Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
com
Power System
GATE - 2020/21
Practice
Analysis
Result
2 Performance of Transmission 1 - 10
Line
3 UG Cable, Insulator Corona, 1-5
HVDC
4 Fault Analysis 1 - 15
Q.03 A three phase overhead transmission line has Q.07 For a single phase overhead line having solid
its conductors horizontally spaced with copper conductors of diameter 1cm, spaced
spacing between adjacent conductors equal to 60cm between centers, the inductance in
‘d’. If now the conductors of the line are mH/km is:
rearranged to form an equilateral triangle of (A) 0.05+0.2In60 (B) 0.2ln60
sides equal to ‘d’ then:
60 60
(A) Average capacitance and inductance will (C) 0.05+0.2In (D) 0.2In
increase 0.5 0.5
(B) Average capacitance will increase and Q.08 The conductors of a 10 km long single phase,
inductance will increase two wire line are separated by a distance of
1.5m. The diameter of each conductor is 1 cm.
(C) Average capacitance will increase and If the conductors are of copper, the inductance
inductance will decrease of the circuit is
(D) Surge impedance loading of the line (A) 50.0 mH (B) 45.3 mH
increases
(C) 23.8 mH (D) 19.6 mH
Q.04 Bundled conductors are employed to improve
the Q.09 Consider a long, two –wire line composed of
solid round conductors. The radius of both
(A)Appearance of the transmission line conductors is 0.25 cm and the distance
(B)Mechanical stability of the line between their centers is 1m. If this distance is
doubled, then the inductance per unit length
2 | Power System
(A) Doubles conductors and ground, and assume that
spacing between sub-conductors is much
(B) Halves
larger than their radius, the maximum electric
(C) Increases but does not double field intensity is experienced at
3R
R 600
60 0
16 1.914 17 1.43
CHAPTER - 2 PERFORMANCE OF TRANSMISSION LINE
Q.01 Two transmission lines are connected in (D) Data insufficient for decision
cascade, whose ABCD parameters are Q.06 For equilateral spacing of conductors of an
untransposed 3 –phase line, we have
A1 B1 1 10300 A2 B2 1 0
C D = ; = (A) Balanced receiving end voltage and no
1 1 C1 1 C2 D2 0.025 -30
0
1
communication interference
Respectively, find the resultant ABCD
parameters. (B) Unbalanced receiving end voltage and
no communication interference
Q.02 In a 400 kV network, 360 kV is recorded at
a 400 kV bus. The reactive power absorbed (C) Balanced receiving end voltage and
by a shunt rated for 50 MVAR, 400 kV communication interference
connected at the bus is
(D) Unbalanced receiving end voltage and
(A) 61.73 MVAR communication interference
(B) 55.56 MVAR Q.07 The velocity of propagation of
(C) 45 MVAR electromagnetic wave on an underground
cable with relative permittivity of 3 will
(D) 40.5 MVAR be…m/sec
Q.03 The surge impedance of a 400 km long
Q.08 A factory draws 100kW at 0.7p.f lagging
overhead transmission line is 400 ohms. For
from a 3–phase, 11kV supply. It is desired
a 200 m length of the same line, the surge
to raise the p.f. to 0.95 lagging using series
impedance will be:
capacitors. Calculate the rating of the
(A) 200 (B) 800 capacitor required.
(C) 400 (D) 100 Q.09 The reflection coefficient for the
transmission line shown in fig. at P is:
Q.04 Two identical three-phase transmission lines
are connected in parallel to supply a total
load of 100 MW at 132 kV and 0.8p.f Transmission line P
lagging at the receiving end. The ABCD z0= 300
z0= surge impedance
constant of each transmission line are as
LOAD 300
follows:
A = D = 0.98 10 ; B = 100 750 Ohms
per phase ; C = 0.0005 900 Siemens per
(A) +1 (B) -1
phase Determine:
(C) 0 (D) 0.5
(a) The ABCD constants of the combined
network Q.10 Series capacitive compensation in EHV
(b) The sending end power factor transmission lines is used to
(A)Reduce the line loading
Q.05 For a 500Hz frequency excitation, a 50km
long power line will be modeled as (B) Improve the stability of the system
(A) Short line (C) Reduce the voltage profile
(B) Medium line (D) Improve the protection of the file
(C) Long line
2 | Power System
Q.11 A cable has the following characteristic L= 11
(A) A (B) 11A
0.201 µH / m and C = 196.2p/F / m. The 3
velocity of wave propagation through the 220
cable is: (C) 220A (D) A
(A) 32m/s 3
Q.16 A 3-phase, 11kV, 50 Hz, 200 kW load has a
(B) 159.24*106m/s power factor of 0.8lag. A delta connected 3–
(C) 0.0312m/s phase capacitor is used to improve the power
factor to unity. The capacitance power phase
(D) 159.24m/s
of the capacitor in microfarads is
Q.12 A shunt reactor of 100MVAr is operated at (A) 3.948 (B) 1.316
98% of its rated voltage and at 96% of its (C) 0.439 (D) 11.844
rated frequency. The reactive power
absorbed by the reactor is: Q.17 A 66 kV, 3-phase, 50Hz, 150km long
overhead transmission line is open circuited
(A) 98MVAr (B) 104.02MVAr at the receiving end. Each conductor has a
