UPS Catalogue
Liebert® NXC UPS Systems from 10 to 40 kVA
Liebert® NXC
UPS Systems from 10 to 40 kVA
Scope 4
System Description 5
Operating Modes 9
Mechanical Data 16
Options 16
Technical Data 17
Liebert® NXC UPS Systems from 10 to 40 kVA
2.3 Performance
Method of specifying the performance and test requirements: IEC/EN 62040-3.
4
Liebert® NXC UPS Systems from 10 to 40 kVA
3 System Description
3.1 Models Available Rating (kVA) Input Output
The Liebert® NXC range includes 10 kVA 380-400-415V 3 Ph + N 380-400-415V 3 Ph + N or 220-230-
the ratings and input/output 240V 1 Ph + N
configurations presented in Table. 1 15 kVA 380-400-415V 3 Ph + N 380-400-415V 3 Ph + N or 220-230-
240V 1 Ph + N
3.2 The System 20 kVA 380-400-415V 3 Ph + N 380-400-415V 3 Ph + N or 220-230-
240V 1 Ph + N
The UPS includes the following
operational components: 30 kVA 380-400-415V 3 Ph + N 380-400-415V 3 Ph + N
• Rectifier 40 kVA 380-400-415V 3 Ph + N 380-400-415V 3 Ph + N
• Battery Charger Table 1. Liebert NXC configurations.
®
• Inverter
Q3
• Static Bypass Switch Removable
Links STS
• Maintenance Bypass Q2
Q3
Removable
Links STS
Q2
Q6
To external battery
5
Liebert® NXC UPS Systems from 10 to 40 kVA
3.3 IGBT Rectifier (AC/DC 3.4 IGBT Battery Charger 3.4.2 Battery management
Converter) (DC/DC Converter) Using advanced battery
3.3.1 Primary input The IGBT DC/DC converter has the management, the Liebert® NXC
following functions: series maximizes battery running
The three-phase current taken
time up to 50%. The main battery
from the commercial AC source is • To recharge the batteries, taking
management features are described
converted to a regulated DC voltage the power from the DC bus, when
as follows:
by the IGBT rectifier. In order to the primary input mains is within
• To avoid battery over discharge as
protect the power components the given tolerances a result of a light load, the UPS will
• To provide the DC power, taken automatically adjust the end of
within the system, each phase of the
from the batteries, to the IGBT discharge voltage according to the
rectifier input is individually fitted
output inverter if the primary back up time
with a fast-acting fuse.
mains is unavailable. • In order to ensure optimum
battery charging it will be possible
As shown in Figure 1, 2 and 3 (Page
3.4.1 Charging method to automatically adjust battery
5), the IGBT rectifier will provide Initially the battery is charged at float voltage as a function of
DC power to the DC/AC output a constant current rate until the ambient temperature measured
converter (IGBT inverter) and to the cell voltage reaches a preset value by a dedicated probe
DC/ DC battery converter (booster (“bulk charge” stage). At the end of • The UPS will calculate the
/ battery charger) when the UPS is the bulk charge stage, the battery remaining battery autonomy time
working in “normal mode”. It will during discharge
will have reached almost 80% of its
• It will be possible to test the
also boost the DC voltage to the capacity.
battery by performing a partial
correct level required by the Inverter
battery discharge either manually
when working in “battery mode”. Following the bulk charge stage, the initiated or at programmable
charger switches to the constant intervals. A brief discharge of the
3.3.2 Total Input Harmonic voltage “boost charge” stage. In battery will be made to confirm
Distortion (THDi) and Power this phase the battery allows the that all the battery blocks and
Factor (PF) remaning capacity to be charged connecting elements are in good
The extremely low current while the current drawn by the working order
battery gradually reduces until it • The partial battery discharge test
distortion injected into the mains
reaches the relevant preset level. results are also used to determine
(THDi) and the close to unity
The boost charge stage may be the remaining battery life
input power factor (see section 9) resulting from the real operating
disabled if it is not compatabile with
means that Liebert® NXC will be conditions such as temperature,
the battery type.
seen by the primary mains source discharge and charging cycles, as
and distribution as a resistive well as discharge depth
The final charging stage reached
load. It will absorb only active • The UPS provides DC overvoltage
will be the “float charge” stage. In
power and the current waveform protection: if the DC voltage
this stage the charger maintains exceeds the maximum value
will be practically sinusoidal, thus the battery voltage at a constant associated with its operational
ensuring total compatibility with level (lower than the boost voltage), status, the microprocessor will
any power source. To this extent where it is safe for preserving long- automatically switch off the
the Liebert® NXC includes all of the term battery function/charge, while battery charger and initiate an
performances offered by load active at the same time preventing self- uninterrupted load transfer to the
filtering devices as standard. discharge. static bypass line.
