Sei sulla pagina 1di 16

1.

METHODOLOGY AREA WISE:


1.1 PODIUM AREA
Surface Preparation:

Careful surface preparation is essential for optimum finish and durability. The
surface needs to be made clean,
dry and sound, free of any contamination by wire brushing, which may harmfully
affect the adhesion of the
membrane. Maximum moisture content should not exceed 5%. Substrate compressive
strength should be at
least 25 Mpa, cohesive bond strength at least 1.5 MPa.

New concrete structures need to dry for at least 28 days. Old, loose coatings,
dirt, fats, oils, organic
substances and dust need to be removed by a grinding machine. Possible surface
irregularities need to be
smoothened. Any loose surface pieces and grinding dust need to be thoroughly
removed.

Clean the wall and floor junctions with compressed air and make angle fillet /
watta with cement : sand mortar
admixed with SBR latex (5% by weight of cement) at the junction of wall and floor.

Repair of cracks & joints:

The careful sealing of existing cracks and joints before the application is
extremely important for long lasting
waterproofing results. Clean concrete cracks and hairline cracks, of dust, residue
or other contamination.
Prime locally with the SBR Latex and allow 2-3 hours to dry. Fill all prepared
cracks with polymer modified
cement sand mortar admixed with SBR Latex .

Clean concrete joints and control joints of dust, residue or other contamination.
Widen and deepen joints (cut
open) if necessary. The prepared movement joint should have a depth of 10-15 mm.
The width: depth ratio of
the movement joint should be at a rate of approx. 2:1. Treat the joints with
polymer modified mortar cement :
sand admixed with SBR Latex (5% by weight of cement). Drill holes at 45 deg angle
and insert PVC nozzles
and needs to be injected by cement slurry admixed with expansive admixture
Pidicrete AM (225gms / bag of
cement).

Application of waterproofing cum Root resistant membrane:

Prime absorbent surfaces like concrete, cement screed with moisture insensitive
Pidipoxy MIEP primer. Allow
the primer to cure for 6 � 8 Hrs to tacky condition.

Stir Dr. Fixit Flexi PU 270 well before using. Pour Flexi PU 270 onto the primed
surface and lay the first coat
over the RCC slab by roller or brush, until all surface is covered. You can use
airless spray allowing a
considerable saving of manpower. After 12-18 hours (not later than 48 hours) apply
another layer of the Flexi
PU 270. The coverage shall be maintained at 1.5 Kg/sqm to achieve Dry Film
Thickness of 1.2mm.
The membrane (both the coats) shall be applied over the angle fillet and shall be
extended over the vertical
wall upto height such that it is terminated at 300mm above Finish Floor Level or
Soil Filling Level.

Allow the membrane to air cure for minimum 3 � 4 days before any activity over it.

Protection & Slope over the waterproof membrane (Horizontal Areas):

Lay 200 GSM geotextile membrane over the waterproofing membrane to create a
separation layer as well a
protection layer from screeding. The geotextile layer shall have 100 mm overlap and
spot bonded and shall be
extended at the wall upto 100mm above the slab floor.

Lay Concrete screed of M20 grade concrete (RMC) over the geotextile membrane
admixed with 12mm dia.
poly-propylene fibers at 0.9Kg/cum to avoid shrinkage cracks so to receive pavers
or Landscaping systems
and to provide slope of 1 : 100. The slope shall be provided in such a way that
there is 40mm minimum
thickness at the point of drain outlet. The screed shall be finished rough with
broom and in shape of watta /
rounding at the wall and floor junctions. The screed shall be cured with water for
minimum 14 days.

After the screed is cured remove all the water, cut joints in screed with grinder
of 10mm wide and 30mm deep
to form panels of 4M X 4M. Clean the joints with compressed air to make it dust
free and leave it for 1 or 2
days to remove the moisture from the joints.

Pack in backer rod of round cross-section inside the joint upto 6mm depth left at
top.

This joint shall be applied with PU primer. Allow to dry for minimum 2 � 3 Hrs to
tacky condition.

Then fill the joints with PU sealant. Allow the sealant to air cure for 2 � 3 days
before covering or laying of
further landscape / hardscape layers / parking layers.

Protection over the waterproof membrane (Vertical Areas):


Over the waterproofing membrane apply 2 coats of Epoxy bonding Agent conforming to
Shear Bond strength
as per ASTM C 881. Sprinkle sand over the primed surface at 2 � 3Kg/sqm when the
bonding agent is wet.
Allow it to dry to form firm key for the plaster.