(C) 96.04MVAr (D) 100.04MVAr resistance of 0.25 /km, an inductive
reactance of 0.5 /km and a capacitive
admittance to neutral of 0.04 10-4S/km
Q.13 A circuit consisting of a single resistor R
and an inductor L in series is driven by a (A) Draw the nominal π –equivalent circuit
25V RMS, 50 Hz sinusoidal voltage source. and indicate the value of each parameter
A capacitor is to be placed in parallel with
the source to improve the power factor. Give (B) Calculate the receiving end voltage if the
that the average power dissipated in the R is sending end voltage is 66kV
100W and that the reactive power delivered
to the L is 75Var, what value of C will yield Q.18 A 50 Hz balanced three-phase, Y-connected
a 0.9 p.f. lagging as seen by the source? supply is connected to a balanced three phase
Q.14 An overhead line having a surge impedance Y-connected load. If the instantaneous
of 400 is connected in series in series with phase- of the supply voltage is Vcos (t)
an underground cable having a surge and the phase - of thee load current is lcos
impedance of 100 . If a surge of 50kV (t -) , the instantaneous three-phase power
travels from the line end towards the line- is
cable junctions, the value of the transmitted
voltage wave at the junction is:
(A) A constant with a magnitude of VI cos
(A) 30Kv (B) 20kV
3
(B) A constant with a magnitude of VI
(C) 80kV (D) -30kV 2
Q.15 A 220kV, 20 km long, 3-phase transmission cos
line has the following A, B, C, D constants.
A= D = 0.96 30, B = 55 650 / phase, (C) Time-varying with an average value of
C= 0.5E -04 800S/ phase 3
VI cos and a frequency of 100Hz
2
PERFORMANCE OF TRANSMISSION LINE | 3
(C) Time-varying with an average value of (B) Calculate the value of the reflected
VI cos and a frequency of 50Hz component of this surge when the first
reflection reaches A.
Q.19 A lossless radial transmission line with
surge impedance loading (C) Calculate the surge current in the cable
BC.
(A) Takes negative VAR at sending end and
zero VAR at receiving end
Q.22 A transmission line has a total series
(B) Takes positive VAR at sending end and
zero VAR at receiving end reactance of 0.2 pu. Reactive power
(C) Has flat voltage profile and unity power compensation is applied at the midpoint of
factor at all points along it
the line and it is controlled such that the
(D) Has sending end voltage higher than
receiving end voltage and unity power factor midpoint voltage of the transmission line is
at sending end. always maintained at 0.98 pu. If voltages at
both ends of the line are maintained at 1.0pu,
Q.20 Consider the model shown in figure of a
transmission line with a series capacitor at its then the steady state power transfer limit of
mid-point. The maximum voltage on the line the transmission line is
is at the location
P j0.1pu P3 j0-1pu P4
1 P 2
(A) 9.8pu (B) 4.9pu
I=1pu
-j0.15pu pf=1
__ (C) 19.6pu (D) 5pu
VS 1pu 00 -V
r
Q.24 A balanced delta connected load of (8 + j6) Q.27 A 3 –phase, 11 –kV generator feeds power to
per phase is connected to a 400 V, 50Hz, a constant power unity power factor load of
3-phase supply lines. If the input power 100 MW through a 3–phase transmission
factor is to be improved to 0.9 by connecting line. The line-to-line at the terminals of the
a bank of star connected the required kVAR machine is maintained constant at 11 kV.
of the bank is The per unit positive sequence impedance of
the line based 100 MVA and 11 kV is j0.2.
(A) 42.7 (B) 10.2 The line-to-line voltage at the load terminals
(C) 28.8 (D) 38.4 is measured to be less than 11 kV. The total
Q.25 The ABCD parameters of a 3-phase overhead reactive power to be injected at the terminals
transmission line are A = D = 0.9 0, B = of the load to increase the line to line voltage
200 900 and C = 0.95 × 10-3 900S. At at the load terminals to 11 kV is
no-load condition a shunt inductive reactor is
connected at the receiving end of the line to (A) 100 MVAR (B) 10.1 MVAR
limit the receiving end voltage to be equal to (C) -100 MVAR (D) -10.1 MVAR
the sending end voltage. The ohmic value of
the reactor is Q.28 An 800 kV transmission line is having per
(A) (B) 2000 phase line inductance of 1.1mH/km and per
lines. The inductance and the capacitance of (C) 2085 MW (D) 2606 MW
(A) 1250 kW (B) 1650 kW (A) 0.85 lag (B) 1.00 lag
(C) 2500 kW (D) 2900 kW (C) 0.80 lag (D) 0.90 lag
Q.30 The generalized circuit constants of a 3- Q.33 The concept of an electrically short, medium
phase, 220 kV rated voltage, medium length and long line is primarily based on the
transmission line are
A = D = 0.936 + j0.016 = 0.936ǀ0.98o (A) Nominal voltage of the line
B = 33.5 + j138 = 142.0ǀ76.4o (B) Physical length of the line
C = (-5.18 + j914) × 10-6 (C) Wavelength of the line
If the load at the receiving end is 50 MW at (D) Power transmitted over the line
220 kV with a power factor of 0.9 lagging.