6
Liebert® NXC UPS Systems from 10 to 40 kVA
1.78
default 1.75
7
Liebert® NXC UPS Systems from 10 to 40 kVA
3.5 DC/AC IGBT Converter supply in the case of distorted mains operating and alarm conditions.
(Inverter) voltage. If the bypass is within the specified
3.5.1 AC voltage generation synchronization window, the control
From the DC voltage of the 3.5.4 Parallel operation logic will automatically transfer the
intermediate circuit, the inverter When multiple UPS are connected critical AC load to the bypass source,
generates sinusoidal AC voltage in parallel powering a common load, after any of the following conditions:
for the user loads on the basis of the DSP control ensures that each • Inverter overload
three-level pulse-width-modulation UPS output current will not differ by • Output voltage abnormal
(PWM). By means of the digital more than 5% of the rated full load • DC bus voltage abnormal
signal processor (DSP), the IGBT current of the UPS. • Parallel system transfer
of the inverter is controlled so that • UPS fault condition
DC voltage is divided into pulsed 3.5.5 Overload • End of discharge reached.
voltage packets. A low-pass filter The inverter is capable of supplying
converts the pulse-width modulated an overload current as specified in 3.6.1 Backfeed protection
signal into sinusoidal AC voltage. section 9.7. For greater currents or When the UPS bypass input line is
No isolation transformer is needed longer time duration, to prevent powered off, there is normally no
for the inverter with great benefits damage to components, the dangerous voltage/current/power
in terms of energy conversion inverter will be self-protecting present on the UPS bypass input.
efficiency, physical size and weight by means of electronic current-
However, when there is a fault in
of the modules. limitation. The control logic will
the bypass static switch (short
disconnect the inverter from the
circuit) there is the risk that electric
3.5.2 Three level converter critical AC load without the need
power appears on the UPS bypass
topology to clear protective devices and the
input terminals. In this case the
The three-level topology adopted critical load will be transferred to the
inverter powers the critical load
for the conversion stages of the static bypass automatically.
and the upstream input power line.
Liebert® NXC has proven to be both
This unexpected dangerous power
the most reliable and efficient. 3.6 Electronic Static Switch
can propagate in the upstream
The increased reliability offered is (Bypass)
The UPS comes complete with distribution through the faulty
a direct result of the three voltage
a Silicon Controlled Rectifier bypass line. Backfeed protection is
switching levels which reduce
the voltage stress of the UPS (SCR) static transfer switch rated a safety device which prevents any
semiconductors, thus ensuring to conduct full load current potential risk from electric shock on
prolonged life of the critical continuously in the maximum the UPS bypass input AC terminals,
components. At the same time the overload conditions as specified in in the event of a failure of the bypass
switching losses also decrease in section 9.6. static switch SCR. The control circuit
proportion to the voltage switching will include a contact (available for
level, resulting in a higher efficiency. The input feed of the bypass can be the user) which activates an external
either the same as the rectifier or isolating device, such as an electro-
3.5.3 Voltage regulation independent, provided they share mechanical relay or a tripping
The advanced vector control the same neutral. coil, upon backfeed detection. In
algorithm enables the real-time The control logic will be managed compliance with IEC/EN 62040-
control of the individual phases by digital algorithms (using vector 1-1:2008, the external isolating
with consequent improvement of control techniques), similar to device is not included in the UPS.
transient responses, short circuit those used for the rectifier and The external isolating device is
behaviour and synchronisms the inverter, sensing the status of defined according to clause 5.1.4 of
between UPS output and bypass the inverter logic signals as well as the previously cited standard.
