Introduction

This handbook has been produced by Water


Corporation to assist builders and plumbers to
work with the Corporation and our regulators
to deliver the best possible outcomes for our
customers, by protecting public health, as well
as public and privately owned assets.

Water Corporation recognises the need for


government bodies, utilities and industry to
work together to identify relevant areas of
responsibility within the industry and the
services delivered to the community.

In addition to their customer obligations, there


are also statutory obligations in protecting
water and sewerage infrastructure. Laws and
Regulations relevant to Water Corporation’s
operations and assets that set out these
obligations are listed within this publication, as
a guide to other documents that need to be
understood when delivering services.

Information provided within this handbook


was accurate at the time of publishing.
Content updates will be made to the online
version as required, www.watercorporation.
com.au/plumbinghandbook

Building and Plumbing Handbook 1


Table of contents

1 Definitions 4 8 Trade Waste 20


2 Working with Water Corporation 5 8.1 Applying for a Trade Waste Permit 20
3 Connection to Water Corporation Mains 6 8.2 Retail food industry 20
3.1 Water supply connections 6 8.3 Grease arrestor and other pre-treatment requirements 20
3.2 Fire services 6 8.4 Sizing of grease arrestors 21
3.3 Flow control devices 6 8.5 Shared grease arrestors 22
3.4 Sewer connections 6 8.6 Non-typical grease arrestors 22
3.5 New sewer connections 7 8.7 Pre-treatment requirements for other industry types 23
3.6 Reporting of lost sewer junctions 8 8.8 Discharge restrictions 23
3.7 Drainage plumbing diagrams 9 9 Development Issues 24
3.8 ‘‘INs and UPs 9 9.1 Isolation of internal lines 24
3.9 Property connections to vacuum wastewater systems 9 9.2 Strata schemes 25
4 Backflow Prevention 10 9.3 Metering 26
4.1 What is backflow? 10 10 Buildings 29
4.2 Backflow Prevention Policy 10 10.1 Proposals to construct, demolish or alter buildings 29
4.3 New developments, redevelopments and changed services 10 10.2 Sewer main alignments 3O
4.4 Backflow prevention device 11 11 Electrical Risks 31
4.5 Backflow regulations and standards 12 12 Partnering with Water Corporation 33
4.6 Ongoing backflow device maintenance 13 12.1 SewerSmart© Plumbers 33
4.7 Submitting the backflow device test report 13 12.2 Waterwise Plumbers 33
4.8 Backflow Smart Testers Program 13 12.3 Backflow Smart Testers Program 33
5 Interpretation of Dial Before You Dig Plans 14 13 Legal Obligations 34
5.1 Water DBYD plan 14 14 Appendix 35
5.2 Sewer DBYD plan 14 14.1 Fire service configurations for backflow protection 35
6 Disconnection from Water Corporation Mains 15 14.2 Backflow boundary protection diagrams 36
6.1 Water supply 16 15 Contact Us 37
6.2 Sewerage 17
7 Maintenance Work 18

2 Water Corporation Building and Plumbing Handbook 3


1 Definitions 2 Working with
Water Corporation

Licensed Plumbing Contractor Dial Before You Dig plans Land owners proposing a building Water and sewer applications
Is a person who holds a plumbing contractor’s A Dial Before You Dig plan is an extract from development or connecting to Water You can also request the following:
licence under the Plumbers Licensing and Water Corporation’s mapping system which Corporation water, sewer or drainage lines
are required by law to make an application o New water meters or services (e.g. fire
Plumbing Standards Regulations 2000. contains detailed information about water,
to Water Corporation. Applications can be services, temporary services and sub-
wastewater and drainage mains. Dial Before
Licensed Tradesperson lodged online via BuilderNet© meters);
You Dig plans are used by licensed plumbers
Is a person who holds a tradesperson’s licence o Work on existing water meters or
when they need to locate sewer connection BuilderNet©
under the Plumbers Licensing and Plumbing services (e.g. relocations, modifications,
points.
Standards Regulations 2000. BuilderNet©, our online lodgement system, is disconnections);
Property Sewer the quickest and easiest way to lodge: o New sewer junctions;
Licensed Tradesperson (drainer) o Work on existing sewer services (e.g.
A conduit laid, wholly or partly at the o Building applications (including sewer
Is a person who holds a tradesperson’s alterations to access chambers, cutting and
expense of the property owner, entirely connections);
(drainage plumbing) licence under the sealing pipes, and installing spigots); and
within the boundaries of the lot, for the o Water service application; and
Plumbers Licensing and Plumbing Standards sewer conversions, connecting properties to
carriage of sewage or wastewater to any o Sewer application;
Regulations 2000. sewers.
Water Corporation sewer.
BuilderNet© is available free of charge, with
Drainage plumbing diagrams (flimsy) Note: These requests are typically submitted
Sewers the exception of standard Water Corporation
by builders, plumbers, consulting engineers
The term drainage plumbing diagram A conduit laid for the carriage of sewage or fees and charges applicable to building and
and developers.
(formally known as a constructed diagram or wastewater. This term does not include a service applications.
flimsy) are certified by a licensed plumbing property sewer. If not specified this means a Dial Before You Dig plans
contractor. The contractor is legally obliged to Please refer to Section 3--
-Connection to
Water Corporation sewer. Dial Before You Dig (DBYD) plans can be
provide the Building Commission with the Water Corporation mains (page. 8), for
further information about pre-connection obtained via Dial Before You Dig © for
drainage plumbing diagram.
requirements. most properties and are provided
electronically in PDF format.
Building applications
DBYD plans show the location of water and
Request quotations and approvals for:
sewer mains, system connections and other
o minor plans for non-habitable structures Water Corporation infrastructure near
(e.g. swimming pools, garages and sheds properties. They are useful to licensed
greater than 40m²); plumbers, surveyors, developers, builders,
o alterations or additions to existing buildings; consulting engineers, hydraulic consultants,
and architects, local government officers and real
o Multi-residential or commercial estate agents.
developments (including associated water
BuilderNet registration
service connections and sewer junctions).
Go to buildernet.watercorporation.com.au
Note: These requests are typically submitted select ‘New Registered User’ and complete the
by builders, hydraulic consultants and form. Registration is required for customers
architects. that intend to use the system on a regular
basis.