The magnitude of line to line sending end Q.34 A 400V, 50 Hz, three phase balanced source
voltage should be supplies power to a star connected load
compared to Generator-3
~ Z =j0.5 pu
QG2
SD1=1pu SD2=1pu
Q.42 Consider a step voltage wave of magnitude
1pu travelling along a lossless transmission (A) 0.2pu (B) 0.268pu
line that terminates in a reactor. The voltage (C) 0.312pu (D) 0.4pu
magnitude across at the instant the
travelling wave reaches the reactor is Q.45 A two bus power system shown in the figure
A
supplies load of 1.0 + j0.5 p.u.
CHAPTER – 03 UG CABLE, INSULATOR CORONA, HVDC
Q.1 Ring main distribution system is preferred to a The ratio of shunt capacitance to mutual
radial system, because capacitance is 0.1. Calculate the voltage across
each insulator, and the string efficiency.
(A) It is less expensive
Q.7 A single phase AC distributor supplies two
(B) Voltage drop in the feeder is less
single phase loads as shown in fig. The voltage
(C) Power factor is higher drop from A to C is:
e2
e1 e2 5C
C
5C
e1
e3 e4
1 j0 5 j0
Conductor
C2
(A) VAB 0, VCD < 0, VAB > VCD
R
C1 C1
(B) VAB > 0. VCD >0. VAB > VCD
B Y C2
(C) VAB 0, VCD > 0, VAB > VCD C1
C2
(D) VAB 0, VCD < 0
Outer Sheath
Q.16 Consider a three-phase, 50Hz, 11kV
distribution system. Each of the conductors is (A) 2.0A (B) 2.4A
suspended by an insulator string having two
identical porcelain insulators. The self (C) 2.7A (D) 3.5A
capacitance of the insulator is 5 times, the Q.18 A distribution feeder of 1km length resistance,
shunt capacitance between the link and the but negligible reactance, is fed from both the
ground, as shown in the figure. The voltages ends by 400V, 50Hz balanced source. Both
across the two insulators are
voltage source S1 and S2 are in phase. The
4 | Power System
feeder supplies concentrated loads of unity
power factor as shown in the figure.
S1 S2
~
400V
400m 200m 200m
p
200m
400V
~
50Hz 200A 100A 200A 50Hz
System 1 System 2
I
+ +
V1 V2
CHAPTER – 04 FAULT ANALYSIS
Q.1 Assertion (A): Zero sequence currents are, Q.4 The three sequence voltage at the point of
by definition, in phase with each other in fault in a power system are found to be
the three winding of any three-phase equal. The nature of the fault is
apparatus.
(A) L-G (B) L-L-L
Assertion (R): They may be caused by
(C) L-L (D) L-L-G
magnetic saturation in the transformer
Q.5 Symmetrical components are used in power
(A) Both A and R are true and R is the
system for the analysis of
correct explanation of A
(B) Both A and R are true but R is not the (A) Balanced 3-phase fault
correct explanation of A
(B) Unbalanced 3-phase fault
(C) A is true but R is false
(C) Normal power system under steady
(D) A is false but r is true condition
Q.2 A balanced 3-phase load is supplied from a (D) Stability of system under disturbance
3-phase supply. The contact in line C of the
triple-pole switch contactor fails to connect Q.6 The positive, Negative and zero sequence
when switched on. If the line-current in per unit impedance of two generators
lines a and b record 25 A each, than the connected in parallel are X1=0.12p.u.
positive-sequence component of the current X2=0.096p.u and X0=0.036p.u. For a L-G
is fault at generator terminal (with 1 pu
voltage) the positive sequence current will
be
a Balanced
3 phase
(A) 7.936 p.u. (B) 11.936 p.u.
b
load
(C) 10.936 p.u. (D) 8.936 p.u.
c
Q.7An unloaded generator with a pre-fault
(A) 14.4 + 30 A
0
(B) 25.0 -30 A
0
voltage 1pu has the following sequence
impedance:
(C) 14.4 -300A (D) 25.0 +300A
Z0=jo.15 pu, Z1=Z2=jo.25 pu
Q.3 A 3-phase, 100 MVA, 11kV generator has
the following p.u. constant. The generator The neutral is grounded with a reactance of
neutral is solidly grounded, X1=X2=3X0= 0.05 pu. The fault current in pu for single-
0.15 . The ratio of the fault current due line to ground fault is
to three-phase dead-short-circuit to that due
(A) 3.75 pu (B) 4.28 pu
to L-G fault would be nearly
(C) 6 pu (D) 7.25 pu
(A) 0.33 (B) 0.56
(C) 0.78 (D) 1.0
Q.8 Fault calculations using computer program
are usually done by
2 | Power system
(A) Ybus method (B) Zbus method (A) Negative sequence currents are present
(C) Both of the above (D) None of these (B) Zero sequence currents are present
Q.9 The current of a single phase load drawn (C) Zero sequence current are absent
from a 3-phase system has
(D) Positive sequence current are present
(A) Zero sequence component of current as
zero Codes:
(B) All unsymmetrical fault Q.14 Assertion (A): the „short-circuit capacity‟
of a bus in large power grid is defined as the
(C) Fault involving ground with neutral of product of the pre-fault voltage and the 3-
system grounded phase fault current at a point very close to
(D) Fault involving ground with floating the bus
neutral
List-II
Fault Analysis | 3
Assertion (R) : The larger short-circuit 0.2, and station S2 has two generator of p.u.