8
Liebert® NXC UPS Systems from 10 to 40 kVA
4 Operating Modes
3.7 Manual Maintenance 4.1 Double Conversion Mode (DCM)
Bypass 4.1.1 Normal (DCM)
The UPS will be fitted with a The UPS inverter continuously supplies the critical AC load. The rectifier draws
manually operated maintenance power from the commercial AC source and converts it into DC power for the
bypass switch enabling the direct inverter and the battery charger. The battery charger maintains the battery in
connection of the critical load to a fully charged and optimum operational condition. The inverter converts the
the bypass AC input power source. DC power into clean and regulated AC power which is supplied to the critical
This manual operation will bypass load (conditioned line).
the rectifier/charger, inverter and The static switch monitors and ensures that the inverter tracks the bypass
static transfer switch to provide supply frequency. In this condition any automatic transfer to the bypass
an alternative path for power flow supply (due to an overload etc.) is frequency synchronized and does not cause
interruption to the critical load.
from the alternate AC supply to
The conversion efficiency in this operating mode is shown below in Figure 6.
the critical load. As a result, it
will be possible to implement a Efficiency
manual uninterrupted bypass of the 96%
complete system in order to enable 95%
maintenance work to be carried out 94%
while the bypass supply continues to 93%
9
Liebert® NXC UPS Systems from 10 to 40 kVA
A protection window (see section 9.6) and a synchronization window (see 4.2.2 Retransfer to Inverter
section 9.7) can be set up to control how the unit behaves in the case of transfer Once the condition causing the
to bypass or retransfer to inverter. transfer to bypass has been resolved,
retransfer of the critical AC load
4.2.1 Transfer to Static Bypass can be manually initiated as soon
If the bypass is within the synchronization window and the inverter is phase- as the inverter is synchronized with
locked with the bypass source, the transfer will be instantaneous. During the the bypass source. During the re-
transfer the output waveform will not exceed the limit set by IEC/EN 62040-3 for transfer the output waveform will
a UPS classified as VFI-SS-111 (Figure 7). not exceed the limit set by IEC/EN
62040-3 for a UPS classified as VFI-
SS-111.
Inverter
voltage If the bypass is whithin the
0 5 10 15 20 25 30 ms
synchronization window, but
inverter cannot be synchronized with
the bypass source when a re-transfer
is manually initiated, an “Interrupted
Bypass
voltage
Transfer Confirm” message appears.
0 5 10 15 20 25 30 ms If the message is confirmed (in order
to avoid hazardous cross current),
Figure 7. Synchronized tansfer. the bypass/inverter changeover
If the bypass is within the protection window but inverter cannot be will be triggered only after a few
synchronized with the bypass source, (the phase difference exceeds 6 degrees milliseconds from when bypass
or frequency is outside the synchronization window), in order to avoid has been disconnected from the
hazardous cross currents, the inverter/bypass changeover is triggered only load. Provided the bypass source
after a few milliseconds from when the inverter is disconnected from the load. remained in the protection windows,
The interruption will be <15ms if the bypass source is above 50Hz and <20ms the interruption will be <15ms if the
if it is below 50Hz - remaining within in the synchronization windows (see bypass source is above 50Hz, <20ms
Figure 8 for details). if it is below 0Hz.
10
Liebert® NXC UPS Systems from 10 to 40 kVA
4.3.1 After a utility AC power defined threshold, the critical AC 4.5.1 Parallel configuration for
outage load is transferred to the inverter. redundancy
If the primary AC source returns If the inverter is synchronized with The number of UPS in parallel is
within tolerance limits prior to a the bypass source, the transfer will greater than the minimum number
UPS automatic end of discharge be instantaneous and during the of UPS necessary to supply the load.
shutdown, the rectifier will transfer the output waveform will Under normal operating conditions,
recommence powering the inverter not exceed the limits set by IEC/ the power delivered to the load
and simultaneously recharging EN 62040-3 for a UPS classified will be equally shared between the
the battery through the battery as VI-SS-111. If the inverter is not number of UPS units connected to
converter. When the inverter has synchronized with the bypass, the parallel bus with a tolerance of
synchronized with the bypass, the in order to avoid hazardous 5%. In the event of failure of one of
UPS will recommence operating in cross current, bypass / inverter the UPS units, the affected unit will
double conversion mode without changeover is triggered only after be disconnected from the parallel
any break (0 ms) in the supply to the a few milliseconds (maximum bus and the load will be supplied
load. 20ms) from when the bypass is from the remaining units without
If the primary AC source does not disconnected from the load. After any break in continuity. In the case
return within tolerance limits and bypass frequency and voltage have that a single UPS overload limit is
the UPS performs an automatic end returned and remained within exceeded, the configuration may
of discharge shutdown, the UPS will deliver the required power without
the predefined limits for at least 5
recommence operating in bypass transferring the load to the bypass
minutes, the load is automatically
mode until it is manually transferred source.