Lay 20mm thick plaster in two coats over the prepared surface of cement sand mortar
admixed with integral
waterproof compound conforming to IS 2645-2003, Pidiproof LW+

For Landscaped portions (Grass & Trees upto 2MTR Height):

The Rolled matrix Drainage layer with filter medium as specified by Landscape
architect / engineer shall be
laid over the protection screed before soil filling.

For Planter Boxes: Separate Anti-Root Treatment above the screed (Trees above 2MTR
height):

Prime the surface with solvent based bituminous primer.

Stick peel and Lay SBS modified cold applied preformed Anti-root membrane Samshield
AR over the primer.
The overlaps shall be minimum 50mm selvedge and self sticking.

The Rolled matrix Drainage layer with filter medium as specified by Landscape
architect / engineer shall be
laid over the protection screed before soil filling.

1.2 TERRACE AREA


1.2.1 Horizontal Areas (Roof Slab):
Surface Preparation:

Careful surface preparation is essential for optimum finish and durability. The
surface needs to be made clean,
dry and sound, free of any contamination by wire brushing, which may harmfully
affect the adhesion of the
membrane. Maximum moisture content should not exceed 5%. Substrate compressive
strength should be at
least 25 Mpa, cohesive bond strength at least 1.5 MPa.

New concrete structures need to dry for at least 28 days. Old, loose coatings,
dirt, fats, oils, organic
substances and dust need to be removed by a grinding machine. Possible surface
irregularities need to be
smoothened. Any loose surface pieces and grinding dust need to be thoroughly
removed.

Clean the wall and floor junctions with compressed air and make angle fillet /
watta with cement : sand mortar
admixed with SBR latex (5% by weight of cement) at the junction of wall and floor.

Repair of cracks & joints:

The careful sealing of existing cracks and joints before the application is
extremely important for long lasting
waterproofing results. Clean concrete cracks and hairline cracks, of dust, residue
or other contamination.
Prime locally with the SBR Latex and allow 2-3 hours to dry. Fill all prepared
cracks with polymer modified
cement sand mortar admixed with SBR Latex .

Clean concrete joints and control joints of dust, residue or other contamination.
Widen and deepen joints (cut
open) if necessary. The prepared movement joint should have a depth of 10-15 mm.
The width: depth ratio of
the movement joint should be at a rate of approx. 2:1. Treat the joints with
polymer modified mortar cement :
sand admixed with SBR Latex (5% by weight of cement). Drill holes at 45 deg angle
and insert PVC nozzles
and needs to be injected by cement slurry admixed with expansive admixture
Pidicrete AM (225gms / bag of
cement).

Application of waterproofing membrane:

Prime absorbent surfaces like concrete, cement screed with moisture insensitive
Pidipoxy MIEP primer. Allow
the primer to cure for 6 � 8 Hrs to tacky condition.

Stir Dr. Fixit Flexi PU 270 well before using. Pour Flexi PU 270 onto the primed
surface and lay the first coat
over the RCC slab by roller or brush, until all surface is covered. You can use
airless spray allowing a
considerable saving of manpower. After 12-18 hours (not later than 48 hours) apply
another layer of the Flexi
PU 270. The coverage shall be maintained at 1.5 Kg/sqm to achieve Dry Film
Thickness of 1.2mm.

The membrane (both the coats) shall be applied over the angle fillet and shall be
extended over the vertical
wall upto height such that it is terminated at 300mm above Finish Floor Level.

Allow the membrane to air cure for minimum 3 � 4 days before any activity over it.

Protection & Slope over the waterproof membrane (Horizontal Areas):


Lay 200 GSM geotextile membrane over the waterproofing membrane to create a
separation layer as well a
protection layer from screeding. The geotextile layer shall have 100 mm overlap and
spot bonded and shall be
extended at the wall upto 100mm above the slab floor.

Lay Concrete screed of M20 grade concrete (RMC) over the geotextile membrane
admixed with 12mm dia.
poly-propylene fibers at 0.9Kg/cum to avoid shrinkage cracks so to receive pavers
or Landscaping systems
and to provide slope of 1 : 100. The slope shall be provided in such a way that
there is 40mm minimum
thickness at the point of drain outlet. The screed shall be finished rough with
broom and in shape of watta /
rounding at the wall and floor junctions. The screed shall be cured with water for
minimum 14 days.