capacity, the larger would be the equivalent reactance 0.4 each
source impedance at the bus
S1 S2
(D) Both A and R are true and R is the
correct explanation of A
~ ~~
(E) Both A and R are true but R is not the 0.4 0.4
0.2
correct explanation of A
(F) A is true but R is false
(G) A is false but r is true
0.2 F 0.2
Q.15 Match List-I ( Symbol for 3-phase
transformer connection) with List-Ii ( Zero- For a 3-phase symmetrical short circuit at
sequence equivalent circuits) and select the the middle of the transmission line ( point
correct answer using the code given below F), what is the change in the value of
the list equivalent reactance with one of the
generator of S2 removed?
List-I List-II
(A) 10% (B) 20%
A A ZO B (C) 30% (D) 40%
A B
R e f . B us
Q.17 How many relays are used to detect inter
phase fault of a three-line system?
(A) One (B) Two
B A ZO B (C) Three (D) Six
A B
R e f . B us
Q.18 For the system shown in the diagram
given below, what is a line-to-ground fault
on the line side of the transformer
ZO
equivalent to?
C A B
A B
R e f . B us
~ F
A B C
(A) 2 1 3 (A) A line-to-ground fault on the generator
side of the transformer
(B) 1 2 3
(B) A line-to-line fault on the generator
(C) 3 2 1 side of the transformer
Q.16 Two power station S1 and S2 are (C) A double line-to-ground fault on the
interconnected through a transmission line generator side of the transformer
of per unit (p.u.) reactance of 0.4 . Station
S1 has one generator of p.u. reactance of
4 | Power system
(D) A 3-phase fault on the generator side of 3. The positive and negative sequence
the transformer networks are not affected by method of
natural grounding.
Q.19 A fault occurring at the terminal of an
unloaded synchronous generator operating Which of the statement are correct?
at its rated voltage has resulted in the
(A) 2 and 3 (B) 1 and 2
following values of current and voltages:
(C) 1 and 3 (D) 1, 2 and 3
Ia0=j2.37p.u.
2
j
Ia1= -j3.05p.u Q.22 If = e 3 , and I=AIs where I is equal to
Ia2= j0.68p.u. phase current vector, and Is is equal to
symmetrical current vector then which one
Va0=Va1=Va2= 0.237p.u of the following matrices is the
symmetrical components transformation
Which one of the following fault has
occurred? matrix A?
Q.21Consider the following statement Q.24 Four identical 100 MVA, 33kV generators
regarding the fault analysis: are operating in parallel, as shown below,
in two bus-bar sections, interconnected
1. The neutral grounding impedance Zn
through a current limiting reactor of X p.u.
appears as 3Zn in zero sequence equivalent
reactance on the generator-base reactance
circuit
of 0.2p.u
2. for faults on transmission lines, 3-phase
fault is the least severe amongst other
faults.
Fault Analysis | 5
100 MVA, 33kV Q.26 Assertion (A): When a line-to-line (L-L)
~~ 33kV
X p.u.
~~ X ' d 20%
faults takes place at the terminal of an
open-circuited generator, phase voltages
33kV
CB X are sometimes „interminate‟, through line-
F(a b c) Lo a d
to-line voltages are always determinable.
L oa d
XM
Ic c XL
(A) Star with isolated neutral-delta
(B) Star with grounded neutral-delta
The series voltage-drop relation would be
(C) Delta-star with grounded neutral
Vaa‟= Ia XL + Ib XM + Ic XM
(D) Delta-delta
Vbb= Ia Xm + Ib XL + IC XM Q.28 The below diagram the layout of a power
station having two generators A and B ,
Vcc‟= Ia XM + Ib Xm + Ic XM
connected to the 11 kV buses which are
The positive, negative and zero-sequence also fed through two transformers C and D
reactance X1, X2 and X0 , respectively, from a 132 kV grid. The 11 kV buses are
would be interconnected through a reactor R.
11kV
the same plant, these generators are being
replaced by a single equivalent generator,
R
Fault the effective impedance of equivalent
0.1pu
generator will be
Feeder Feeder
(A) 0.05p.u. (B) 0.15p.u.
The reactance of A,B, C,D and R in p.u. on
a common MVA-and kV-base. All the (C) 0.25p.u. (D) 0.45p.u.
generated voltages in A,B and grid are each
Q.32 The load current in short circuit
1.0p.u. and assumed as in phase at the time calculation are neglected because
of fault.
1. Short-circuit current are much larger
The steady state symmetrical fault-current then the load currents
for a 3-phase fault on the 11 kV feeders is
2. Short-circuit current are greatly out of
(A) 10 pu (B) 15 pu phase with load currents.
(C) 20 pu (D) 25 pu
Which of these statements is/are correct?