and instantaneously transferred
to the inverter. Alternatively, it
back to the bypass source. In this
can be set to start in static bypass 4.5.2 Parallel configuration for
mode the system can charge the
mode and automatically transfer capacity
battery as normal.
to double conversion mode after a The number of UPS in parallel is
Eco mode is not available for parallel
time delay, from the moment the equal to the minimum number of
UPS installation.
rectifier start is complete and the UPS necessary to supply the load.
bypass source is back within the Under normal operating conditions,
synchronization windows. The time 4.5 Parallel Mode the power delivered to the load
delay is selectable between 1 and For higher capacity and/or reliability, will be equally shared between the
1440 minutes (default: 10 minutes). the outputs of multiple UPS (of the number of UPS units connected to
During the selected delay, the UPS same rating) can be set up in parallel the parallel bus with a tolerance of
will charge the battery and phase- with a built-in controller ensuring 5%. In the event of a unit failure or
lock the inverter with bypass. If the automatic load sharing. Liebert® overload, the system will transfer
inverter is unable to phase-lock the NXC is able to connect up to four the load to the bypass source.
bypass at the end of the selected units in parallel without the need
window, the load will remain fed for an additional parallel board, 4.5.3 Common battery
by the bypass and the user will be allowing maximum reliability and When UPS are connected in parallel,
prompted to confirm or cancel an flexibility. At anytime, a single unit each UPS can use the same battery,
interrupted transfer. can be upgraded to parallel. The achieving cost and space savings.
parallel option consists of screened It should be noted that in a parallel
4.4 Eco Mode data cables connecting one unit redundant system using common
If Eco mode is selected for the to the next in a loop ring bus. The battery mode, the batteries are not
purpose of saving energy, the bypass loop ring bus will allow the parallel redundant and the availability is
is the preferred source. Only when configuration to correctly share the consequently reduced. Common
the voltage and/or frequency of the system load even in the case of an battery banks cannot be used in the
bypass supply are/is beyond the pre- interruption in the data cable. Dual Bus mode.
11
Liebert® NXC UPS Systems from 10 to 40 kVA
12
Liebert® NXC UPS Systems from 10 to 40 kVA
5.2 LCD Display Menu Page System the UPS has run from inverter and
Descriptions In the case of a parallel set up of two from bypass, since the last counter
In order to maximize the reliability or more UPS, this page will display reset.
of the system, the control unit will the total apparent, active and
monitor a large volume of real- reactive power. Version
time data for the rectifier, inverter This page will show the firmware of
and battery. All vital operating Battery all UPS components such as monitor
conditions will be constantly This page will display battery board, rectifier, inverter and bypass.
monitored and controlled for bus voltage and current battery
irregularities. The system will react temperature, remaining battery 5.3 Communication and
automatically before a critical back up time, percentage of Signal Interfaces
situation arises, either for the UPS battery life when compared to a 5.3.1 Parallel Port
or the load, ensuring load supply new battery, battery boost or float As standard, Liebert® NXC comes
despite the difficult operating charging status. complete with serial ports,
conditions. allowing up to four units to
Events intercommunicate in order to work
By using the appropriate soft-keys, This page will display the events effectively as a parallel system. The
it will also be possible to access that resulted in the current mode control logic is integrated in the
real-time data and set a number of of operation, ignoring transient unit so that no additional board
system parameters via the following conditions that have been resolved. or options are needed apart from
menu pages: the serial cable. The parallel cable
Records configuration forms a closed loop to
Main This page will display the complete avoid the possibility of a single point
This page will display line to neutral history log of the past 1024 events. of failure.
voltages and currents, line to line
voltage, frequency and power factor Settings 5.3.2 Dual Bus Port
for each phase of the main line This page will enable the operator to As standard, Liebert® NXC comes
supplying the rectifier. set parameters such as date, time, complete with serial ports to allow
communication settings, system UPS or groups of parallel UPS to
Bypass password, contrast and display. communicate and synchronize with
This page will display line to neutral each other in a dual bus system. The
voltages and currents, line to line Commands control logic is integrated in the unit
voltage and frequency for each This page will enable the operator to so that no additional board or option
phase of the bypass line. start/stop or schedule programmed is needed a part from the serial
battery and system tests, or force cable. The dual bus configuration
Output battery charge equalization from 1 forms a closed loop to avoid the
This page will display line to neutral to 36 hours. possibility of a single point of failure.
