DT1M DIN Rail Surge Protection Class I+II 25 kA – DT1M27510R

Surges and voltage transients are a major cause of expensive electronic equipment failure and business disruption. Damage may
result in the loss of capital outlays, such as computers and communications equipment, as well as consequential loss of revenue
and profits due to unscheduled system down-time. nVent ERICO offers multiple series of surge protective devices (SPDs) suitable
for a vast range of applications that provide reliable protection from voltage transients on power distribution systems. The DT1M
Series DIN Rail Surge Protective Devices provide reliable and efficient protection against voltage transients within the IEC Class
I (25 kA) environment. Tested and independently certified to the IEC standard, the DT1M Series provides a range of compact, safe
and high surge rated performance features for the harsh IEC Class I environment and suitable for protection within a wide range of
applications.

Additionally, the nVent ERICO DT1M Series sets itself apart from the competition with an innovative and unique technology. This
technology advancement provides spark gap-like performance with MOV current extinction. The same technology allows the DT1M
Series to be thinner than the competition by as much as 50% and can also be universally coordinated with any Class II or Class III
SPD.

• Spark gap surge performance with MOV-like current extinction


• Universally coordinated with any Class II or Class III surge protection devices
• Follow current limitation, no tripping of a 16 A gG fuse
• Compact, yet high surge rated pluggable design, using minimum DIN rail width
• Retaining clip ensures enhanced vibration and shock resistance performance
• Red/Green status indication and change-over contacts standard for remote monitoring
• Includes thermal disconnect for safe end of life

Part Number DT1M27510R


Nominal System Voltage (Un) 240 VAC
Max Continuous Operating Voltage (Uc) 275 VAC
Nominal Discharge Current (In), IEC 25 kA 8/20 μs
Max Discharge Current (Imax), IEC 65 kA 8/20 μs
Impulse Current (Iimp) 25 kA 10/350 μs
Voltage Protection Level (Up) 1.550 V
Back-Up Fuse @ Isccr 315 A @ 50 kA
Response Time 100 ns Max
Short Circuit Current Rating (Isccr) 50 kA
Distribution System TN-C
TN-S
TT (L-N)
Protection Modes L-N
Part Number DT1M27510R
L-PE
L-PEN
N-PE (TN-S)
Follow Current Interrupt Rating (Ifi) 50 kA
Temporary Over Voltage 120 min (Ut/mode) 442 V Safe Fail
Technology Thermal Disconnect
Connection, Solid 35 mm² Max
Connection, Stranded 25 mm² Max
Torque (TQ) 4,5 N-m
Altitude 2.000 m Max
Humidity 5 – 95 % RH
Temperature -40 to 70 °C
Enclosure Material UL® 94V-0 Thermoplastic
Enclosure Rating IP 20
Mounting 35 mm top hat DIN rail
Remote Contact Switching Capacity 1,0 A @ 250 VAC
1,0 A @ 125 VAC
0,5 A @ 48 VDC
0,5 A @ 24 VDC
0,5 A @ 12 VDC
Remote Contacts Yes
Status Indication Mechanical flag
Depth (D) 85 mm
Height (H) 90 mm
Width (W) 18 mm
Replacement Module DT1M275M
Complies With EN 61643-11 Type 1, Type 2
IEC® 61643-11 Class I, Class II
Standard Packaging Quantity 1 pc
UPC 78285698727
EAN-13 0782856987277

IEC is a registered trademark of the International Electrotechnical Commission. UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.
 
WARNING
nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from
your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent 's instructions and warnings may cause product
malfunction, property damage, serious bodily injury and death and/or void your warranty.
 
© 2019 nVent  All rights reserved
nVent, nVent CADDY, nVent ERICO, nVent ERIFLEX and nVent LENTON are owned by nVent or its global affiliates.
All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

Potrebbero piacerti anche