Q.29 a 3-phase transformer having zero- (A) Neither 1 nor 2 (B) 2 alone
sequence impedance of Z0 has the zero-
sequence network as shown in the figure (C) 1 alone (D) 1 and 2
below. The connections of its windings are
Q.33 Two identical unloaded generators are
Re fernce bus connected in parallel as shown in figure.
Both the generator are having positive,
negative and zero sequence impedance of
Z0
j0.4 p.u., j0.3 p.u. and j0.15p.u.
Primary Secondary
respectively. If the pre-fault voltage is
(A) Star-star 1p.u. for a line-to-ground (L-G) fault at the
terminal at the generators, the fault current,
(B) Delta-delta in p.u. is__________
(C) Star-delta
(D) Delta-star with neutral grounded ~
Q.30 If all the sequence voltage at the fault
point in a power system are equal, then the
~
fault is a Q.34 A 50 MVA, 10kV, 50Hz, star-connected,
(A) three-phase fault unloaded three-phase alternator has a
synchronous reactance of 1p.u. and a sub-
(B) Line to ground fault transient reactance of 0.2p.u.. If a 3-phase
(C) Line to line fault short circuit occurs close to the generator
Fault Analysis | 7
terminals, the ratio of initial and final Q.38 A three phase, 100MVA , 25kV generator
values of the sinusoidal component of the has solidly grounded neutral. The positive,
short circuit current is _____ negative and zero sequence reactance of
the generator are 0.2pu, 0.2pu and 0.05pu,
Q.35 The magnitude of three-phase fault
respectively, at the machine base
current at buses A and B of a power system
quantities. If a bolted single phase to
are 10pu and 8 pu, respectively. Neglect all
ground fault occurs at the terminals of the
resistance in the system and consider the
unloaded generator, the fault current in
pre-fault system to be unloaded. The pre-
amperes immediately after the fault is
fault voltage at all buses in the system is
_____
1.0pu. The voltage magnitude at bus B
during a three-phase fault at bus A is 0.8pu. Q.39 In an unbalanced three phase system,
The voltage magnitude at bus. A during a phase current Ia=1 (-900) pu, negative
three-phase fault at bus B, in pu, is ____ sequence current Ib2=4 (-1500)pu , zero
sequence current IC0=3 900pu. The
Q.36 A sustained 3-phase fault occurs in the
magnitude of phase current Ib in pu is
power-system shown in figure. The current
and voltage phasors during the fault 9 on a (A) 1.00 (B) 7.81
common reference), after the natural
(C) 11.53 (D) 13.00
transient have died down are also shown.
Where is the fault located?
I1 I3
V1 Q S V2 Q.40 A 2-bus system and corresponding zero
~ ~ sequence network are in the figure.
R P
I2 I4
(option)
V2
V1
Bus1
T1 T 2 Bus 2
I3
I2
I4
I1
X Gn ~ ~ X MN
E Ad
F1
I F1
A
IF 2
F2 B
EBd
~ ~
VF 1 VF 2
Choose 25kV as the base voltage at the Voltage base= 400kV (Line to Line)
generator G1 and 200MVA as the base. (Nominal system frequency=50Hz
The impedance diagram is
The reference voltage for phase „a‟ is
defined as v(t)= Vmcos( t)
j 0.27 j0.42 j 0.27
Asymmetrical three phase fault occurs at
centre of the line.i.e. point „F‟ at time t0.
j0.18 j0.18 The positive sequence impedance from
(A)
source S1 to point „F‟ equal 0.004+ j0.04
G1 ~ ~ G2
pu. The wave from correspond phase „a‟
fault current from bus X revels that
j0.27 j 0.62 j0.27
decaying dc offset current is negative and
in magnitude at its maximum initial value.
j0.18 j 0.18 Assume that the negative sequence
( B)
impedances are equal to positive sequence
G1 ~ ~ G2 impedances, and the zero sequence
impedances are three time positive
j 0.3 j 0.42 j0.3 sequence impedances
Q.46 The instant (t0) of the fault will be
j 0.21 j0.21
(C )
(A) 4.682 ms (B) 9.667 ms
G1 ~ ~ G2
(C) 14.667 ms (D) 19.667 ms
X 1 300
1 (C) 6.667 (D) 8.553
(C) Van1= ,Van2=
3 Q.57 A 3-phase transmission line supplies -
Y 2 300
1 connected load Z. The conductor „c‟ of the
3 line develops an open circuit fault as
shown in figure. The current in the lines
X 1 600 , Van2=
1 are as shown on the diagram. The positive
(D) Van1=
3 sequence current component in line „a‟ will
Y 2 600
1 be
3
Q.54 The parameters of a transposed overhead
transmission line are given as:
12 | Power system
a
Ia 10 0 0 A (A) 1.31. -1070 (B) 0.332 -1200A
