the ground terminal.
(b) Mounting
Procedure 8-3
NWD-107462-05E Maintenance
Trouble Shooting 8-13
2. Mount the IDU into the original position of the mounting rack and tighten
screws.
3. Reconnect the IF cables, signal cables and the power cable to the original
position in the following order.
4. Form the wiring, and fix the cables using cable binder to the mounting rack.
Notes:
1. Do not cross the cables on front of indicators and power switch used for
maintenance.
Maintenance NWD-107462-05E
8-14 Trouble Shooting
NWD-107462-05E Maintenance
Trouble Shooting 8-15
Procedure 8-4
Maintenance NWD-107462-05E
8-16 Trouble Shooting
Procedure 8-5
2. Retrieve the current alarms and check if the ODU alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
8.3.4.2 TX Power
This message indicates that TX power level of the ODU is lower than 3 dB.
Procedure 8-6
NWD-107462-05E Maintenance
Trouble Shooting 8-17
8.3.4.3 TX Input
This message indicates that TX IF signal level is out of range from -29 dBm ± 5 dB.
Procedure 8-7
8.3.4.4 RX Level
This message indicates that RX level is lower than -72dBm ~ -94dBm level (Alarm
detection level depends on modulation schemes and bit rates).
Procedure 8-8
Procedure 8-9
8.3.4.6 LO REF
This message indicates that Loss of Ref LO signal of ODU is detected.
Procedure 8-10
2. If the LO REF ALM is detected yet, replace the ODU with a spare.
This step is the end of the procedure.
Maintenance NWD-107462-05E
8-18 Trouble Shooting
Procedure 8-11
1. Exchange the ODU with correct type or set correct modulation setting.
This step is the end of the procedure.
Procedure 8-12
Procedure 8-13
3. If the Power Supply alarm is detected yet, remove the connector and the
FUSE, check the FUSE and replace it if broken.
4. Reinsert the FUSE and the connector. Retrieve the current alarms, and check if
the alarm is cleared. If the alarm is not cleared, contact NEC for the appropriate
maintenance support.
NWD-107462-05E Maintenance
Trouble Shooting 8-19
Procedure 8-14
2. Retrieve the current alarms, and check if the FAN Fail alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 8-15
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 8-16
1. Check if there is any alarm in the indicated facility port/line or in the equipment
at another side.
3. Retrieve the current alarms, and check if the CLK FAIL alarm is cleared.
4. If the CLK FAIL alarm is detected yet, check whether any alarm of the indicated
port/line is cleared.
5. If the any alarm is reported on the indicated port/line, clear it by other procedures
according to the trouble shooting.
6. Retrieve the current alarms, and check if the CLK FAIL alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-107462-05E
8-20 Trouble Shooting
Procedure 8-17
3. Retrieve the current alarms, and check if the CLK Drift alarm is cleared.
4. If the CLK Drift alarm is detected yet, check whether any alarm of the indicated
port/line is cleared.
5. If the any alarm is reported on the indicated port/line, clear it by other procedures
according to the trouble shooting.
6. Retrieve the current alarms, and check if the CLK Drift alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.5.6 LTI
This message indicates that the IDU does not synchronize with any reference clock
source. If this condition occurs, the problem is on the optical fiber/electrical cable or on
the far-end NE.
Procedure 8-18
3. Retrieve the current alarms, and check if the LTI alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
NWD-107462-05E Maintenance
Trouble Shooting 8-21
Procedure 8-19
3. Retrieve the current alarms, and check if the EXT CLK LOS alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 8-20
1. Check if an alarm occurs in the equipment at another side, and clear it to normal
state.
2. Retrieve the current alarms, and check if the EXT CLK AIS alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 8-21
3. Retrieve the current alarms, and check if the EXT CLK LOF alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-107462-05E
8-22 Trouble Shooting
Procedure 8-22
1. If the EXT CLK Out signal and the EXT CLK In signal are completely separated
as frequency at the equipment connected the EXT CLK In/Out, ignore this alarm.
2. Change the reference clock source from EXT CLK In to other reference clock
source by the maintenance command.
3. Retrieve the current alarms, and check if the EXT CLK Loop alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
4. If not use the EXT CLK In as system clock, delete it from the reference clock
source and clear the maintenance command.
