SAUDI ELECTRICITY COMPANY

WESTERN OPERATING AREA

RGC # 110192
A MULTI-STOREY BUILDING IN
JEDDAH ADMINISTRATIVE OFFICE

PACKAGE - 1

MECHANICAL HVAC
CALCULATIONS

ISSUED FOR CONSTRUCTION

Prepared by:

RADICON-GULF CONSULT
Al-Khobar, Saudi Arabia

MAY 2011
MULTI-STORY PARKING BUILDING (PACKAGE-1)
HVAC Load Analysis
for

SUADI ELECTRICITY COMPANY


Western Area Administration
Jeddah, K.S.A.

Prepared By:
AAD
Radicon Gulf Consult
PO 468 Al-Khobar
31952, KSA

Saturday, October 23, 2010


CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 2

General Project Data Input


General Project Information
Project file name: D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking
Bldg-110192- Packaged-1.CHV
Project title: MULTI-STORY PARKING BUILDING (PACKAGE-1)
Designed by: AAD
Project date: July 28, 2010
Project location: JEDDAH, SAUDI ARABIA
Client name: SUADI ELECTRICITY COMPANY
Client address: Western Area Administration
Client city: Jeddah, K.S.A.
Company name: Radicon Gulf Consult
Company representative: AAD
Company address: PO 468 Al-Khobar
Company city: 31952, KSA
Barometric pressure: 29.882 in.wg.
Altitude: 36 feet
Latitude: 21 Degrees
Mean daily temperature range: 22 Degrees
Starting & ending time for HVAC load calculations: 7am - 6pm
Floor heat loss coefficient: 0.64 Btuh per foot of slab
Number of unique zones in this project: 50

Building Default Values


Calculations performed: Both heating and cooling loads
Lighting requirements: 2.00 Watts per square foot
Equipment requirements: 2.00 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 200 Btuh per person
Zone sensible safety factor: 10 %
Zone latent safety factor: 10 %
Zone heating safety factor: 10 %
People diversity factor: 80 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 9.0 feet
Building default wall height: 14.0 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 0 0 0 0 0 C C C C C C C C C C C C C 0 0 0 0 0 0
2 0 0 0 0 0 C C C C C C C C C C C C C 0 0 0 0 0 0
3 0 0 0 0 0 C C C C C C C C C C C C C 0 0 0 0 0 0
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 9 0.045 No Yes
2 2 0.048 Yes No

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 B 0.063 D
2 G 0.070 L
Wall #2 Description: Self-closing double door, metal, heavy construction, light color.

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.355 8 18
Partition #1 Description: 8 inch concrete block partition wall, adjoining shipping and receiving area

Master Glass
Glass Summer Winter Glass Interior Interior Room Glass Glass
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef Const Width Height
1 0.280 0.280 0.440 1 0.000 M 30.000 10.000
2 0.280 0.280 0.440 1 0.000 M 4.000 7.000
3 0.550 0.630 0.400 4 0.000 M 30.000 12.000
4 0.720 0.720 0.800 1 0.250 M 4.000 3.000

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 4

Air Handler Input


Air Handler Number 1 Input Data
Name: 5th - Floor Area ( A H U )
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 75
Static pressure across fan (in.wg.): 0.00
Summer supply duct temp rise (deg.F): 1.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 2.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 20 CFM/Pr
Cooling infiltration: 20 CFM/Pr
Heating ventilation: 20 CFM/Pr
Heating infiltration: 20 CFM/Pr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

Air Handler Number 2 Input Data


Name: 4th - Floor Area ( A H U )
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 5

Air Handler Input (cont'd)


Air Handler Number 2 Input Data
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 75
Static pressure across fan (in.wg.): 0.00
Summer supply duct temp rise (deg.F): 1.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 2.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 20 CFM/Pr
Cooling infiltration: 20 CFM/Pr
Heating ventilation: 20 CFM/Pr
Heating infiltration: 20 CFM/Pr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

Air Handler Number 3 Input Data


Name: Ground & 1st-3rd Floor Area ( P A C U )
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 75
Static pressure across fan (in.wg.): 0.00
Summer supply duct temp rise (deg.F): 1.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 2.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 20 CFM/Pr
Cooling infiltration: 20 AC/Hr
Heating ventilation: 20 CFM/Pr
Heating infiltration: 20 AC/Hr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 6

Air Handler Input (cont'd)


Air Handler Number 3 Input Data
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

Air Handler Number 5 Input Data


Name: G-009 U- Drive Rm. Mini Split
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 75
Static pressure across fan (in.wg.): 0.00
Summer supply duct temp rise (deg.F): 1.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 2.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 20 CFM/Pr
Cooling infiltration: 20 AC/Hr
Heating ventilation: 20 CFM/Pr
Heating infiltration: 20 AC/Hr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

Air Handler Number 6 Input Data


Name: G-010 Com. Rm. Mini Split (typical)
Terminal type: Constant Volume
Method for CV Sum of Peaks

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 7

Air Handler Input (cont'd)


Air Handler Number 6 Input Data
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 75
Static pressure across fan (in.wg.): 0.00
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 20 CFM/Pr
Cooling infiltration: 20 CFM/Pr
Heating ventilation: 20 CFM/Pr
Heating infiltration: 20 CFM/Pr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

Air Handler Number 7 Input Data


Name: G-023 Com. Rm. Mini Split (typical)
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 75
Static pressure across fan (in.wg.): 0.00

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 8

Air Handler Input (cont'd)


Air Handler Number 7 Input Data
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 0 CFM/Pr
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 CFM/Pr
Heating infiltration: 0 AC/Hr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

Air Handler Number 8 Input Data


Name: G-013/020 Electrical Room Mini Split
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 75
Static pressure across fan (in.wg.): 0.00
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 0 CFM/Pr
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 CFM/Pr
Heating infiltration: 0 AC/Hr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 9

Air Handler Input (cont'd)


Air Handler Number 8 Input Data
Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

Air Handler Number 9 Input Data


Name: 1-109/114 To 3-309/314 Elec. Rm. Split
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 75
Static pressure across fan (in.wg.): 0.00
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 0 CFM/Pr
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 CFM/Pr
Heating infiltration: 0 AC/Hr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

Air Handler Number 10 Input Data


Name: R-601 Utility Room Mini Split
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 10

Air Handler Input (cont'd)


Air Handler Number 10 Input Data
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 75
Static pressure across fan (in.wg.): 0.00
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 20 CFM/Pr
Cooling infiltration: 20 CFM/Pr
Heating ventilation: 20 CFM/Pr
Heating infiltration: 20 CFM/Pr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

Air Handler Number 11 Input Data


Name: G-001 Guard House
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 95.0
Leaving cooling coil temp (deg.F): 55.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 75
Static pressure across fan (in.wg.): 0.00
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 11

Air Handler Input (cont'd)


Air Handler Number 11 Input Data
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 0 CFM/Pr
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 CFM/Pr
Heating infiltration: 0 AC/Hr
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 118 81 50% 75 35.77 25
July 118 81 50% 75 35.77 25
June 118 81 50% 75 35.77 25
Winter 57 75

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 12

Zone Input
Zone 1: R-601 Utility Room (193.6512 sq.ft) (Group 10)
Air Handler number: 10 Zone occurrences: 1
Zone length: (feet) 14.76 Zone width (feet): 13.12
Lighting Watts: 264 Equipment Watts: 310
Number of people in zone: 2 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 194 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 14.76 13.12 193.7 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 14.70 192.9 NW
2 1 B 0.063 D 13.12 13.12 172.1 NE
3 1 B 0.063 D 13.12 14.70 192.9 SE
4 1 B 0.063 D 13.12 13.12 172.1 SW
5 2 G 0.070 L 7.22 3.28 23.7 NE

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 2 0.280 0.440 7.00 4.00 1.000 28.0 0 90 3

Zone 2: 5-522/523 Office Space (22967 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 193.00 Zone width (feet): 119.00
Lighting Watts: 31,326 Equipment Watts: 29,140
Number of people in zone: 188 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 2,000 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 22,967 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 193.00 119.00 22,967.0 Yes

Part Type U-Factor Cool TD Heat TD Height Width Area


4 1 0.355 8.000 18.000 13.12 52.00 682.2

Wall Type ASHRAE# U-Factor Color Height Width Area Direction

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 13

Zone Input (cont'd)


Zone 2: 5-522/523 Office Space (22967 sq.ft) (Group 1)
1 1 B 0.063 D 13.12 89.00 1,167.7 SW
2 1 B 0.063 D 13.12 89.00 1,167.7 NE
3 1 B 0.063 D 13.12 173.00 2,269.8 NW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 3.000 900.0 0 90 1
2 1 0.280 0.440 10.00 30.00 3.000 900.0 0 90 2
3 1 0.280 0.440 10.00 30.00 4.000 1,200.0 0 90 3

Zone 3: 5-507 Com. Room (255.408 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 18.78 Zone width (feet): 13.60
Lighting Watts: 411 Equipment Watts: 2,556
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 255 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 18.78 13.60 255.4 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 13.60 178.4 NW

Zone 4: 5-506 Storage Room (168.3432 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 12.36 Zone width (feet): 13.62
Lighting Watts: 325 Equipment Watts: 337
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/sq.ft Cooling ventilation value: 0.050
Cooling infiltration method: CFM/Pr Cooling infiltration value: 0.050
Heating ventilation method: CFM/sq.ft Heating ventilation value: 0.050
Heating infiltration method: CFM/Pr Heating infiltration value: 0.050
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 168 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 12.36 13.62 168.3 Yes

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 14

Zone Input (cont'd)


Zone 5: 5-509 Electrical Room (168.3432 sq.ft) (Group 1)
Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 13.62 Zone width (feet): 12.36
Lighting Watts: 367 Equipment Watts: 200
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 168 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 13.62 12.36 168.3 Yes

Zone 6: 5-513 Service Core (156 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 12.00 Zone width (feet): 13.00
Lighting Watts: 196 Equipment Watts: 155
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/sq.ft Cooling ventilation value: 0.100
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.100
Heating ventilation method: CFM/sq.ft Heating ventilation value: 0.100
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.100
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 156 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 19.22 31.13 598.3 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 12.00 157.4 NW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 0.100 30.0 0 90 1

