Water Flow Rates for Pipe Sizes with Excel

Formulas, Using the Hazen Williams


Formula
Limitations on the Hazen Williams Formula for Water
Flow Rate Calculations
The Hazen Williams formula is an empirical equation that can be used
for turbulent flow of water at typical ambient temperatures. The turbulent
flow requirement is not very limiting. Most practical applications of water
transport in pipes are in the turbulent flow regime. For a review of this
topic see the article, 'Reynolds Number and Laminar & Turbulent Flow.'
Strictly speaking, the Hazen Williams formula applies to water at 60oF,
but it works quite well for a reasonable range of water temperatures
above or below 60oF. For fluids with viscosity different from water, or for
water temperatures far above or below 60oF, the Darcy Weisbach
Equation works better than the Hazen Williams Formula. Click on the
following link for more details about the Darcy Weisbach Equation.
Following presentation and discussion of several forms of the Hazen
Williams equation in the next couple of sections, a downloadable Excel
spreadsheet template will be presented and discussed for making Hazen
Williams water flow rate calculations, using Excel formulas.

Forms of the Hazen Williams Formula


There are several different forms of the Hazen Williams Formula in use
for water flow rate calculations. It can be written in terms of water
velocity or water flow rate, in terms of pressure drop or head loss, and
for several different sets of units. The traditional form of the Hazen
Williams formula is:

U.S. units: V = 1.318 C R0.633 S0.54, where:


 V = water flow velocity in ft/sec
 C = Hazen Williams coefficient, dependent on the pipe material
and pipe age
 R = Hydraulic radius, ft (R = cross-sectional area/wetted perimeter)
 S = slope of energy grade line = head loss/pipe length = hL/L,
which is dimensionless
S.I. units: V = 0.85 C R0.633 S0.54, where:
 V is in m/s and R is in meters
The Hazen Williams Formula is used primarily for pressure flow in pipes,
for which the hydraulic radius is one fourth of the pipe diameter (R =
D/4). Using this relationship and Q = V(πD2/4), for flow in a circular pipe,
the Hazen Williams formula can be rewritten as shown in the next
section.
Water Flow Rates for Pipe Sizes over a Range of
Diameters with the Hazen Williams Formula
For flow of water under pressure in a circular pipe, the Hazen Williams
formula shown above can be rewritten into the following convenient
form:
in U.S. units: Q = 193.7 C D2.63 S0.54, where:
 Q = water flow rate in gal/min (gpm)
 D = pipe diameter in ft
 C and S are the same as above
in S.I. units: Q = 0.278 C D2.63 S0.54, where
 Q is in m3/s and D is in meters
The Hazen Williams formula can also be expressed in terms of the
pressure difference (ΔP) instead of head loss (hL) across the pipe length,
L, using ΔP = ρghL:
In S.I. units, a convenient form of the equation is: Q = (3.763 x 10-6) C
D2.63(ΔP/L)0.54, where
 Q is water flow rate in m3/hr,
 D is pipe diameter in mm
 L is pipe length in m,
 ΔP is the pressure difference across pipe length, L, in kN/m 2
In U.S. units: Q = 0.442 C D2.63 (ΔP/L)0.54, where
 Q is water flow rate in gpm,
 D is pipe diameter in inches
 L is pipe length in ft,
 ΔP is the pressure difference across pipe length, L, in psi
This is a form of the Hazen Williams formula that is convenient to use for
estimating water flow rates for pipe sizes and lengths in U.S. units, as
illustrated in the section after next on the second page.

The second page of this article has a table with values for the Hazen
Williams coefficient, a table with example water flow rate calculations for
several PVC pipe lengths and diameters, and a link to download a
spreadsheet template with Excel formulas to make the water flow rate
calculations.

Values for the Hazen Williams Coefficient


In order to use the Hazen Williams formula for water flow rate
calculations, values of the Hazen Williams coefficient, C, are needed for
the pipe material being used. Values of C are available in many
handbooks, textbooks, and on internet sites. C values typically used for
some common pipe materials are shown in the table at the left.

Example Calculation of Water Flow Rates for Pipe


Sizes and Lengths
The table below was prepared using the equation: Q = 0.442 C
D2.63 (ΔP/L)0.54, with units as given above, to calculate the water flow rates
for PVC pipe with diameters from 1/2 inch to 6 inches and length from 5
ft to 100 ft, all for a pressure difference of 20 psi across the particular
length of pipe. The Hazen Williams coefficient was taken to be 150 per
the table in the previous section.
………………………………………..WATER FLOW RATE IN
GPM………………………………………
…………………. …………………………….Pipe Diameter in
Inches………………………………………
length,
ft……..0.5…….0.75……..1………1.5………2………2.5………3……….4
……….5…………6
….5…………….23……..66……..140…….407…….868…..1560……2520
….5371…..9659……15,601
…10……………16……..45………96……..280…….597…..1073……1733
….3694…..6643……10,730
…15……………13……..36………77……..225…….479……862…….139
3….2968…..5337……..8620
…20……………11……..31………66……..193…….410……738…….119
2….2541…..4569……..7380
…40…………….7………21………46……..132…….282……508……..820
…..1747…..3142……..5076
..100……………4………13………28………81……..172……309……..500
…..1065…..1916……..3096
The table shows a pattern that you should intuitively expect. For a given
pressure difference driving the flow, the water flow rate increases as
diameter increases for a given pipe length and the water flow rate
decreases as pipe length increases for a given pipe diameter. The
equation above can be used to calculate water flow rates for pipe sizes
and lengths with different pipe materials and pressure driving forces,
using the Hazen Williams equation as demonstrated in the table above.