(C) 0.996 -1200A (D) 3.510 -810A
Z Z Q.60 A 20-MVA, 6.6kV, 3-phase alternator is
I b 10 180 A
0 connected to a 3-phase transmission on
b Ic 0 Z line. The per unit positive sequence,
c
negative sequence and zero sequence
(A) 5.78 300 (B) 5.78 900 impedance of the alternator are j0.1, and
j0.04 respectively. The neutral of the
(C) 6.33 900 (D) 10.00 300 alternator is connected to ground through
an inductive reactor of j0.05 p.u. The per
Q.58 A 3-phase generator rated at 110MVA, unit positive, negative and zero sequence
11kV is connected through circuit breakers impedances of the transmission line are
to a transformer. The generator is having j0.1 and j0.3 respectively. All per unit
direct axis sub-transient reactance Xd”= value are based on the machine rating. A
19% transient reactance 26%, Xd‟=26% and solid ground fault occurs at one phase of
synchronous reactance=130%. The the far end of the transmission line. The
generator is operating at no load and rated voltage of the alternator neutral with
voltage when a three phase short circuit respect to ground during the fault is
fault occurs between the breakers and the
transformer. The magnitude of initial (A) 513.8V (B) 889.9V
symmetrical rims current in the breakers (C) 1112.0V (D) 642.2V
will be
(A) 4.44 kA (B) 22.20 kA
Q.61 A generator is connected to a transformer
(C) 30.39 kA (D) 38.45 kA which feed another transformer through a
short feeder. The zero sequence impedance
value are expressed in pu on a common
Q.59 A three-phase alternator generating base and are indicated in figure. The
unbalanced voltage is connected to an Thevenin‟s equivalent zero sequence
unbalanced load through a 3-phase impedance at point B is
transmission line as shown in figure, the
X0 0.03 X 0 0.1 X 0 0.05 X 0 0.07
neutral of the alternator and the star point
of the load are solidly grounded. The phase
voltage of the alternator are Ea=10 00,
~ B
0.25
Eb=10 -900V, Ec=10 1200V. The 0.25
Q.64 For the configuration shown in fig. 14, the Q.68 For the network shown in fig, the zero
breaker connecting a large system to bus 2 sequence reactance in p.u. are indicated.
is initially open. The system 3-phase fault The zero sequence driving point reactance
level at bus-3 under this condition is not of the node 3 is:
known. After closing the system breaker,
1 2 3
the 3-phase fault level at bus 1 was found
to be 0.5p.u. What will be new 3-phase
X 10 0.05
fault level at system bus 3 after the X 90 0.2
X 90 0.1
interconnection? All unit value are on
X 10 0.15
common bases. Per fault load current are
neglected and pre fault voltages are (A) 0.12 (B) 0.30
assumed to be 1.0 p.u. at all buses.
(C) 0.10 (D) 0.20
j0.2 4 j0.2 1 2 3
E = 1p.u j0.3 Q.69 The system shown in figure feeds two
~
Gen
~
System
loads-
(A) a factory load of 15 MVA consisting
Q.65 the severity of line-to-ground and three of induction motor and
phase fault at the terminals of an unloaded
synchronous generator is to be same. If the (B) A domestic load of 10 MW at 0.8p.f.
terminal voltage is 1.0 p.u. and Z1=Z2= lagging at 6kV. If the induction motor are
j0.1p.u., Z0=j0.05p.u. for the alternator, rated at 6 kV and take 5 times rated current
then the required inductive reactance for at zero p.f. at starting, calculate the dip in
neutral grounding is: voltage at domestic load bus bar when all
the induction motors are started at the same
(A) 0.0166p.u. (B) 0.05p.u. time.
(C) 0.1p.u. (D) 0.15p.u.
Q.66 For given base voltage and base volt-
amperes, the per unit impedance value of
14 | Power system
C j 0.05B6kV level on bus 1 is to be restricted to
15MVA
j 0.0 4
j 0.1 j0.15 j0.06 IM L oad 1500MVA. Calculate, on 100MVA base.
~ A
10MW 100 MVA 200MVA
11kV 132kV 33kV
11kV j 0.05 6kV
0.8 pf Lag
~ 10% ~ 8%
CHAPTER – 05 POWER SYSTEM STABILITY
Q.1 Two 50Hz generating units operate in (C) 5 p.u. (D) 6 p.u.
parallel within the same power plant and Q.6 If the inertia constant H=8 MJ/MVA for
have the following ratings: a 50 MVA generator, the stored energy
Unit 1: 500 MVA, 0.85 power factor, is
20 kV, 3000rpm, H1=5 MJ/MVA (A) 50 MJ (B) 8 MJ
Unit 2: 200 MVA, 0.9 power factor, 20 (C) 400 MJ (D) 6.25 MJ
kV, 1500 rpm, H2=5 MJ/MVA.
