Preface
FR200H series is a enhanced type during all FRECON inverters group, special design for
HVAC, air conditioner and water-supply industry, use for fan, pumps and other loads, support 2
modes water supply of fixed variable-frequency pump and cycle variable-frequency pumps, flexible
control logic of add/reduce pumps, dormancy/awaken based on pressure, timing rotate control and
other special functions.
When debugging the product, please refer to debugging guide in the user manual. Product
maintenance please refers to FR200 user manual.
IMPORTANT NOTES
◆To illustrate the details of the products,pictures in this manual based on products with outer
casing or safety cover being removed.When using this product, please be sure to well install
outer casing or covering by the rules, and operating in accordance with the manual contents.
◆The illustrations this manual for illustration only and may vary with different products you have
ordered.
◆The company is committed to continuous improvement of products, product features will
continue to upgrade, and the information provided is subject to change without notice.
◆If you are using have questions; please contact our regional agents or our customer service
center. Customer Service Tel 0755 -33067999.
◆The company's other products please visit our website: http://www.frecon.com.cn
-1-
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
Contents
Preface ........................................................................................................................................ - 1 -
Contents ...................................................................................................................................... - 2 -
Chapter 1 Product Information ................................................................................................... - 3 -
1.1 Nameplate information ....................................................................................................... - 3 -
1.2 Information of FR200H Product Model ................................................................................ - 4 -
1.3 Terminal Configuration ........................................................................................................ - 4 -
1.4 Configuration, Mounting Dimensions and Weight ................................................................ - 8 -
Chapter 2 Debugging Guide ..................................................................................................... - 10 -
Chapter 3 List of Parameters .................................................................................................... - 11 -
3.1 Standard Function Parameters ......................................................................................... - 11 -
Chapter 4 Maintenance and troubleshooting .......................................................................... - 27 -
-2-
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
Model Explanation
Model show on product nameplate contains information below
FR200 H-4T-7.5G/011P B
Brake unit:
Product series code: None: No Braking Unit
FR200H B: Built-in brake unit(30kW
following built,37 ~ 75kW optional
built,No built above 90kW)
-3-
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
1.2 Information of FR200H Product Model
Table 1-1FR200HProduct model and technical data
Power Rated Rated output
Model No. Applicable motor
capacity Input current current
kW HP
KVA A A
3-Phase: 380V,50/60Hz Range: -15%~+30%
FR200H-4T-0.7G/1.5PB 1.5 3.4 2.5 0.75 1
FR200H-4T-1.5G/2.2PB 3 5.0 4.2 1.5 2
FR200H-4T-2.2GB 4 5.8 5.5 2.2 3
FR200H-4T-4.0G/5.5PB 6 11 9.5 3.7、4 5
FR200H-4T-5.5G/7.5PB 8.9 14.6 13 5.5 7.5
FR200H-4T-7.5G/011PB 11 20.5 17 7.5 10
FR200H-4T-011G/015PB 17 26 25 11 15
FR200H-4T-015G/018PB 21 35 32 15 20
FR200H-4T-018G/022PB 24 38.5 37 18.5 25
FR200H-4T-022G/030PB 30 46.5 45 22 30
FR200H-4T-030G/037PB 40 62 60 30 40
FR200H-4T-037G/045P
