Shutdown SIS
Previous Screen
i02848556
Illustration 1 g01425628
The terminals and heat sinks are live at hazardous voltages when power
is applied and for up to 8 minutes after power is removed.
OT OK - If the governor is not operating properly, refer to the engine manual in order to
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 01/08/2010
G3520C Generator Set GZM00001-UP(SEBP3869 - 20) - Document Structure Página 2 de 2
STOP.
2. Verify that the sensing and input power leads are connected securely.
OT OK - If the sensing or input power leads are not connected securely, tighten the
connections.
STOP.
3. Verify that the voltage regulator stability range is set to the proper range.
OT OK - If the stability range setting is incorrect, reset the stability range.
STOP.
4. Verify that the stability level is properly set. If the stability level is not properly set, reset the
stability level.