After the screed is cured remove all the water, cut joints in screed with grinder
of 10mm wide and 30mm deep
to form panels of 4M X 4M. Clean the joints with compressed air to make it dust
free and leave it for 1 or 2
days to remove the moisture from the joints.

Pack in backer rod of round cross-section inside the joint upto 6mm depth left at
top.

This joint shall be applied with PU primer. Allow to dry for minimum 2 � 3 Hrs to
tacky condition.

Then fill the joints with PU sealant. Allow the sealant to air cure for 2 � 3 days
before covering or laying of
further landscape / hardscape layers / parking layers.

Protection over the waterproof membrane (Vertical Areas):

Over the waterproofing membrane apply 2 coats of Epoxy bonding Agent conforming to
Shear Bond strength
as per ASTM C 881. Sprinkle sand over the primed surface at 2 � 3Kg/sqm when the
bonding agent is wet.
Allow it to dry to form firm key for the plaster.

Lay 20mm thick plaster in two coats over the prepared surface of cement sand mortar
admixed with integral
waterproof compound conforming to IS 2645-2003, Pidiproof LW+

1.2.2 Vertical Areas (Parapet Walls):


Surface Preparation:
Surface under treatment should be sound, made clean and free from dirt, oil and
other loose material.

Masonry / plastered / concrete surfaces should be fully cured (minimum 28 days)


prior to application.

All surface cracks, undulations and voids must be repaired appropriately before
application. All cracks above
5mm needs to be cut to "V" shape, cleaned with air, applied with SBR latex bonding
agent, SBR Latex and
shall be filled with polymer modified mortar, cement:sand:SBR Latex (Mix =
1:4:0.1). All cracks below 5mm
shall be cut opened, cleaned and shall be filled with Crack X shrinkfree.

The entire surface to be coated must be in SSD condition prior to application of


coating.

Application:

Mix the prepacked Fastflex using slow speed mechanical mixer, add powder component
slowly to the polymer
in a clean container.
Stir till smooth and homogeneous slurry, without any lumps, is achieved. Do not
dilute with water.
Allow the mixed slurry to stand for 5-10 minutes for releasing trapped air during
mixing.

Apply 1st coat of Fastflex slurry by brush, roller or trowel. Allow it to dry
completely for 6-8 hrs.
Apply 2nd coat of Fastflex slurry by brush, roller or trowel over the first coat.
The second coat shall be applied in
90 degree direction to the first coat.

The coverage shall be maintained to be 2.2Kg/sqm to achieve DFT of 1.5mm.


Allow the coating to air cure for 7 days before application/installation of
cladding.

Protection to waterproof coating (Vertical areas):

Apply bond coat over the waterproof coating with modified cement slurry with SBR
Latex,
Sprinkle sand over the bond coat when it is wet @ 2-3 kg/sqm and allow it to dry to
form firm key to the plaster,
Lay 12mm thick plaster in two coats over the prepared surface of cement sand mortar
admixed with integarl

waterproofing compound Pidiproof LW+


1.3 TOILETS / BATHROOMS
Surface Preparation:
Clean the surfaces with Wire brushing & washing the entire surface area with water
jet, so as to make the

surface totally dust free to receive the treatment.


Fill water to the entire area upto sunk height for 24Hrs to 48 Hrs to check all the
weak points / leakages in the
slab. Mark those areas and empty the water.

All the points where marking is done / hollow areas, drill holes, fix PVC nozzles
at interval as per the
requirement and judgement of the manufacturer. Inject cement slurry admixed with
expansive agent Pidicrete
AM @ 225 gms per bag of cement using gravitational pressure / grout pump to seal
the areas.

Clean the wall and floor junctions with compressed air and make angle fillet /
watta with cement : sand mortar
admixed with SBR Latex (5% by weight of cement) at the junction of wall and floor.

Repair of cracks:

The careful sealing of existing cracks and joints before the application is
extremely important for long lasting
waterproofing results. Clean concrete cracks and hairline cracks, of dust, residue
or other contamination.
Prime locally with the SBR Latex and allow 2-3 hours to dry. Fill all prepared
cracks with polymer modified
cement sand mortar admixed with SBR Latex.

Application of waterproofing membrane:

Shake the liquid component well to a homogenous milky colour.

