Troubleshooting
G3516B Engines
Media Number -RENR2270-07 Publication Date -01/04/2006 Date Updated -10/04/2006

i02112698

Generator Output Power Readings Do ot Match


SMCS - 5574-035-PWR

This information only applies to engines that use charge density feedback in order to control
emissions.

The Electronic Control Module (ECM) monitors the generator's output power in order to accurately
control the air/fuel ratio. The ECM uses an output from one of the following sources in order to
monitor the generator's output power:

 Electronic Modular Control Panel II+ (EMCP II+)

 Programmable Logic Controller (PLC)

 Wattmeter

The PLC and the wattmeter are also called power sensors.

Probable Causes
The following probable causes apply if the generator is equipped with the EMCP II+:

 There is an incorrect calibration value for the AC Transformer Box + (ATB+).

 A potential transformer in the ATB+ is faulty.

 A current transformer in the ATB+ is faulty.

 The ATB+ is faulty.

 There is an incorrect value for one or more of the parameters for the fuel.

 There is an incorrect value for one or more of the "Power Monitoring" parameters.

The following probable causes apply if the generator is equipped with a power sensor:

 There is a faulty potential transformer for the power sensor.

 There is a faulty current transformer for the power sensor.

 The power sensor is faulty.

 There is a problem with the wiring between the power sensor and the ECM.

 There is an incorrect value for one or more of the parameters for the fuel.

https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/med... 14/05/2010
Service Information System Página 2 de 3

 The offset voltage at the input to the ECM from the power sensor is too high.

 There is an incorrect value for one or more of the "Power Monitoring" parameters.

Read the rest of this procedure before you adjust the "Power Monitoring" parameters.

Recommended Repairs
Generators that are Equipped with EMCP II+

Verify that the transformers and the ATB+ are operating correctly. Refer to the appropriate service
literature for the EMCP II+.

Verify that the values for the "Air/Fuel Ratio Control" configuration parameters are correct. Refer to
Troubleshooting, "Electronic Control System Parameters".

Verify that the values for the "Power Monitoring" configuration parameters are correct. Refer to
Troubleshooting, "Electronic Control System Parameters".

Generators that are Equipped with a Power Sensor

Verify that the transformers for the power sensor are operating correctly. Refer to the service
literature for the power sensor.

Verify that the power sensor is operating correctly. Refer to the service literature for the power
sensor.

Verify that the values for the "Air/Fuel Ratio Control" configuration parameters are correct. Refer to
Troubleshooting, "Electronic Control System Parameters".

Check the wiring between the power sensor and the ECM for corrosion and for pinch points. Refer to
Troubleshooting, "Inspecting Electrical Connectors".

The ECM must receive an accurate voltage from the power sensor. If the voltage is not accurate, the
ECM may not accurately control the air/fuel ratio. When the generator's output is zero, the voltage
from the power sensor must be less than 0.01 VDC. This voltage is called the offset voltage.

Use the following procedure in order to determine if the offset voltage is too high. Perform this
procedure before you adjust the "Power Monitoring" parameters.

ote: This measurement must be taken at the ECM P1 connector. The engine must be stopped.

1. If the engine is running, stop the engine.

2. Insert 7X-1710 Multimeter Probes into terminals P1-19 and P1-25. Connect a digital voltmeter
to the probes. The polarity of the connections is not important.

3. Verify that the probes are making good contact with the terminals inside the connector.
Measure the DC voltage at the terminals.

The voltage is acceptable if the voltage is less than ±0.01 VDC.

If the voltage is less than ±0.01 VDC, the values for the "Power Monitoring" parameters may

https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/med... 14/05/2010
Service Information System Página 3 de 3

be incorrect. Refer to Systems Operation/Testing and Adjusting, "Electronic Control System


Parameters".

If the voltage is greater than ±0.01 VDC, the circuit between the power sensor and the ECM
must be calibrated. Refer to Troubleshooting, "Generator Output Power Sensor - Calibration".

Copyright 1993 - 2010 Caterpillar Inc. Fri May 14 14:31:00 UTC-0300 2010