Sei sulla pagina 1di 2

ENFINITY® Heat Pump

Job Information
Technical Data Sheet
Job Name WSHP_fact
Date 8/20/2018
Submitted By Harold Hidalgo
Software Version 06.80
Unit Tag WSHP 120 kBTH_LH_220V3ph_Std_Tstat

Unit Overview
Model Number Voltage Air Flow Fluid Flow Cooling Cooling Heating Heating
V/Hz/Phase CFM gpm Capacity Efficiency Capacity Efficiency
Btu/hr EER @ design Btu/hr COP @ design
WCCH2120 208-230/60/3 4000 30.00 119031 13.20 131565 4.17

Unit
Model Number: WCCH2120
Unit Type: Enfinity - Horizontal, Standard Range
Unit Construction: Standard 1/2-inch Fiberglass Insulation
Approval: ETL, CETL, ARI
Refrigerant Type Refrigerant Weight
R-410A 74.0 oz

Unit Performance
Air & Water Flow
Airflow Total External Static Pressure Fluid Flow Fluid Type Fluid Pressure Drop
4000 CFM 0.86 inH₂O 30.00 gpm / 3.00 gpm/ton Water 18.61 ft H₂O
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of EER @ design
Entering Leaving Entering Leaving Total Sensible Rejection
°F °F Dry Bulb Wet Bulb Dry Bulb Wet Bulb Btu/hr Btu/hr Btu/hr
°F °F °F °F
85.0 95.0 80.0 67.0 59.8 57.2 119031 85607 149813 13.20
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption COP @ design
Entering Leaving Entering Leaving Total Btu/hr
°F °F Dry Bulb Dry Bulb Btu/hr
°F °F
70.0 63.3 70.0 100.5 131565 100016 4.17

Electrical
Unit Voltage Minimum Voltage Total Unit MCA Total Unit Full Load Current
208-230/60/3 197 V 43.40 A 39.50 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
15.60 A 110.0 A 8.30 A 50 A

Page 1 of 2 www.DaikinApplied.com
ENFINITY® Heat Pump
Physical
Unit
Length Height Width Weight Connections
Shipping Operating Water, FPT Condensate, FPT
78.00 in 29.00 in 44.00 in 792 lb 704 lb 1.25 0.88 in
Cabinet
Construction Type Piping Hand Condensate Drain Pan
Standard 1/2-inch Fiberglass Insulation Right Hand Galvanized Steel
Fan Controls
Type Motor Drive Type
Type Horsepower Type
Belt Drive - Integral HP
DWDI FC 3.000 HP Belt Microtech III
Motor
Airstream
Air Filter
Discharge Return (Quantity) Height x Width x Depth
Straight Discharge Left Hand Return Air (3) 19 in x 28 in x 2 in

Options
Heating
Heat Exchanger: Copper Inner Tube / Steel Outer Tube
Filter Options
Filter Options: Standard 2" 4-Sided, Throwaway
Controls
Control Transformer: 75VA Control Transformer
Condensate Overflow: Sensor

Warranty
Unit Warranty:

AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and
determined to comply with the requirements of the standards for Heating and Cooling Equipment UL-1995 for
the United States and CAN/CSA-C22.2 NO.236 for Canada.

Accessories
Optional
Part Number Description
910121746 Non-Programmable, 2-Stage (2H/2C)

Page 2 of 2 www.DaikinApplied.com