Always add powder to polymer under constant stirring using slow speed paddle mixer
to achieve smooth and
homogeneous slurry.
Allow to stand for about 5 mins to release entrapped air.
Apply first coat of Dr. Fixit Pidifin 2K all over the floor surface in bathroom
extending on side walls up to full

height covering the angle fillet.

While the coating is still wet place the glass fibre mesh (2.5 mm x 2.5 mm grid) on
the angle fillet extending
about 50 mm on floor surface and 50 mm on walls and allow it to soak completely
with material.
Before the coating dries apply immediately another coat of Dr. Fixit Pidifin 2K
only on the angle fillet
completely covering the mesh thus embedding it firmly between two coats of Dr.
Fixit Pidifin 2K.

Allow the coating to dry completely for 6 to 8 hrs before applying second coat all
over the floor area and walls
upto full height.
The angle fillet area now has three coats of Dr. Fixit Pidifin 2K with mesh
embedded firmly within the coating.

The coverage of the coating shall be 1.5 Kg/sqm to achieve DFT of 1mm,
Allow the coating to dry completely for 3-4 days. Do not cure with water but keep
coating moist using wet
hessian cloth.

Pond Test:

Ponding of the slab shall be carried out to check the efficacy of waterproof
coating by filling water to 50mm
depth for 24-48 Hrs.

Protection to waterproof coating (Horizontal areas � Sunk slab):

Lay 20mm cement sand mortar to provide protection & bedding over the waterproof
coating.
Lay all the pipes in position.
Lay AAC blocks in pattern to create slope and fill the sunken portions.
Fill the joints of the AAC blocks with cement:sand mortar admixing waterproofing
compound, Pidiproof LW+
Lay 20mm screed over the AAC block of 1:4 cement:sand mix brooming the surface and
rounding the

junctions of floor and wall.


Ponding and curing shall be done for 7 days.

Protection to waterproof coating (Vertical areas):

Apply bond coat over the waterproof coating with modified cement slurry with SBR
Latex,
Sprinkle sand over the bond coat when it is wet @ 2-3 kg/sqm and allow it to dry to
form firm key to the plaster,
Lay 12mm thick plaster in two coats over the prepared surface of cement sand mortar
admixed with integarl
waterproofing compound Pidiproof LW+

Tiling Work:

All the tiling work shall be carried out over the protective plaster / layer with
ROFF NonSkid Tile Adhesive and
the joints shall be filled with epoxy tile grout. (all as per manufacturer
specification).

1.4 SWIMMING POOL / WATERBODIES


Surface Preparation:
Surface under treatment should be sound, made clean and free from dirt, oil and
other loose material.
Concrete surfaces should be fully cured (minimum 28 days) prior to application.

All the construction joints shall be opened in U groove and shall be cleaned and
filled by C:M (1:4) modified
with SBR latex, Pidicrete URP.

All surface cracks, undulations and voids must be repaired appropriately before
application. All cracks needs
to be cut to "V" shape, cleaned with air, applied with SBR latex bonding agent,
Pidicrete URP and shall be
filled with polymer modified mortar, cement:sand:Pidicrete URP (Mix = 1:4:0.1). The
entire surface to be
coated must be in SSD condition prior to application of coating.

Application of waterproofing membrane:

Mix the prepacked Dr. Fixit Fastflex using slow speed mechanical mixer, add powder
component slowly to the
polymer in a clean container.
Stir till smooth and homogeneous slurry, without any lumps, is achieved. Do not
dilute with water.
Allow the mixed slurry to stand for 5-10 minutes for releasing trapped air during
mixing.

Apply 1st coat of Fastflex slurry by brush, roller or trowel. Allow it to dry
completely for 6-8 hrs.
Place the glass fibre mesh (2.5 mm x 2.5 mm grid) at angle fillet portions and at
all construction joint areas
when the 1st coat is wet.

Apply 2nd coat of Fastflex slurry by brush, roller or trowel over the first coat.
The second coat shall be applied in

90 degree direction to the first coat.


Apply 3rd coat of Fastflex slurry by brush, roller or trowel over the second coat.
The third coat shall be applied
in 90 degree direction to the second coat.

The coverage shall be maintained to be 1Kg/sqm/coat. All the three coats shall be
applied on floor and wall
upto full height extending to the other side of the wall upto 200mm depth.
Allow the coating to cure for 3 � 4 days before application of protection layer.

