Document No.: UBL3&4‐E‐1‐LO‐EF‐CWO‐001P Rev. 4 Date: 05 May 2015
Document Title: P&I Diagram Main Cooling Water System for Unit 3 Comment No.: 1485/PGE/UBL3&4‐EPCC/2015‐C Contractor Name: Consortium of Sumitomo Corporation and PT Rekayasa Industri Status : Not Approved
No. References EMPLOYER’S COMMENTS By CONTRACTOR’S RESPONSES
1. Suction and Discharge Refer to Cause and Effect Diagram, pressure on suction and discharge line of CTR Contractor agreed. Pressure Hot Well Pump Hot Well Pump will be indicate on DCS 2. Hot Well Pump mechanical Refer to C&E Diagram and Setting Value, flow will Indicate on DCS and CTR Contractor agreed. seal water initiate alarm and Trip the pump when flow ≤ 0.36 m3/hr (Low)