1 General presentation
CBR is an outdoor pole mounted single-phase circuit breaker for railway applications,
based on the combination of vacuum switching together with low-pressure gas insulation
technology.
CBR is available in one-pole or two-pole versions. The two-pole version is for the double
supply system catenary + feeder.
All pole components are mounted inside a fully welded stainless steel tank providing a
sealed-for-life gasket free enclosure. No maintenance is required.
Remotely controlled, CBR has also a mechanical and manual opening command for
emergency or security purposes. A position indicator clearly visible from the ground gives a
reliable status of the contact.
CBR has been designed and tested to meet or exceed the requirements of all relevant
standards:
IEC 62271-100, 60376, 60529, , 60694, 60815
CENELEC EN 50124, 50125, 50152-1, 50163, 60529, 60721-3&4
2 Scope of supply
Item Description
CBR is available in single pole or two pole versions. A two-pole version has two identical
poles to operate in synchronization (for example feeder and catenary autotransformer).
Installation
Sealed-for-life tank
The vacuum switch is mounted in a fully welded anti-corrosion stainless steel tank
providing a sealed-for-life gasket free enclosure.
Insulation gas is SF6 at low pressure (0.5 bar relative). The low level of gas leakage gives
a lifetime over 30 years.
For safety of personnel, a pressure relief device is welded on the tank in the event of
internal arc fault.
Pressure sensor
CBR is equipped with a SF6 pressure monitoring device. The low pressure level (0.3bar) is
signalled through contacts normally closed when pressure is correct.
This information is transferred to the Central Control Centre.
Vacuum interrupter
Load interruption is achieved using the latest generation of AREVA vacuum interrupters:
axial magnetic field arc control for better performance.
Actuator
Operation is by a magnetic actuator, an efficient bistable mechanism with permanent
magnets installed in the sealed-for-life tank. This arrangement replaces the motor-operated
spring type. Figure here below illustrates the operating sequences. In closed or open
position, the field of the permanent magnet ensures two stable positions. For a command,
a current discharge in a coil creates a high magnetic field to move the contact. The opening
operation is guaranteed by an extra spring to ensure independent speed whatever the
energy on the coil.
Auxiliary contacts
Auxiliary contacts are directly linked with the moving part of the vacuum bottle. Three pairs
(3NO+3NC) of auxiliary contacts are available for customer purpose. Additional contacts
through relays can be added in the control unit.
Bushings
CBR technical description in Eng 01-2010 Page 4 / 16
A pole is equipped with patented EPDM bushings giving long term life, even in hostile
environments. The bushings are welded on the tank to eliminate all risk of leakage.
A pressure tight plug and socket arrangement enables simple connection. A shielded cable
which length depends on the elevation of the pole links the pole-top circuit breaker to the
down-pole control unit.
Elevation of the pole Cable length
H<3m 3.5m or 4 m
3.5 < H < 5.5 m 6.5 m
5.5 < H < 7 m 8m
For the VL Version, another cable is installed for the CT’s terminals.
Indicator
Manual opening
VL version option
For a substation installation, a dedicated support structure (2.5m height) allows the CBR
installation above the structure for a one-pole version or at 1.5m distance for a two-pole
version.
Control cabinet
Located at the bottom of the pole, the control cabinet monitors the following functions
• Indication of Circuit Breaker position
• Indication of capacitor charge (closing)
• Operation counter
• Control Interface
• Local or remote operation
The control of the Circuit Breaker can be achieved remotely from the CTCC (Central Traffic
Control Centre).
1. Local / remote function
A switch selects the function. In option, this switch can be locked by key in both
positions or by padlock.
2. Opening operation:
Remotely from the Central Traffic Control Centre: direct electric connection to
the opening coil.
Tripping from the protection relay
Locally from the push button (option)
Manually pulling an accessible ring on the support with a hook stick.
Automatically in case of loss of dc supply.
3. Closing operation:
The closing coil energy is provided by a capacitor. The capacitor voltage is
permanently monitored. A low voltage prevents all operations. Capacitor charge
status is displayed on the man machine interface. Closing command is achieved if
all conditions are fulfilled (open position, capacitors voltage, no alarm)
4. Capacitor discharge Switch
This switch allows the discharge of the capacitors before any intervention inside the
electronic control.
Supplies protection
The three circuits are protected by fuses with following ratings:
- 2A for Uc
- 6A for Um
- 10A for 230Vac
In option, fuses can be replaced by mini circuit breakers
4 Options
Open / close operation in local mode
The push buttons “Open” and “Close” are working only if the local mode is activated.
The local / remote control could be one of the three possibilities:
Push button to validate the local open / close operation
Switch “local / remote” - two positions
Switch “Local / remote” - two positions locked by key or padlock in both position.
In local mode, all electrical orders from the Central Control Centre are deactivated.
Security window for closing command: To avoid all wrong information on closing operation
(interference or permanent signal), the closing order operates if its pulse length is between
0.3s and 2s and will activated on the dropping edge of the pulse. A pulse longer than 5s
raises an alarm.
0.3s< pulse length <
Closing operation
The circuit breaker closes on the
dropping edge of the signal.
Additional contacts
To increase the 3NO + 3NC contacts originally provided, one or two relays can be installed
in the cabinet to get either 4NO+4NC or 8NO+8NC contacts.
Switching performance of additional auxiliary contacts 15A @230Vac
2A @ 220Vdc
CT’s terminals
The CT’s cable is connected to dedicated terminals which can
ensure the short circuit of the secondary.
Cabinet lighting
A fluorescent light of 6w @ 230Vac can be installed with an automatic switching at door
opening.
Options Choice
Routine tests
On each product
• Visual control
• Marking
• Power frequency test (dry)
• Measurement of the main contact resistance
• Operating time control
• Mechanical tests (closing and opening operations)
• Leakage test
• Control cabinet operations
Mechanical characteristics
Dimensions
Interrupter Switch Pole diameter mm 390
Overall width mm 1595
Depth mm 480
Height mm 1291
Height (VL version) mm 1950
Brackets for steel pole (catenary structure ) height mm 420
Support for s/station height mm 2500
Installation Outdoor
Pole mounted or
S/Station
Altitude m 1000
Temperature range °C -25 to+40°C
1000
100
10
1000 10000 100000
Current in Amp
Capacitor 10000µF 1
Relay 110Vdc 1
Contactor 110Vdc 1
Fig: VL Version