57 76 75 37 50
FR200H-4T-037G/045PB
FR200H-4T-045G/055P
69 92 91 45 60
FR200H-4T-045G/055PB
FR200H-4T-055G/075P
85 113 112 55 70
FR200H-4T-055G/075PB
FR200H-4T-075G/090P
114 157 150 75 100
FR200H-4T-075G/090PB
FR200H-4T-090G/110P 134 160* 176 90 125
FR200H-4T-110G/132P 160 190* 210 110 150
FR200H-4T-132G/160P 192 232* 253 132 175
FR200H-4T-160G/185P 231 282* 304 160 210
FR200H-4T-185G/200P 240 326* 350 185 250
FR200H-4T-200G/220P 250 352* 377 200 260
FR200H-4T-220G/250P 280 385* 426 220 300
FR200H-4T-250G/280P 355 437* 470 250 330
FR200H-4T-280G/315P 396 491* 520 280 370
FR200H-4T-315G/355P 445 580* 600 315 420
FR200H-4T-355G/400P 500 624* 650 355 470
FR200H-4T-400G/450P 565 690* 725 400 530
FR200H-4T-450G/500P 623 765* 800 450 600
1.3 Terminal Configuration
1.3.1 Main Circuit Terminals
a: 1.5~2.2kWMain Circuit Terminals
Upload and
Control circuit
download interfaces
terminals
Main circuit
terminals
(+) (-) R S T UV
POWER
-4-
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
b:4~18.5kW Main Circuit Terminals
-5-
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
e: 110~315kW Main Circuit TerminalsSchematic
DI1 DI2 DI3 DI4 COM Y1 Y2 GND AO1 AO2 485+ 485- R2A R2B R2C
+24V PLC COM DI5 DI6 DI7/HI +10V AI1 AI2 AI3 GND PE R1A R1B R1C
-7-
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
Normally open
R2A-R2C
terminal
Normally
R2B-R2C
closedterminal
485
Rate:
485+-485- Communication
4800/9600/19200/38400/57600/
Terminals
485 115200bps
485
Communication Termination resistor is set by the
Communication
GND toggle switch on the control panel
shielded
RS485
ground
Shield PE Shield Ground Ground terminal for shield
External
Use standard network cable
operation
Auxiliary Maximum cable distance: 50m
panel interface
Interface
Parameter
UP/DOWNLOAD
copy interface
4X
W1 d
W
Fig. 1-11 1.5~18.5kW Wall installation diagram
b: 22~400kW Dimensions and wall mounting dimensions
D d W1 W1
H1
H1
H
W1 4x
d
W W D
Fig.1-12 22~160kW Wall installation diagram (1) Fig. 1-13185~400kW Wall installation diagram (2)
-8-
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
Table 1-4 Configuration, mounting dimensions and weight
External and installation dimensions(mm)
Mounting Weight
Model NO.
W W1 H H1 D Hole (Kg)
Diameter
3-Phase: 380V,50/60Hz Range: -15%~+30%
FR200H-4T-0.7G/1.5PB
FR200H-4T-1.5G/2.2PB 117 107 187 177 160 4.5 1.9
FR200H-4T-2.2GB
FR200H-4T-4.0G/5.5PB
FR200H-4T-5.5G/7.5PB 146 131 249 236 177 5.5 3.2
FR200H-4T-7.5G/011PB
FR200H-4T-011G/015PB
198 183 300 287 185 5.5 5.4
FR200H-4T-015G/018PB
FR200H-4T-018G/022PB
FR200H-4T-022G/030PB 255 176 459 443 220 7 15.5
FR200H-4T-030G/037PB
FR200H-4T-037G/045P
270 130 590 572 260 7 27.5
FR200H-4T-045G/055P
FR200H-4T-055G/075P
357 230 590 572 260 7 37
FR200H-4T-075G/090P
FR200H-4T-090G/110P
FR200H-4T-110G/132P 430 320 830 802 293 12 77.7
FR200H-4T-132G/160P
FR200H-4T-160G/185P
FR200H-4T-185G/200P 500 180 1107 1078 328 14 138.5
FR200H-4T-200G/220P
FR200H-4T-220G/250P
FR200H-4T-250G/280P 660 230 1160 1130 340 14 190
FR200H-4T-280G/315P
FR200H-4T-315G/355P
FR200H-4T-355G/400P 810 300 1140* 1110 400 14 196
FR200H-4T-400G/450P
-9-
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
FR200H series special purpose inverter for multi-pumps constant pressure water supply specially
developed for constant pressure water supply industry, featured with 2 modes below:
Mode 1: fixed variable frequency control mode wirings:
220V
R1A R2A
KA1 KA2
L1 R U R1C R2C
L2 S V M1
L3 T FR200H W
KM2 KM3 KM4 KM5
FWD
DI1 R1A
REV
DI2 R1C M2
Default Signal
DI3 R2A
Q2
DI4 R2C
Q3
DI5 Inside the dotted line is power-
Q4 DI6 24V
M3 frequency pumps, can be added on
Q5 DI7 Y1 KA1 customers’ requirements up to 4 pcs
COM
Y2 KA2
10V
Given
AI1
Feedback M4
AI2
GND
M5
R1A R2A
KA1 KA2
R1C R2C
KM1
L1 R U
L2 S V M1 KM1 KM2 KM3 KM4
L3 T FR200H W
FWD KM2
DI1 R1A
REV DI2 R1C
Default Value
DI3 R2A
Q2
DI4 R2C
Q3 KM3
DI5
Q4 DI6 24V M2
Q5 DI7 Y1 KA1
COM
Y2 KA2 KM4
10V
Given
AI1
Feedback