For further information, visit the website or


contact 13 13 95.
4 Water Corporation Building and Plumbing Handbook 5
3 Connection to Water
Corporation mains

It is an offence to interfere with, alter or 3.3 Flow control devices 3.4 Sewer connections
connect to a Water Corporation water or Flow control devices (FCDs) have been Connections to Water Corporation sewer
sewer main without prior approval from installed in water services for all commercial mains are provided via a connection point,
Water Corporation. and multi-residential developments. which must be installed or supervised by a
3.1 Water supply connections Water Corporation representative. It is an
The device limits the water supply flow rate to
offence to connect private plumbing work
Connections to Water Corporation mains the flow applied for and what has been paid
to this connection point without approval.
are provided by a meter and builders for through infrastructure contributions.
There is a risk to lives and health if the
standpipe, which must be installed by
Note: FCDs control the rate at which the water correct precautions are not taken.
Water Corporation.
is supplied to a property and will not reduce In addition to obtaining Water Corporation
To comply with regulation 24(2), missing or water pressure. A pressure reducing valve approval to connect to sewer mains, licenced
damaged meters or damage to water services Typical flow control devices, image
(PRV) is required for this. FCDs are located on plumbers are required to adhere to PLB courtesy of Maric Flow Control
or pipe work must be reported to Water the downstream face of a meter and it is the requirements, please visit the Building
Corporation on 13 13 75. plumber’s responsibility to ensure that it Commission website for further information.
remains in place when the internal pipework is 3.5 New sewer connections
3.2 Fire services
fixed to the meter. It is essential that the licensed plumbing Construction of the property sewers within a
Fire services may be provided for the purpose contractor/builder confirms there is adequate property is the responsibility of the land owner.
of supplying water for fire fighting and the It is an offence to tamper with a meter, fall to the sewer main prior to starting building In those situations where a new sewer
necessary testing of firefighting equipment. including the removal of the FCD. FCDs construction. The conditions a builder must connection point (sewer junction) is cut into a
Water Corporation provide these services may be the cause of a flow lower than is comply with are included with the approval. sewer main it must be installed or supervised
under certain conditions, subject to entering required by the property owner. In this
by a Water Corporation representative.
into an agreement. case, the customer will need to apply for Other important requirements are:
a higher flow and pay the appropriate It is the responsibility of the licensed plumber
Unauthorised use o Confirm location of the sewer connection
infrastructure contributions. to:
point;
o Examples of unauthorised use of fire
FCDs can potentially cause turbulence that o Provide for overflow relief; o Ensure an application has been lodged and
services include washing down trucks and
affects the accuracy of turbine type meters, o Corporation access chambers must be kept payment made to Water Corporation for the
driveways, connecting domestic supply
which are generally larger than 40mm. To clear for ease of access; connection;
(including reticulation) via the fire service. If
minimise the risk, the FCD must be placed a o Maintain minimum cover levels on o Excavate to the sewer, and make the site
a plumber has identified a cross Corporation sewer mains;
minimum of one metre from the meter. Prior safe for one of our representatives to cut in
connection, they must advise the customer o Exercise caution when changing site levels;
to making an application for a water supply the sewer connection;
that water use from a fire service for o Verify the location of existing pipe work
connection, the builders/plumber must o Construct the property connection into the
purposes other than fire fighting is illegal. prior to construction or connection;
ensure there is adequate space between the property boundary;
Fire services are subject to backflow o Obtain separate approval where industrial
property boundary and the building to install o Provide as constructed information showing
protection requirements (see Section 4). or commercial waste will be discharged; (see
the necessary pipework to accommodate the ‘ins and ups’. (Refer to Section 3.8 for
spacing between the FCD and the meter. Section 8); and
further detail);
o Provide backflow prevention devices for o Show all boundary traps and other fittings;
specified industrial and commercial
developments (see Section 4). and
o Ensure that the property connection
(junction) is greater than or equal to the
diameter of the internal property sewers
connection to it.

6 Water Corporation Building and Plumbing Handbook 7


lot boundary
one vent required
between I.S and first fixture

Boundary/running traps On occasions licensed plumbers experience


difficulty in locating the junction, see section road ground level
Boundary traps shall be installed on all 5 for information on how to interpret Water
property connections where the junction is Corporation plans. The following explains I.S
located on: the process and any pre-requisite actions for
vacuum sewer
reporting a lost sewer junction.
o Sewers that are 300mm or larger in
diameter; Prior to reporting a lost junction, the licenced
o IO or IS sewers where the downstream plumber must confirm that:
sewer is 300mm or larger in diameter; and
o Any Water Corporation sewers, regardless
1. There is a valid and current approval from property sewer
of diameter, that conveys a pumped gravity sewer
the Water Corporation to connect to the
discharge.
sewer.
As per Water Corporations design standards, 2. They have the name of the licensed collection chamber

and the applicable Australian Plumbing plumber responsible for the site.
Standards. 3. They have excavated at least 1 metre either
side of the given measurement and 0.6 o Water Corporation will not be able to assist UP Measurements
For further information about the provision metres deeper than the depth established if the plumber/builder has not followed this In those situations where the property
of boundary traps on property connections from the DBYD plan. process, there is no record of a current sewers has been brought into a property,
please contact Water Corporations Building application to connect to the sewer --- and or
Note: Report of a lost junction will only the as-constructed sketch must include UP
Services on 13 13 95. a copy of the plan is not available on site.
be accepted from the licensed plumber measurements from the invert of the sewer
Gullies in flood prone areas responsible for the site. *The licensed plumber is responsible for the safety of main to the connection end points within
site excavations at all times. the property (refer to section 3.4)
All external gullies in flood prone areas,
o All reports shall be made by contacting
including the North West Region (26 degrees **Prior to backfilling the excavation it is recommended It is always assumed that the pipe is brought
Water Corporation on 13 13 95.
south of the Earth’s equatorial plane), must be that photographs are taken to support of your Lost IN before UP unless it is otherwise stated.
o You will be asked to confirm that the
fitted with ‘‘pop up’’ covers. Junction Report.
prerequisite steps have been undertaken. 3.9 Property connections to vacuum
3.6 Reporting of lost sewer junctions o You will be required to accept that Water 3.7 Drainage plumbing diagrams wastewater systems
Corporation may seek to recover any costs
The builder/plumber is required to confirm the The Australian Standard AS/NZS 3500:2018
should the junction be located within the Please refer to the drainage plumbing
location and depth of a sewer connection point Part 2 Clause 3.18 specifies installation
correct limits. guidance note on the Building Commission
prior to work on-site commencing. Water requirements. Licensed plumbers are expected
o Where the excavation can be safely website for further information on Drainage
Corporation provides a diagram showing the to be aware of these requirements.
secured, you will be required to do so Plumbing diagrams.
location of sewer connection points (junctions)
pending resolution.* 3.8 ‘‘INs and UPs’’ Note: Vacuum sewer schemes may have a
at the time an application to connect is made.
o Where the excavation cannot be secured, restricted capacity. If you intend to connect
When establishing the position of the IN Measurements
you will be required to backfill.** anything other than a single residence, such
connection point, must be particularly careful o On receipt of a lost junction report, Water In situations where the property sewers as commercial or industrial properties, to a
where the connection is relatively long or Corporation undertakes to expedite a (property connection) has been brought into a vacuum wastewater system you should
where there are ‘‘in and up’’ measurements resolution. property the as constructed sketch must obtain advice on
provided. o You will be advised at the time of making a include IN measurements from the centreline 13 13 95.
report of the likely resolution date. of the sewer main to the connection end
points within the property (refer to section The diagram above illustrates a connection
3.4). where the collection chamber is located
outside the property boundary.
8 Water Corporation Building and Plumbing Handbook 9
4 Backflow Prevention

