(Reference translation) 6A-031 600V CVQ cable
1. Scope of application
This product shall be used for a trunk cable for low voltage underground construction works and incoming electrical
line for our customers.
2. Type
Copper conductors are used, and the following types are classified based on the number of wire cores and conductor
cross-sectional areas.
Table 1
3.2 Conductors
As for conductors, annealed copper wires prescribed in JCS C 3102 (annealed copper wires for electricity) or other
similar kinds shall be used. A round compression strand shall be mainly made by twisting a strand concentrically and
compression-molding it in a circular shape. The direction of an outermost layer twisting shall be right (S).
3.3 Insulators
Cross-linked polyethylene is covered concentrically on conductors with a thickness of the attached table. However,
dropping of cross-linked polyethylene into conductors shall be avoided. In this case, a separator can be installed in a
part where cross-linked polyethylene touches to conductors. The average thickness of insulators must be more than
90% of a value from the attached table, and a minimum measured value must be more than 80% of the value from the
attached table.
Furthermore, thermoplastic materials by using cross-linked polyethylene coating materials from the removed parts
of power distribution equipment of our company (in the rest, we called them as XLPE recycled materials) mixed with
polyethylene raw material shall be used for insulators. However, the mixing rate of XLPE recycled materials shall be
25%.
2
DISCLAIMER: This translation may be used for reference purposes only. This English version is not an official translation of the original Japanese
document. In cases where any differences occur between the English version and the original Japanese version, the Japanese version shall prevail. This
translation is subject to change without notice. Tokyo Electric Power Company, Incorporated shall accept no responsibility or liability for damage or loss
caused by any error, inaccuracy, misunderstanding, or changes with regard to this translation.
Any reproduction and any use for other purposes is strictly prohibited. Tokyo Electric Power Company, Incorporated
(Reference translation) 6A-031 600V CVQ cable
3.5 Sheath
Black vinyl shall be coated on wire cores with a thickness shown in the attached table. The average sheath thickness
must be more than 90% of a value from the attached table, and a minimum measured value must be more than 85% of
the value from the attached table.
3.9 Dimensions
Dimensions are based on the attached table as a standard.
(The section below is intentionally left blank)
3
DISCLAIMER: This translation may be used for reference purposes only. This English version is not an official translation of the original Japanese
document. In cases where any differences occur between the English version and the original Japanese version, the Japanese version shall prevail. This
translation is subject to change without notice. Tokyo Electric Power Company, Incorporated shall accept no responsibility or liability for damage or loss
caused by any error, inaccuracy, misunderstanding, or changes with regard to this translation.
Any reproduction and any use for other purposes is strictly prohibited. Tokyo Electric Power Company, Incorporated
(Reference translation) 6A-031 600V CVQ cable
4. Performance
Cable performance is as in Table 2 when tests in Section 6 are carried out.
Table 2
Item Performance
4
DISCLAIMER: This translation may be used for reference purposes only. This English version is not an official translation of the original Japanese
document. In cases where any differences occur between the English version and the original Japanese version, the Japanese version shall prevail. This
translation is subject to change without notice. Tokyo Electric Power Company, Incorporated shall accept no responsibility or liability for damage or loss
caused by any error, inaccuracy, misunderstanding, or changes with regard to this translation.
Any reproduction and any use for other purposes is strictly prohibited. Tokyo Electric Power Company, Incorporated
(Reference translation) 6A-031 600V CVQ cable
5. Wire display
The following items shall be continuously displayed on wire cores in an appropriate way that they cannot be erased
easily. Furthermore, in the case of using XLPE recycle materials, ‘CVQ/R’ shall be displayed.
a. Nominal voltage: Example: '600 V'
b. Product name and its abbreviation: Example: ' CVQ'
c. The number of wire cores and a conductor cross-sectional area: Example: '3 x 150 + 1 x 100 mm2'
d. Name of manufacturer or its abbreviation
e. Date of production Example :'2008'
f. A product to which electrical appliances and materials safety act applies shall display type certification.
b. Heating test
This test shall be performed by Section 4.17 of JIS C 3005 (test methods for rubber and plastic insulation
wires). Furthermore, a strain rate is as in Table 4-B. After heating a test piece for 96 hours in the circulating
air at 120±3 ° c, take it out, leave it for 4 hours at room temperature, and perform a test described in Section
6.6 (1) a within 96 hours.
Conductor
cross-sectional area Load (N)
2
(mm )
22-38 14.7
60 19.6
100-200 24.5
250 29.4
t = Insulator thickness
d = Conductor diameter
D = Insulator outer diameter
Test piece
Conductor
6
DISCLAIMER: This translation may be used for reference purposes only. This English version is not an official translation of the original Japanese
document. In cases where any differences occur between the English version and the original Japanese version, the Japanese version shall prevail. This
translation is subject to change without notice. Tokyo Electric Power Company, Incorporated shall accept no responsibility or liability for damage or loss
caused by any error, inaccuracy, misunderstanding, or changes with regard to this translation.
Any reproduction and any use for other purposes is strictly prohibited. Tokyo Electric Power Company, Incorporated
(Reference translation) 6A-031 600V CVQ cable
a. Test piece
Take a piece whose length is approximately 30 mm from a finished product. Place the piece parallel to a wire
axis direction and cut it in the shape of an arc to form a test piece.
b. Preparation of a test piece
Place a test piece on a rod whose length is about 35mm and sectional shape is semicircular with the same
diameter as the diameter of a conductor or wire core before a test piece cutting out. (See a figure below)
c. Load
Loads described in the following table shall be applied.
Conductor
cross-sectional area Load (N)
2
(mm )
22 7.35
38-250 9.81
Pressure direction
Parallel plates
t = Sheath thickness
d = Diameter of semicircular rod
D=d+t
Test piece t=D-d
Rod
7
DISCLAIMER: This translation may be used for reference purposes only. This English version is not an official translation of the original Japanese
document. In cases where any differences occur between the English version and the original Japanese version, the Japanese version shall prevail. This
translation is subject to change without notice. Tokyo Electric Power Company, Incorporated shall accept no responsibility or liability for damage or loss
caused by any error, inaccuracy, misunderstanding, or changes with regard to this translation.
Any reproduction and any use for other purposes is strictly prohibited. Tokyo Electric Power Company, Incorporated
(Reference translation) 6A-031 600V CVQ cable
Striking method
Blow Unit: mm
Gripping tool
R 1.57±0.12
Test piece
6.35±0.25
c. Test method
In this method, take a liquid that does not affect on a test piece at -15±0.5° as a heat transmitting medium
(hereinafter ‘medium’). Put the medium in a testing machine in advance and adjust it at -15±0.5° c. Install a test
piece gripping tool and soak the test piece into the medium for 2.5±0.5 minutes. After that, record a temperature,
give a blow, and examine if it is damaged or not. Here, a test piece is damaged means that it is cracked into more
than two pieces, and the generation of a chink or a break does not include for that.
8
DISCLAIMER: This translation may be used for reference purposes only. This English version is not an official translation of the original Japanese
document. In cases where any differences occur between the English version and the original Japanese version, the Japanese version shall prevail. This
translation is subject to change without notice. Tokyo Electric Power Company, Incorporated shall accept no responsibility or liability for damage or loss
caused by any error, inaccuracy, misunderstanding, or changes with regard to this translation.
Any reproduction and any use for other purposes is strictly prohibited. Tokyo Electric Power Company, Incorporated
(Reference translation) 6A-031 600V CVQ cable
be performed by using Section 6 Test method, and this product must pass all the above provisions.
