b3865/866/885-V VAV
Controllers with Built-in Actuator
• Native BACnet MS/TP communications • The b3866-V model is identical to the b3865-V,
with the exception that it also offers damper
• Support for 18 BACnet object types, including
position feedback and two analog outputs to
Trends, Schedules, Calenders, and Loops
control reheat valves, lighting ballasts, etc.
• Low-cost VAV control in compact package
• The b3885-V has a reduced I/O point count for
• Built-in damper actuator simplifies smaller VAV applications.
hardware installation
• All VAV models feature Flash memory, user
• Universal inputs with Form A, Form K, and memory for programs, and a fast (32-bit)
analog outputs for flexible control options processor for faster can times, with plenty of
• Non-volatile Flash memory for application additional memory available for data logging of
program and operating system storage your critical data.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-B3865/866/885-A4.BU.N.EN.12.2011.0.00.CC
03
The non-volatile Flash memory stores your operating pulsed control of lighting, heat, and fan units or24VAC ,
SENSOR
OUT4 13
9 IN 5 0.5A
system and application programs, so that in the event for bi-directional control of dampers
USE COPPER CONDUCTORS and ONLY valves; or OUT3 12
10 2 4VAC
INPUT: CLASS 2 POWER ONLY
of a power loss, your application is restored when configured into
11 one Form
24VAC ,K Tri-state
0.42A, 10VA, 50/60HZoutput and one
power is returned. In addition, the Flash memory Form A output. (Note: Any two consecutive Triac
allows for easy upgrades of your operating system via outputs can be configured as a Form K output.)
Outputs are (LOW)
rated for AC loads only. The b3866-V
software downloads, eliminating the need to swap out
memory chips. Each controller, except the b3885-V, controller also offers AIRtwoFLOW
INPUT (0-10V) analog outputs. 866-V
includes an on-board battery to safeguard your
(HIGH)
Connection Labels
Damper Actuator
The integrated damper actuator allows simple
865-V
(LOW)
AIR FLOW
direct mounting of the controller directly over the (HIGH)
INPUT
AIR FLOW
an easy method to tailor the controller to meet your INPUT
(HIGH)
AIR FLOW
change setpoints, balance VAV boxes, monitor INPUT
(HIGH)
occupancy status, and turn equipment on and off.
An enhanced version of the Smart Sensor is also
available with a four-digit custom LCD that provides 1 IN 1
COM 12
RS-485
the following icons: PM, %, °, Setpoint, Cool, Heat, 2 IN 2
UNIVERSAL
INPUTS
PORT
COM 11
SHIELD 10
CFM, Fan, OA, and SP. 3 RET CAUTION
MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED
TO DE-ENERGIZE THIS EQUIPMENT
BEFORE SERVICING.
This equipment complies with part 15
of the FCC rules. Operation is subject
to the following two conditions. TRIAC REF 9
(1) This device may not cause harmful
interference.
(2) This device must accept any DIGITAL
interference received, including NOT USED 8
interference that may cause OUTPUTS
undesired operation.
24VAC , OUT4 7
0.5A
USE COPPER CONDUCTORS ONLY OUT3 6
4 2 4VAC
INPUT: CLASS 2 POWER ONLY
5 24VAC , 0.42A, 10VA, 50/60HZ
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-B3865/866/885-A4.BU.N.EN.12.2011.0.00.CC
05
b3865/866/885-V Controller
Electrical User LEDs Universal Inputs
Power Status Indicator LEDs: Connections
24 VAC, +10%-15%, 50/60 Hz, CPU CPU Active Model b3865-V: Four inputs and
Class 2 Limited Power Green = Active two returns
Power Consumption Model b3866-V: Four inputs and
Less than 10 VA Airflow Input two returns
Overload Protection Range Model b3885-V: Two inputs and
Fused, MOV protected 0 to 1˝ W.C. (0-250 Pa) one return
Resolution Input Voltage Range
Mechanical 0.0013˝ W.C. (0.33Pa) @ 73°F (23°C) 0 to 5.115 VDC
Operation Environment Accuracy Input Impedance
32° to 122°F (0-50°C), ± 0.05˝ W.C. (12.50 Pa) @ 73°F (23°C) 10K ohm to 5.120 V
10 - 90% RH (non-condensing) Input Voltage Resolution
Dimensions Damper Shaft Mounting Screws 5.0 mV
7.75˝ W x 6.25˝ L x 2.5˝ H Torque Minimum Digital Resolution
(197 mm W x 159 mm L x 63 mm H) Varies according to shaft material 10 bits
Weight Torque Maximum Input Voltage Accuracy
2.50 lbs (1.04 kg) 30 inch-pounds (3.4 Nm) ± 15mV
Hex Screws Temperature Range
Battery 10-32 (with supplied hex wrench) -30° to 230°F (-34° to 110°C)
Replaceable, rechargeable battery. Damper Actuator Motor Temperature Accuracy
Provides 30 days typical accumulated Shaft Diameter ± 1° F from -10° to 150°F
power failure backup of RAM memory. 1/2” (with a 3/8” adapter) ( ± 0.56°C from -23° to +66°C)
All data stored in Flash on power loss. 12.6 mm (with a 9.45 mm adapter) Counter Frequency
Shaft Torque 4 Hz @ 50% duty cycle
Communications 53 inch-pounds (5.989 Nm) Input Protection
RS-485 port for implementing Damper Speed ± 1000 V transients
BACnet MS/TP connection, including: 180 sec. @ 60 Hz and 216 sec @ 50 Hz: Input Filter
Three-position removable screw terminal for 90° adjustable end limits with two 16 Hz with one pole RC filter
Standard service port, four-position set screws Connector
shrouded connector Motor Removable, 5 mm screw terminal
LEDs: Type: 24 VAC synchronous
TD = Transmit Enable Motor Protection: Mechanical clutch
RD = Received Data Manual clutch override with a
Wired/Wireless Field Bus push-button release
RS-485 port for implementing Hardware position feedback
Wireless BACnet connection, including: (model b3866-V only)
Standard service port, four-position
shrouded connector
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-B3865/866/885-A4.BU.N.EN.12.2011.0.00.CC
06
b3865/866/885-V Controller
Smart Sensor Interface Analog Outputs Agency Listings
Connections Connections FCC Rules and Regulations CFR 47,
Model b3865-V: One input, Model b3865-V: Not available Part 15, Class A, ICES-003,
SPWR, and return Model b3866-V: Two analog outputs AS/NZS 3548, European Union (EU)
Model b3866-V: One input, and one return Directive 2002/96/EC
SPWR, and return Model b3885-V: Not available
Model b3885-V: Not available Analog Output Channels Required Models
Digital Outputs Two, voltage only b3865-V
Connections Voltage Output Range BACnet 865-V VAV Controller
Model b3865-V: Three triac outputs 0 – 10 V b3866-V
and one reference Output Source Current BACnet 866-V VAV Controller
Model b3866-V: Three triac outputs 5 mV Maximum b3885-V
and one reference Voltage Output Load BACnet 885-V VAV Controller
Model b3885-V: Two triac outputs 2K ohm Minimum Impedance b3865-V-WL
and one reference Voltage Output Resolution Wireless BACnet 865-V VAV Controller
SPST Accuracy 50 mV b3866-V-WL
0.1 second for pulse width modulation Digital Resolution Wireless BACnet 866-V VAV Controller
Contact Ratings 8 bits b3885-V-WL
0.5 A Maximum, 24 VAC Output Voltage Accuracy Wireless BACnet 885-V VAV Controller
Connector 100 mV
Removable, 5mm screw terminal Connector
Removable, 5mm screw terminal
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.