Installation

WARNINGS

• This detector does not operate without electrical power. As fires


frequently cause power interruption, discuss further safeguards

SIGA-PS Intelligent •
with your local fire protection specialist.

This detector will not sense fires in areas where smoke cannot
Photoelectric Smoke Detector reach the detector. Smoke from fires in walls, roofs, or on the
opposite side of closed doors may not reach the detector.
Installation Sheet • Photoelectric detectors have a wide range of sensing capabilities,
but are best suited for detecting slow, smoldering fires.

Notes

• The dust cover (supplied) must remain on the detector during


installation, and then be removed prior to operation. The dust
cover is not a substitute for removing the detector during new
construction or heavy remodeling.

• Do not use a detector guard with this detector unless the


combination has been evaluated and found suitable.

• To ensure proper operation, store the detector within the


recommended ranges. Allow the detector to stabilize to room
temperature before applying power.
• Maintenance (regular or selected) should be planned in
accordance with the requirements of the authority having
jurisdiction to ensure proper operation. Refer to NFPA 72 and
CAN/ULC-S536.
Description • Under normal conditions this unit does not require calibration. If
The Signature Series SIGA-PS Intelligent Photoelectric Smoke calibration is required, call Customer Service at 1-800-655-4497 to
Detector is an intelligent analog device that uses an optical sensing arrange for return to the factory.
chamber to detect smoke. The detector analyzes the sensor data to
See Technical Bulletin P/N 270145-EN for additional information
determine when an alarm is initiated.
and cleaning instructions.
The detector continuously monitors changes in sensitivity due to the • NFPA code requires that a calibrated sensitivity test be performed
environment (e.g., dirt, smoke, temperature, humidity) and notifies the upon completion of the original installation and following any
loop controller of its condition. The SIGA-PS issues a dirty sensor modifications or additions to the system. Signature Series devices
warning when it reaches its preset limit. This notifies the operator of can perform this test and generate a system sensitivity report.
the need for service while the detector is still operating within UL/ULC
limits. • In Canada, your installation must meet the requirements of
CAN/ULC-S524 Standard for the Installation of Fire Alarm
LEDs: The SIGA-PS detector has two LEDs that show its state. Systems, and the local authority having jurisdiction.
• Normal: Green LED flashes • Test the detector with Smoke Detector Tester and Model 1490
• Alarm: Red LED flashes Adapter/Tube Accessory, manufactured by Home Safeguard, Inc.
• Stand-alone alarm: Green and red LEDs glow continuously or SOLO A4 aerosol manufactured by SDi.
Electronic addressing: The loop controller automatically assigns To install the detector:
addresses to the detectors. Custom addresses can be assigned to the
detectors via laptop computer. No addressing switches are used. 1. Push a small screwdriver into the tamper-resist access slot while
rotating the detector counterclockwise to remove the detector.
Stand-alone operation: If isolated from the loop controller, the
detector alarms when smoke levels exceed its preset value. Refer to You can permanently disable the tamper-resist mechanism by
the applicable fire alarm control panel manual for verification of stand- breaking and removing the plastic lever arm from the base. See
alone capabilities. Figure 1 for the locations of tamper-resist features.

Self-diagnostics: The SIGA-PS contains a microprocessor capable of 2. Install and wire the base as described in the installation sheet
performing comprehensive self-diagnostic tests and storing results. supplied with the base.
Details such as hours of operation, last maintenance date, sensitivity
3. Remove the serial number label from the detector and attach it to
values, and number of alarms and troubles are stored in nonvolatile
the project documentation.
memory. These can be retrieved and reviewed as desired.
4. Connect the detector to the base by rotating the detector clockwise
until it snaps into the locked position.
5. Before initial testing, remove the dust cover from the detector and
notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.

P/N 387014P-EN • REV 10 • ISS 10MAR16 1/2


Figure 1: Tamper resist features

(1)

(2)

(1) Tamper-resist lever arm on base (break off to disable)


(2) Access slot for tamper-resist mechanism

Specifications

Voltage 15.2 to 19.95 VDC


Current
Normal 45 µA
Alarm 45 µA
Stand-alone alarm 18 mA
Air velocity 0 to 5,000 ft./min (0 to 25.39 m/s)
UL/ULC smoke 0.67 to 3.77%/ft. obscuration
sensitivity
Environmental Automatic
compensation
Distance from ceiling 12 in. (305 mm) max.
(wall mounted)
Compatible bases
Standard SIGA-SB, SIGA-SB4
Relay SIGA-RB, SIGA-RB4
Isolator SIGA-IB, SIGA-IB4
Audible SIGA-AB4, SIGA-AB4G, SIGA-AB4GT,
SIGA-AB4G-LF
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Relative humidity 0 to 93% noncondensing
Storage temperature −4 to 140°F (−20 to 60°C)

Contact information
For contact information, see www.edwardsfiresafety.com.

© 2016 Walter Kidde Portable Equipment, Inc.


All rights reserved.

2/2 P/N 387014P-EN • REV 10 • ISS 10MAR16