Zone 7: 5-503 Toilet And Wash (510 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 15.00 Zone width (feet): 34.00
Lighting Watts: 695 Equipment Watts: 1,020
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 15

Zone Input (cont'd)


Zone 7: 5-503 Toilet And Wash (510 sq.ft) (Group 1)
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 50.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 50.000
Heating ventilation method: CFM/Pr Heating ventilation value: 50.000
Heating infiltration method: CFM/Pr Heating infiltration value: 50.000
Winter exhaust air CFM: 900 Summer exhaust air CFM: 900
Minimum supply CFM: 800 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 510 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 25.43 15.86 403.3 Yes

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.12 34.00 446.1

Zone 8: 5-522 Office/Hall Way (4865.55 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 163.00 Zone width (feet): 29.85
Lighting Watts: 6,636 Equipment Watts: 9,731
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/sq.ft Cooling ventilation value: 0.100
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.100
Heating ventilation method: CFM/sq.ft Heating ventilation value: 0.100
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.100
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 4,866 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 163.00 31.45 5,126.4 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 29.85 391.6 NE

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 1.000 300.0 0 90 1

Zone 9: 5-500 Floor Lobby (1903.236 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 59.70 Zone width (feet): 31.88
Lighting Watts: 2,596 Equipment Watts: 3,806
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 15.000

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 16

Zone Input (cont'd)


Zone 9: 5-500 Floor Lobby (1903.236 sq.ft) (Group 1)
Cooling infiltration method: CFM/Pr Cooling infiltration value: 15.000
Heating ventilation method: CFM/Pr Heating ventilation value: 15.000
Heating infiltration method: CFM/Pr Heating infiltration value: 15.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 1,903 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 59.70 31.88 1,903.2 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 31.88 418.3 NW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 0.270 81.0 0 90 1

Zone 10: 5-522/524 Office Space (22967 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 193.00 Zone width (feet): 119.00
Lighting Watts: 31,327 Equipment Watts: 29,140
Number of people in zone: 188 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 22,967 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 193.00 119.00 22,967.0 Yes

Part Type U-Factor Cool TD Heat TD Height Width Area


4 1 0.355 8.000 18.000 13.12 63.00 826.6

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 89.00 1,167.7 SW
2 1 B 0.063 D 13.12 89.00 1,167.7 NE
3 1 B 0.063 D 13.12 173.00 2,269.8 SE
5 2 G 0.070 L 7.22 3.28 23.7 NE

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 3.000 900.0 0 90 1
2 1 0.280 0.440 10.00 30.00 3.000 900.0 0 90 2
3 1 0.280 0.440 10.00 30.00 4.000 1,200.0 0 90 3

Zone 11: 5-521 Com. Room (255.408 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 17

Zone Input (cont'd)


Zone 11: 5-521 Com. Room (255.408 sq.ft) (Group 1)
Zone length: (feet) 18.78 Zone width (feet): 13.60
Lighting Watts: 411 Equipment Watts: 2,556
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 255 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 18.78 13.60 255.4 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 13.60 178.4 SE

Zone 12: 5-520 Storage Room (168.3432 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 12.36 Zone width (feet): 13.62
Lighting Watts: 325 Equipment Watts: 337
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/sq.ft Cooling ventilation value: 0.050
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.050
Heating ventilation method: CFM/sq.ft Heating ventilation value: 0.050
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.050
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 168 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 12.36 13.62 168.3 Yes

Zone 13: 5-500 Electrical Room (168.3432 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 12.36 Zone width (feet): 13.62
Lighting Watts: 367 Equipment Watts: 200
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 18

Zone Input (cont'd)


Zone 13: 5-500 Electrical Room (168.3432 sq.ft) (Group 1)
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 168 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 12.36 13.62 168.3 Yes

Zone 14: 5-501 Coffee Corner (162.56 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 12.70 Zone width (feet): 12.80
Lighting Watts: 439 Equipment Watts: 1,650
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 163 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 12.70 12.80 162.6 Yes

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 13.12 12.70 166.6

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 12.70 166.6 NW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 0.150 45.0 0 90 1

Zone 15: 5-513 Service Core (156 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 12.00 Zone width (feet): 13.00
Lighting Watts: 213 Equipment Watts: 155
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/sq.ft Cooling ventilation value: 0.100
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.100
Heating ventilation method: CFM/sq.ft Heating ventilation value: 0.100
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.100
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 19

Zone Input (cont'd)


Zone 15: 5-513 Service Core (156 sq.ft) (Group 1)
Ceil. exposed to plenum (sq.ft): 156 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 19.22 31.13 598.3 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 13.00 170.6 SE

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 0.100 30.0 0 90 1

Zone 16: 4-422/423 Office Space (22967 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 193.00 Zone width (feet): 119.00
Lighting Watts: 31,326 Equipment Watts: 27,900
Number of people in zone: 180 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 2,000 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 22,967 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


4 1 0.355 8.000 18.000 13.12 52.00 682.2
5 1 0.355 8.000 18.000 193.00 119.00 22,967.0

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 89.00 1,167.7 SW
2 1 B 0.063 D 13.12 89.00 1,167.7 NE
3 1 B 0.063 D 13.12 173.00 2,269.8 NW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 3.000 900.0 0 90 1
2 1 0.280 0.440 10.00 30.00 3.000 900.0 0 90 2
3 1 0.280 0.440 10.00 30.00 4.000 1,200.0 0 90 3

Zone 17: 4-407 Com. Room (255.408 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 18.78 Zone width (feet): 13.60
Lighting Watts: 384 Equipment Watts: 3,155
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 20

Zone Input (cont'd)


Zone 17: 4-407 Com. Room (255.408 sq.ft) (Group 2)
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 255 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 13.12 18.78 246.4

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 13.60 178.4 NW

Zone 18: 4-406 Store Room (168.3432 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 12.36 Zone width (feet): 13.62
Lighting Watts: 325 Equipment Watts: 337
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/sq.ft Cooling ventilation value: 0.050
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.050
Heating ventilation method: CFM/sq.ft Heating ventilation value: 0.050
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.050
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 168 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Zone 19: 4-409 Electrical Room (168.3432 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 13.62 Zone width (feet): 12.36
Lighting Watts: 367 Equipment Watts: 200
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 168 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.36 12.36 165.1

Zone 20: 4-413 Service Core E (156 sq.ft) (Group 2)

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 21

Zone Input (cont'd)


Zone 20: 4-413 Service Core E (156 sq.ft) (Group 2)
Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 12.00 Zone width (feet): 13.00
Lighting Watts: 212 Equipment Watts: 312
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/sq.ft Cooling ventilation value: 0.100
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.100
Heating ventilation method: CFM/sq.ft Heating ventilation value: 0.100
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.100
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 156 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 12.00 13.00 156.0
3 1 0.355 8.000 18.000 13.12 13.00 170.6

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 13.00 170.6 NE

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 0.100 30.0 0 90 1

Zone 21: 4-403 Toilet And Wash (510 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 15.00 Zone width (feet): 34.00
Lighting Watts: 695 Equipment Watts: 1,020
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 50.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 50.000
Heating ventilation method: CFM/Pr Heating ventilation value: 50.000
Heating infiltration method: CFM/Pr Heating infiltration value: 50.000
Winter exhaust air CFM: 900 Summer exhaust air CFM: 900
Minimum supply CFM: 800 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 510 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.12 34.00 446.1

Zone 22: 4-422 Office/Hall Way (5126.35 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 163.00 Zone width (feet): 31.45
Lighting Watts: 6,992 Equipment Watts: 10,253
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 22

Zone Input (cont'd)


Zone 22: 4-422 Office/Hall Way (5126.35 sq.ft) (Group 2)
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/sq.ft Cooling ventilation value: 0.100
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.100
Heating ventilation method: CFM/sq.ft Heating ventilation value: 0.100
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.100
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 5,126 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 163.00 31.45 5,126.4

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 31.45 412.6 NE

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 1.000 300.0 0 90 1

Zone 23: 4-400 Floor Lobby (1903.236 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 59.70 Zone width (feet): 31.88
Lighting Watts: 2,596 Equipment Watts: 3,806
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 15.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 15.000
Heating ventilation method: CFM/Pr Heating ventilation value: 15.000
Heating infiltration method: CFM/Pr Heating infiltration value: 15.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 1,903 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 59.70 31.88 1,903.2

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 31.88 418.3 NW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 0.270 81.0 0 90 1

Zone 24: 4-422/424 Office Space (22967 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 193.00 Zone width (feet): 119.00
Lighting Watts: 22,967 Equipment Watts: 27,900
Number of people in zone: 180 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 23

Zone Input (cont'd)


Zone 24: 4-422/424 Office Space (22967 sq.ft) (Group 2)
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 22,967 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


4 1 0.355 8.000 18.000 13.12 63.00 826.6
5 1 0.355 8.000 18.000 193.00 119.00 22,967.0

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 89.00 1,167.7 SW
2 1 B 0.063 D 13.12 89.00 1,167.7 NE
3 1 B 0.063 D 13.12 173.00 2,269.8 SE
6 2 G 0.070 L 7.22 3.28 23.7 SW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 3.000 900.0 0 90 1
2 1 0.280 0.440 10.00 30.00 3.000 900.0 0 90 2
3 1 0.280 0.440 10.00 30.00 4.000 1,200.0 0 90 3

Zone 25: 4-421 Com. Room (255.408 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 18.78 Zone width (feet): 13.60
Lighting Watts: 348 Equipment Watts: 3,155
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 255 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 18.78 13.60 255.4

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 13.60 178.4 SE

Zone 26: 4-420 Store Room (168.3432 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 12.36 Zone width (feet): 13.62

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 24

Zone Input (cont'd)


Zone 26: 4-420 Store Room (168.3432 sq.ft) (Group 2)
Lighting Watts: 229 Equipment Watts: 337
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/sq.ft Cooling ventilation value: 0.050
Cooling infiltration method: CFM/sq.ft Cooling infiltration value: 0.050
Heating ventilation method: CFM/sq.ft Heating ventilation value: 0.050
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.050
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 168 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 12.36 13.62 168.3