Pond Test:

Ponding of the slab shall be carried out to check the efficacy of waterproof
coating by filling water to full depth
for 48 Hrs. Remove water after 48 Hrs. Allow the coating to dry for 24 Hrs.

Protection to waterproof coating (Horizontal areas):

Lay cement sand mortar to provide protection to the coating laid to slope to the
drainage point.

This mortar shall be minimum 40mm thick and shall admixed with integarl
waterproofing compound, Pidiproof
LW+.

Protection to waterproof coating (Vertical areas):

Apply bond coat over the waterproof coating with modified cement slurry with SBR
Latex,
Sprinkle sand over the bond coat when it is wet @ 2-3 kg/sqm and allow it to dry to
form firm key to the plaster,
Lay 15mm thick plaster in two coats over the prepared surface of cement sand mortar
admixed with integarl

waterproofing compound Pidiproof LW+

Tiling Work:

All the tiling work shall be carried out over the protective plaster / layer with
ROFF Glass Tile Adhesive and the
joints shall be filled with epoxy tile grout. (all as per manufacturer
specification).
1.5 WATER TANK INTERNAL AREA (OHT / UGT)
Surface Preparation:
Surface under treatment should be sound, made clean and free from dirt, oil and
other loose material.

Masonry / plastered / concrete surfaces should be fully cured (minimum 28 days)


prior to application.
All the construction joints shall be opened in U groove and shall be cleaned and
filled by C:M (1:4) modified
with SBR latex, Pidicrete URP.

All surface cracks, undulations and voids must be repaired appropriately before
application. All cracks above
5mm needs to be cut to "V" shape, cleaned with air, applied with SBR latex bonding
agent, Pidicrete URP and
shall be filled with polymer modified mortar, cement:sand:Pidicrete URP (Mix =
1:4:0.1). All cracks below 5mm
shall be cut opened, cleaned and shall be filled with shrinkfree crack filling
material, Crack X shrinkfree.

The entire surface to be coated must be in SSD condition prior to application of


coating.

Application of waterproofing membrane:

Mix the prepacked Dr. Fixit Fastflex using slow speed mechanical mixer, add powder
component slowly to the
polymer in a clean container.
Stir till smooth and homogeneous slurry, without any lumps, is achieved. Do not
dilute with water.
Allow the mixed slurry to stand for 5-10 minutes for releasing trapped air during
mixing.

Apply 1st coat of Fastflex slurry by brush, roller or trowel. Allow it to dry
completely for 6-8 hrs.
Apply 2nd coat of Fastflex slurry by brush, roller or trowel over the first coat.
The second coat shall be applied in
90 degree direction to the first coat.

The coverage shall be maintained to be 2.2Kg/sqm to achieve DFT of 1.5mm.


Allow the coating to cure for 3 � 4 days before application of protection layer.

Protection to waterproof coating (Horizontal areas):

Lay cement sand mortar to provide protection to the coating laid to slope to the
drainage point.

This mortar shall be minimum 40mm thick and shall admixed with integarl
waterproofing compound, Pidiproof
LW+.
Protection to waterproof coating (Vertical areas):

Apply bond coat over the waterproof coating with modified cement slurry with SBR
Latex,
Sprinkle sand over the bond coat when it is wet @ 2-3 kg/sqm and allow it to dry to
form firm key to the plaster,
Lay 15mm thick plaster in two coats over the prepared surface of cement sand mortar
admixed with integarl

waterproofing compound Pidiproof LW+

Protection cum Hygiene coat:

First stir the Base and Hardener of Dr. Fixit Dampguard thoroughly in their
individual packs to achieve the

uniform consistency.
Pour the Base part in appropriate container followed by the Hardener part and mix
them thoroughly together to
a homogeneous smooth paste.

Dilute the mixed compound with water (In ratio of 1 part Base: 1 part Hardener: 1
part water) by slow addition
and mix it thoroughly until a brushable consistency is obtained.
Apply the first brush coat of mixed of Dampguard. Allow drying for 6 to 8 hrs.
Apply second brush coat of mixed Dampguard. Allow it to cure completely for 24
hours.
Allow the coating to cure for minimum 4 days before doing ponding test.
The coverage shall be 7.5 to 8.5 m2 per kg per coat.

Pond Test:

Ponding of the tank shall be carried out to check the efficacy of waterproof
coating by filling water to the tank
as instructed by the structural engineer and check for 24-48 Hrs.
1.6 STPS / ETPS
Surface Preparation:
Surface under treatment should be sound, made clean and free from dirt, oil and
other loose material.