An ongoing threat to the quality of Water connection to a property (including fire


Corporation’s drinking water supply is the services). At this point, fire services that were o The applicable backflow information sheet 4.4 Backflow prevention device
flow of water backwards from a customer’s installed prior to May 2010, are not required (directed towards the applicant), based on The containment backflow prevention device
property through their property’s water to install a boundary device unless the fire the assessed backflow risk (high, medium or must be installed on the customer’s side of the
service connection (fire services included). service is being altered at the property low); and water connection at the property boundary,
boundary. This policy is supported by o Plumber’s information sheet (designed for and belongs to the owner of the property.
This water may be contaminated by the the applicant to provide to their nominated
relevant legislation and plumbing standards.
activities within the property, and may cause licensed plumbing contractor and/or The installation of a containment backflow
death, health problems or an inconvenience to 4.3 New developments, redevelopments hydraulics consultant). prevention device does not eliminate the
persons ingesting or using the water. and changed services need for zone and individual backflow
Site-specific activities will determine the prevention devices that may be required
4.1 What is backflow? At the time of building approval, development
final level of backflow risk and for certain under plumbing standards. Water
application, redevelopment or changes to
Backflow is the reversal of the normal commercial and industrial processes may Corporation does not manage zone or
existing water services, the applicant will be
direction of water flow in a water supply default the property risk rating to high. individual backflow protection.
informed of the property’s risk rating.
plumbing system. It occurs when the water
If a property owner considers the risk rating All backflow prevention devices that are
delivery main is at a lower pressure than the The following building application types will
assigned to their property is higher than the installed at the boundary must be registered.
internal plumbing system (backsiphonage). be assessed for backflow risk:
risk of activities being carried out, then the This information should be submitted to
Backsiphonage can occur when there is a
o New developments; property owner may appeal this rating. Water Corporation by a licensed plumbing
burst or ruptured water main, or when there
o Redevelopments of existing facilities; contractor qualified to test the devices no
are periods of high demand. Excessive The property owner must consult a suitably
o Changes to any existing water service; later than 5 working days after the test is
demand during fire fighting operations can qualified licensed plumbing contractor or
o Additions/alterations (including where no carried out.
also result in backsiphonage. hydraulic consultant first, and submit an
water service applications are included,
appeal form to Water Corporation within 28 The following conditions should be noted:
Backflow can also occur if a water pump (such applicable only if the property has existing
days of receiving risk rating advice. Water
as a bore pump) is cross connected to the meters); o Boundary containment backflow prevention
Corporation will advise the property owner of
internal water plumbing system, and is o Multiple residence and/or commercial devices are required to be installed as part of
the outcome of the review.
pumping bore water at a higher pressure than (includes where no water service the plumbing system downstream, and as
the water mains pressure (backpressure). applications are included, applicable only if o The risk rating of a property determines close as practicable to the property’s water
the property has existing meters); the minimum requirement for the type of meter (or property boundary if no water
If a property’s drinking water supply is
o Any applications that involve a fire service; backflow prevention device(s). meter is available). Refer to the Appendix on
inadvertently interconnected with a source of
and o Irrespective of the risk rating of a property, page 44.
pollution, either through a cross connection or
o Any applications where the minimum all fire services are rated medium risk and o No connections are permitted between the
simply a hose submerged in a container of
water service size applied for is greater than require (as a minimum) a medium rated meter outlet and the containment device.
liquid, then these pollutants could enter the
25mm in size (except fire services, where device to be installed. o If continuity of supply is critical to your
water supply when there is an overpressure
the backflow advice applies regardless of o If the future land use is unknown, the risk client, consideration should be given to
on the private property side or a sudden drop
the service size). rating will default to high. connecting duplicate devices in parallel.
in water mains pressure.
o Where there is mixed use on a property, the o If the property has more than one water
Building application approvals also include:
4.2 Backflow Prevention Policy risk rating will default to high. service, you will need to install a device/s
o A backflow approval sticker as part of the o Changes in the activities within a property at the connection point for each of those
Water Corporation’s Backflow Prevention
approved site plan document; can result in a change of the backflow risk services.
Policy requires the installation of approved
rating and the backflow device(s) required.
backflow prevention containment devices
at the boundary of every water service