Zone 27: 4-419 Electrical Room (168.3432 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 12.36 Zone width (feet): 13.62
Lighting Watts: 367 Equipment Watts: 200
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 168 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 12.36 13.62 168.3

Zone 28: 4-401 Coffee Corner (162.56 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 12.70 Zone width (feet): 12.80
Lighting Watts: 221 Equipment Watts: 1,650
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 163 Exposed floor slab perimeter (sq.ft): 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 25

Zone Input (cont'd)


Zone 28: 4-401 Coffee Corner (162.56 sq.ft) (Group 2)
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.12 12.70 166.6

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


2 1 B 0.063 D 12.80 12.70 162.6 SW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 0.150 45.0 0 90 2

Zone 29: 4th Flr. Service Core E (156 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 12.00 Zone width (feet): 13.00
Lighting Watts: 212 Equipment Watts: 155
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/sq.ft Cooling ventilation value: 0.050
Cooling infiltration method: CFM/Pr Cooling infiltration value: 0.050
Heating ventilation method: CFM/sq.ft Heating ventilation value: 0.050
Heating infiltration method: CFM/sq.ft Heating infiltration value: 0.050
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 156 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 12.00 13.00 156.0
3 1 0.355 8.000 18.000 13.12 13.00 170.6

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 13.00 170.6 SE

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 0.100 30.0 0 90 1

Zone 30: 3-300 Lounge Area (1650 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 50.00 Zone width (feet): 33.00
Lighting Watts: 2,250 Equipment Watts: 3,300
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 2,000 Latent Btuh equipment load: 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 26

Zone Input (cont'd)


Zone 30: 3-300 Lounge Area (1650 sq.ft) (Group 3)
Ceil. exposed to plenum (sq.ft): 1,650 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 50.00 33.00 1,650.0 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 50.00 656.0 NW
2 1 B 0.063 D 13.12 50.00 656.0 SW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 1.000 300.0 0 90 1
2 1 0.280 0.440 10.00 30.00 0.040 12.0 0 90 1
3 1 0.280 0.440 10.00 30.00 1.000 300.0 0 90 2
4 1 0.280 0.440 10.00 30.00 0.040 12.0 0 90 2

Zone 31: 3-304 Toilet & Wash (377.2 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 23.00 Zone width (feet): 16.40
Lighting Watts: 514 Equipment Watts: 754
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 50.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 50.000
Heating ventilation method: CFM/Pr Heating ventilation value: 50.000
Heating infiltration method: CFM/Pr Heating infiltration value: 50.000
Winter exhaust air CFM: 700 Summer exhaust air CFM: 700
Minimum supply CFM: 630 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 377 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.12 15.00 196.8
2 1 0.355 8.000 18.000 13.12 15.00 196.8

Zone 32: 3-301 Floor Lobby (1089 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 33.00 Zone width (feet): 33.00
Lighting Watts: 1,485 Equipment Watts: 2,178
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 15.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 15.000
Heating ventilation method: CFM/Pr Heating ventilation value: 15.000
Heating infiltration method: CFM/Pr Heating infiltration value: 15.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 1,089 Exposed floor slab perimeter (sq.ft): 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 27

Zone Input (cont'd)


Zone 32: 3-301 Floor Lobby (1089 sq.ft) (Group 3)
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.12 33.00 433.0

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


2 1 B 0.063 D 13.12 33.00 433.0 NE

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 3 0.550 0.400 12.00 30.00 1.000 360.0 0 90 2

Zone 33: 3-302 Coffee Corner (162.56 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 12.70 Zone width (feet): 12.80
Lighting Watts: 439 Equipment Watts: 1,650
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 163 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 13.12 12.80 167.9

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 12.70 166.6 SW

Zone 34: 2-100 Lounge Area (1650 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 50.00 Zone width (feet): 33.00
Lighting Watts: 2,250 Equipment Watts: 3,300
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 2,000 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 1,650 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Wall Type ASHRAE# U-Factor Color Height Width Area Direction

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 28

Zone Input (cont'd)


Zone 34: 2-100 Lounge Area (1650 sq.ft) (Group 3)
1 1 B 0.063 D 13.12 50.00 656.0 NW
2 1 B 0.063 D 13.12 50.00 656.0 SW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 1 0.280 0.440 10.00 30.00 1.000 300.0 0 90 1
2 1 0.280 0.440 10.00 30.00 0.040 12.0 0 90 1
3 1 0.280 0.440 10.00 30.00 1.000 300.0 0 90 2
4 1 0.280 0.440 10.00 30.00 0.040 12.0 0 90 2

Zone 35: 2-204 Toilet & Wash (377.2 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 23.00 Zone width (feet): 16.40
Lighting Watts: 514 Equipment Watts: 754
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 50.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 50.000
Heating ventilation method: CFM/Pr Heating ventilation value: 50.000
Heating infiltration method: CFM/Pr Heating infiltration value: 50.000
Winter exhaust air CFM: 700 Summer exhaust air CFM: 700
Minimum supply CFM: 630 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 377 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.12 16.40 215.2
2 1 0.355 8.000 18.000 13.20 16.40 216.5

Zone 36: 2-101 Floor Lobby (1089 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 33.00 Zone width (feet): 33.00
Lighting Watts: 1,485 Equipment Watts: 2,178
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 15.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 15.000
Heating ventilation method: CFM/Pr Heating ventilation value: 15.000
Heating infiltration method: CFM/Pr Heating infiltration value: 15.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 1,089 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 13.12 33.00 433.0

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 2 G 0.070 L 13.12 33.00 433.0 NE

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 29

Zone Input (cont'd)


Zone 36: 2-101 Floor Lobby (1089 sq.ft) (Group 3)
Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 3 0.550 0.400 12.00 30.00 1.000 360.0 0 90 1

Zone 37: 2-102 Coffee Corner (162.56 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 12.70 Zone width (feet): 12.80
Lighting Watts: 439 Equipment Watts: 1,650
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 163 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 13.12 26.00 341.1

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 12.70 166.6 SW

Zone 38: 1-100 Lounge Area (1650 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 50.00 Zone width (feet): 33.00
Lighting Watts: 2,250 Equipment Watts: 3,300
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 2,000 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 1,650 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


3 1 0.355 8.000 18.000 33.00 50.00 1,650.0

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 119.00 1,561.3 NW
2 1 B 0.063 D 13.12 155.00 2,033.6 SW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 30

Zone Input (cont'd)


Zone 38: 1-100 Lounge Area (1650 sq.ft) (Group 3)
1 1 0.280 0.440 10.00 30.00 1.000 300.0 0 90 1
2 1 0.280 0.440 10.00 30.00 0.040 12.0 0 90 1
3 1 0.280 0.440 10.00 30.00 1.000 300.0 0 90 2
4 1 0.280 0.440 10.00 30.00 0.040 12.0 0 90 2

Zone 39: 1-104 Toilet & Wash (377.2 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 23.00 Zone width (feet): 16.40
Lighting Watts: 514 Equipment Watts: 754
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 50.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 50.000
Heating ventilation method: CFM/Pr Heating ventilation value: 50.000
Heating infiltration method: CFM/Pr Heating infiltration value: 50.000
Winter exhaust air CFM: 700 Summer exhaust air CFM: 700
Minimum supply CFM: 630 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 377 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.12 16.40 215.2
2 1 0.355 8.000 18.000 13.12 16.40 215.2

Zone 40: 1-101 Floor Lobby (1089 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 33.00 Zone width (feet): 33.00
Lighting Watts: 1,485 Equipment Watts: 2,178
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 15.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 15.000
Heating ventilation method: CFM/Pr Heating ventilation value: 15.000
Heating infiltration method: CFM/Pr Heating infiltration value: 15.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 1,089 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.12 33.00 433.0

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


2 1 B 0.063 D 13.12 33.00 433.0 NE

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 3 0.550 0.400 12.00 30.00 1.000 360.0 0 90 2

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 31

Zone Input (cont'd)


Zone 41: 1-102 Coffee Corner (162.56 sq.ft) (Group 3)
Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 12.70 Zone width (feet): 12.80
Lighting Watts: 439 Equipment Watts: 1,650
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 163 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 12.70 26.00 330.2

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 12.70 166.6 SW

Zone 42: G-005 Toilet & Wash (377.2 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 23.00 Zone width (feet): 16.40
Lighting Watts: 514 Equipment Watts: 754
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 50.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 50.000
Heating ventilation method: CFM/Pr Heating ventilation value: 50.000
Heating infiltration method: CFM/Pr Heating infiltration value: 50.000
Winter exhaust air CFM: 700 Summer exhaust air CFM: 700
Minimum supply CFM: 630 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 377 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.12 16.40 215.2
2 1 0.355 8.000 18.000 13.12 16.40 215.2

Zone 43: G-002 Ground Floor Lobby (1089 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 33.00 Zone width (feet): 33.00
Lighting Watts: 1,485 Equipment Watts: 2,178
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 32

Zone Input (cont'd)


Zone 43: G-002 Ground Floor Lobby (1089 sq.ft) (Group 3)
Cooling ventilation method: CFM/Pr Cooling ventilation value: 15.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 15.000
Heating ventilation method: CFM/Pr Heating ventilation value: 15.000
Heating infiltration method: CFM/Pr Heating infiltration value: 15.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 1,089 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 13.12 33.00 433.0

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


2 2 G 0.070 L 13.12 33.00 433.0 NW
3 2 G 0.070 L 13.12 33.00 433.0 SE

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 3 0.550 0.400 12.00 30.00 1.000 360.0 0 90 2
2 3 0.550 0.400 12.00 30.00 1.000 360.0 0 90 3

Zone 44: G-003 Coffee Corner (162.56 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 12.70 Zone width (feet): 12.80
Lighting Watts: 221 Equipment Watts: 1,650
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 13 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 163 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 12.70 26.00 330.2

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 13.12 12.70 166.6 SW

Zone 45: G-009 U- Drive Office Room (247.5 sq.ft) (Group 5)