9
DISCLAIMER: This translation may be used for reference purposes only. This English version is not an official translation of the original Japanese
document. In cases where any differences occur between the English version and the original Japanese version, the Japanese version shall prevail. This
translation is subject to change without notice. Tokyo Electric Power Company, Incorporated shall accept no responsibility or liability for damage or loss
caused by any error, inaccuracy, misunderstanding, or changes with regard to this translation.
Any reproduction and any use for other purposes is strictly prohibited. Tokyo Electric Power Company, Incorporated
(Reference translation) 6A-031 600V CVQ cable
8. Other
8.1 General matters
(1) Except items prescribed in this specification, necessary items to satisfy product performance and functionality
shall be determined after consultation with our company.
(2) This specification can be changed with our company’s approval if substantial profits are expected for use and in
manufacturing by changing a part of it.
(3) When deemed necessary by our company, process on-site and material inspections, etc. can be performed.
8.2 Packing
A strand of cables shall be wound around a tough drum, and its starting part is held outside of the drum. The drum
must have strength so that its winding frame etc. perfectly withstands by a fall from the height of 50cm on a wooden
board. (The body diameter of a drum is more than 12 times of the outer diameter of a finished cable.)
Also, the following items shall be displayed on the side of a drum in an appropriate way that they cannot be erased
easily.
a. Name
b. Nominal voltage
c. The number of wire cores
d. Nominal cross-sectional area
e. Length
f. Net mass
g. Total mass
h. Name of a manufacturer or its abbreviation and a registered trademark
i Date of production
10
DISCLAIMER: This translation may be used for reference purposes only. This English version is not an official translation of the original Japanese
document. In cases where any differences occur between the English version and the original Japanese version, the Japanese version shall prevail. This
translation is subject to change without notice. Tokyo Electric Power Company, Incorporated shall accept no responsibility or liability for damage or loss
caused by any error, inaccuracy, misunderstanding, or changes with regard to this translation.
Any reproduction and any use for other purposes is strictly prohibited. Tokyo Electric Power Company, Incorporated
(Reference translation) 6A-031 600V CVQ cable
Attached table the structure table of a 600V copper conductor single-core 4 wire-stranding CVQ cable.
Insulator thickness (mm) 1.2 1.5 1.2 2.0 1.5 2.0 2.0 2.5 2.0
Outer diameter after insulation (mm) 7.9 12.3 9.7 16.0 12.3 18.7 16.0 24.0 18.7
Sheath thickness (mm) 1.5 1.5 1.5 1.5 1.5 1.6 1.5 1.8 1.6
Outer diameter with a sheath
10.9 15.3 12.7 19.0 15.3 21.9 19.0 27.6 21.9
(approx. mm)
Finished (wire stranding) outer diameter
27 36 44 52 64
(approx. mm)
Conductive resistance 20°
0.849 0.311 0.491 0.187 0.311 0.124 0.187 0.0754 0.124
(Ω /km)
Electric Testing voltage
2000 2500 2500 3000 2500 3000 3000 3000 3000
test (V.1 min.)
Insulation resistance
1500 1000 1500 1000 1000 900 1000 900 900
(M Ω.km)
Approximate mass (kg/km) 1230 2630 4180 6160 9850
11
DISCLAIMER: This translation may be used for reference purposes only. This English version is not an official translation of the original Japanese
document. In cases where any differences occur between the English version and the original Japanese version, the Japanese version shall prevail. This
translation is subject to change without notice. Tokyo Electric Power Company, Incorporated shall accept no responsibility or liability for damage or loss
caused by any error, inaccuracy, misunderstanding, or changes with regard to this translation.
Any reproduction and any use for other purposes is strictly prohibited. Tokyo Electric Power Company, Incorporated
(Reference translation) 6A-031 600V CVQ cable
12
DISCLAIMER: This translation may be used for reference purposes only. This English version is not an official translation of the original Japanese
document. In cases where any differences occur between the English version and the original Japanese version, the Japanese version shall prevail. This