10 Water Corporation Building and Plumbing Handbook 11


o All fire services are rated as medium risk, Regulations for backflow prevention 4.6 Ongoing backflow device maintenance 4.8 Backflow Smart Testers Program
and the installation of a medium risk rated The requirement to have and maintain Testable backflow prevention devices at the The Backflow Smart Testers Program allows
device is required, as a minimum (excludes backflow prevention devices at the boundary property boundary must be installed on high plumbing businesses with accredited backflow
fires services installed prior to May 2010). of a property is supported by legislation, or medium risk properties. These require testers who have already registered, and agree
o The installation of some forms of backflow including the following regulations: testing; to submit test reports through our web
prevention devices will reduce water application only, to be promoted through our
o Regulations 42 and 43 Water Services o At commissioning, after any maintenance;
pressure/ flow rate downstream of the website. To participate in this program visit:
Regulations 2013 and
device. If the water pressure and/or flow www.watercorporation.com.au/
o Every 12 months by a licensed plumbing
rate is critical to your client, then this backflowsmartsignup
Due to the potentially serious nature of a contractor, permitted to test the devices.
should be discussed with your client prior
backflow incident, Water Corporation can
to choosing and installing the final Water Corporation will send an annual
in accordance with these regulations serve
backflow prevention device. reminder letter to the property owner for
an order on a property owner or occupier
to install backflow devices. these boundary devices. Failure to maintain a
Work related to the installation of backflow
backflow device will result in the serving of a
devices is identified as plumbing work and
The regulations also provide for penalties for non-compliance notice to the property owner
is therefore covered by the Plumbing
non-compliance under the Water Services or occupier.
Regulations. Compliance with the plumbing
Act 2012 (WA). Water Corporation has the
standards will therefore be monitored by Backflow test reports must be submitted
power to restrict or disconnect water
the PLB; you are required to notify the PLB online to Water Corporation no later than 5
services, to protect the drinking water supply
of your intention to carry out the work. working days after the test is carried out.
from potential contamination caused by a
Only licensed plumbers who are backflow event from a property.
Water Corporation do not manage
qualified to install, test and certify Standards for backflow prevention zone or individual type backflow
backflow prevention devices are prevention and do not accept test
In addition to all plumbing regulations,
permitted to carry out such works. licensed plumbing contractors must also reports for these types of devices.
Water Corporation will inspect properties to apply the following standards for backflow
4.7 Submitting the Backflow Device
ensure ongoing compliance with its Backflow prevention:
Test Report
Prevention Policy. o AS/NZS 3500:2018 Plumbing and Drainage Test reports for boundary containment
4.5 Backflow Regulations and Standards Part 1: Water Services. backflow must be submitted online.
o AS/NZS 2845:2010 Water Supply-Backflow To register for online lodgement visit:
Water Corporation requirements relating to
Prevention Devices Part 1: Materials, design www.watercorporation.com.au/
the installation, maintenance and testing of a
and performance requirements. backflowlodgement
backflow prevention device are supported by
o AS 2845:2010 Water Supply-Backflow
legislation and plumbing standards.
Prevention Devices Part 2: Air gaps and
break tanks.
o AS 2845:2010 Water Supply-Backflow
Prevention Devices Part 3: Field testing and
maintenance.

12 Water Corporation Building and Plumbing Handbook 13


5 Interpretation of DBYD
Plans

DBYD plans are extracts from Water 5.1 Water DBYD plan 5.2 Sewer DBYD plan The graphic for Lot 111 reflects the
Corporation’s mapping system that, among The following water DBYD plan is Some junctions in older areas (typically measurement which indicates it has been
other things, show the location of sewer intended as a guide. those prior to 1986) have not been brought brought in 1.3 metres and up 1.9 metres from
connection points. It is essential for all into properties or up to one metre below the sewer line. Common in older suburbs, the
plumbers to be able to interpret DBYD plans. ground level. Licensed plumbers must not sewer connection point may not be brought
rely on previous experience or the graphical into the property, and it is the licensed
When using DBYD plans there are limitations
representation of DBYD plans when locating plumber’s responsibility to correctly interpret
in how the information may be used. Users
sewer connection points. the DBYD plan.
must not rely entirely on the plan. When
the information is critical, the pipe position The example below illustrates why it is Refer to Section 10.3 for direction on how to
must be physically confirmed prior to any necessary to accurately interpret DBYD plans. estimate depths to Water Corporation sewer
mechanical excavation or boring. While the connection for Lot 517 is shown pipes. The following sewer DBYD plan is
outside the property line, the dimensions intended as a guide:
Refer to the DBYD Plan legend information
for further assistance with interpreting show the connection point has been brought
DBYD plans. in 2.7 metres and up 1.9 metres from the
sewer line.

S24 19.5 534 48.1


14.3
1O462-223

U1.9 16.4 U1.9 37.4 45.7


|1.8
|1.8
517
|1.7

BOONA
37.4 41.5
5.7

2.47
111 14.3 111 12.7 U1.9 |1.8 36.2
U1.9 2.7 32.9 |1.8

230VC
|1.3

63.8

179
U1.9 |2.3
CT

CT
25.6
S2S 20

2.46

150VC
27.7
525
|1.8

144
31.2
12.8
1OOCI

12.6 14.5 16.2


1O9 1O 10916.5 8.210
|1.8 |1.8

2.25
U1.9

S18
5.3 |1.4 159VC
518 578

3.85
150AC

1.20
3.4

3.79
|1.8 |1.9 |1.9 134 150AC
4112
4.0 150
4112
2.24 3.84 |1.8 132 3.59
|2.3
2OSCI
1.93
3.79 3.78

3.85
WALANNA

3.0
WALANNA
42.7
524

12.9
8.5 26.1
13.9
16.6 U1.6
EO7S7 4111 28
4111
E0757
(150)

EO7S6 E0756 1.25 300HDPE


2OSCI

0.64 0.65 1.26 306


71.2
1.45 1.46
59.2
6.9

4.43
6.0
67 67

230VC
34184
2825

KILKENNY CI P.M
225VC
SODAV

1OOSC
1OOSC
2OSS-S

MH

RD
37647

17696
37647
3308

E1066 E1066
E1O66 E1O66 163
161
24.1

14 Water Corporation Building and Plumbing Handbook 15


6 Disconnection from Water
Corporation Mains

6.1 Water supply The diagram below illustrates 6.2 Sewerage The diagrams below illustrate correct sewer
Prior to the demolition of any building, how the connection for a Prior to the demolition of any building the disconnections.
the landowner is required to apply to temporary standpipe may be landowner is required to engage a licensed Note: For PVC pipes the seal must comprise
Water Corporation for the water service made. plumber to disconnect the building from the an approved cap glued to the pipe. For
to be disconnected (Water Service Act sewer main and ensure the sewer connection earthenware pipes the approved cap must be
2012 point is left sealed, compliant with the relevant cemented to the pipe.
Section 95). plumbing standards. Refer to the Building
Commission website for more information.
In cases where redevelopment is pending,
the water meter may be left, subject to the
installation of a standpipe by a licensed
plumber, compliant with AS/NZS 3500:2018
Part 1. Where a landowner, builder or licensed Inspection shaft rising shaft
plumber chooses to leave the water meter on
ground level
site, they will be responsible for any damage
to the water service or water theft.