Air Handler number: 5 Zone occurrences: 1
Zone length: (feet) 15.00 Zone width (feet): 16.50
Lighting Watts: 367 Equipment Watts: 1,680
Number of people in zone: 2 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 10 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 33

Zone Input (cont'd)


Zone 45: G-009 U- Drive Office Room (247.5 sq.ft) (Group 5)
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 248 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 15.00 16.50 247.5
2 1 0.355 8.000 18.000 9.51 32.00 304.3

Zone 46: G-010 Com. Room (251.7728 sq.ft) (Group 6)


Air Handler number: 6 Zone occurrences: 1
Zone length: (feet) 19.19 Zone width (feet): 13.12
Lighting Watts: 648 Equipment Watts: 600
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 12 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 252 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


2 1 0.355 8.000 18.000 12.13 24.24 294.0
3 1 0.355 8.000 18.000 19.19 13.12 251.8

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 12.13 19.19 232.8 NW

Zone 47: G-023 Com. Room (176.548 sq.ft) (Group 7)


Air Handler number: 7 Zone occurrences: 1
Zone length: (feet) 19.19 Zone width (feet): 9.20
Lighting Watts: 433 Equipment Watts: 600
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 12 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 177 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 34

Zone Input (cont'd)


Zone 47: G-023 Com. Room (176.548 sq.ft) (Group 7)
Part Type U-Factor Cool TD Heat TD Height Width Area
2 1 0.355 8.000 18.000 12.13 37.59 456.0

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 12.13 19.19 232.8 SW

Zone 48: G-013/020 Elec. Room Typ. (311.0588 sq.ft) (Group 8)


Air Handler number: 8 Zone occurrences: 1
Zone length: (feet) 21.32 Zone width (feet): 14.59
Lighting Watts: 576 Equipment Watts: 200
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 12 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 311 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 14.59 21.32 311.1
2 1 0.355 8.000 18.000 12.13 61.16 741.9

Zone 49: 1-09/114 To 3-309/314 Elec. Room Typ. (311.0588 sq.ft) (Group 9)
Air Handler number: 9 Zone occurrences: 1
Zone length: (feet) 21.32 Zone width (feet): 14.59
Lighting Watts: 576 Equipment Watts: 200
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 12 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 311 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Part Type U-Factor Cool TD Heat TD Height Width Area


1 1 0.355 8.000 18.000 14.59 21.32 311.1
2 1 0.355 8.000 18.000 12.13 61.16 741.9

Zone 50: G-001 Guard House (359.0708 sq.ft) (Group 11)


Air Handler number: 11 Zone occurrences: 1
Zone length: (feet) 20.66 Zone width (feet): 17.38
Lighting Watts: 718 Equipment Watts: 155

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 35

Zone Input (cont'd)


Zone 50: G-001 Guard House (359.0708 sq.ft) (Group 11)
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 9 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: CFM/Pr Cooling ventilation value: 20.000
Cooling infiltration method: CFM/Pr Cooling infiltration value: 20.000
Heating ventilation method: CFM/Pr Heating ventilation value: 20.000
Heating infiltration method: CFM/Pr Heating infiltration value: 20.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 2,000 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 359 Exposed floor slab perimeter (sq.ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 9 0.045 No 20.66 17.38 359.1 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.063 D 8.50 17.38 147.7 NE
2 1 B 0.063 D 8.50 20.66 175.6 SE
3 1 B 0.063 D 8.50 17.38 147.7 SW
4 1 B 0.063 D 8.50 20.66 175.6 NW

Glass Type S.U-F. Shd C. Height Width Quan Area Shade Tilt Ref
1 4 0.720 0.800 3.00 4.00 4.000 48.0 0 90 1
2 4 0.720 0.800 3.00 4.00 5.000 60.0 0 90 2
3 4 0.720 0.800 3.00 4.00 4.000 48.0 0 90 3
4 4 0.720 0.800 3.00 4.00 5.000 60.0 0 90 4

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 36

Building Summary Loads


Building peaks in June at 4pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 58,113 51,779 3.50 0 121,716 121,716 2.33
Wall 15,849 19,810 1.34 0 44,418 44,418 0.85
Glass 16,888 107,983 7.31 0 274,582 274,582 5.26
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 179,572 12.15 0 440,716 440,716 8.43
Lighting 162,741 0 0.00 0 610,826 610,826 11.69
Equipment 193,337 0 0.00 0 725,663 725,663 13.89
People 600 0 0.00 132,000 165,000 297,000 5.68
Partition 68,760 483,314 32.71 0 214,806 214,806 4.11
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 18,747 0 0.00 476,108 865,007 1,341,114 25.67
Heat. Vent. 18,747 363,977 24.64 0 0 0 0.00
Cool. Infil. 16,011 0 0.00 440,583 819,215 1,259,798 24.11
Heat. Infil. 16,019 342,106 23.16 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 24,301 24,301 0.47
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 147,447 147,447 2.82
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 108,457 7.34 0 163,431 163,431 3.13
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 1,477,425 100.00 1,048,691 4,176,412 5,225,102 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 363,977 24.64 476,108 865,007 1,341,114 25.67
Infiltration 342,106 23.16 440,583 819,215 1,259,798 24.11
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 662,886 44.87 132,000 2,304,458 2,436,458 46.63
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 108,457 7.34 0 187,732 187,732 3.59
Building Totals 1,477,425 100.00 1,048,691 4,176,412 5,225,102 100.00

Check Figures
Total Building Supply Air (based on a 20° TD): 152,348 CFM
Total Building Vent. Air (12.31% of Supply): 18,747 CFM
Total Conditioned Air Space: 123,320 Sq.ft
Supply Air Per Unit Area: 1.2354 CFM/Sq.ft
Area Per Cooling Capacity: 283.2165 Sq.ft/Ton
Cooling Capacity Per Area: 0.0035 Tons/Sq.ft
Total Heating Required With Outside Air: 1,477,425 Btuh
Total Cooling Required With Outside Air: 435.43 Tons

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MULTI-STORY PARKING BUILDING (PACKAGE-1)
Hell Page 2
Air Handler #1 - 5th - Floor Area ( A H U 1) - Summary Loads
Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
5-522/523 Office
24,565 55,358 539,564 54,043 8/P 8/P
2 Space
246 2,851 26,049 0 1,965 1,965
5pm June
322,293 0.12 1.06 0 2,149 2,331

3 5-507 Com. Room 255 1,183 13,700 562 8/P 8/P


6pm June 3 61 661 0 20 20
3,351 0.24 2.59 0 46 59

5-506 Storage
168 150 3,316 370 0.06/ft² 0.06/ft²
4 Room
2 8 160 0 10 10
6pm June
2,209 0.05 0.95 0 6 14

5-509 Electrical
168 1,286 6,161 370 8/P 8/P
5 Room
2 66 297 0 13 13
6pm June
2,209 0.39 1.77 0 50 27

6 5-513 Service Core 156 1,883 10,134 220 0.06/ft² 0.06/ft²


9am June 1 97 489 0 9 9
2,047 0.62 3.14 0 73 44

5-503 Toilet And


510 4,202 8,545 1,122 Direct Direct
7 Wash
5 216 413 0 920 920
6pm June
6,691 0.42 0.81 0 163 37

5-522 Office/Hall
5,624 12,909 111,441 12,373 8/P 8/P
8 Way
56 665 5,380 0 450 450
9am June
73,787 0.12 0.96 0 501 481

9 5-525 Store Room 120 388 2,339 264 0.06/ft² 0.06/ft²


6pm June 1 20 113 0 7 7
1,576 0.17 0.94 0 15 10

5-500 Floor
Lobby/Coffee 1,165 4,802 33,551 1,320 8/P 8/P
10 Corner 6 247 1,620 0 48 48
5pm August 15,285 0.21 1.39 0 186 145

5-522/524 Office
25,112 56,838 533,730 55,246 8/P 8/P
11 Space
251 2,928 25,767 0 2,009 2,009
4pm August
329,469 0.12 1.03 0 2,206 2,306

M:\ ...\Multi-Story ... 25-10-10.CHV Monday, December 20, 2010, 01:53 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MULTI-STORY PARKING BUILDING (PACKAGE-1)
Hell Page 3
Air Handler #1 - 5th - Floor Area ( A H U 1) - Summary Loads (cont'd)
Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM

12 5-521 Com. Room 255 1,160 13,702 562 8/P 8/P


6pm August 3 60 661 0 20 20
3,351 0.23 2.59 0 45 59

5-520 Storage
168 704 3,870 370 0.06/ft² 0.06/ft²
13 Room
2 36 187 0 10 10
6pm June
2,209 0.22 1.11 0 27 17

5-500 Electrical
168 691 5,566 370 8/P 8/P
14 Room
2 36 269 0 13 13
6pm June
2,209 0.21 1.60 0 27 24

15 5-501 Kitchen 66 996 1,867 0 Direct Direct


6pm June 0 51 90 0 100 100
866 0.78 1.37 0 39 8

16 5-515 Service Core 156 1,883 10,134 220 0.06/ft² 0.06/ft²


9am June 1 97 489 0 9 9
2,047 0.62 3.14 0 73 44
Zone Peak Totals: 58,658 144,432 1,297,617 127,414
Total Zones: 15 579 7,439 62,647 0 5,606 5,606
Unique Zones: 15 769,597 0.13 1.07 0 5,606 5,606