8.3.5.11 E1 LOS
This message indicates that a failure of the E1 LOS (Loss Of Signal) is detected from
the incoming signal on the indicated facility. If this condition occurs, the problem is
on the cable connection or on the far-end NE.
Procedure 8-23
3. Retrieve the current alarms, and check if the LOS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
8.3.5.12 E1 AIS
This message indicates that a failure of the AIS (Alarm Indication Signal) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the indicated line in the far-end NE.
NWD-107462-05E Maintenance
Trouble Shooting 8-23
Procedure 8-24
2. Retrieve the current alarms, and check if the AIS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
This step is the end of the procedure.
This message indicates that the E1 port, which is not enabled, received signal.
Procedure 8-25
3. Retrieve the current alarms, and check if the Usage Error alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of the SNCP PPS-FAIL (Path Protection Switch
failed) is detected from the incoming signal on the indicated facility. If this condition
occurs, the problem is on both receiving signals.
Procedure 8-26
1. Check if the secondary path is available and the cross connect configuration is
valid.
3. Retrieve the current alarms, and check if the PPS-FAIL alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-107462-05E
8-24 Trouble Shooting
Procedure 8-27
3. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of the ETH LOS (Loss Of Signal) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the optical fiber or on the far-end NE.
Procedure 8-28
3. Retrieve the current alarms, and check if the LOS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
8.3.5.17 ETH TF
This message indicates that a failure has been detected in the installed SFP modules.
The possible cause is SFP module failure.
Procedure 8-29
2. Retrieve the current alarms, and check if the TF alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
NWD-107462-05E Maintenance
Trouble Shooting 8-25
This message indicates that a failure has been detected in the port. The possible cause
is SFP type error or the port configuration error in the LCT.
Procedure 8-30
1. For the Ethernet port and STM-1 port, confirm their port configurations in the
LCT.
3. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared.
4. If the SFP Type Mismatch alarm is detected yet, check whether the SFP type of
these ports is correct.
6. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
7. For other ports, check whether the SFP type of these ports is correct first.
8. If not, remove the SFP module, and insert the correct SFP module to specified
port.
9. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
This message indicates that a failure has been detected in the registered port. The
possible cause is removed of the SFP module.
Procedure 8-31
1. Pull out the SFP module, and reinsert it into the port.
2. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared.
3. If the SFP Unequipped alarm is detected yet, confirm that the SFP module is
located in the specified port, if not, move it to the right port.
Maintenance NWD-107462-05E
8-26 Trouble Shooting
4. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of Ethernet Link down is detected on the
indicated port. If this condition occurs, the problem is on the optical fiber or on the
far-end NE.
Procedure 8-32
3. Retrieve the current alarms, and check if the LAN LINK alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 8-33
1. Check if an alarm occurs in the far-end NE that is associated with the indicated
MEP, and clear it to normal state.
2. Retrieve the current alarms, and check if the ETH-OAM LOC alarm is cleared.
3. If the alarm is not cleared, confirm their MEG/MEP configurations in the LCT.
5. Retrieve the current alarms, and check if the ETH-OAM LOC alarm is cleared.
NWD-107462-05E Maintenance
Trouble Shooting 8-27
6. If the ETH-OAM LOC alarm is detected yet, check whether the MEG/MEP
configuration on the far-end NE is correct.
8. Retrieve the current alarms, and check if the ETH-OAM LOC alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of Mismerge is detected on the indicated MEP.
The possible cause is the unexpected ETH-CC frames received from far-end NE or
the MEG/MEP configuration error in the LCT.
Procedure 8-34
3. Retrieve the current alarms, and check if the ETH-OAM Mismerge alarm is
cleared.
4. If the ETH-OAM Mismerge alarm is detected yet, check whether the MEG/MEP
configuration on the far-end NE is correct.
6. Retrieve the current alarms, and check if the ETH-OAM Mismerge alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
This message indicates that a mismatch of the ETH-CC transmit period is detected
on the indicated MEG. The possible cause is the mismatch of the MEG configuration
between the far-end NE and local NE in the LCT.
Procedure 8-35
Maintenance NWD-107462-05E
8-28 Trouble Shooting
3. Retrieve the current alarms, and check if the ETH-OAM Unexpected Period
alarm is cleared.
4. If the ETH-OAM Unexpected Period alarm is detected yet, check whether the
MEG/MEP configuration on the far-end NE is correct.