property sewer inspection shaft


DN 12 dr brass
lugged hose tap
U-bolt flow from property

star picket
cut and seal

main sewer

DN 15 copper tube

square on back
copper tube
black nylon cable ground level
tied as required
760mm
200mm max

1500 - 1650mm
150mm min

inspection shaft square on back

hose connection
F.S.L square on back
vacuum breaker main sewer

flow from property

cut and seal

20Fx15C
copper alloy conetite elbow
NOTE: for PVC pipes the seal must comprise an approved cap glued to the pipe.
For earthenware pipes the approved cap must be cemented to the pipe.
16 Water Corporation Building and Plumbing Handbook 17
7 Maintenance work

This section provides guidelines for 2. Property owners are responsible for the Detailed below is the process to be followed
customers and licensed plumbers relating cost of any CCTV requirements where the when plumbers become aware of a blockage
to maintenance responsibility for CCTV is initiated by a licensed plumber. in a sewer connection, where it fits the
blockages in property sewers. The sewer circumstances outlined on (page 28):
Water Corporation will not reimburse licensed
property connection is the pipe between
plumbers for clearing any blockage where it is 1. Contact Water Corporation’s Service Faults
the inspection shaft and the junction on
found to be in the property connection, and and Emergency number on 13 13 75.
the Corporation’s sewer main, shown as A
will subsequently clear it from the inspection
and B on page 29. 2. Advise the customer service representative
shaft.
of the situation.
The guidelines ensure that property owners
3. If Water Corporation determine that an
will not be responsible for excavation to 3. Obtain a work order number from the
excavation is required to repair the sewer
excessively deep sewers or for excavation in customer service representative. Keep a
property connection, the Corporation will
another property. They apply to the record of the number.
assist the plumber when:
inspection shaft (IS sewers), long sewerage
connections and jointly used main drains o the depth of the required excavation is 4. Invoice Water Corporation referencing the
(other than in strata schemes). 2.5 metres or more; and/or work order number.
o excavation is required outside the 5. Water Corporation will pay the licensed
1. Property owners are responsible for the property.
cost of clearing any blockage in their sewer plumber a standard fee, as agreed with
property connection, where the blockage The diagram below illustrates the intent and the plumbing industry. The fee is intended
can be cleared from the inspection shaft. interpretation of this application. to cover travel costs and the onsite
assessment. Water Corporation expect
that no costs will be borne by the property
owner.
one vent required
lot boundary

between I.S and first fixture

ground level
road

I.S

vacuum sewer

property sewer
gravity sewer

collection chamber
18 Water Corporation Building and Plumbing Handbook 19
8 Trade Waste

Trade waste or industrial waste is any Blockages and overflows impact the
Minimum pre-treatment required Examples of typical business
wastewater discharged from business other community and our ability to provide
than waste from office facilities or staff customers effective wastewater services. Cafes, restaurants, Function centres
amenities. Under the Water Services Act 2012, all Lunch bar, deli taverns/hotels
Installation of a
businesses involved in the retail food industry Takeaway shops quick service restaurants
If disposing trade waste into our wastewater Water Corporation
must obtain written permission in the form of Fish and Chips catering establishments
system, business operators are legally accepted
a trade waste permit before discharging any Kebab shops food manufacturing
required to have a trade waste permit. If the grease arrestor
waste into our wastewater system, and Butcher shops school canteens
wrong waste goes down the system, it could Bakeries
comply with all permit conditions including
cause serious harm to public health and the
the installation or upgrade of a grease Childcare centres Takeaway pizza only
environment.
arrestor. Installation of a Fish retail (No other type of food
8.1 Applying for a Trade Waste Permit Water Corporation (wet processing) prepared on site)
8.3 Grease arrestor and other pre-treatment
Complete a trade waste application form, requirements (for the food industry) accepted School canteen Donut shop
along with any relevant supplement In-sink and floor (no cooking)
During the trade waste application
forms and submit to Water Corporation strainer units Bakery (bread only,
assessment process, our trade waste officers
with site hydraulic drawings (plumbing no pies or cakes)
assess if a grease arrestor is required based
design drawings) for assessment prior to
on the type of activities being undertaken. In
commencing any discharge of trade
general, retail food businesses that prepare
waste. See www.watercorporation.com.au Only pre-treatment devices, which are Note: Water Corporation has a minimum
and cook on site require a grease arrestor.
for an application and supplement forms. accepted for use by Water Corporation should grease arrestor size of 540 litres and a
The list below shows typical pre-treatment be installed and connected to the sewer. For maximum size of up to 6000 litres. Although
8.2 Retail food industry (for more information on pre-treatment products larger sizes from 3000 to 6000 litres have
requirements for different types of retail food
all other industry type visit: been approved for individual use by Water
businesses.
requirements, see section 8.7) www.watercorporation.com.au/ Corporation, these are not approved to be
The grease and fat contained in wastewater pretreatmentproducts used in series. Customers wishing to install
can accumulate both in your drains and our these larger grease arrestors should seek our
8.4 Sizing of grease arrestors
wastewater system, resulting in odorous approval before installation.
and toxic gases, corrosion, blockages and The size of a grease arrestor is critical in
ensuring the wastewater discharged from Peak Flow Rates Method
wastewater overflows.
a greasy waste producer has the optimum Where the hourly peak wastewater flow rate
conditions for efficient suspended solids, oil is known, this can be used as the ‘Calculated
and grease removal. Grease Arrestor Size’ (see Recommended
Grease Arrestor Size table) to determine the
Two methods can be used to determine the
recommended size.
appropriate size of a grease arrestor. Both
are based on ensuring the wastewater has a Fixture Unit Rating Method
minimum retention time of one hour. The grease arrestor size, in litres, is the sum
of the fixture unit ratings of all fixtures that
feed into the grease arrestor multiplied by
100 (see Fixture Rating table). Using the
Peak Flow Rates Method determine the
recommended grease arrestor.