M:\ ...\Multi-Story ... 25-10-10.CHV Monday, December 20, 2010, 01:53 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MULTI-STORY PARKING BUILDING (PACKAGE-1)
Hell Page 4
Air Handler #1 - 5th - Floor Area ( A H U 1) - Total Load Summary
Air Handler Description: 5th - Floor Area ( A H U 1) Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 3.94 HP
Fan Input: 75% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 116° DB, 81° WB, 104.07 grains, Htg: 57° DB
Indoor Conditions: Clg: 75° DB, 50% RH, Htg: 75° DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 144,432 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 108,839 Btuh 5,606 CFM
Supply Duct sensible loss: 16,048 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 269,319 Btuh
Heating Supply Air: 160,479 / (.999 X 1.08 X 20) = 7,439 CFM
Winter Vent Outside Air (75.4% of supply) = 5,606 CFM
Zone space sensible gain: 1,253,75
Btuh
7
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 9,993 Btuh
Supply duct sensible gain: 68,821 Btuh
Reserve sensible gain: 43,854 Btuh
Total sensible gain on supply side of coil: 1,376,425 Btuh
Cooling Supply Air: 1,376,425 / (.999 X 1.1 X 20) = 62,646 CFM
Summer Vent Outside Air (8.9% of supply) = 5,606 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 252,502 Btuh 5,606 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 252,502 Btuh
Total sensible gain on air handling system: 1,628,927 Btuh
Zone space latent gain: 101,931 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 148,542 Btuh
Total latent gain on air handling system: 250,473 Btuh
Total system sensible and latent gain: 1,879,400 Btuh
Check Figures
Total Air Handler Supply Air (based on a 20° TD): 62,646 CFM
Total Air Handler Vent. Air (8.95% of Supply): 5,606 CFM
Total Conditioned Air Space: 58,658 Sq.ft
Supply Air Per Unit Area: 1.0680 CFM/Sq.ft
Area Per Cooling Capacity: 374.5 Sq.ft/Ton

M:\ ...\Multi-Story ... 25-10-10.CHV Monday, December 20, 2010, 01:53 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MULTI-STORY PARKING BUILDING (PACKAGE-1)
Hell Page 5
Air Handler #1 - 5th - Floor Area ( A H U 1) - Total Load Summary (cont'd)
Check Figures
Cooling Capacity Per Area: 0.0027 Tons/Sq.ft
Heating Capacity Per Area: 4.59 Btuh/Sq.ft
Total Heating Required With Outside Air: 269,319 Btuh
Total Cooling Required With Outside Air: 156.62 Tons

M:\ ...\Multi-Story ... 25-10-10.CHV Monday, December 20, 2010, 01:53 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MULTI-STORY PARKING BUILDING (PACKAGE-1)
Hell Page 6
Air Handler #2 - 4th - Floor Area ( A H U ) - Summary Loads
Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
4-422/423 Office
24,565 58,203 498,373 54,043 8/P 8/P
17 Space
246 2,998 24,061 0 1,965 1,965
5pm June
322,293 0.12 0.98 0 2,276 2,319

18 4-407 Com. Room 255 1,300 13,407 562 8/P 8/P


7am June 3 67 647 0 20 20
3,351 0.26 2.53 0 51 62

19 4-406 Store Room 168 45 2,969 370 0.06/ft² 0.06/ft²


6pm June 2 2 143 0 10 10
2,209 0.01 0.85 0 2 14

4-409 Electrical
168 545 5,200 370 8/P 8/P
20 Room
2 28 251 0 13 13
6pm June
2,209 0.17 1.49 0 21 24

21 4-413 Service Core 156 1,883 10,134 220 0.06/ft² 0.06/ft²


9am June 1 97 489 0 9 9
2,047 0.62 3.14 0 74 47

4-403 Toilet And


510 4,233 8,115 1,122 Direct Direct
22 Wash
5 218 392 0 920 920
6pm June
6,691 0.43 0.77 0 166 38

4-422 Office/Hall
5,624 7,898 101,610 12,373 8/P 8/P
23 Way
56 407 4,906 0 450 450
9am June
73,787 0.07 0.87 0 309 473

24 4-425 Store Room 120 402 2,137 264 0.06/ft² 0.06/ft²


6pm June 1 21 103 0 7 7
1,576 0.17 0.86 0 16 10

4-400 Floor
Lobby/Coffee 1,165 3,764 31,071 1,320 8/P 8/P
25 Corner 6 194 1,500 0 48 48
5pm August 15,285 0.17 1.29 0 147 145

4-422/424 Office
25,112 60,298 498,278 55,246 8/P 8/P
26 Space
251 3,106 24,056 0 2,009 2,009
3pm August
329,469 0.12 0.96 0 2,358 2,319

M:\ ...\Multi-Story ... 25-10-10.CHV Monday, December 20, 2010, 01:53 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MULTI-STORY PARKING BUILDING (PACKAGE-1)
Hell Page 7
Air Handler #2 - 4th - Floor Area ( A H U ) - Summary Loads (cont'd)
Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
27 4-421 Com. Room 255 1,191 13,275 562 8/P 8/P
6pm August 3 61 641 0 20 20
3,351 0.24 2.51 0 47 62

4-420 Storage
168 170 3,031 370 0.06/ft² 0.06/ft²
28 Room
2 9 146 0 10 10
6pm June
2,209 0.05 0.87 0 7 14

4-419 Electrical
168 541 5,197 370 8/P 8/P
29 Room
2 28 251 0 13 13
6pm June
2,209 0.17 1.49 0 21 24

30 4-401 Kitchen 66 996 1,867 0 Direct Direct


6pm June 0 51 90 0 100 100
866 0.78 1.37 0 39 9

31 4-415 Service Core 156 1,881 10,130 220 0.06/ft² 0.06/ft²


9am June 1 97 489 0 9 9
2,047 0.62 3.14 0 74 47
Zone Peak Totals: 58,658 143,349 1,204,793 127,414
Total Zones: 15 579 7,384 58,165 0 5,606 5,606
Unique Zones: 15 769,597 0.13 0.99 0 5,606 5,606

M:\ ...\Multi-Story ... 25-10-10.CHV Monday, December 20, 2010, 01:53 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MULTI-STORY PARKING BUILDING (PACKAGE-1)
Hell Page 8
Air Handler #2 - 4th - Floor Area ( A H U ) - Total Load Summary
Air Handler Description: 4th - Floor Area ( A H U ) Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 3.66 HP
Fan Input: 75% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.93 --- This system occurs 2 time(s) in the building. ---
Air System Peak Time: 4pm in August.
Outdoor Conditions: Clg: 117° DB, 81° WB, 101.57 grains, Htg: 57° DB
Indoor Conditions: Clg: 75° DB, 50% RH, Htg: 75° DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 143,349 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 108,839 Btuh 5,606 CFM
Supply Duct sensible loss: 15,928 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 268,116 Btuh
Heating Supply Air: 159,276 / (.999 X 1.08 X 20) = 7,384 CFM
Winter Vent Outside Air (75.9% of supply) = 5,606 CFM
Zone space sensible gain: 1,158,54
Btuh
8
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 9,278 Btuh
Supply duct sensible gain: 63,898 Btuh
Reserve sensible gain: 46,238 Btuh
Total sensible gain on supply side of coil: 1,277,962 Btuh
Cooling Supply Air: 1,277,962 / (.999 X 1.1 X 20) = 58,165 CFM
Summer Vent Outside Air (9.6% of supply) = 5,606 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 258,661 Btuh 5,606 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 258,661 Btuh
Total sensible gain on air handling system: 1,536,623 Btuh
Zone space latent gain: 101,931 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 142,369 Btuh
Total latent gain on air handling system: 244,300 Btuh
Total system sensible and latent gain: 1,780,924 Btuh
Check Figures
Total Air Handler Supply Air (based on a 20° TD): 58,165 CFM
Total Air Handler Vent. Air (9.64% of Supply): 5,606 CFM
Total Conditioned Air Space: 58,658 Sq.ft
Supply Air Per Unit Area: 0.9916 CFM/Sq.ft
Area Per Cooling Capacity: 395.2 Sq.ft/Ton

M:\ ...\Multi-Story ... 25-10-10.CHV Monday, December 20, 2010, 01:53 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr MULTI-STORY PARKING BUILDING (PACKAGE-1)
Hell Page 9
Air Handler #2 - 4th - Floor Area ( A H U ) - Total Load Summary (cont'd)
Check Figures
Cooling Capacity Per Area: 0.0025 Tons/Sq.ft
Heating Capacity Per Area: 4.57 Btuh/Sq.ft
Total Heating Required With Outside Air: 268,116 Btuh
Total Cooling Required With Outside Air: 148.41 Tons

M:\ ...\Multi-Story ... 25-10-10.CHV Monday, December 20, 2010, 01:53 PM


CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 43

Air Handler #3 Summary Loads


Zn Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
Description
No People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Peak Time
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1,650 5,788 33,585 0 20/P 20/P
3-300 Lounge Area
30 0 298 2,000 0 0 0
4pm June
21,648 0.18 1.21 0 187 287

377 2,767 5,990 0 50/P 50/P


3-304 Toilet & Wash
31 0 143 630 700 0 0
6pm June
4,949 0.38 1.67 700 89 90

1,089 7,625 38,642 0 15/P 15/P


3-301 Floor Lobby
32 0 393 1,970 0 0 0
9am June
14,288 0.36 1.81 0 247 283

163 1,815 10,110 754 20/P 20/P


3-302 Coffee Corner
33 1 94 515 0 20 20
3pm August
2,133 0.58 3.17 0 59 74

1,650 4,318 30,129 0 20/P 20/P


2-100 Lounge Area
34 0 222 2,000 0 0 0
4pm June
21,648 0.13 1.21 0 140 287

377 3,034 6,109 0 50/P 50/P


2-204 Toilet & Wash
35 0 156 630 700 0 0
6pm June
4,949 0.41 1.67 700 98 90

1,089 7,635 38,733 0 15/P 15/P


2-101 Floor Lobby
36 0 393 1,975 0 0 0
9am June
14,288 0.36 1.81 0 247 283

163 3,033 10,651 754 20/P 20/P


2-102 Coffee Corner
37 1 156 543 0 20 20
3pm August
2,133 0.96 3.34 0 98 78

1,650 18,763 41,687 0 20/P 20/P


1-100 Lounge Area
38 0 966 2,125 0 0 0
6pm August
21,648 0.59 1.29 0 607 305

377 3,025 6,105 0 50/P 50/P


1-104 Toilet & Wash
39 0 156 630 700 0 0
6pm June
4,949 0.41 1.67 700 98 90

1,089 7,625 38,642 0 15/P 15/P


1-101 Floor Lobby
40 0 393 1,970 0 0 0
9am June
14,288 0.36 1.81 0 247 283

163 2,956 10,617 754 20/P 20/P


1-102 Coffee Corner
41 1 152 541 0 20 20
3pm August
2,133 0.94 3.33 0 96 78

377 3,025 6,105 0 50/P 50/P


G-005 Toilet & Wash
42 0 156 630 700 0 0
6pm June
4,949 0.41 1.67 700 98 90

G-002 Ground Floor 1,089 12,227 55,965 0 15/P 15/P


43 Lobby 0 630 2,853 0 0 0
5pm June 14,288 0.58 2.62 0 395 409

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 44

Air Handler #3 Summary Loads (cont'd)


