Sei sulla pagina 1di 1

GAS/VAPOR & STEAM RELIEF SIZING CALCULATION

Calculation according API-RP-520 7th edition, January 2000)


API STD 520 eight edition, Dec 2008, Example1
RELIEF VALVE DATA
Discharge to HP-flare Fluid Vapor
Set pressure (Pset) (barg) 5.17 Vapor-gas / Steam relief (V / S) V

PROCESS DATA
Back pressure (P2)
VALVE DATA

(bara) 1.00 Relieving temperature (T) (°C) 75


Accumulation (%) 10.00 Molweight gas/vapor (M) 51.00
Accumulated press. (P1) (bara) 6.70 Compressibility (Z) (@ relief cond.) 0.90
Specific heat ratio cp/cv (k) 1.11
Required relief load (W) (kg/h) 24270.0

RELIEF VALVE ORIFICE CALCULATION


X VAPOR / GAS O STEAM Abbr. Description unit
Check for subcritical flow only in case of steam relief A Calculated orifice area mm²
Check for subcritical flow using W Required mass flow kg/hr
1 . 904⋅W
the following formula A= C k-value coefficient
P1⋅K d⋅K b⋅K c⋅K n⋅K sh
T Relieving temperature K
P2 2 k

P k+1( ) k−1
Calculated Kn with

K n=
2. 764⋅P1−1000
3. 324⋅P1 −1061
M
Z

P1
Compressibility factor
Mol weight
Upstream relieving pressure
kg/kmole
bara
X Critcal flow vapor/gas O Subcritical flow vapor/gas P2 Back pressure bara
F2 Coefficient subcritical flow
A=
131. 6⋅W
C⋅K d⋅P1⋅K b⋅K c


T⋅Z
M
A=
0 .179⋅W

√T⋅Z
F 2⋅K d⋅K c M⋅P1⋅( P1−P2 )
k
r
Kd
Specific heat ratio Cp/Cv
Pressure ratio (P2/P1)
Discharge coefficient
Calculated C with Calculated F2 with Kb
Back Pressure Coefficient

√(
k +1
2
) √(
Kc

( )
(k −1) /k
k 1−r Combination correction factor
C=520⋅ k⋅
k+1
k−1
F2 =
k−1 )
⋅(r)2 /k⋅
1−r
Kn
Ksh
Napier correction factor
Superheat correction factor
STANDARD ORIFICE AREAS (acc. API-RP-526)
Orifice tag D E F G H J K L M N -->
Area (mm²) 71 126 198 325 506 830 1186 1841 2323 2800 etc
Area (sq. inch) 0,110 0,196 0,307 0,503 0,785 1,287 1,838 2,835 3,600 4,340 etc

CORRECTION FACTORS CALCULATED ORIFICE


Discharge coefficient (Kd) 0.975 Type of flow Critical
Back pressure coeff. (Kb)
CALC. DATA

1.0 k-value coefficient (C) 328


K-VALUES

Comb. Rupture disk factor (Kc) 1.0 Coefficient subcritical flow (F2) -
Calculated orifice (mm²) 3697
Napier correction factor (Kn) - Recommended orifice (mm²) 4116
Superheat steam cor. factor (Ksh) 1.0 Orifice TAG (acc API-RP-526) P

NOTES :

Potrebbero piacerti anche