20 Water Corporation Building and Plumbing Handbook 21


Fixture unit ratings 8.7 Pre-treatment requirements for other 8.8 Discharge restrictions
industry types Dishwashers and glasswashers
Fixture Fixture Unit Rating Fixture Fixture Unit Rating
Most trade waste discharges to sewer will Dishwashers and glasswashers are not to
Steamer 1 Kitchen sink 3 require some form of pre-treatment. For discharge into grease arrestors, due to their use
Wok (per burner) 1 Double kitchen sink 3 example, businesses such as, mechanical of detergents, high water temperatures and
servicing, vehicle/plant washing, fuel stations, surge loads. This can overload the arrestor or
Hand Basin 1 Pot sink 5
etc. that generate oily wastewater discharge, can liquefy or emulsify oil and grease, allowing
Rinse sink 3 Double pot sink 5 will require an oil/water separator. These come it to be discharged to sewer.
in various types such as the Coalescing Plate
Combi Oven 5
Separator (CPS) Vertical Gravity Separator (VGS)
or Hydrocyclone.
Swimming pools
Recommended grease arrestor sizes
For these and other types of approved The backwash and drainage from domestic
pre-treatment products, that may swimming pools or spas must not be
Maximum Number Calculated Grease Arrestor Recommended Grease
be applicable to your business, visit: connected or discharged to the sewer. Refer to
of Fixture Units Size Range (litres) Arrestor Size (litres)
www.watercorporation.com.au/ Water Services Act 2012 Section 88(1) (g)
7 100 - 700 540 pretreatmentproducts
Storm water
13 701 - 1300 1000
Typical drawings of pre-treatment apparatus
Storm water from domestic or commercial
17 1301 - 1700 1500 are also available on Water Corporation
premises must not be connected or discharged
website. More complex wastewater may
26 1701 - 2600 2000 to the sewer as it is considered a prohibited
require the producer of the waste to engage a
discharge.
40 2601 - 4000 2 x 2000 in series wastewater treatment or plumbing consultant,
to design a suitable treatment system to meet
our acceptance criteria.
8.5 Shared grease arrestors Where the fixture unit loading is too high for Food waste disposal units
a single grease arrestor, and it is not practical (garbage grinders)
Water Corporation will only approve shared Only pre-treatment devices, which are
tenancy grease arrestors when the property to connect grease arrestors in series, the The installation of garbage grinders on any
waste streams are to be split, and diverted to accepted for use by Water service connected to the sewer is prohibited.
owner or the owner’s designated agent (such
individual grease arrestors to accommodate Corporation should be installed and
as a shopping centre manager), agrees to take
responsibility, and applies for a trade waste the fixture loadings. connected to the sewer. Always check
permit. with your supplier prior to purchasing
8.6 Non-typical grease arrestors
any pre-treatment product.
In circumstances where Water Corporation Water Corporation may accept the use of
approve businesses to share a grease arrestor, other types of grease arrestors, such as those
the minimum size can be calculated using that may include the use of filters. These
either method. If using method one, the types of grease arrestors may be subject to
combined fixture unit rating of all businesses specific conditions or use restrictions. It is
sharing the grease arrestor must be used. The recommended that prior to the installation of
minimum size for a shared arrestor is 1000 such arrestors, customers seek advice from
litres. us.
22 Water Corporation Building and Plumbing Handbook 23
9 Development Issues

Licensed plumbers need to be aware that 9.1 Isolation of internal lines Isolation of internal lines
issues affecting plumbing work may arise At the time of subdivision, internal water or
during the development of land. sewer lines may be isolated from the building
A development of land includes: they are servicing. The problem is more severe
New internal B
if the sewer connection point or the water sewer main
o amalgamation by subdivision of two Sewer line
new lot 1
or more lots; meter is isolated, as illustrated in the Isolation
A
o any green title or strata subdivision; of internal lines diagram (on page 25).
and
o any building on a land parcel.
An example on the next page highlights where
The main areas that plumbers should be a single lot was subdivided into two, existing

new boundary
aware of are: internal water and sewer lines extend into the
new Lot 2. Prior to the subdivision being
o internal sewer or water lines that extend finalised, it is necessary to provide a new
into another lot when a lot is subdivided; sewer connection point at B and realign the
o water meters located in a new lot separated sewer line going to A, so it is entirely within new lot 2

new internal
from an existing house; the new Lot 1 to a new connection point at B.

water line
o sub-meters that may be required on a
multi-residential development or strata The water connection point at X would need X Water Main

scheme. to be relocated to Y and an additional meter


provided for in the subdivision process.
Plumbing should be rationalised for any
development, to minimise the number of
meters and sewer connection points. This
makes the property easier to manage and
may reduce the annual service charges for the
land.
9.2 Strata schemes In order to do this the developer may choose to
Through the strata subdivision process install dormant plumbing (water and sewer)
--
- Water Corporation will ensure that access and/or relocate any existing internal plumbing.
to our services is available at the boundary Dormant sewer or water lines are a section of
of the Strata Scheme in accordance with our internal plumbing laid in the ground for future
Operating Licence requirements and connection of a building to the sewer or water
servicing standards. The developer is mains. Dormant lines may be laid during the
responsible for ensuring that all lots development of the strata to avoid the need for
proposed under the Strata Scheme have strata neighbours to intrude upon each other
adequate access to these services, and that to install the lines after the scheme is
any existing plumbing is adequately established.
protected.

Refer to the Plumbing Licencing Boards


Technical notes on Survey Strata Lots for
further information on strata schemes.
24 Water Corporation Building and Plumbing Handbook 25
9.3 Metering For all sub-meter installations, the work must
Access comply with the standards and instructions
issued by Water Corporation at the time of
Water Corporation is the owner of the meters
the work being carried out. 30cm 120cm
and associated fittings. It is illegal to tamper clearance needed clearance needed
with any part of the meter and customers Water Corporation is responsible for horizontally around above the meter
the meter
have an obligation to maintain 24/7 clear maintaining the sub-meter and tails. The
access for the meter to be read and replaced. strata company is responsible for all
internal pipework which must be
Multi-unit developments
undertaken by a licensed plumber.
There are two metering options available to
all residential properties and non-residential Further information about the installation
strata properties that require metering at an requirements and application process can 30cm 10-1Scm above GL
individual unit level. be found at: Water Corporation > Applying
for Services
Upon request, Water Corporation may
provide multiple unit developments with Above ground meter installation clearance
metering facilities under one of the options distances
below.
o As a safety requirement, bridging cable
1. Fit individual meters at an agreed road (earthing strap) must be attached onto the
frontage adjacent to a water main for vertical copper pipe on both ends of the
individually subdivided, or strata titled lots. meter assembly.
o Vertical pipework is not to be set in
2. Fit a master meter at an agreed road concrete, brick paving, bitumen etc, as
frontage adjacent to a water main which some flexibility in the pipework is required 20mm Water meter assembly requirements o For properties with multi metering
connects to sub-meters via private internal for meter replacement. Note: Water Corporation does not have arrangements, Water Corporation is only
plumbing. o Water Corporation personnel must have control over what the plumbing industry can responsible for tail to tail assembly.
access to meter assembly at all times. install and can only apply its specifications o No branch or fitting to be connected within
o PVC and/or MDPE (plastic) fittings or pipe, and requirements when asked to take over one metre (1,000mm) from valve.
if used, must be at least 225mm below the metering for the property.
ground level.
o The clearances shown here are required to o Existing installations are likely to be fitted
facilitate meter reading and/or replacement with a stopcock.
when required. This is a requirement under o All new 20mm installation are being fitted
Water Services Regulations 2013, N23. with the right angle ball valve.
26 Water Corporation Building and Plumbing Handbook 27
10 Buildings