Q.7 For a fault in a power system, the term
The equivalent inertia constant H in critical clearing time is related to
MJ/MVA on 100 MVA base is
(A) Reactive power limit
(A) 2.5 (B) 5.0
(B) Transient stability limit
(C) 10.0 (D) 35.0
(C) Short circuit current limit
Q.2 If a 500 MVA, 11kV three-phase
generator at 50 Hz feeds, through a (D) Steady state stability limit
transfer impedance of (0.0 j 0.605) Q.8 A 50 MVA, 11 kV, 3-phase generator
per phase, an infinite bus also at 11 kV; has a stored energy of 400 MJ. Its inertia
then the maximum steady state power constant is
transfer on the base of 500 MVA and 11 (A) 4 (B) 8
kV is (C) 2 (D) 16
(A) 1.0 pu (B) 0.8 pu Q.9 The steady state stability limit of a
(C) 0.5 pu (D) 0.4 pu synchronous machine connected to
Q.3 For 800 MJ stored energy in the rotor at infinite bus is 2.2 p.u. Infinite bus
synchronous speed, what is the inertia voltage is 1.1 p.u. The transfer reactance
constant H for a 50 Hz, four pole turbo- between generator and infinite bus is
generator rated 100 MVA, 11 kV? (A) j0.5 (B) –j0.5
(A) 2.0 MJ/MVA (B) 4.0 MJ/MVA (C) j1.0 (D) –j1.0
(C) 6.0 MJ/MVA (D) 8.0 MJ/MVA Q.10 Two identical synchronous machines
Q.4 The steady state stability limits for having same inertia constant are
round rotor and salient pole 3-phase connected in parallel and swinging
synchronous generator are attained at together. The effective inertia constant
the values of power angle is 4 MJ/MVA. Then each machine has
an inertia constant of
(A) = π/2and = π/2, respectively
(A) 2 MJ/MVA (B) 4 MJ/MVA
(B) < π/2and < π/2, respectively
(C) 8 MJ/MVA (D) 16 MJ/MVA
(C) < π/2and = π/2, respectively Q.11 Transient state stability is generally
(D) = π/2and < π/2, respectively improved by
Q.5 An alternator having an induced e.m.f. (A) Using high speed governors on
of 1.6 p.u. is connected to an infinite bus machines
of 1.0 p.u. If the bus bar has reactance of (B) Using low inertia machines
0.2 p.u., what is the maximum power (C) Dispensing with neutral grounding
that can be transferred?
(D) Any of the above
(A) 2 p.u. (B) 2.67 p.u.
2 | Power System
Q.12 A 2-pole, 50 Hz, 11 kV, 100 MW the system are also shown in the figure.
alternator has a moment of inertia of The infinite bus voltage magnitude is
10,000 kg.m2. The value of inertia 1.0p.u. A three phase fault occurs at the
constant, H is middle of line 2. The ratio of the
(A) 3.9s (B) 4.3s maximum real power that can be
transferred during the pre-fault
(C) 4.6s (D) 4.9s condition to the maximum real power
Q.13 Equal-area criterion is employed to that can be transferred under the faulted
determine: condition is __________.
(A) The steady-state stability Generator insternalbus
j0.1
Infinite bus
j0.5
(B) The transient stability Line 1
j0.2
(C) The reactive power limit ~
j0.5
(D) The rating of a circuit breaker Line 2
j0.1
Q.14 Statement (I) : Equal-area criterion can
be used to determine the stability of Q.17 The synchronous generator shown in the
single machine infinite bus system. figure is supplying active power to an
Statement (II) : AN infinite bus system infinite bus via two short, lossless
has infinite inertia and constant voltage. transmission lines, and is initially in
steady state. The mechanical power
Codes: input to the generator and the voltage
(A) Both Statement (I) and Statement magnitude E are constant. If one line is
(II) are individually true and tripped at time t1 by opening the circuit
Statement (II) is the correct breakers at the two ends (although there
explanation of statement (I). is no fault), then it is seen that the
(B) Both Statement (I) and Statement generator undergoes a stable transient.
(II) are individually true but Which one of the following waveforms
Statement (II) is not the correct of the rotor angle shows the transient
explanation of statement (I). correctly ?
(C) Statement (I) is true but Statement
(II) is false.
Line 1
(D) Statement (I) is false but Statement Infinite Bus
Xs
(II) is true. ~
Eδ 10
Q.15 A 40 MVA, 11 kV, 3-phase, 50 Hz, 4- Line 2
pole turbo-alternator has an inertia
constant of 15 sec. An input of 20 MW (a)
δ
(b)
δ
(c) δ (d) δ
rotating axis
(D) Angular displacement of an axis
fixed to the rotor with respect to a δ One line trips
synchronously rotating axis. 130 0
CHAPTER – 06 LOAD FLOW ANALYSIS
0
Q.5 In Gauss-Seidel load flow method, the
number of iterations may be reduced if (A) 2.0 (B) 3.5
the correction in voltage at each bus is (C) 0.5 (D) 4.5
multiplied by Q.9 Assertion (A): Bus admittance matrix is
(A) Gauss constant a sparse matrix.
(B) Acceleration factor Reason (R): In load flow studies, one of
(C) Blocking factor the buses is taken as a slack bus.
2 | Power System
(A) Both A and R are true and R is the buses are converted to PQ type. In this
correct explanation of A iteration,
(B) Both A and R are true but R is NOT (A) the number of unknown voltage
the correct explanation of A angles increases by two and the number
(C) A is true but R is false of unknown voltage magnitude
(D) A is false but R is true increases by two.
Q.10 For a synchronous generator connected (B) The number of unknown voltage
to an infinite bus through a transmission angles remains unchanged and the
line, how are the change of voltage number of unknown voltage magnitude
( V ) and the change of frequency ( f ) increases by two.
related to the active power (P) and the (C) The number of unknown voltage
reactive power (Q)? angles remains increases by two and the
(A) ( V ) is proportional to P and f to number of unknown voltage magnitude
Q decreases by two.