voltage and current, frequency,
line to line voltage and load power Efficiency Curve 5.3.3 Service and Commissioning
factor. This page will show the load level Port
and the actual system efficiency on Liebert® NXC is equipped with
Load a graphical representation of the a RS232 and/or a USB port to
For each phase, this page will display efficiency curve. allow the Customer Engineer to
apparent, active and reactive set the most appropriate system
power supplied to the load, load Runtime parameters during commissioning
percentage and crest factor. This menu will show the total time or subsequent phases. It also
13
Liebert® NXC UPS Systems from 10 to 40 kVA
enables the complete history log closed) of external switches (when • Compatibility with Liebert®
to be downloaded when system provided with the necessary auxiliary Multilink shutdown software
status checks are necessary, contact) located downstream of the • A dedicated web page for
facilitating trouble shooting during UPS output. A second port senses the monitoring the UPS
maintenance. status of external switches located on • Interface with Liebert® Nform
an overall wrap-around bypass line alarm notification software
5.3.4 Back feed detection port (of a single UPS or a parallel set). IntelliSlot relay card provides
Liebert® NXC includes a contact The UPS uses the combination of contact closures for remote
(available for the user) suitable for status information of these two monitoring of alarm conditions of
activating an external isolating switches to turn off the inverter or Emerson Network Power UPS.
device, such as an electro- prevent the inverter being turned on.
mechanical relay or a tripping coil, This ensures that the wrap around Through a set of FORM C relay
upon backfeed detection. switch and any of the output external outputs the card notifies the
switches of a parallel system are not following status:
5.3.5 Remote Emergency Power closed at the same time. • On Battery
Off port • Low Battery
Liebert® NXC can be remotely 5.3.9 On generator status signal • On Bypass
powered off in the case an external When a signal is sent to this • Summary Alarm
signal is sent to this port. port, Liebert® NXC activates the • On UPS
“generator mode” limiting the
5.3.6 Optocoupler Interfaces (10 – battery charging power and the 5.4.2 Liebert® IS-485L
20 kVA only) input power to the percentage set by The Liebert® IntelliSlot 485 card
Three optocoupler contacts are commissioning software. allows monitoring and control
installed in the unit providing the of Emerson Network Power UPS
following alarms: 5.3.10 Intellislot through Liebert® SiteScan Web or
• Summary alarm The Liebert® NXC is equipped with any existing Building Management
• On Battery independent intellislot bays available System. It delivers MODBUS or
• On Bypass for communication cards such as Liebert® proprietary protocol via the
SNMP, Modbus and Contact Closure EIA-485 port.
5.3.7 BCB Monitor and Control port cards. The number of Intellislot bays
(30 and 40 kVA only) is one for the 10, 15 and 20 kVA units The Liebert® IntelliSlot 485 card
Liebert® NXC is equipped with a and three for the 30 and 40 kVA provides:
port able to sense the status (open/ units. • Ease of integration with industry
closed) of an external Battery Circuit standard open protocol
Breaker (when provided with the 5.4 Communication Cards • Interface with Liebert® SiteScan
necessary auxiliary contact) and 5.4.1 IS-WEBL Web software
triggers an alarm in the case it trips. IntelliSlot Web cards deliver SNMP, • Proactive analysis of parametric
It can also force the Breaker to trip Telnet and Web-Management data to ensure facility uptime
when battery end of discharge is capabilities to Emerson Network
reached or emergency power off/ Power UPS. The cards manage a 5.5 Monitoring
local or remote is activated. wide range of operating parameters, 5.5.1 Liebert® Multilink software
sending data over Ethernet Liebert® Multilink automated
5.3.8 External Bypass and Output networks via secure HTTPS protocol shutdown software provides safe,
switch status (30 and 40 kVA only) and alarms and notification via remote shutdown for a single
Liebert® NXC is equipped with a SNMP traps. computer or a large network of
port able to sense the status (open/ IntelliSlot web cards provide: workstations. Available for most
14
Liebert® NXC UPS Systems from 10 to 40 kVA
popular operating systems, Liebert® party devices through a network a unique feature that allows trained
Multilink offers comprehensive of microprocessor based control Customer Engineers to remain in
UPS status reporting and displays modules. Features include real-time constant electronic contact with
UPS instrumentation on screen. enhanced trend reporting and event the service center, and therefore
During an extended utility failure, management. the UPS. The UPS will automatically
Liebert® Multilink warns computer dial up the service center at defined