10.1 Proposals to construct, demolish or Builders and licensed plumbers working for
Overall space required alter buildings Land Developers should also consider the
for reading and replacement of meter is 700mm
Any person proposing to build, demolish or following points.
alter any building or construction activity in 1. That our water and wastewater services
an area served by a Water Corporation water are adequate for the proposed building or
Customer
or sewer main must obtain approval and pay development. In some circumstances, it
Water Corporation Responsibility Responsibility
the prescribed application fees prior to will be necessary to extend or enlarge the
requirement under section 82(1) of the Water property.
Approximate face to face length: 300mm Services Act).
80mm to 2. Wherever possible, all survey levels provided
Rotate valve
should be in Australian Height Datum (AHD)
60mm to
Rotate elbow
Water Corporation provides guidance for
Tail Tail single residential and some other building as it assists in ensuring the building can be
(40mm Long) (40mm Long)
types. Builders must refer to our Residential adequately served by the sewer, and makes
Meter
Guidelines for Designers document to assist the design of piling easier. This is particularly
with the self-assessment of design prior to important where the ground level has been
lodgement of an application. altered.
Water Flow
The self-assessment allows you to identify 3. Builders are responsible for establishing the
the requirements to protect our sewer assets location of sewer connection points prior
Finished Ground Level
from the effects of building and construction to starting any works. In the event that the
activities. It is intended to maintain adequate connection point cannot serve the proposed
access to Water Corporation sewer assets building, or it is not located in the correct
whilst assisting the protection of your position, the builder will be responsible
proposed works from any future damage. for any additional works necessary. This is
The Residential Guidelines for Designers can particularly important in the redevelopment
only be applied to the following building or of lots in older suburbs.
construction activities within the prescribed 4. In some circumstances, the builder
Installing meters below ground level proximity of our sewer mains: may need to have the location of Water
in a box o Single residential buildings Corporation’s pipe work confirmed by
Currently only one meter box has been o Single Storey Addition/Alteration to existing survey.
residential buildings
assessed by Water Corporation as acceptable: o Below ground swimming pools, spas or 5. Licensed plumbers are required by law to
tanks
o METER BOX MMR 21099, Service Box, apply to Water Corporation prior to
o Sheds
Meter, Supplier --
- Stockbrands Co Pty Ltd, connecting a property to the sewer mains.
o Retaining walls.
53 Edward St, Osborne Park, WA 6017. On some occasions this application is
o D1200 METER BOXES are not acceptable. For any other building and construction made by the builder, however if in doubt
activities not listed above, you will need to licensed plumbers are advised to contact
refer to our Protection of Services Manual the Corporation on 13 13 95.
(Guidelines for Designers).

28 Water Corporation Building and Plumbing Handbook 29


11 Electrical Risks

6. Licensed plumbing contractors are required To eliminate any potential risk caused by
to submit a drainage plumbing diagram underground directional drilling activities
when they are the responsible person for into private, local government or Water
drainage plumbing work that involves the Corporation sewers and drains, it’s
installation, alteration or extension of important to refer to Western Power for
drainage plumbing. Refer to the Building more information:
Commission Drainage Plumbing Diagram
www.westernpower.com.au/safety-access/
homepage for further information.
working-near-our-network/
10.2 Sewer Main Alignments
Licensed plumbers must exercise caution when
Information on Sewer Main Alignments can clearing blockages in or near sewer lines
be found in the Residential Guidelines for particularly in the front verge. The safety of
Designers document. plumbers is at risk if cutting tools are used to
Please refer to our full Guidelines for Designers clear the blockage that is potentially caused by
manual for guidance to protect Water live electrical cables.
Corporation’s water, sewer and drainage Warning --
- Licensed plumbers:
Power companies and their electrical
services, and requirements for access to those contractors are required to take all prescribed o Mechanical devices and high pressure
services, where building and/or construction precautions to prevent the cross boring of cutters can cut into a cable, presenting
activities are carried out in their proximity. electrical cables into sewers, drains and other a serious electric shock or electrocution.
pipes and conduits. However, Western Power o Never attempt to clear a blockage unless
If you require assistance please contact
advises that live cables can often penetrate you are absolutely certain that a power
us on 13 13 95 or email building.services@
drainage pipes, storm water pipes, sewer cable is not the cause.
watercorporation.com.au
mains and sewer connections to properties. o Do not make assumptions about the
For more information please refer to the installation or location of underground
Western Power website. power cables.

This occurs due to high boring activity levels. In


some instances this may be undetected until
the property owner or tenant reports and
seeks to clear a sewer or drain blockage.