(B) ( V ) is proportional to Q and f to (D) The number of unknown voltage
P angles remains unchanged and the
number of unknown voltage magnitude
(C) Both V and f are proportional to
decreases by two.
P
Q.14 A 3-bus power system network consists
(D) Both V and f are proportional to of 3 transmission line. The bus
Q admittance matrix of the uncompensated
Q.11 Which one of the following statement is system is
correct? The elements of each row of a -j6 j3 j4
YBUS matrix for load flow studies in j3 -j7 j5 pu.
power system add up to zero.
j4 j5 -j8
(A) Always
If the shunt capacitance of all
(B) If the shunt, admittances at the buses
transmission line is 50% compensated,
are ignored
the imaginary part of the 3rd row 3rd
(C) If mutual couplings between column element (in pu) of the bus
transmission line are absent admittance matrix after compensation is
(D) If both (B) and (C) are satisfied (A) –j7.0 (B) –j8.5
Q.12 A power system has 100 buses including (C)-j7.5 (D) –j9.0
10 generator buses. For the load flow
Q.15 Determine the correctness or otherwise
analysis using Newton-Rephson method
of the following Assertion [a] and
in polar coordinates, the size of the
Reason [r]
Jacobean is
Assertion: Fast decoupled load flow
(A) 189 189 (B) 100 100
method. Given approximate load flow
(C) 90 90 (D) 180 180 solution because it uses several
Q.13 In a 100 bus power system, there are 10 assumptions.
generators. In a particular iteration of Reason: Accuracy depends on the
Newton-Rephson load flow technique power mismatch vector tolerance
(in polar coordinates), two of the PV
Load Flow Analysis | 3
(A) Both [a] and [r] are true [r] is the Q.19 For a power system network with n
correct reason for [a] nodes, Z33 of its bus impedance matrix
(B) Both [a] and [r] are true [r] is not the is j0.5 per unit. The voltage at node 3 is
correct reason for [a] 1.32 -100 per unit. If a capacitor
(C) Both [a] and [r] are false. having reactance of –j3.5 per unit is now
(D) [a] is false and [r] is true. added to the network between node 3
Q.16 A 183-bus power system has 150 PQ and the reference node, the current
buses and 32 PV buses. In the general drawn by the capacitor per unit is
case, to obtain the load flow solution (A) 0.3251000 (B) 0.325800
using Newton-Raphson method in polar
coordinates, the minimum number of (C) 0.371 1000 (D) 0.433800
simultaneous equations to be solved is Q.20 The bus admittance matrix of a three-
__________. bus three-line system is
Statement for linked Answer -13 10 5
Questions 17 and 18: Y=j 10 -18 10
In the following network, the voltage 5 10 -13
magnitudes at all buses are equal to 1
p.u. the voltage phase angles are very If each transmission line between the
small, and the line resistances are buses is represented by an equivalent
negligible. All the line reactance’s are π-network the magnitude of the shunt
equal to j1. susceptance of the line connecting bus 1
Bus 1(slack) j1Ω and 2 is
Bus 2
~ ~ (A) 4 (B) 2
P2 =0.1pu
(C) 1 (D) 0
j1Ω j1Ω
Q.21 A three-bus network is shown in the
figure below indicating the p.u.
Bus 3 P =0.2pu
3 impedance of each element.
Q.17 If the base impedance and the line-to- 1 2 3
line base voltage are 100 and 100kV,
j 0.2
respectively, then the real p[power in j 0.1 -j 0.08 j 0.1
MW delivered by the generator
connected at the slack bus is The Bus admittance matrix, Y-bus, of
(A) -10 (B) 0 the network is
(C) 10 (D) 20 0.3 -0.2 0
Q.18 The voltage phase angles in red at buses (A) j -0.2 0.12 0.08
2 and 3 are 0 0.08 0.02
(A) 2 0.1, 3 0.2
-15 5 0
(B) 2 0, 3 0.1 (B) j 5 7.5 -12.5
j0.2 j0.2
CHAPTER – 07 POWER SYSTEM PROTECTION
(A) i1 =1/ 3 A, i2 = 0A
Opersting coil
(B) i1 =0 A, i 2 = 0 A
(C) i1 =0 A, i2 = 1/ 3 A
(A) 0.1875A (B) 0.2A
(D) i1 =1/ 3 A, i2 = 1/ 3 A (C) 0.375A (D) 60kA
Q.3 A negative sequence relay is commonly Q.6 A three-phase 33kV oil circuit breaker is
used to protect rated 1200A, 2000MVA 3s. The
(A) an alternator (B) a transformer symmetrical breaking current is
(C) a transmission line (D) a bus bar (A) 1200 A (B) 3600 A
Q.4 The over current relays the line (C) 35 kA (D) 104.8 kA
protection and loads connected at the Q.7 A two machine power system is shown
buses are shown in the figure. below. Transmission line XY has
2 | Power System
positive sequence impedance of Z1 n 1 Transmission 3
Line
(A) = Q
(B) = P
16 (D) 17 MHO 18 (C) = U 19 3.636 20 (D)
(D) = T
(E) = S
(A) = S
500 (B) = R
21 (B) 22 23 (A) 24 25 (A)
ohm (C) = Q
(D) = P
At bus
26
(2)