users of impending power loss and 5.6 Trellis™ Platform intervals to provide detailed
automatically initiates the safe Liebert® NXC can be integrated information that will be analyzed
shutdown of operating systems in Emerson Network Power’s in order to predict short-term
should the UPS battery capacity Trellis™ platform. A real-time problems. The communication of
run low. The software allows infrastructure optimization
UPS data to the LIFE™ command
configurable responses to UPS platform that enables the unified
center will be transmitted in the
status changes, including email management of data centre IT and
following conditions:
and pagers as well as on screen facilities infrastructure. The Trellis™
notification via pop-up messages. platform software can manage
capacity, track inventory, plan • ROUTINE: settable at intervals of
5.5.2 Liebert Nform centralized
®
changes, visualize configurations, between five minutes and two
monitoring software analyze and calculate energy usage, days (typically once a day)
Liebert® Nform will monitor the UPS and optimize cooling and power • EMERGENCY: when a problem
via SNMP protocol. Authenticated equipment as well as enable for occurs or parameters are beyond
alarm management, trend analysis virtualization. tolerance limits
and event notification delivers a The Trellis™ platform monitors • MANUAL: following a request from
comprehensive monitoring solution. the data center, providing a the command center
Available in a variety of versions to thorough understanding of system
suit anything from small computer dependencies to help IT and facilities During the call the command center
rooms to multiple location organizations keep the data center will:
distributed IT networks, Liebert® running at peak performance. This • Identify the UPS connected
Nform enables: unified and complete solution, • Request the data stored in the UPS
• Condition based system state delivers the power to see the real memory since the last connection
recording situation in your data center, make • Request real-time information
• Alarm event exporting to disk the right decision and take action from the UPS (selectable)
• SMTP email with confidence.
• Execution of external program The service center will analyze
• Shut down clients 5.7 LIFE™.net historical data and issue a regular
In order to increase the overall
detailed report to the customer
5.5.3 Liebert® Sitescan Web availability of the system, Liebert®
containing information of the UPS
enterprise monitoring system NXC will be compatible with an
operational condition and any
Liebert® Sitescan Web allows users optional LIFE™.net communication
to monitor and control virtually kit, providing connection to the critical states.
any piece of critical facility support LIFE™.net diagnostic service center. The LIFE™ .net center allows LIFE™
equipment - whether it is located LIFE™.net will allow the remote SMS delivery system option, where
in the next room, or in a facility diagnosis of the UPS through a TCP/ the customer may receive SMS
on the other side of the globe. IP connection (Internet connection), notification which will be activated
The web based system provides telephone lines or GSM link in order in the event of one of the following:
centralized supervision of Emerson to ensure maximum availability of • Mains power failure
Network Power precision cooling, the UPS throughout its operational • Mains power recovery
UPS and distribution units as well life. The monitoring will be a real 24- • Bypass line failure
as any other analog or digital third hour, 365 day service as a result of • Load supplied by reserve
15
Liebert® NXC UPS Systems from 10 to 40 kVA
6 Mechanical Data
6.1 Enclosure defined specifications. Airflow will 6.3 Cable Entry
The UPS will be housed in a space- be controlled according to load For the 10 – 20 kVA range the cable
saving enclosure with front doors demand. In the event that one of the entry is from the bottom/rear of the
and removable panels. The standard cooling fans experiences a fault, the UPS. For the 30 and 40 kVA entry is
degree of protection is IP 20. The UPS will be immediately notified of from the front.
standard color of the enclosure the condition via the user interface
will be ZP-7021. The UPS will be and through the LIFE™ .net service. 6.4 Dust Filters
equipped with casters to facilitate The cooling air entry will be from For the 30 and 40 kVA range,
installation and ease of movement/ the front and air exit will be at the Class G2 dust filters according to
relocation of the unit. back of the unit. The enclosure will EN779 standard are available to
be installed with at least 200 mm protect the UPS air intake in dusty
6.2 Ventilation of free space between the device environments.
Forced air cooling will ensure that and back wall in order to allow
all components operate within unhindered exit of cooling air.
