Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Model
Product brand name SENTRON
Product designation ACB
Design of the product IEC 60947-2
Design of the auxiliary switch 4 NO + 4 NC
Design of the operating mechanism Pushbutton
Voltage
Rated insulation voltage Ui 1 000 V
Protection class
Protection class IP IP20
Protective function of the overcurrent release LSIN
Dissipation
Power loss [W] / for rated value of the current / at AC 90 W
/ in hot operating state / per pole
Electricity
Operating current / at 45 °C / rated value 2 500 A
Continuous current / rated value 2 500 A
Adjustable pick-up value current
● of the current-dependent overload release / 2 500 A
Full-scale value
● of instantaneous short-circuit trip unit / initial 3 750 A
value
● of instantaneous short-circuit trip unit / Full- 30 000 A
scale value
Main circuit
Operating frequency
● 1 / rated value 50 Hz
● 2 / rated value 60 Hz
Operating voltage
● at AC / at 50/60 Hz / rated value 690 V
Operating current
● at 40 °C / rated value 2 500 A
● at 50 °C / rated value 2 500 A
● at 55 °C / rated value 2 500 A
● at 60 °C / rated value 2 500 A
● at 65 °C / rated value 2 500 A
● at 70 °C / rated value 2 280 A
Suitability
Suitability for use Plant / motor protection
Adjustable parameters
Adjustable pick-up value current
● of the L-trip / with I4t characteristic / initial value 1 000 A
● of the L-trip / with I4t characteristic / Full-scale 2 500 A
value
Adjustable pick-up value current / of the current- 1 000 A
dependent overload release / initial value
Product details
Product component
● Trip indicator Yes
● Voltage trigger Yes
● undervoltage release No
Product extension / optional / motor drive No
Product function
Product function
● Ground fault protection No
● Phase failure detection Yes
Short circuit
Operational short-circuit current breaking capacity
(Ics)
● at 415 V / rated value 66 kA
● at 500 V / rated value 66 kA
● at 690 V / rated value 50 kA
Maximum short-circuit current breaking capacity (Icu)
● at 415 V / rated value 66 kA
● at 500 V / rated value 66 kA
● at 690 V / rated value 50 kA
Connections
Type of electrical connection / for main current circuit busbar connection
Mechanical Design
Height 440.5 mm
Width 590 mm
Environmental conditions
Ambient temperature
● during operation / minimum -20 °C
● during operation / maximum 70 °C
● during storage / minimum -40 °C
● during storage / maximum 70 °C
Certificates
Reference code
● acc. to DIN EN 61346-2 Q
● acc. to DIN EN 81346-2 Q
other
Miscellaneous
Further information
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3WL1225-2EB42-4GA4-Z N61+T40
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3WL1225-2EB42-4GA4-Z N61+T40
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3WL1225-2EB42-4GA4-Z N61+T40
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
275
327.5
15
440
401
275
15
150
123.5
76
270 85 20 90 130 130 130
570 10 130 45
150 106
210 127
230
30
30 90
13
.5
35
139 128
590
L2
L3
-Q
X8.1
X8.2
X5.2
X6.2
X8.3
X8.4
X6.7
X6.4
X5.8
X5.4
X5.6
X6.14
X6.10
X6.12
X5.10
-A1 ETU45B
I> S
I >> I
N N
-F1
In = 2500A
Ir = 1000A-2500A -S11
Isd = 3125A-30000A
Ii = 3750A - 30000A; MAX=0.8*Ics
IN = 0.5* In / 1* In / OFF
-Q1
-T1
-Y1
-T2
-T3
-F5
X8.10
X6.13
X6.11
X8.9
X6.8
X5.1
X6.9
X6.1
X6.3
X5.7
X5.9
X5.3
X5.5
L1
L2
L3
N
N / L-
L (Long Time Delay / Überlastschutz); S (Short Time Delay / Kurzschlussschutz, kurzzeitverzögert); I (Instantaneous / Kurzschlussschutz, unverzögert); N (Neutral Protection / Neutralleiterschutz);
S11 (Internal motor shutdown switch, if spring is tensioned / Interner Motorabstellschalter, wenn Feder gespannt); F1 (1st auxiliary release / Erster Hilfsauslöser); F5 (Maglatch for trip unit / Auslösemagnet);
S1 - S8 (Auxiliary switch / Hilfsschalter); Y1 (Closing coil / Einschaltmagnet);