30 Water Corporation Building and Plumbing Handbook 31


12 Partnering with
Water Corporation

Before commencing work, determine if 12.1 SewerSmart© Plumbers systems; and


property in the vicinity of a blockage is Partnering with metropolitan plumbing o installing flow regulators and all other water
connected to underground power. If you are companies, the SewerSmart© program works efficient plumbing products.
unsure, the following may indicate that an under a Memorandum of Understanding in Water Corporation encourage customers to
underground power cable may have caused accrediting SewerSmart© Plumbers, who are utilise the services offered by endorsed
the blockage. available 24 hours a day, 7 days a week, 365 Waterwise Plumbers, with their contact details
What to look for at the property days a year to answer and attend customer listed on our website.
calls in relation to sewer blockages. As 90% of
o Is there a green dome on the property The Waterwise Plumbers program has become
calls to Water Corporation for sewer blockages
boundary? an integral component of the Enviro West
are found to be the customer’s responsibility,
o Is there an underground pit within the plumber training and endorsement program
the process aids customer satisfaction.
property or on the verge? facilitated by the Master Plumber & Gasfitters
o Are there any signs of recent excavations? SewerSmart© Plumbers undertake an Association.
o Does the property have overhead or accreditation course in understanding and
underground power from the street to the reading sewer plans; have access to our 12.3 Backflow Smart Testers Program
building? mapping system, providing quicker and easier The Backflow Smart Testers Program allows
access to internal sewer connections, and are plumbing businesses with accredited backflow
What to look for in the street
given a fast-tracked reimbursement in relation testers who register and agree to submit test
o Is the area serviced by underground power to SewerSmart© call outs. reports through our web application.
to either multiple or single properties?
o Are there poles with cables attached that To obtain SewerSmart© Plumber details To be eligible for the Backflow Smart Testers
run from the top of the pole to the ground? contact Program, all of your certified backflow
o Is there a green cabinet displaying a danger 13 13 75 or visit our website on: testers must also be separately registered to
warning sign? www.watercorporation.com.au/faults/sewer- submit test report forms online, visit
o Are there any signs of recent excavations? blockage-or-overflow www.watercorporation.com.au/
backflowsmartsignup.
Tools and equipment 12.2 Waterwise Plumbers
Water Corporation has had a rewarding The program advantages are:
Consider the use of alternative blockage
cleaning tools, such as lower pressure jet- association with the plumbing industry
o Registered testers will have their business
washers. CCTV technology can also be used through the Waterwise Plumbers program,
details listed on our website, and will be
to positively identify the cause of blockages. developed in 2003.
identifiable to our customers, who may
Water Corporation offer a training course, choose to engage a Backflow Smart Tester
hosted by the Master Plumber and Gasfitters to undertake work on their behalf.
Association, for plumbers who wish to join o Customers will have access to an online
Assistance with locating underground power the program. The training covers all activities search tool for backflow testing companies
Western Power on 13 13 51 related to water efficiency and plumbing. in their area.
https://westernpower.com.au/ o Water Corporation backflow test reminder
Training includes: and compliance letters will refer customers
Horizon Power on 13 23 51 o domestic water auditing; to the Backflow Smart Testers Program.
https://horizonpower.com.au/ o installing and plumbing of domestic
rainwater tanks;
o installing grey water systems;
o installing hot water circulation pumps and
32 Water Corporation Building and Plumbing Handbook 33
13 Legal Obligations 14 Appendix

The Legal References table describes some of 14.1 Fire Service configurations for backflow protection
the responsibilities plumbers have under the
following water legislation:
Explanation of notes to backflow boundary protection diagrams
o Water Services Act 2012
o Water Services Regulations 2013 Note 1 All backflow prevention devices internal to the property boundary or downstream
of a Water Corporation service (metered or otherwise that shall be located just
These requirements recognise the licensed
within a property boundary) must comply according to the following plumbing
plumber’s role in protecting water and
standards: AS/NZS 3500.1:2018, AS/NZS 2845.1:2010, AS 2845.2:2010 and AS
sewerage infrastructure and ensure that the
2845.3:2010.
interests of all customers are protected.
Note 2(a) A suitably rated backflow prevention device must be installed at the boundary
based upon the maximum level of backflow risk assigned to the Customer’s
property.

Note 2(b) If the water service is <=25 mm in size and the customer’s property is rated as a
LOW form of backflow risk then Water Corporation’s water service meter shall
provide the necessary level of low backflow protection as the service meter has an
integral dual check valve as part of its design.

Note 2(c) If the water service is >25 mm in size and the customer’s property is rated as a
LOW form of backflow risk then a low rated form of backflow prevention must be
installed, as a minimum, downstream of the service meter.

Note 2(d) Where testable mechanical valve type backflow prevention devices are installed, the
isolation valve upstream of the line strainer and the isolation valve immediately
after the device must be resilient seated.

Note 2(e) Where flow rate and/or pressure does not allow the use of a mechanical valve
type backflow prevention device then refer to note 3.

Note 3 An Air Gap (AG) / Break Tank (BT) provides a low level form of backflow prevention
protection. A Registered Air Gap (RAG) / Registered Break Tank (RBT) provides a
high level form of backflow prevention protection and is commonly used as an
alternative form of low / medium or high level of backflow prevention protection in
scenarios where flow rate and / or pressure becomes a possible operational issue
to a customer and / or DFES (Department of Fire and Emergency Services).

Note 4 Except with Water Corporation’s written authority, no branch or fitting shall
be connected to a private service pipe within a distance of one meter on the
consumer’s side of our stop-cock or water meter.

34 Water Corporation Building and Plumbing Handbook 35


14.2 Backflow boundary protection diagrams
15 Contact Us
Typical mechanical valve backflow Typical AG/BT backflow containment
containment protection arrangement protection arrangement for fire
for fire services boundary services at boundary

Water Corporation drinking water Water Corporation drinking water

size to be size to be
determined isolation valve determined isolation valve BuilderNet© is the most effective and efficient way of lodging your
by customer or equivalent by customer or equivalent
requirements requirements service connection and building applications with Water Corporation.

as close to the
Water Faults, emergencies and security 13 13 75
Corporation
boundary as practically meter 24 Hours

}
possible no branch
connections permitted
at this zone
double check
detector
assembly
no branch connections
permitted at this zone
} AG/BT backflow
prevention Building services and subdivision enquiries
8am --
13 13 95
- 5pm weekdays

BuilderNet helpline (08) 9424 8411


8am --
- 5pm weekdays
fire hydrant

fire hydrant
Waterwise helpline 13 10 39
hydrant hydrant
or booster or booster
24 hours
cabinet cabinet
booster inlets

booster inlets
Website www.watercorporation.com.au
Email building.services@watercorporation.com.au

flow flow

Typical mechanical valve backflow Typical AG/BT backflow containment


containment protection drinking protection arrangement for drinking
water services at boundary (noteS) water services at boundary (noteS)

WaterCorporation
Water Corporationdrinking
drinkingwater
water Water Corporation drinking water

sizetotobe
size be size to be
determined
determined isolationvalve
isolation valve determined isolation valve
by customer
by customer orequivalent
or equivalent by customer or equivalent
requirements
requirements requirements

Water Corporation Water Corporation }


meter meter

no branch
connections
permitted in this
zone (note 4)
mechanical valve
assembly appropriate
to teh risk level
no branch
connections
permitted in this
zone (note 4)
}} AG/BT backflow
prevention
(note 2 and 3)

flow flow