Sei sulla pagina 1di 6

BACnet

b3865/866/885-V VAV
Controllers with Built-in Actuator

The Andover ContinuumTM b3865-V, b3866-V and b3885-V are


native BACnet controllers that communicate on an RS-485 field
bus as Master devices using the MS/TP BACnet protocol.
02

BACnet b3865/866/885-V VAV Controllers


with Built-in Actuator
Features

The controllers are highly intelligent,


low-cost VAV box controllers that come
equipped with a built-in actuator to
streamline hardware installation and save
commissioning time. Universal inputs, an
airflow sensor, Form A triac-based outputs,
and an integrated damper actuator
make these controllers perfect for VAV
applications. The b3865/866-V models
feature a room sensor input, which supports
our Andover Continuum Smart Sensor, or
any standard room temperature sensor.

• The b3865-V is the base model with four universal


inputs, an airflow sensor, three Form A triac-based
Product AT A GLANCE outputs, and an integrated damper actuator.

• Native BACnet MS/TP communications • The b3866-V model is identical to the b3865-V,
with the exception that it also offers damper
• Support for 18 BACnet object types, including
position feedback and two analog outputs to
Trends, Schedules, Calenders, and Loops
control reheat valves, lighting ballasts, etc.
• Low-cost VAV control in compact package
• The b3885-V has a reduced I/O point count for
• Built-in damper actuator simplifies smaller VAV applications.
hardware installation
• All VAV models feature Flash memory, user
• Universal inputs with Form A, Form K, and memory for programs, and a fast (32-bit)
analog outputs for flexible control options processor for faster can times, with plenty of
• Non-volatile Flash memory for application additional memory available for data logging of
program and operating system storage your critical data.

• Easy on-line software updates

• Local extended storage of log data b3865-V b3866-V b3885-V

• On-board airflow sensor Universal Inputs 4 4 2


Airflow Sensor Yes Yes Yes
• Optional Andover Continuum Smart
Sensor Display Smart Sensor Input Yes Yes No
Form A Triac Outputs 3 3 2
• Complies with B-AAC BACnet profile
Analog Outputs - 2 -
• Support for Wireless BACnet Field
Integrated Yes Yes Yes
Bus communications Actuator
Service Port Yes Yes Yes
Wireless Option Yes Yes Yes

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3865/866/885-A4.BU.N.EN.12.2011.0.00.CC
03

BACnet b3865/866/885-V VAV Controllers


with Built-in Actuator
Features (continued)

As native BACnet controllers, the b3865/866/885-V Dimension Drawing


models can communicate with other BACnet
devices on the MS/TP network, in strict accordance
with ANSI/ASHRAE standard 135-2004. By
connecting to the Andover Continuum bCX1, the
controllers, or other MS/TP devices can share and
gather data from the wider Ethernet/IP network
of controllers. Among those Ethernet controllers
can be Andover Continuum controllers (BACnet or
Andover Continuum Infinet) or third party BACnet
IP devices. All Andover devices, both BACnet and
Andover Continuum Infinet, are fully compatible with
the Andover Continuum CyberStation front-end
software, a fully native BACnet Operator Workstation
(B-OWS) application.

A Highly Intelligent Controller


Andover Continuum field controllers are highly
intelligent and the VAV models are no exception.
TAC designs the Andover Continuum field controllers
to handle schedules, alarms and trends locally so
there is no reliance on any supervisory controllers.
Since each controller is programmable and can
operate independently, the Andover Continuum
is highly reliable. Furthermore, each controller is
“peer-to-peer” and can share data with any Andover from being lost if power is removed.
Continuum or third party BACnet controller.
Inputs
Optional Wireless BACnet The inputs consists of two or four full-range
The b3865/866/885-V BACnet controllers can Universal inputs that accept voltage (0-5VDC),
also communicate using a wireless mesh BACnet digital (on/off), counter signals (up to 4Hz), or
865-V
(LOW)

