RVC-3/6/8/10/12 RELAY SETTING

PROCEDURE
By Soham Dasgupta (Engineer, Service–PGHVC&F)
RVC-3/6/8/10/12
MOUNTING OF RVC RELAY
STEP-1

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 2
RVC-3/6/8/10/12
MOUNTING OF RVC RELAY
STEP-2

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 3
RVC-3/6/8/10/12
MOUNTING OF RVC RELAY
STEP-3

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 4
RVC-3/6/8/10/12
WIRING DETAILS OF RELAY

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 5
RVC-3/6/8/10/12
PROCEDURE TO CONNECT WIRES

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 6
RVC-3/6/8/10/12
INTRODUCTION TO RELAY SCREEN

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 7
RVC-3/6/8/10/12
RELAY SETTING PROCEDURE
STEP-1

RVC relay will show Auto Screen as shown


in the picture. Following Parameters can be
seen by pressing (+) and (-) button
1. Cos Ø
2. Vrms
3. Irms
4. THDV

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 8
RVC-3/6/8/10/12
STEP-2

Press MODE/= button 2 times to enter


in AUTO SET Mode

Press +/- button to set all parameters


automatically

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 9
RVC-3/6/8/10/12
STEP-3
Press MODE/= button 1 time to enter
in MANUAL SET Mode.
Following parameters can be set in manual
Mode:
1. Target Cos Ø
2. C/k
3. Phase Sequence
4. Delay Time
5. Output Sizes
6. Regenerative Cos Ø
7. Relay Operation Mode
8. O/V or U/V Setting
9. THDV Setting

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 10
RVC-3/6/8/10/12
STEP-4

Press MODE/= button 1 time to enter


in Target Cos Ø

Default Value is 0.70 Lag

Recommended setting is 1.00

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 11
RVC-3/6/8/10/12
STEP-5

Press MODE/= button 1 time to enter


in Phase Shift option

Phase shift is based on Voltage and


current input. Please refer table to keep
correct phase shift.

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 12
RVC-3/6/8/10/12
PHASE SHIFT CHART

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 13
RVC-3/6/8/10/12
PHASE SHIFT CHART

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 14
RVC-3/6/8/10/12
PHASE SHIFT CHART

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 15
RVC-3/6/8/10/12
STEP-6

Press MODE/= button 1 time to enter in C/k option

Calculate C/k from above mentioned formula and


Press +/- button to set the same

C/k value must be in between 0.01 to 5.00

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 16
RVC-3/6/8/10/12
STEP-7

Press MODE/= button 1 time to enter in Time Delay option

Recommended setting for LV is 40 Seconds


Recommended setting for HV is 300/600 Seconds

Press +/- button to set the proper time delay

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 17
RVC-3/6/8/10/12
STEP-8

Press MODE/= button 1 time to enter in Output Step Sizes option

Smallest kvar step to be considered as size 1

Example: If we have 5,5,10,10 kvar stages


then 5 kvar stage size will be 1 and 10 kvar
stage size will be 2

Press MODE/= button and +/- button to set


correct step size

Max value of Step size can be 9

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 18
RVC-3/6/8/10/12
STEP-9

Press MODE/= button 1 time to enter in Relay Operation mode after Output
Sizes option

Relay operation mode can be kept in CIR/LIN


mode

Recommended setting is CIR

CIR means operation will be in CIRCULAR/FIFO


mode

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 19
RVC-3/6/8/10/12
STEP-10

Press MODE/= button 1 time to enter in Target Regenerative CosØ

Recommend to keep it as DIS

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 20
RVC-3/6/8/10/12
STEP-11

Press MODE/= button 1 time to enter in Vrms MAX/Over Voltage protection

Recommend to keep it at 1.1 X System Voltage

Press +/- button to set the parameter

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 21
RVC-3/6/8/10/12
STEP-12

Press MODE/= button 1 time to enter in Vrms MIN/Under Voltage protection

Recommend to keep it at 0.9 X System Voltage

Press +/- button to set the parameter

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 22
RVC-3/6/8/10/12
STEP-13

Press MODE/= button 1 time to enter in THDV/Total Harmonic Distortion


Voltage protection

Recommend to keep it at 5-8% based on


system voltage

Press +/- button to set the parameter

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 23
RVC-3/6/8/10/12
STEP-14

Press MODE/= button 1 time to enter in AUTO mode

Press +/- button to check following


parameters with main incomer:
1. Power Factor
2. Current
3. Voltage

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 24
RVC-3/6/8/10/12
Flow Chart for Setting Procedure
Press
Press Manual
Switch ON Mode/=
Mode/= Settings
Relay button
button
Press
Set Phase Set Target Mode/=
Cos Ø AU SET
Shift button

Set
Set Step Set Relay Regenerative
Set Time
Set C/k Operation
Delay Size Target
Mode Cos Ø

Keep Relay in Auto Mode and Set THDV Set V min Set V max
Check PF, Current, Voltage wrt protection protection protection
Incomer to ensure proper value value value
operation

RVC-3/6/8/10/12 Relay Setting Procedure


April 8, 2019 Slide 25
Thank You

April 8, 2019 Slide 26 RVC-3/6/8/10/12 Relay Setting Procedure