Masonry / plastered / concrete surfaces should be fully cured (minimum 28 days)


prior to application.
All the construction joints shall be opened in U groove and shall be cleaned and
filled by C:M (1:4) modified
with SBR latex, Pidicrete URP.

All surface cracks, undulations and voids must be repaired appropriately before
application. All cracks above
5mm needs to be cut to "V" shape, cleaned with air, applied with SBR latex bonding
agent, Pidicrete URP and
shall be filled with polymer modified mortar, cement:sand:Pidicrete URP (Mix =
1:4:0.1). All cracks below 5mm
shall be cut opened, cleaned and shall be filled with shrinkfree crack filling
material, Crack X shrinkfree.

The entire surface to be coated must be in SSD condition prior to application of


coating.

Application of waterproofing membrane:

Mix the prepacked Fastflex using slow speed mechanical mixer, add powder component
slowly to the polymer
in a clean container.
Stir till smooth and homogeneous slurry, without any lumps, is achieved. Do not
dilute with water.
Allow the mixed slurry to stand for 5-10 minutes for releasing trapped air during
mixing.

Apply 1st coat of Fastflex slurry by brush, roller or trowel. Allow it to dry
completely for 6-8 hrs.
Apply 2nd coat of Fastflex slurry by brush, roller or trowel over the first coat.
The second coat shall be applied in
90 degree direction to the first coat.

The coverage shall be maintained to be 2.2Kg/sqm to achieve DFT of 1.5mm.


Allow the coating to cure for 3 � 4 days before application of protection layer.

Protection to waterproof coating (Horizontal areas):

Lay cement sand mortar to provide protection to the coating laid to slope to the
drainage point.

This mortar shall be minimum 40mm thick and shall admixed with integarl
waterproofing compound, Pidiproof
LW+.
Protection to waterproof coating (Vertical areas):

Apply bond coat over the waterproof coating with modified cement slurry with SBR
Latex,
Sprinkle sand over the bond coat when it is wet @ 2-3 kg/sqm and allow it to dry to
form firm key to the plaster,
Lay 15mm thick plaster in two coats over the prepared surface of cement sand mortar
admixed with integarl

waterproofing compound Pidiproof LW+

Protection & Chemical resistant coating:

Apply with a brush or roller a priming coat of MIEP to the prepared surface. Allow
the primer to dry (maximum
24 hours) before application of solvent free epoxy coating, Pidipoxy EC-SF.

Transfer part A in a suitable clean container, add part B to it and stir with a low
speed electrical drill with
attached paddle stirrer at 250 � 300 rpm for 3 -5 minutes to a homogeneous &
uniform colour mix.

Apply the mix material by brush, roller or airless spray at approximately 3-4 m2 /
kg / coat at 175 -200 microns
DFT.

Intercoat application time is 8 to 10 hours. If earlier coat has cured for longer
duration, roughen the surface by
sanding & then subsequent second coat should be applied.

Allow to cure for minimum 7 days before going for ponding test.

1.7 PIPE INLET / OUTLET


Sealing of Pipe inlet/outlet & Drainage pipes and Bore packing:
The surface of the pipe shall be free from dust, laitance, oil and water. The core
cut shall be free from debris,
dust or any foreign materials.

Unroll the Bathseal tape to required length and wrap around the pipe by removing
release film from one side
of the tape. The length of the tape shall be taken in such a way that the overlap
of tape maintains to be
150mm.

Insert the pipe with Bathseal tape wrapped into the core and support it with
formwork from below the slab or
support from the periphery of the wall so that the gap around the pipe and the core
shall be uniform
throughout.

Remove the release film from other side of the Bathseal tape just before bore
packing activity.

The bore packing shall be done with Non-shrink free flow cementitious grout,
Pidigrout 10M, so that there is no
air entrapment / voids creating.

Mixing of grout: Pidigrout 10M is ready to use cementitious material to be mixed


with water @ ratio of
w/p=0.13 � 10.15 (depending upon the flowability required). The mixing can be done
either with paddle mixer /
trowel.

2. BILL OF QUANTITY (BOQ): As attached separate Excel sheet


NOTE: All the waterproofing works shall be executed by our inhouse Application
company "M/s
NINA waterproofing systems Pvt Limited" and the Composite Supply Apply Corporate
Warranty
shall be given by Pidilite Industries Limited.