network. Simply plug Andover Continuum Wireless temperature signals,AIR plus


FLOWan on-board air flow
INPUT
Adapters into the service ports of the BACnet sensor. The (HIGH)
b3865/866-V models also offer an
controllers with wireless compatible firmware to additional input to support the Andover Continuum
create a wireless mesh network that sends and Smart Sensor, or any standardCAUTION room temperature
COM 18
receives BACnet messages. Because the native sensor. 1 IN 1 MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED RS-485
TO DE-ENERGIZE THIS EQUIPMENT COM 17
2 IN 2 PORT
BACnet communications are used wirelessly, the BEFORE SERVICING.
SHIELD 16
bCX1 connects the entire wireless BACnet network Outputs 3 RET UNIVERSAL
INPUTS
to the wired BACnet networks in your system, The b3865/866-V 4
IN 3
controllers contain three Form
This equipment complies with part 15
5 IN 4
regardless of manufacturer. A Triac-based outputs. The to theb3885-V controller
of the FCC rules. Operation is subject
following two conditions.
(1) This device may not cause harmful
6 RET interference.
contains two Form A Triac-based outputs.
(2) This device must accept any
interference received, including
interference that may cause
These TRIAC REF 15
7 SPWR
outputs can be usedSMART separately for on/off or
undesired operation.
Increased Reliability with Flash Memory 8 RET
DIGITAL
OUTPUTS
OUT5 14

The non-volatile Flash memory stores your operating pulsed control of lighting, heat, and fan units or24VAC ,
SENSOR
OUT4 13
9 IN 5 0.5A
system and application programs, so that in the event for bi-directional control of dampers
USE COPPER CONDUCTORS and ONLY valves; or OUT3 12
10 2 4VAC
INPUT: CLASS 2 POWER ONLY
of a power loss, your application is restored when configured into
11 one Form
24VAC ,K Tri-state
0.42A, 10VA, 50/60HZoutput and one
power is returned. In addition, the Flash memory Form A output. (Note: Any two consecutive Triac
allows for easy upgrades of your operating system via outputs can be configured as a Form K output.)
Outputs are (LOW)
rated for AC loads only. The b3866-V
software downloads, eliminating the need to swap out
memory chips. Each controller, except the b3885-V, controller also offers AIRtwoFLOW
INPUT (0-10V) analog outputs. 866-V
includes an on-board battery to safeguard your
(HIGH)

runtime data — protecting all point data and log data


CAUTION COM 21
1 IN 1 MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED RS-485
TO DE-ENERGIZE THIS EQUIPMENT COM 20
Schneider Electric One High Street, North Andover, MA 01845 USA 2 +1
Telephone: IN 2 978 975 9600 PORT
BEFOREFax: +1 978 975 9674
SERVICING. www.schneider-electric.com/buildings
SHIELD 19
3 RET UNIVERSAL
SDS-B3865/866/885-A4.BU.N.EN.12.2011.0.00.CC A07 18
4 IN 3 INPUTS
ANALOG
This equipment complies with part 15 OUTPUTS RET 17
5 IN 4 of the FCC rules. Operation is subject
to the following two conditions. 0-10 VDC
04

BACnet b3865/866/885-V VAV Controllers


with Built-in Actuator
Features (continued)

Connection Labels
Damper Actuator
The integrated damper actuator allows simple
865-V
(LOW)

AIR FLOW
direct mounting of the controller directly over the (HIGH)
INPUT

existing damper shaft. This eliminates the need


for separate mounting, wiring, and positioning of CAUTION COM 18
the damper motor. Also, the actuator has a built-in 1 IN 1 MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED RS-485
TO DE-ENERGIZE THIS EQUIPMENT COM 17
clutch button to temporarily disengage the direct- 2 IN 2
BEFORE SERVICING.
PORT
SHIELD 16
drive gears during commissioning. The controller 3 RET UNIVERSAL
4 INPUTS
actuator may be preset for a limited range of IN 3
This equipment complies with part 15
5 IN 4 of the FCC rules. Operation is subject
motion using the mechanical “stops” provided. to the following two conditions.
(1) This device may not cause harmful
6 RET interference.
(2) This device must accept any
interference received, including
interference that may cause TRIAC REF 15
7 SPWR undesired operation.
Software Capabilities 8 RET
SMART
DIGITAL
OUTPUTS
OUT5 14
SENSOR
The dynamic memory of the b3865/866/885-V 9 IN 5
24VAC , OUT4 13
0.5A
controllers can be allocated for any combination 10 2 4VAC
USE COPPER CONDUCTORS ONLY OUT3 12
INPUT: CLASS 2 POWER ONLY
of programs, scheduling, alarming, and data 11 24VAC , 0.42A, 10VA, 50/60HZ