8 Options
Where options described in this The transformer can be connected 8.2 Battery Cubicle
chapter are added to the UPS, the to the input or to the output of the Matching battery cubicles will be
data presented in the standard UPS.
available.
technical data tables may vary. These options will provide the
Some options may not be available following benefits: UPS/battery connection cables will
simultaneously on the same UPS. • Full galvanic isolation for medical be available on request.
and other critical applications
8.1 Integrated Isolation • Installation in distribution without 8.3 Remote LED Panel
Transformer (T version) neutral A remote alarm panel will be
Liebert® NXC can be customized • Installation with two independent
available to display important
to provide full galvanic isolation input sources with different
for specific load requirements by neutrals messages from the UPS relay card.
adding an isolation transformer that • Load protection in installations The length of the connecting cable
can be housed in the UPS cabinet. with 4-pole switching devices. must not exceed 100m.
16
Liebert® NXC UPS Systems from 10 to 40 kVA
Input Breaker / Switch (Q1) 3 Pole Breaker 63 A Type C 3 Pole Breaker 100 A Type C
Current THD at full linear load (5) (THDI%) <4% (3/3) <15% (3/1) <4%
Duration of progressive power walk-in (s) 5 seconds to reach full rated current (selectable 5 - 30 seconds in 5 second intervals)
1. Rectifier operates at any of the Nominal supply voltages and frequencies without further adjustment.
2. If the input frequency is within this range the UPS is able to switch to bypass if needed.
3. EN 62040-3 / 50091-3: at Nominal load and input voltage 400V, battery charged.
4. EN 62040-3 / 50091-3: at Nominal load and input voltage 400V, battery charging at maximum Nominal power.
5. Calculated at input THDv <2%.
17
Liebert® NXC UPS Systems from 10 to 40 kVA
9.6 Bypass
Nominal voltage (1) (Vac) 380 V/400 V/415 V (three-phase and sharing neutral with the bypass input)
Upper limit: +10,+15, or +20, default: +15
Voltage protection windows(2) (%Vac) Lower limit: -10, -20, -30, -40, default: -20
(delay time to accept steady bypass voltage: 10 sec)
Nominal frequency(3) (Hz) 50/60
Frequency protection window(2) (%) ±20 ( ±10 selectable )
Rated current @400 V (A) 14.4 21.7 28.9 43.3 57.7
Bypass Input breaker/switch (Q2) - 3 Pole Breakers 100 A Type D 3 Pole Breakers 125 A Type C
Maintenance Input breaker/switch (Q3) - 3 Pole Breakers 63 A Type C 3 Pole Breakers 100 A Type C
Neutral conductor sizing (A) 87 87
Transfer time with inverter synchronous to bypass (ms) ≤2
Transfer delay time with inverter not ≤20
(ms)
synchronous to bypass (40, 60, 80, 100, selectable)
Overload 105% (min) 60
125% (min) 5
150% (min) 1
400% (ms) 1000
>400% (ms) < 200
SCR(4) I2T @ Tvj =125°C, 8.3 -10ms (kA2s) 5.5 9.1
ITSM @ Tvj =125°C, 10ms (kA 1.05 1.35
18
Liebert® NXC UPS Systems from 10 to 40 kVA
19
Liebert® NXC UPS Systems from 10 to 40 kVA
Heat Losses
Normal mode 100% load (kW) 0.536 0.785 1.109 1.512 2.151
Eco mode (kW) 0.184 0.276 0.405 0.439 0.585
No load (kW) 0.178 0.350
Note: 400 Vac input and output, battery fully charged, full-Nominal linear load.
20
Liebert® NXC UPS Systems from 10 to 40 kVA
Notes
21
Liebert® NXC UPS Systems from 10 to 40 kVA
Notes
22
Liebert® NXC UPS Systems from 10 to 40 kVA
Notes
23
Ensuring The High Availability
Of Mission-Critical Data And Applications.
While every precaution has been taken to ensure accuracy and completeness Asia
of this literature, Emerson Network Power and/or its affiliates makes no
representations or warranty about the accuracy, reliability, completeness, or 7/F, Dah Sing Financial Centre
timeliness of the materials and disclaims any and all liability for damages resulting 108 Gloucester Road, Wanchai
from use of this information or for any errors or omissions.
Hong Kong
©2013 Emerson Network Power. All rights reserved
Tel: +852 2572220
Fax: +852 28029250
MKA4CAT0UKNXC Rev.1-02/2013
Emerson, Business-Critical Continuity and Emerson Network Power are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2013 Emerson Electric Co.