6. Retrieve the current alarms, and check if the ETH-OAM Unexpected Period
alarm is cleared. If the alarm is not cleared, contact NEC for the appropriate
maintenance support.
This message indicates that a failure of the ETH-OAM RDI (Remote Defect
Indicate) is detected from the incoming ETH-CC frame on the indicated MEP. If this
condition occurs, the problem is an alarm detected at the peer MEP.
Procedure 8-36
2. Clear conditions that cause the alarm in the MEG that belongs to a peer MEP.
3. Retrieve the current alarms, and check if the ETH-OAM RDI alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.5.25 Temperature
This message indicates that the temperature in the IDU is over the workable temperature.
This possible cause is that the room temperature is uncontrolled.
Procedure 8-37
1. Check if there is any problem in the air conditioner on the IDU room.
3. Retrieve the current alarms, and check if the Temperature alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
4. (Wait 1 hour at least after the room temperature is fallen down under the
workable temperature.)
NWD-107462-05E Maintenance
Trouble Shooting 8-29
8.3.6.1 LOF
Procedure 8-38
2. If the RX LEV metering value is NOT correct, clear it according to "RX LEV
ALM" of the troubleshooting.
4. If the RX LEV metering value and MODEM configuration are correct, replace
the IDU with a spare.
8.3.6.2 Frame ID
Procedure 8-39
This message indicates “Radio signal degradation (High BER threshold detection)”.
Procedure 8-40
2. If the RX LEV metering value is NOT correct, clear it according to "RX LEV
ALM" of the troubleshooting.
Maintenance NWD-107462-05E
8-30 Trouble Shooting
3. If the RX LEV metering value is correct, replace the IDU with a spare.
This message indicates “Radio signal degradation (Low BER threshold detection)”.
Procedure 8-41
2. If the RX LEV metering value is correct, replace the IDU with a spare.
3. If the RX LEV metering value is NOT correct, clear it according to "RX LEV
ALM" of the troubleshooting.
Procedure 8-42
2. If the RX LEV metering value is correct, replace the IDU with a spare.
3. If the RX LEV metering value is NOT correct, clear it according to "RX LEV
ALM" of the troubleshooting.
This message indicates “IF cable between IDU - ODU is in short condition”.
Procedure 8-43
2. If IF CABLE SHORT alarm is cleared, a failure may occur on the IF cable side.
Confirm the IF cable.
NWD-107462-05E Maintenance
Trouble Shooting 8-31
3. If IF CABLE SHORT alarm is not cleared, replace the IDU with a spare.
MODEM port”.
Procedure 8-44
2. If the RX LEV metering value is correct, replace the IDU with a spare.
3. If the RX LEV metering value is NOT correct, clear it according to "RX LEV
ALM" of the troubleshooting.
8.3.6.8 RDI
Procedure 8-45
3. Retrieve the current alarms, and check if the RDI alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
8.3.6.9 UAE
Procedure 8-46
1. Check the current alarms, and if there are any other alarms, clear these alarms at
first according to the troubleshooting.
2. After clearing every alarm, retrieve the current alarm, and check if the UAE is
Maintenance NWD-107462-05E
8-32 Trouble Shooting
not cleared with any alarms, contact NEC for the appropriate maintenance
support.
Procedure 8-47
Procedure 8-48
8.3.6.12 Unlocked
Procedure 8-49
1. Check the equipment clock setting. Refer to operation manual for detail.
NWD-107462-05E Maintenance
Trouble Shooting 8-33
8.3.7.1 Unequipped
This message indicates that the configured card is not detected in the IDU. The possible
cause is equipment configuration file mismatch, generated in the different equipment that
includes the option card is downloaded.
Procedure 8-50
1. Execute “shipment” procedure with the LCT. The IDU will be rebooted.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates there are some errors in card control bus.
Procedure 8-51
This message indicates that a failure has been detected in the port. The possible cause
is SFP type error or the port configuration error in the LCT.
Procedure 8-52
1. For the Ethernet port and STM-1 port, confirm their port configurations in the
LCT.
3. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared.
4. If the SFP Type Mismatch alarm is detected yet, check whether the SFP type of
these ports is correct.