logging using the powerful Andover Plain English


programming language. Our object-oriented Plain
English language with intuitive keywords provides
866-V
(LOW)

AIR FLOW
an easy method to tailor the controller to meet your INPUT
(HIGH)

exact requirements. Programs are entered into the


controller using Andover Continuum CyberStation.
CAUTION
Programs are then stored and executed by the 1 IN 1 MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED
COM 21
RS-485
COM 20
controller. Programming multiple b3865/866/885-V 2 IN 2 TO DE-ENERGIZE THIS EQUIPMENT
BEFORE SERVICING.
PORT
SHIELD 19
controllers is inherently easy with Plain English. 3 RET UNIVERSAL
INPUTS A07 18
A complete copy of one controller’s programs can 4 IN 3 ANALOG
This equipment complies with part 15 OUTPUTS RET 17
5 IN 4
be loaded directly into other controllers without of the FCC rules. Operation is subject
to the following two conditions.
(1) This device may not cause harmful
0-10 VDC
AO6 16
6 RET interference.
changing any point names or programs. (2) This device must accept any
interference received, including
interference that may cause TRIAC REF 15
7 SPWR undesired operation.
DIGITAL
SMART OUT5 14
8 RET OUTPUTS
Smart Sensor Interface 9 IN 5
SENSOR 24VAC , OUT4 13
0.5A
The b3865/866-V controllers provide a built-in 10 2 4VAC
USE COPPER CONDUCTORS ONLY OUT3 12
INPUT: CLASS 2 POWER ONLY
connection for an Andover Continuum Smart 11 24VAC , 0.42A, 10VA, 50/60HZ

Sensor. The Smart Sensor provides a two-character


LED display and a six-button programmable
keypad that enables operators and occupants to
885-V
(LOW)

AIR FLOW
change setpoints, balance VAV boxes, monitor INPUT
(HIGH)
occupancy status, and turn equipment on and off.
An enhanced version of the Smart Sensor is also
available with a four-digit custom LCD that provides 1 IN 1
COM 12
RS-485
the following icons: PM, %, °, Setpoint, Cool, Heat, 2 IN 2
UNIVERSAL
INPUTS
PORT
COM 11

SHIELD 10
CFM, Fan, OA, and SP. 3 RET CAUTION
MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED
TO DE-ENERGIZE THIS EQUIPMENT
BEFORE SERVICING.
This equipment complies with part 15
of the FCC rules. Operation is subject
to the following two conditions. TRIAC REF 9
(1) This device may not cause harmful
interference.
(2) This device must accept any DIGITAL
interference received, including NOT USED 8
interference that may cause OUTPUTS
undesired operation.
24VAC , OUT4 7
0.5A
USE COPPER CONDUCTORS ONLY OUT3 6
4 2 4VAC
INPUT: CLASS 2 POWER ONLY
5 24VAC , 0.42A, 10VA, 50/60HZ

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3865/866/885-A4.BU.N.EN.12.2011.0.00.CC
05