Zn Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
Description
No People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Peak Time
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
163 2,956 9,798 754 20/P 20/P
G-003 Coffee Corner
44 1 152 500 0 20 20
3pm August
2,133 0.94 3.07 0 96 72
Zone Peak Totals: 11,465 86,591 342,869 3,017
Total Zones: 15 4 4,460 19,512 2,800 80 80
Unique Zones: 15 150,421 0.39 1.70 2,800 2,800 2,800

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 45

Air Handler #3 Total Load Summary


Air Handler Description: Ground & 1st-3rd Floor Area ( P A C U ) Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 1.23 HP
Fan Input: 75% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in June.
Outdoor Conditions: 117° DB, 81° WB, 101.57 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in June at 9am is different from
the total system peak time, hence the air system CFM was computed using a zone sensible load of 319,898.
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 84,882 Btuh
Infiltration sensible loss: 1,708 Btuh 80 CFM
Outside Air sensible loss: 54,361 Btuh 2,800 CFM
Supply Duct sensible loss: 9,621 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 150,573 Btuh
Heating Supply Air: 96,212 / (.999 X 1.08 X 20) = 4,460 CFM
Winter Vent Outside Air (62.8% of supply) = 2,800 CFM
Zone space sensible gain: 312,460 Btuh
Infiltration sensible gain: 4,093 Btuh
Draw-thru fan sensible gain: 3,112 Btuh
Supply duct sensible gain: 21,435 Btuh
Reserve sensible gain: 62,829 Btuh
Total sensible gain on supply side of coil: 403,931 Btuh
Cooling Supply Air: 407,275 / (.999 X 1.1 X 19) = 19,512 CFM
Summer Vent Outside Air (14.4% of supply) = 2,800 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 129,192 Btuh 2,800 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 129,192 Btuh
Total sensible gain on air handling system: 533,123 Btuh
Zone space latent gain: 704 Btuh
Infiltration latent gain: 2,201 Btuh
Outside air latent gain: 71,108 Btuh
Total latent gain on air handling system: 74,014 Btuh
Total system sensible and latent gain: 607,136 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 19,512 CFM
Total Air Handler Vent. Air (14.35% of Supply): 2,800 CFM
Total Conditioned Air Space: 11,465 Sq.ft
Supply Air Per Unit Area: 1.7019 CFM/Sq.ft
Area Per Cooling Capacity: 226.6056 Sq.ft/Ton
Cooling Capacity Per Area: 0.0044 Tons/Sq.ft
Total Heating Required With Outside Air: 150,573 Btuh
Total Cooling Required With Outside Air: 50.59 Tons

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 46

Air Handler #5 Summary Loads


Zn Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
Description
No People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Peak Time
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
G-009 U- Drive Office 248 4,733 12,036 1,509 20/P 20/P
45 Room 2 244 581 0 40 40
3pm June 2,354 0.98 2.35 0 40 40
Zone Peak Totals: 248 4,733 12,036 1,509
Total Zones: 1 2 244 581 0 40 40
Unique Zones: 1 2,354 0.98 2.35 0 40 40

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 47

Air Handler #5 Total Load Summary


Air Handler Description: G-009 U- Drive Rm. Mini Split Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.04 HP
Fan Input: 75% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.89 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 1pm in June.
Outdoor Conditions: 116° DB, 81° WB, 104.42 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in June at 3pm is different from
the total system peak time, hence the air system CFM was computed using a zone sensible load of 11,926.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 3,879 Btuh
Infiltration sensible loss: 854 Btuh 40 CFM
Outside Air sensible loss: 777 Btuh 40 CFM
Supply Duct sensible loss: 526 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 6,035 Btuh
Heating Supply Air: 5,259 / (.999 X 1.08 X 20) = 244 CFM
Winter Vent Outside Air (16.4% of supply) = 40 CFM
Zone space sensible gain: 9,847 Btuh
Infiltration sensible gain: 1,962 Btuh
Draw-thru fan sensible gain: 93 Btuh
Supply duct sensible gain: 638 Btuh
Reserve sensible gain: 101 Btuh
Total sensible gain on supply side of coil: 12,640 Btuh
Cooling Supply Air: 12,757 / (.999 X 1.1 X 20) = 581 CFM
Summer Vent Outside Air (6.9% of supply) = 40 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,802 Btuh 40 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 1,802 Btuh
Total sensible gain on air handling system: 14,441 Btuh
Zone space latent gain: 352 Btuh
Infiltration latent gain: 1,186 Btuh
Outside air latent gain: 1,060 Btuh
Total latent gain on air handling system: 2,598 Btuh
Total system sensible and latent gain: 17,039 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20° TD): 581 CFM
Total Air Handler Vent. Air (6.89% of Supply): 40 CFM
Total Conditioned Air Space: 248 Sq.ft
Supply Air Per Unit Area: 2.3458 CFM/Sq.ft
Area Per Cooling Capacity: 174.3035 Sq.ft/Ton
Cooling Capacity Per Area: 0.0057 Tons/Sq.ft
Total Heating Required With Outside Air: 6,035 Btuh
Total Cooling Required With Outside Air: 1.42 Tons

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 48

Air Handler #6 Summary Loads


Zn Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
Description
No People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Peak Time
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
252 4,127 7,121 0 20/P 20/P
G-010 Com. Room
46 0 191 344 0 0 0
7am June
3,054 0.76 1.37 0 0 0
Zone Peak Totals: 252 4,127 7,121 0
Total Zones: 1 0 191 344 0 0 0
Unique Zones: 1 3,054 0.76 1.37 0 0 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 49

Air Handler #6 Total Load Summary


Air Handler Description: G-010 Com. Rm. Mini Split (typical) Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 HP
Fan Input: 75% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 1.00 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 7am in June.
Outdoor Conditions: 98° DB, 76° WB, 101.75 grains
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 4,127 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 4,127 Btuh
Heating Supply Air: 4,127 / (.999 X 1.08 X 20) = 191 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 7,121 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 55 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 7,176 Btuh
Cooling Supply Air: 7,176 / (.999 X 1.1 X 19) = 344 CFM
Summer Vent Outside Air (0.0% of supply) = 0 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 0 Btuh 0 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 0 Btuh
Total sensible gain on air handling system: 7,176 Btuh
Zone space latent gain: 0 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 0 Btuh
Total latent gain on air handling system: 0 Btuh
Total system sensible and latent gain: 7,176 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 344 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 252 Sq.ft
Supply Air Per Unit Area: 1.3654 CFM/Sq.ft
Area Per Cooling Capacity: 421.0204 Sq.ft/Ton
Cooling Capacity Per Area: 0.0024 Tons/Sq.ft
Total Heating Required With Outside Air: 4,127 Btuh
Total Cooling Required With Outside Air: 0.60 Tons

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 50

Air Handler #7 Summary Loads


Zn Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
Description
No People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Peak Time
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
177 3,495 5,999 0 20/P 20/P
G-023 Com. Room
47 0 162 290 0 0 0
6pm August
2,142 0.92 1.64 0 0 0
Zone Peak Totals: 177 3,495 5,999 0
Total Zones: 1 0 162 290 0 0 0
Unique Zones: 1 2,142 0.92 1.64 0 0 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 51

Air Handler #7 Total Load Summary


Air Handler Description: G-023 Com. Rm. Mini Split (typical) Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 HP
Fan Input: 75% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 1.00 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in August.
Outdoor Conditions: 113° DB, 80° WB, 100.42 grains
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 3,495 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 3,495 Btuh
Heating Supply Air: 3,495 / (.999 X 1.08 X 20) = 162 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 5,999 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 46 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 6,046 Btuh
Cooling Supply Air: 6,046 / (.999 X 1.1 X 19) = 290 CFM
Summer Vent Outside Air (0.0% of supply) = 0 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 0 Btuh 0 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 0 Btuh
Total sensible gain on air handling system: 6,046 Btuh
Zone space latent gain: 0 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 0 Btuh
Total latent gain on air handling system: 0 Btuh
Total system sensible and latent gain: 6,046 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 290 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 177 Sq.ft
Supply Air Per Unit Area: 1.6405 CFM/Sq.ft
Area Per Cooling Capacity: 350.4367 Sq.ft/Ton
Cooling Capacity Per Area: 0.0029 Tons/Sq.ft
Total Heating Required With Outside Air: 3,495 Btuh
Total Cooling Required With Outside Air: 0.50 Tons

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 52

Air Handler #8 Summary Loads


Zn Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
Description
No People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Peak Time
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
G-013/020 Elec. 311 7,401 6,202 0 20/P 20/P
48 Room Typ. 0 343 299 0 0 0
6pm June 3,773 1.10 0.96 0 0 0
Zone Peak Totals: 311 7,401 6,202 0
Total Zones: 1 0 343 299 0 0 0
Unique Zones: 1 3,773 1.10 0.96 0 0 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 53

Air Handler #8 Total Load Summary


Air Handler Description: G-013/020 Electrical Room Mini Split Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 HP
Fan Input: 75% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 1.00 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in June.
Outdoor Conditions: 113° DB, 80° WB, 100.42 grains
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 7,401 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 7,401 Btuh
Heating Supply Air: 7,401 / (.999 X 1.08 X 20) = 343 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 6,202 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 48 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 6,250 Btuh
Cooling Supply Air: 6,250 / (.999 X 1.1 X 19) = 299 CFM
Summer Vent Outside Air (0.0% of supply) = 0 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 0 Btuh 0 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 0 Btuh
Total sensible gain on air handling system: 6,250 Btuh
Zone space latent gain: 0 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 0 Btuh
Total latent gain on air handling system: 0 Btuh
Total system sensible and latent gain: 6,250 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 299 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 311 Sq.ft
Supply Air Per Unit Area: 0.9625 CFM/Sq.ft
Area Per Cooling Capacity: 597.2602 Sq.ft/Ton
Cooling Capacity Per Area: 0.0017 Tons/Sq.ft
Total Heating Required With Outside Air: 7,401 Btuh
Total Cooling Required With Outside Air: 0.52 Tons

