• Lessons Learned
• NCS Cold Stores is a wholly owned subsidiary of QAF Ltd provides cold storage and
warehousing solutions to the food and marine products market through its Jurong
facility, which has 26 cold rooms and storage area totalling 50,000 cubic metres.
• The cold rooms were served by a centralised ammonia refrigeration plant, with a
two-stage compression system.
– Energy assessments
Phase 3
• Application for
Phase 1 GREET scheme
• Preliminary • Development of
assessment M&V plan
• Application for • Project
EASe scheme implementation
Phase 2 Phase 4
• Detailed • Measurement &
assessment verification
• Data analysis and • Continuous
conceptual monitoring
recommendations
PHASE 1 – PRELIMINARY ASSESSMENT
• A preliminary energy assessment was conducted in Nov 2008 with the following
key objectives:
• Upon approval of EASe, a detailed energy assessment was carried out to ascertain
the observations and findings made in the preliminary assessment.
– Identification that the existing compressors had de-rated capacities that are
insufficient to support the design conditions.
PHASE 2 – DETAILED ASSESSMENT
Avg 38 °C
Avg 10 °C
Design -10 °C
PHASE 2 – DETAILED ASSESSMENT
• Various discussions were carried out to go over the details of the energy retrofit,
with key emphasis placed upon the approach for the measurement and
verification of energy savings.
U-bend not
suitable for flow
measurement
PHASE 4 – MEASUREMENT & VERIFICATION
Proposed location
PHASE 4 – MEASUREMENT & VERIFICATION
PHASE 4 – MEASUREMENT & VERIFICATION
PHASE 4 – MEASUREMENT & VERIFICATION
PHASE 4 – MEASUREMENT & VERIFICATION
– Liquid flow
• Savings of 21% in COP were achieved which equates to an estimated 700 MWh
savings ($150,000) in annual energy consumption and costs.
• Achieving energy savings through retrofit requires high level of commitment from
top management to field engineers: