Company: Date: 02/05/2019

Anchor Designer™ Engineer: Page: 1/6


Software Project:
Version 2.7.6990.1 Address:
Phone:
E-mail:

1.Project information
Customer company: Project description:
Customer contact name: Location:
Customer e-mail: Fastening description:
Comment:

2. Input Data & Anchor Parameters


General Base Material
Design method:ACI 318-14 Concrete: Normal-weight
Units: SI units (metric) Concrete thickness, h (mm): 120
State: Uncracked
Anchor Information: Compressive strength, f’c (MPa): 31.03
Anchor type: Cast-in-place Ψc,V: 1.4
Material: AWS Type B Reinforcement condition: A tension, A shear
Diameter (inch): 0.500 Supplemental reinforcement: Yes
Effective Embedment depth, hef (mm): 70 Reinforcement provided at corners: Yes
Anchor category: - Ignore concrete breakout in tension: No
Anchor ductility: Yes Ignore concrete breakout in shear: No
hmin (mm): 102 Ignore 6do requirement: No
Cmin (mm): 32 Build-up grout pad: No
Smin (mm): 51
Base Plate
Length x Width x Thickness (mm): 200 x 250 x 25
Yield stress: 235.00 N/mm²

Profile type/size: C9X20

Recommended Anchor
Anchor Name: Headed Stud - 1/2"Ø AWS Type B Headed Stud

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Company: Date: 02/05/2019
Anchor Designer™ Engineer: Page: 2/6
Software Project:
Version 2.7.6990.1 Address:
Phone:
E-mail:

Load and Geometry


Load factor source: ACI 318 Section 5.3
Load combination: not set
Seismic design: No
Anchors subjected to sustained tension: Not applicable
Apply entire shear load at front row: No
Anchors only resisting wind and/or seismic loads: No

Strength level loads:

Nua [kN]: -255.00


Vuax [kN]: 35.00
Vuay [kN]: 0.00
Mux [kNm]: 0.00
Muy [kNm]: 0.00
Muz [kNm]: 0.00

<Figure 1>

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Company: Date: 02/05/2019
Anchor Designer™ Engineer: Page: 3/6
Software Project:
Version 2.7.6990.1 Address:
Phone:
E-mail:

<Figure 2>

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Company: Date: 02/05/2019
Anchor Designer™ Engineer: Page: 4/6
Software Project:
Version 2.7.6990.1 Address:
Phone:
E-mail:

3. Resulting Anchor Forces


Anchor Tension load, Shear load x, Shear load y, Shear load combined,
Nua (kN) Vuax (kN) Vuay (kN) √(Vuax)²+(Vuay)² (kN)
1 3.4 8.8 0.0 8.8
2 3.4 8.8 0.0 8.8
3 0.0 8.8 0.0 8.8
4 0.0 8.8 0.0 8.8
Sum 6.7 35.0 0.0 35.0
Maximum concrete compression strain (‰): 0.54 <Figure 3>
Maximum concrete compression stress (N/mm²): 16.23
Resultant tension force (kN): 6.74
Resultant compression force (kN): 261.74
Eccentricity of resultant tension forces in x-axis, e'Nx (mm): 0
Eccentricity of resultant tension forces in y-axis, e'Ny (mm): 0
Eccentricity of resultant shear forces in x-axis, e'Vx (mm): 0
Eccentricity of resultant shear forces in y-axis, e'Vy (mm): 0

4. Steel Strength of Anchor in Tension (Sec. 17.4.1)


Nsa (kN) f fNsa (kN)
56.78 0.75 42.59

5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.4.2)


Nb = kclaÖf’chef1.5 (Eq. 17.4.2.2a)
kc la f’c (MPa) hef (mm) Nb (kN)
10.0 1.00 31.03 70 32.66
fNcbg =f (ANc / ANco)Yec,NYed,NYc,NYcp,NNb (Sec. 17.3.1 & Eq. 17.4.2.1b)
ANc (mm2) ANco (mm2) ca,min (mm) Yec,N Yed,N Yc,N Ycp,N Nb (kN) f fNcbg (kN)
62771 43911 185 1.000 1.000 1.25 1.000 32.66 0.75 43.77