Maintenance NWD-107462-05E
8-34 Trouble Shooting
6. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
7. For other ports, check whether the SFP type of these ports is correct first.
8. If not, replace the SFP module, and insert the correct SFP to specified port.
9. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
This message indicates that a failure has been detected in the registered port. The
possible cause is removed of the SFP module.
Procedure 8-53
1. Pull out the SFP module, and reinsert it into the port.
2. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared.
3. If the SFP Unequipped alarm is detected yet, confirm that the SFP module is
located in the specified port, if not, move it to the right port.
4. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.5 STM-1LOS
This message indicates that a failure of the LOS (Loss Of Signal) is detected from
the incoming signal on the indicated facility. If this condition occurs, the problem is
on the optical fiber or on the far-end NE.
NWD-107462-05E Maintenance
Trouble Shooting 8-35
Procedure 8-54
3. Retrieve the current alarms, and check if the LOS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
8.3.7.6 TF
This message indicates that a failure has been detected in the installed SFP modules.
The possible cause is SFP module failure.
Procedure 8-55
2. Retrieve the current alarms, and check if the TF alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
8.3.7.7 RS LOF
This message indicates that a failure of the LOF (Loss Of Frame) is detected from
the incoming signal on the indicated facility. If this condition occurs, the problem is
on the cable or on the far-end NE.
Procedure 8-56
3. Retrieve the current alarms, and check if the LOF alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
8.3.7.8 RS TIM
This message indicates that a failure of the RS TIM (Trace Identifier Mismatch) is
Maintenance NWD-107462-05E
8-36 Trouble Shooting
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is on the J0 setting or at the far-end NE setting.
Procedure 8-57
2. Clear the condition if the receive byte is not same as expected value.
3. Retrieve the current alarms, and check if the RS TIM alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.9 MS AIS
This message indicates that a failure of the MS AIS (Alarm Indication Signal) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is at the far-end NE.
Procedure 8-58
3. Retrieve the current alarms, and check if the MS AIS alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.10 MS RDI
This message indicates that a failure of the MS RDI (Remote Defect Indicate) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is an alarm detected at the far-end NE.
Procedure 8-59
3. Retrieve the current alarms, and check if the MS RDI alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
NWD-107462-05E Maintenance
Trouble Shooting 8-37
8.3.7.11 AU AIS
This message indicates that a failure of the AU AIS (Alarm Indication Signal) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is on the MSA function in the far-end NE.
Procedure 8-60
2. Clear conditions that cause the alarm for the far-end NE.
3. Retrieve the current alarms, and check if the AU AIS alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.12 AU LOP
This message indicates that a failure of the AU LOP (Loss Of Pointer) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the MSA function in the far-end NE.
Procedure 8-61
2. Clear conditions that cause the alarm for the far-end NE.
3. Retrieve the current alarms, and check if the AU LOP alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.13 HP UNEQ
Maintenance NWD-107462-05E
8-38 Trouble Shooting
Procedure 8-62
3. Retrieve the current alarms, and check if the HP UNEQ alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.14 HP TIM
This message indicates that a failure of the HP TIM (Trace Identifier mismatch) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is on the J1 setting or on the far-end NE setting.
Procedure 8-63
2. Clear the condition if the receive byte is not same as expected value.
3. Retrieve the current alarms, and check if the HP TIM alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.15 HP PLM
This message indicates that a failure of the HP PLM (Payload Mismatch) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the configuration in the far-end NE.
Procedure 8-64
3. Retrieve the current alarms, and check if the HP PLM alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
NWD-107462-05E Maintenance
Trouble Shooting 8-39
8.3.7.16 HP RDI
This message indicates that a failure of the HP RDI (Remote Defect Indicate) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is an HP alarm detected in the far-end NE.
Procedure 8-65
3. Retrieve the current alarms, and check if the HP RDI alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.17 LOM
This message indicates that a failure of the LOM (Loss Of Multi frame) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the HPA function at the far-end NE.
Procedure 8-66
3. Retrieve the current alarms, and check if the LOM alarm is cleared. If the alarm
is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.18 TU AIS
This message indicates that a failure of TU AIS (Alarm Indication Signal) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the LPA function in the far-end NE.
Procedure 8-67
Maintenance NWD-107462-05E
8-40 Trouble Shooting
3. Retrieve the current alarms, and check if the TU AIS alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.19 TU LOP
This message indicates that a failure of the TU LOP (Loss Of Pointer) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the HPA function at the far-end NE.
Procedure 8-68
3. Retrieve the current alarms, and check if the TU LOP alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.20 LP UNEQ
Procedure 8-69
3. Retrieve the current alarms, and check if the LP UNEQ alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
NWD-107462-05E Maintenance
Trouble Shooting 8-41
8.3.7.21 LP-RDI
This message indicates that a failure of the LP RDI (Remote Defect Indicate) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is an LP alarm detected at the far-end NE.
Procedure 8-70
3. Retrieve the current alarms, and check if the LP RDI alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.7.22 LP-PLM
This message indicates that a failure of the LP PLM (Payload Mismatch) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the configuration at the far-end NE.
Procedure 8-71
3. Retrieve the current alarms, and check if the LP PLM alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
8.3.8.1 Unequipped
This message indicates that the configured card is not detected in the IDU. The possible
cause is equipment configuration file mismatch, generated in the different equipment that
includes the option card is downloaded.
Maintenance NWD-107462-05E
8-42 Trouble Shooting
Procedure 8-72
1. Execute “shipment” procedure with the LCT. The IDU will be rebooted.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates there are some errors in card control bus.
Procedure 8-73
8.3.8.3 E1 LOS
This message indicates that a failure of the E1 LOS (Loss Of Signal) is detected from
the incoming signal on the indicated facility. If this condition occurs, the problem is
on the cable connection or on the far-end NE.
Procedure 8-74
3. Retrieve the current alarms, and check if the LOS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
8.3.8.4 E1 AIS
This message indicates that a failure of the AIS (Alarm Indication Signal) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the indicated line in the far-end NE.
NWD-107462-05E Maintenance
Trouble Shooting 8-43
Procedure 8-75
2. Retrieve the current alarms, and check if the AIS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
This step is the end of the procedure.
This message indicates that the E1 port, which is not enabled, received signal.
Procedure 8-76
3. Retrieve the current alarms, and check if the Usage Error alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates there are some errors in card control bus.
Procedure 8-77
Maintenance NWD-107462-05E
8-44 Trouble Shooting
8.3.10.1 Unequipped
This message indicates that the configured card is not detected in the IDU. The possible
cause is equipment configuration file mismatch, generated in the different equipment that
includes the option card is downloaded.
Procedure 8-78
1. Execute “shipment” procedure with the LCT. The IDU will be rebooted.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates there are some errors in card control bus.
Procedure 8-79
This message indicates that packet to TDM jitter buffer underrun is detected on the
pseudo-wire connection. If this condition occurs, the problem is on the cable
connection or on the far-end NE, or caused by packet jitter in the network.
Procedure 8-80
3. Retrieve the current alarms, and check if the TDM Buffer Underrun alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
4. Increasing jitter buffer size may solve the issue if the alarm is caused by packet
jitter in the network.
NWD-107462-05E Maintenance
Trouble Shooting 8-45
This message indicates that all of member ports belonged to the radio group are
down.
Procedure 8-81
Maintenance NWD-107462-05E
8-46 Trouble Shooting
Figure 8-15 Alarm Action Table for STM-1 Interface (Channelized Mode)
NWD-107462-05E Maintenance
Trouble Shooting 8-47
Figure 8-16 Alarm Action Table for STM-1 Interface (Through Mode)
Maintenance NWD-107462-05E
8-48/END Trouble Shooting
8.3.12.3 E1 Interface
NWD-107462-05E Maintenance
Abbreviations 9-1
9. ABBREVIATIONS
Maintenance NWD-107462-05E
9-2 Abbreviations
ETH-LT ETH- Link Trace function IEEE Institute of Electrical and Electronics
NWD-107462-05E Maintenance
Abbreviations 9-3
Maintenance NWD-107462-05E
9-4 Abbreviations
NWD-107462-05E Maintenance
Abbreviations 9-5
WG Waveguide
WR Warning
WRR Weighted Round Robin
WS Wayside
WWW World Wide Web
XCTRL XPIC Control
X-DEM XPIC Demodulator
XFP 10(X) Gigabit Small Form Factor
Pluggable
XIF XPIC IF
XPD Cross Polarization Discrimination Ratio
XPIC Cross Polarization Interference
Canceller
XREF XPIC Reference
Maintenance NWD-107462-05E
9-6/END Abbreviations
NWD-107462-05E Maintenance