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 54

Air Handler #9 Summary Loads


Zn Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
Description
No People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Peak Time
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1-09/114 To 3-
311 7,401 6,202 0 20/P 20/P
309/314 Elec. Room
0 343 299 0 0 0
49 Typ.
3,773 1.10 0.96 0 0 0
6pm June
Zone Peak Totals: 311 7,401 6,202 0
Total Zones: 1 0 343 299 0 0 0
Unique Zones: 1 3,773 1.10 0.96 0 0 0

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 55

Air Handler #9 Total Load Summary


Air Handler Description: 1-109/114 To 3-309/314 Elec. Rm. Split Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 HP
Fan Input: 75% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 1.00 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 6pm in June.
Outdoor Conditions: 113° DB, 80° WB, 100.42 grains
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 7,401 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 7,401 Btuh
Heating Supply Air: 7,401 / (.999 X 1.08 X 20) = 343 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 6,202 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 48 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 6,250 Btuh
Cooling Supply Air: 6,250 / (.999 X 1.1 X 19) = 299 CFM
Summer Vent Outside Air (0.0% of supply) = 0 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 0 Btuh 0 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 0 Btuh
Total sensible gain on air handling system: 6,250 Btuh
Zone space latent gain: 0 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 0 Btuh
Total latent gain on air handling system: 0 Btuh
Total system sensible and latent gain: 6,250 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19° TD): 299 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 311 Sq.ft
Supply Air Per Unit Area: 0.9625 CFM/Sq.ft
Area Per Cooling Capacity: 597.2602 Sq.ft/Ton
Cooling Capacity Per Area: 0.0017 Tons/Sq.ft
Total Heating Required With Outside Air: 7,401 Btuh
Total Cooling Required With Outside Air: 0.52 Tons

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 56

Air Handler #10 Summary Loads


Zn Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
Description
No People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Peak Time
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
194 2,091 7,593 1,541 20/P 20/P
R-601 Utility Room
1 2 97 348 0 40 40
4pm June
2,541 0.50 1.80 0 40 40
Zone Peak Totals: 194 2,091 7,593 1,541
Total Zones: 1 2 97 348 0 40 40
Unique Zones: 1 2,541 0.50 1.80 0 40 40

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 57

Air Handler #10 Total Load Summary


Air Handler Description: R-601 Utility Room Mini Split Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 HP
Fan Input: 75% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.83 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in June.
Outdoor Conditions: 116° DB, 81° WB, 104.07 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in June at 4pm is different from
the total system peak time, hence the air system CFM was computed using a zone sensible load of 7,483.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 1,236 Btuh
Infiltration sensible loss: 854 Btuh 40 CFM
Outside Air sensible loss: 777 Btuh 40 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 2,867 Btuh
Heating Supply Air: 2,091 / (.999 X 1.08 X 20) = 97 CFM
Winter Vent Outside Air (41.3% of supply) = 40 CFM
Zone space sensible gain: 5,485 Btuh
Infiltration sensible gain: 1,972 Btuh
Draw-thru fan sensible gain: 55 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 98 Btuh
Total sensible gain on supply side of coil: 7,611 Btuh
Cooling Supply Air: 7,637 / (.999 X 1.1 X 20) = 348 CFM
Summer Vent Outside Air (11.5% of supply) = 40 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 1,802 Btuh 40 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 1,802 Btuh
Total sensible gain on air handling system: 9,412 Btuh
Zone space latent gain: 352 Btuh
Infiltration latent gain: 1,175 Btuh
Outside air latent gain: 1,060 Btuh
Total latent gain on air handling system: 2,587 Btuh
Total system sensible and latent gain: 11,999 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20° TD): 348 CFM
Total Air Handler Vent. Air (11.51% of Supply): 40 CFM
Total Conditioned Air Space: 194 Sq.ft
Supply Air Per Unit Area: 1.7947 CFM/Sq.ft
Area Per Cooling Capacity: 193.6597 Sq.ft/Ton
Cooling Capacity Per Area: 0.0052 Tons/Sq.ft
Total Heating Required With Outside Air: 2,867 Btuh
Total Cooling Required With Outside Air: 1.00 Tons

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 58

Air Handler #11 Summary Loads


Zn Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
Description
No People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Peak Time
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
359 4,364 17,880 770 20/P 20/P
G-001 Guard House
50 1 202 2,000 0 20 20
4pm August
3,052 0.56 5.57 0 20 20
Zone Peak Totals: 359 4,364 17,880 770
Total Zones: 1 1 202 2,000 0 20 20
Unique Zones: 1 3,052 0.56 5.57 0 20 20

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 59

Air Handler #11 Total Load Summary


Air Handler Description: G-001 Guard House Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.13 HP
Fan Input: 75% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.98 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in August.
Outdoor Conditions: 117° DB, 81° WB, 101.57 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 3,936 Btuh
Infiltration sensible loss: 427 Btuh 20 CFM
Outside Air sensible loss: 388 Btuh 20 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 4,752 Btuh
Heating Supply Air: 4,364 / (.999 X 1.08 X 20) = 202 CFM
Winter Vent Outside Air (9.9% of supply) = 20 CFM
Zone space sensible gain: 16,802 Btuh
Infiltration sensible gain: 1,023 Btuh
Draw-thru fan sensible gain: 319 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 25,821 Btuh
Total sensible gain on supply side of coil: 43,965 Btuh
Cooling Supply Air: 43,965 / (.999 X 1.1 X 20) = 2,001 CFM
Summer Vent Outside Air (1.0% of supply) = 20 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 923 Btuh 20 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 923 Btuh
Total sensible gain on air handling system: 44,888 Btuh
Zone space latent gain: 176 Btuh
Infiltration latent gain: 550 Btuh
Outside air latent gain: 508 Btuh
Total latent gain on air handling system: 1,234 Btuh
Total system sensible and latent gain: 46,122 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20° TD): 2,001 CFM
Total Air Handler Vent. Air (1.00% of Supply): 20 CFM
Total Conditioned Air Space: 359 Sq.ft
Supply Air Per Unit Area: 5.5727 CFM/Sq.ft
Area Per Cooling Capacity: 93.4225 Sq.ft/Ton
Cooling Capacity Per Area: 0.0107 Tons/Sq.ft
Total Heating Required With Outside Air: 4,752 Btuh
Total Cooling Required With Outside Air: 3.84 Tons

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 60

Air System #1 (5th - Floor Area ( A H U ) ) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 57.767 55.000
Draw-Thru Fan 10,251 0.145 467
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 70,601 1.000 3,213
Zone Loads 303,705 6.959 1,301,699 18.437 59,245
Sensible Reserve 29,474 0.417 1,341
Zone Condition 303,705 64.726 1,412,025 75.000 64,267
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 8,075 CFM 213,952 4.902 363,691 5.151
Blow-Thru Fan 0 0.000
Entering Coil Condition 517,657 69.628 1,775,716 80.151 64,267

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 64,267 x( 80.151 - 55.000 ) = 1,775,716 Btuh


TLH = 0.999 x 0.68 x 64,267 x( 69.628 - 57.767 )= 517,652 Btuh
----------
SUM = 2,293,368 Btuh
GTH = 0.999 x 4.50 x 64,267 x( 30.146 - 22.159 ) = 2,306,790 Btuh
Total System Load = 2,276,034 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 2,306,790 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 466,158 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 466,158 / 970 = 480.6 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 80.15 Dry bulb temperature: 64.87
Wet bulb temperature: 65.31
Relative humidity: 45.32
Enthalpy: 30.15 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 95.00
Wet bulb temperature: 53.30
Relative humidity: 89.78
Enthalpy: 22.16 Btu/lbm

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 61

Air System #2 (4th - Floor Area ( A H U )) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 58.387 55.000
Draw-Thru Fan 10,274 0.145 468
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 70,757 1.000 3,220
Zone Loads 277,385 6.342 1,304,977 18.443 59,394
Sensible Reserve 29,124 0.412 1,326
Zone Condition 277,385 64.728 1,415,131 75.000 64,408
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 7,773 CFM 197,399 4.513 358,640 5.069
Blow-Thru Fan 0 0.000
Entering Coil Condition 474,784 69.241 1,773,771 80.069 64,408

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 64,408 x( 80.069 - 55.000 ) = 1,773,771 Btuh


TLH = 0.999 x 0.68 x 64,408 x( 69.241 - 58.387 )= 474,767 Btuh
----------
SUM = 2,248,538 Btuh
GTH = 0.999 x 4.50 x 64,408 x( 30.065 - 22.255 ) = 2,260,653 Btuh
Total System Load = 2,242,659 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 2,260,653 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 824,616 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 824,616 / 970 = 850.1 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 80.07 Dry bulb temperature: 70.52
Wet bulb temperature: 65.20
Relative humidity: 45.20
Enthalpy: 30.07 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 95.00
Wet bulb temperature: 53.46
Relative humidity: 90.73
Enthalpy: 22.26 Btu/lbm

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 62

Air System #3 (Ground & 1st-3rd Floor Area ( P A C U )) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 64.506 56.000
Draw-Thru Fan 3,112 0.145 149
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 21,435 1.000 1,027
Zone Loads 2,905 0.219 319,898 14.924 15,326
Sensible Reserve 62,829 2.931 3,010
Zone Condition 2,905 64.725 407,275 75.000 19,512
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 2,800 CFM 71,108 5.366 129,192 6.027
Blow-Thru Fan 0 0.000
Entering Coil Condition 74,014 70.091 536,467 81.027 19,512

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 19,512 x( 81.027 - 56.000 )= 536,466 Btuh