6. Pullout Strength of Anchor in Tension (Sec. 17.4.3)


fNpn = fYc,PNp = fYc,P8Abrgf’c (Sec. 17.3.1, Eq. 17.4.3.1 & 17.4.3.4)
Yc,P Abrg (mm2) f’c (MPa) f fNpn (kN)
1.4 380 31.03 0.70 92.43

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Company: Date: 02/05/2019
Anchor Designer™ Engineer: Page: 5/6
Software Project:
Version 2.7.6990.1 Address:
Phone:
E-mail:

8. Steel Strength of Anchor in Shear (Sec. 17.5.1)


Vsa (kN) fgrout f fgroutfVsa (kN)
56.78 1.0 0.65 36.91

9. Concrete Breakout Strength of Anchor in Shear (Sec. 17.5.2)


Shear perpendicular to edge in x-direction:
Vbx = min|0.0.6(le / da)0.2ÖdalaÖf0.6210.6’cca11.5; 9laÖf0.6210.6’cca11.5| (Eq. D-35 & Eq. D-34)
le (mm) da (mm) la f’c (MPa) ca1 (mm) Vbx (kN)
70 13 1.00 31.03 185 46.66
fVcbgx = f (AVc / AVco)Yec,VYed,VYc,VYh,VVbx (Sec. 17.3.1 & Eq. 17.5.2.1b)
AVc (mm2) AVco (mm2) Yec,V Yed,V Yc,V Yh,V Vbx (kN) f fVcbgx (kN)
77400 154013 1.000 1.000 1.400 1.521 46.66 0.75 37.44

Shear parallel to edge in x-direction:


Vby = min|7(le / da)0.2ÖdalaÖf’cca11.5; 9laÖf’cca11.5| (Eq. 17.5.2.2a & Eq. 17.5.2.2b)
le (mm) da (mm) la f’c (MPa) ca1 (mm) Vby (kN)
70 13 1.00 31.03 267 70.66
fVcbgx = f (2)(AVc / AVco)Yec,VYed,VYc,VYh,VVby (Sec. 17.3.1, 17.5.2.1(c) & Eq. 17.5.2.1b)
AVc (mm2) AVco (mm2) Yec,V Yed,V Yc,V Yh,V Vby (kN) f fVcbgx (kN)
70200 320000 1.000 1.000 1.400 1.826 70.66 0.75 59.43

10. Concrete Pryout Strength of Anchor in Shear (Sec. 17.5.3)


fVcpg = fkcpNcbg = fkcp(ANc / ANco)Yec,NYed,NYc,NYcp,NNb (Sec. 17.3.1 & Eq. 17.5.3.1b)
kcp ANc (mm2) ANco (mm2) Yec,N Yed,N Yc,N Ycp,N Nb (kN) f fVcpg (kN)
2.0 84937 43911 1.000 1.000 1.250 1.000 32.66 0.70 110.55

11. Results
Interaction of Tensile and Shear Forces (Sec. 17.6.)
Tension Factored Load, Nua (kN) Design Strength, øNn (kN) Ratio Status
Steel 3.37 42.59 0.08 Pass
Concrete breakout 6.74 43.77 0.15 Pass (Governs)
Pullout 3.37 92.43 0.04 Pass

Shear Factored Load, Vua (kN) Design Strength, øVn (kN) Ratio Status
Steel 8.75 36.91 0.24 Pass
T Concrete breakout x+ 35.00 37.44 0.93 Pass (Governs)
|| Concrete breakout y- 17.50 59.43 0.29 Pass (Governs)
Pryout 35.00 110.55 0.32 Pass

Interaction check Nua/fNn Vua/fVn Combined Ratio Permissible Status


Sec. 17.6..2 0.00 0.93 93.5 % 1.0 Pass

1/2"Ø AWS Type B Headed Stud with hef = 70 mm meets the selected design criteria.

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Company: Date: 02/05/2019
Anchor Designer™ Engineer: Page: 6/6
Software Project:
Version 2.7.6990.1 Address:
Phone:
E-mail:

12. Warnings
- Designer must exercise own judgement to determine if this design is suitable.

Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com