BACnet b3865/866/885-V VAV Controllers


with Built-in Actuator
Specifications

b3865/866/885-V Controller
Electrical User LEDs Universal Inputs
Power Status Indicator LEDs: Connections
24 VAC, +10%-15%, 50/60 Hz, CPU CPU Active Model b3865-V: Four inputs and
Class 2 Limited Power Green = Active two returns
Power Consumption Model b3866-V: Four inputs and
Less than 10 VA Airflow Input two returns
Overload Protection Range Model b3885-V: Two inputs and
Fused, MOV protected 0 to 1˝ W.C. (0-250 Pa) one return
Resolution Input Voltage Range
Mechanical 0.0013˝ W.C. (0.33Pa) @ 73°F (23°C) 0 to 5.115 VDC
Operation Environment Accuracy Input Impedance
32° to 122°F (0-50°C), ± 0.05˝ W.C. (12.50 Pa) @ 73°F (23°C) 10K ohm to 5.120 V
10 - 90% RH (non-condensing) Input Voltage Resolution
Dimensions Damper Shaft Mounting Screws 5.0 mV
7.75˝ W x 6.25˝ L x 2.5˝ H Torque Minimum Digital Resolution
(197 mm W x 159 mm L x 63 mm H) Varies according to shaft material 10 bits
Weight Torque Maximum Input Voltage Accuracy
2.50 lbs (1.04 kg) 30 inch-pounds (3.4 Nm) ± 15mV
Hex Screws Temperature Range
Battery 10-32 (with supplied hex wrench) -30° to 230°F (-34° to 110°C)
Replaceable, rechargeable battery. Damper Actuator Motor Temperature Accuracy
Provides 30 days typical accumulated Shaft Diameter ± 1° F from -10° to 150°F
power failure backup of RAM memory. 1/2” (with a 3/8” adapter) ( ± 0.56°C from -23° to +66°C)
All data stored in Flash on power loss. 12.6 mm (with a 9.45 mm adapter) Counter Frequency
Shaft Torque 4 Hz @ 50% duty cycle
Communications 53 inch-pounds (5.989 Nm) Input Protection
RS-485 port for implementing Damper Speed ± 1000 V transients
BACnet MS/TP connection, including: 180 sec. @ 60 Hz and 216 sec @ 50 Hz: Input Filter
Three-position removable screw terminal for 90° adjustable end limits with two 16 Hz with one pole RC filter
Standard service port, four-position set screws Connector
shrouded connector Motor Removable, 5 mm screw terminal
LEDs: Type: 24 VAC synchronous
TD = Transmit Enable Motor Protection: Mechanical clutch
RD = Received Data Manual clutch override with a
Wired/Wireless Field Bus push-button release
RS-485 port for implementing Hardware position feedback
Wireless BACnet connection, including: (model b3866-V only)
Standard service port, four-position
shrouded connector

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3865/866/885-A4.BU.N.EN.12.2011.0.00.CC
06

BACnet b3865/866/885-V VAV Controllers


with Built-in Actuator
Specifications (continued)

b3865/866/885-V Controller
Smart Sensor Interface Analog Outputs Agency Listings
Connections Connections FCC Rules and Regulations CFR 47,
Model b3865-V: One input, Model b3865-V: Not available Part 15, Class A, ICES-003,
SPWR, and return Model b3866-V: Two analog outputs AS/NZS 3548, European Union (EU)
Model b3866-V: One input, and one return Directive 2002/96/EC
SPWR, and return Model b3885-V: Not available
Model b3885-V: Not available Analog Output Channels Required Models
Digital Outputs Two, voltage only b3865-V
Connections Voltage Output Range BACnet 865-V VAV Controller
Model b3865-V: Three triac outputs 0 – 10 V b3866-V
and one reference Output Source Current BACnet 866-V VAV Controller
Model b3866-V: Three triac outputs 5 mV Maximum b3885-V
and one reference Voltage Output Load BACnet 885-V VAV Controller
Model b3885-V: Two triac outputs 2K ohm Minimum Impedance b3865-V-WL
and one reference Voltage Output Resolution Wireless BACnet 865-V VAV Controller
SPST Accuracy 50 mV b3866-V-WL
0.1 second for pulse width modulation Digital Resolution Wireless BACnet 866-V VAV Controller
Contact Ratings 8 bits b3885-V-WL
0.5 A Maximum, 24 VAC Output Voltage Accuracy Wireless BACnet 885-V VAV Controller
Connector 100 mV
Removable, 5mm screw terminal Connector
Removable, 5mm screw terminal

© 2007-2011 Schneider Electric. All rights reserved.

All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3865/866/885-A4.BU.N.EN.12.2011.0.00.CC December 2011 gg