TLH = 0.999 x 0.68 x 19,512 x( 70.091 - 64.506 )= 74,014 Btuh
----------
SUM = 610,480 Btuh
GTH = 0.999 x 4.50 x 19,512 x( 30.433 - 23.448 )= 612,462 Btuh
Total System Load = 607,136 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 612,462 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 150,573 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 150,573 / 970 = 155.2 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 81.03 Dry bulb temperature: 63.70
Wet bulb temperature: 65.68
Relative humidity: 44.33
Enthalpy: 30.43 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 56.00 Dry bulb temperature: 95.00
Wet bulb temperature: 55.42
Relative humidity: 96.53
Enthalpy: 23.45 Btu/lbm

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 63

Air System #5 (G-009 U- Drive Rm. Mini Split) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 60.826 55.000
Draw-Thru Fan 93 0.145 4
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 638 1.000 29
Zone Loads 1,538 3.901 11,926 18.697 543
Sensible Reserve 101 0.158 5
Zone Condition 1,538 64.727 12,757 75.000 581
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 40 CFM 1,060 2.688 1,802 2.825
Blow-Thru Fan 0 0.000
Entering Coil Condition 2,598 67.415 14,558 77.825 581

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 581 x( 77.825 - 55.000 )= 14,558 Btuh


TLH = 0.999 x 0.68 x 581 x( 67.415 - 60.826 )= 2,598 Btuh
----------
SUM = 17,156 Btuh
GTH = 0.999 x 4.50 x 581 x( 29.231 - 22.633 )= 17,214 Btuh
Total System Load = 17,039 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 17,214 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 6,035 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 6,035 / 970 = 6.2 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 77.82 Dry bulb temperature: 72.05
Wet bulb temperature: 64.08
Relative humidity: 47.38
Enthalpy: 29.23 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 95.00
Wet bulb temperature: 54.08
Relative humidity: 94.47
Enthalpy: 22.63 Btu/lbm

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 64

Air System #6 (G-010 Com. Rm. Mini Split (typical)) Psychrometric Analysis
System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 64.725 56.000
Draw-Thru Fan 55 0.145 3
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 0 0.000 7,121 18.856 341
Sensible Reserve 0 0.000 0
Zone Condition 0 64.725 7,176 75.000 344
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 0 CFM 0 0.000 0 0.000
Blow-Thru Fan 0 0.000
Entering Coil Condition 0 64.725 7,176 75.000 344

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 344 x( 75.000 - 56.000 )= 7,176 Btuh


TLH = 0.999 x 0.68 x 344 x( 64.725 - 64.725 )= 0 Btuh
----------
SUM = 7,176 Btuh
GTH = 0.999 x 4.50 x 344 x( 28.120 - 23.482 )= 7,166 Btuh
Total System Load = 7,176 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 7,166 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 4,127 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 4,127 / 970 = 4.3 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 75.00 Dry bulb temperature: 75.00
Wet bulb temperature: 62.54
Relative humidity: 50.00
Enthalpy: 28.12 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 56.00 Dry bulb temperature: 95.00
Wet bulb temperature: 55.47
Relative humidity: 96.87
Enthalpy: 23.48 Btu/lbm

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 65

Air System #7 (G-023 Com. Rm. Mini Split (typical)) Psychrometric Analysis
System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 64.725 56.000
Draw-Thru Fan 46 0.145 2
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 0 0.000 5,999 18.856 287
Sensible Reserve 0 0.000 0
Zone Condition 0 64.725 6,046 75.000 290
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 0 CFM 0 0.000 0 0.000
Blow-Thru Fan 0 0.000
Entering Coil Condition 0 64.725 6,046 75.000 290

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 290 x( 75.000 - 56.000 )= 6,045 Btuh


TLH = 0.999 x 0.68 x 290 x( 64.725 - 64.725 )= 0 Btuh
----------
SUM = 6,045 Btuh
GTH = 0.999 x 4.50 x 290 x( 28.120 - 23.482 )= 6,037 Btuh
Total System Load = 6,046 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 6,037 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 3,495 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 3,495 / 970 = 3.6 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 75.00 Dry bulb temperature: 75.00
Wet bulb temperature: 62.54
Relative humidity: 50.00
Enthalpy: 28.12 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 56.00 Dry bulb temperature: 95.00
Wet bulb temperature: 55.47
Relative humidity: 96.87
Enthalpy: 23.48 Btu/lbm

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 66

Air System #8 (G-013/020 Electrical Room Mini Split) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 64.725 56.000
Draw-Thru Fan 48 0.145 2
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 0 0.000 6,202 18.856 297
Sensible Reserve 0 0.000 0
Zone Condition 0 64.725 6,250 75.000 299
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 0 CFM 0 0.000 0 0.000
Blow-Thru Fan 0 0.000
Entering Coil Condition 0 64.725 6,250 75.000 299

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 299 x( 75.000 - 56.000 )= 6,249 Btuh


TLH = 0.999 x 0.68 x 299 x( 64.725 - 64.725 )= 0 Btuh
----------
SUM = 6,249 Btuh
GTH = 0.999 x 4.50 x 299 x( 28.120 - 23.482 )= 6,241 Btuh
Total System Load = 6,250 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 6,241 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 7,401 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 7,401 / 970 = 7.6 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 75.00 Dry bulb temperature: 75.00
Wet bulb temperature: 62.54
Relative humidity: 50.00
Enthalpy: 28.12 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 56.00 Dry bulb temperature: 95.00
Wet bulb temperature: 55.47
Relative humidity: 96.87
Enthalpy: 23.48 Btu/lbm

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 67

Air System #9 (1-109/114 To 3-309/314 Elec. Rm. Split) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 64.725 56.000
Draw-Thru Fan 48 0.145 2
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 0 0.000 6,202 18.856 297
Sensible Reserve 0 0.000 0
Zone Condition 0 64.725 6,250 75.000 299
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 0 CFM 0 0.000 0 0.000
Blow-Thru Fan 0 0.000
Entering Coil Condition 0 64.725 6,250 75.000 299

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 299 x( 75.000 - 56.000 )= 6,249 Btuh


TLH = 0.999 x 0.68 x 299 x( 64.725 - 64.725 )= 0 Btuh
----------
SUM = 6,249 Btuh
GTH = 0.999 x 4.50 x 299 x( 28.120 - 23.482 )= 6,241 Btuh
Total System Load = 6,250 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 6,241 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 7,401 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 7,401 / 970 = 7.6 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 75.00 Dry bulb temperature: 75.00
Wet bulb temperature: 62.54
Relative humidity: 50.00
Enthalpy: 28.12 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 56.00 Dry bulb temperature: 95.00
Wet bulb temperature: 55.47
Relative humidity: 96.87
Enthalpy: 23.48 Btu/lbm

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 68

Air System #10 (R-601 Utility Room Mini Split) Psychrometric Analysis
System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 58.258 55.000
Draw-Thru Fan 55 0.145 3
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 1,527 6.471 7,483 19.598 341
Sensible Reserve 98 0.258 4
Zone Condition 1,527 64.729 7,637 75.000 348
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 40 CFM 1,060 4.490 1,802 4.719
Blow-Thru Fan 0 0.000
Entering Coil Condition 2,587 69.219 9,438 79.719 348

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 348 x( 79.719 - 55.000 )= 9,438 Btuh


TLH = 0.999 x 0.68 x 348 x( 69.219 - 58.258 )= 2,587 Btuh
----------
SUM = 12,025 Btuh
GTH = 0.999 x 4.50 x 348 x( 29.976 - 22.235 )= 12,091 Btuh
Total System Load = 11,999 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 12,091 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 2,867 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 2,867 / 970 = 3.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 79.72 Dry bulb temperature: 67.57
Wet bulb temperature: 65.08
Relative humidity: 45.71
Enthalpy: 29.98 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 95.00
Wet bulb temperature: 53.42
Relative humidity: 90.51
Enthalpy: 22.24 Btu/lbm

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 69

Air System #11 (G-001 Guard House) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 64.190 55.000
Draw-Thru Fan 319 0.145 15
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 726 0.535 17,825 8.109 811
Sensible Reserve 25,821 11.746 1,175
Zone Condition 726 64.725 43,965 75.000 2,001
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 20 CFM 508 0.374 923 0.420
Blow-Thru Fan 0 0.000
Entering Coil Condition 1,234 65.099 44,888 75.420 2,001

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.10 x 2,001 x( 75.420 - 55.000 )= 44,887 Btuh


TLH = 0.999 x 0.68 x 2,001 x( 65.099 - 64.190 )= 1,234 Btuh
----------
SUM = 46,122 Btuh
GTH = 0.999 x 4.50 x 2,001 x( 28.281 - 23.155 )= 46,096 Btuh
Total System Load = 46,122 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 46,096 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 4,752 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 4,752 / 970 = 4.9 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 75.42 Dry bulb temperature: 73.22
Wet bulb temperature: 62.77
Relative humidity: 49.59
Enthalpy: 28.28 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 95.00
Wet bulb temperature: 54.94
Relative humidity: 99.61
Enthalpy: 23.16 Btu/lbm

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 70

Air System #1 (5th - Floor Area ( A H U ) ) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 71

Air System #2 (4th - Floor Area ( A H U )) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 72

Air System #3 (Ground & 1st-3rd Floor Area ( P A C U )) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 73

Air System #5 (G-009 U- Drive Rm. Mini Split) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 74

Air System #6 (G-010 Com. Rm. Mini Split (typical)) Psychrometric Chart
ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 75

Air System #7 (G-023 Com. Rm. Mini Split (typical)) Psychrometric Chart
ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 76

Air System #8 (G-013/020 Electrical Room Mini Split) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 77

Air System #9 (1-109/114 To 3-309/314 Elec. Rm. Split) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 78

Air System #10 (R-601 Utility Room Mini Split) Psychrometric Chart
ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

D:\MY PROJECTS\RGC 110192\PACKAGE-1\Multi-Story Parking Bldg-110192- Packaged-1.CHV Saturday, October 23, 2010, 4:33 PM
CHVAC - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Radicon-Gulf & PI Consult MULTI-STORY PARKING BUILDING (PACKAGE-1)
Al-Khobar, 31952 Page 79

Air System #11 (G-001 Guard House) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition