GENERAL NOTES / LEGEND

1.1 This set of drawings is to be read in conjunction with the architectural, mechanical
and electrical drawings (unless they do not occur), and any discrepancies between
them shall be reported to the Engineer immediately.

1.2 No scaling of dimensions is permitted on these drawings. Only written dimensions


which, unless otherwise stated, are given in millimetres, may be deemed to be
correct. If any dimension seems doubtful, the Engineer should be consulted.

1.3 All existing dimensions and levels are to be checked on site and verified. Any
discrepancies or variations from the drawings shall be reported immediately.
No work shall commence nor any material be ordered until the Engineer is
notified accordingly.

1.4 All work is to comply with the most recent revisions of the National Building
Regulations (NBR) and the latest editions of the relevant SABS codes of practice
and standard methods.

1.5 All building materials are to comply with the latest editions of the relevant SABS
specifications.

1.6 These designs and/or drawings are not sold, and are subject to recall. Reproduction
or copying rights are reserved solely to Renca Engineers under copyright law.
These drawings have been delivered and received on the following express conditions:

(a) they are not to be used in any way which may be construed as being against
the interests and/or benefits of Renca Engineers;
(b) they and all copies shall be returned to Renca Engineers
immediately on demand;
(c) all information disclosed by these drawings shall be deemed
to be confidential and treated as such.
FOUNDATION NOTES
1. Foundation excavations are to be approved in writing by the engineer prior to
casting.

2. A 50mm thick class 15/38 blinding layer is to be cast underthe full extent of all
reinforced concrete bases.

3. Backfilling shall be done with approved material placed in layers having a maximum
depth of 150mm before compaction and each layer shall be compacted to 95% mod.
Aashtodensity or as directed bythe engineer.

4. Manual compaction of soil is to take place only within 50mm of walls.

5. Poor founding material below foundations shall be removed to the depth ordered by
the engineer and backfilled with mass concrete of class 15/38.
CLIENT PLAN NUMBER

CLIENT PLAN No.

REFERENCE DRAWINGS
NUMBER REVISION DRAWING DESCRIPTION

1000 11570 750 5165 1100 1930 1000 -- -- --

3540 750 875


APPROVED BY COUNCIL / CLIENT

1100 x 350D RC STRIPFOOTING

CITY ENGINEER / CLIENT REG. NO. DATE

1100 x 350D R.C STRIPFOOTING

1100
AMENDMENTS CODE

A,B,C.../ : BEFORE TENDER /A : BY CLIENT


0 / : TENDER DRAWING /B : BY ARCHITECT
1,2,3.../ : AFTER TENDER /C : BY MECHANICAL OR ELECTRICAL
Z / : AS BUILT /D : BY GECOR
/E : BY OTHER ( )
DATE INITIAL No./CODE REVISION DESCRIPTION
07/08/2017 RN A/B COUNCIL SUBMISSION
1100 x 350 REINFORCED CONCRETE STRIPFOOTING
1000 x 350D REINFORCED CONCRETE STRIPFOOTING

1000 x 350D REINFORCED CONCRETE STRIPFOOTING


1100

250

750X250D R.C STRIPFOOTING

6905
OFFICES
PROVINCE OFFICE E-MAIL
Eastern Cape Port Elizabeth (081) 555-3258 ricardo@gecor.co.za
3227

Visit or contact us online at www.gecor.co.za


750

STRIPFOOTING
600x250D RC
750X250D REINFORCED CONCRETE STRIPFOOTING
70 Civil, Structural & Electrical Engineers. Environmental & Project Management
180

1460

CLIENT
750 x 250D RC STRIPFOOTING

1000 x 350D RC STRIPFOOTING

750 x 250D REINFORCED CONCRETE BASE


2754

1000
750

750

MR JEGELS
680

GARAGE X 3

1400 x 250D REINFORCED CONCRETE FOOTING


PROJECT
1000x1000x350D
RC BASE BB01

750

750X250D REINFORCED CONCRETE STRIPFOOTING

PROPOSED NEW DWELLING AT


1000

750 x 250D REINFORCED CONCRETE BASE ERF 1817

3645
37 EDMODS ROAD

4160
LOVEMORE HEIGHTS
750X250D RC STRIPFOOTING
4305

2080

DRAWING TITLE
750 x 250D RC STRIPFOOTING
2580

BASEMENT FOUNDATION
LAYOUT
600

600
195

600 x 250D RC STRIPFOOTING

1200
APPROVED BY GECOR ENGINEERS
750

750 x 250 REINFORCED CONCRETE STRIPFOOTING 1200 x 1200 x 350


RC BASE BA01
3540 750 395 ENGINEER/TECHNOLOGIST REG. NO. DATE
4685 1410 SCALE DRAWN
AS SHOWN R.N
750 9020 750 1980 750 5095 1200
DESIGNED RN CHECKED RC
FOR CONSTRUCTION PLAN NUMBER REVISION NO. DATE SAVED
BASEMENT AND LOWER STOREY PLAN
SCALE 1:50 PAPER SIZE A1 218024-100-01 A 11 MAY 2018