AI2
GND
- 10 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
- 15 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
0: Current limit disabled
F11.00 Current limit control 1: Current limit mode 1 2 ×
2: Current limit mode 2
F11.01 Current limit 100.0~200.0% 150.0% ×
Frequency decreasing
time(limit current in
F11.02 0.0~6000.0s 5.0s △
constant speed
operation)
Current limit mode 2
F11.03 0.1~100.0% 3.0% △
proportion gain
Current limit mode 2 0.00~10.00 s (0.00: integral
F11.04 10.00s △
integral time is invalid)
0: Overvoltage stall disabled
Overvoltage Stall
F11.05 1: Overvoltage stall mode 1 1 ×
Control
2: Overvoltage stall mode 2
Overvoltage Stall 600~800V(380V inverter) 730V
F11.06 ×
Voltage 320~400V(220V inverter) 370V
Overvoltage Stall
F11.07 0.1~100.0% 50.0% △
Mode 2 Proportion Gain
Overvoltage Stall
F11.08 Mode 2 frequency 0.00~50.00Hz 5.00Hz △
limited
Unit's place: Bus undervoltage
0: Fault reported and coast to
stop
1: Stop according to the stop
mode
2: Fault reported but continue
torun
3: Fault protection disabled
Ten's digit :Power input phase
F11.10 Protection action 1 Loss (Err09)(Same as unit's 03330 ×
place )
Hundred's digit :Power output
phase loss(Err10)(Same as unit's
place )
Thousand's digit:Motor
overload(Err11)(Same as unit's
place )
Ten thousand's digit:Inverter
overload(Err12)(Same as unit's
place )
External equipment fault(Err13)
0: Fault reported and coast to
stop
1: Stop according to the stop
mode
2: Fault reported but continue
F11.11 Protection action 2 torun 00000 ×
Ten's digit: EEPROM read/write
fault (Err15) (Same as unit's
place)
Hundred's digit: Communication
overtime error (Err18) (Same as
unit's place)
Thousand's digit: PID feedback
- 16 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
loss (Err19) (Same as unit's
place)
Ten thousand's digit: Continuous
running time reached (Err20)
(Same as unit's place)
Unit's place: Module temperature
detection disconnection(Err24)
0: Fault reported and coast to
stop
1: Stop according to the stop
mode
F11.12 Protection action 3 2: Fault reported but continue to 00030 ×
run
Ten's digit: Load becoming 0
(Err25) (Same as unit's place)
Hundred's digit:reserved
thousand's digit:reserved
Ten thousand's digit:reserved
0: Current running frequency
1: Set frequency
Frequency selection for
2: Frequency upper limit
F11.14 continuing to run upon 1 ×
3: Frequency lower limit
fault
4: Backup frequency upon
abnormality
Backup frequency upon
F11.15 0.00~Fmax 0.00Hz ×
abnormality
Motor overload
F11.17 30.0~300.0s 60.0s ×
protection time
Unit's place: detection option:
0: Always detect
1: Detect at constant speed only
Ten's digit :compared object
F11.18 Overload alarm 0: Rated current of motor 000 ×
1: Rated current of drive
Hundred’s digit:report error or not
0:Do not report
1:Report
Overload alarm
F11.19 20.0~200.0% 130.0% ×
threshold
Overload alarm
F11.20 activated time that 0.1~60.0s 5.0s ×
exceeding threshold
Inverter overheat Model
F11.21 50~overheatTemperature ×
warning threshold defined
Detection level of power
F11.22 5.0~100.0% 20.0% ×
loss
Detection time of power
F11.23 0.1~60.0s 5.0s ×
loss
Action selection at 0: Disabled
F11.24 instantaneous power 0 ×
1: Enabled
failure
Decel time at
F11.25 instantaneous power 0.0~6000.0s 5.0s △
failure
0: Disabled
F11.26 Rapid current limit 0 ×
1: Enabled
F11.27 Times of automatic 0~20 0 ×
- 17 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
reset
Interval of automatic
F11.28 0.1~100.0s 1.0s ×
reset
DO action during fault 0: Not act
F11.29 0 ×
auto reset 1: Act
Instant Power-failure
F11.30 60.0%~Recovery Voltage 80%
Bus Voltage
Instant Power-failure
F11.31 Power Failure Voltage~100.0% 85%
Recovery Voltage
Instant Power-failure
F11.32 Voltage Adjustment 0.01~10.00s 0.1
Time
Instant Power-failure
F11.33 0.1~100.0% 40.0%
Gain K
Instant Power-failure 0.00~10.00s (0.00: Integral
F11.34 0.1
Integral Time Ti Invalid)
Group F13 Process PID
0: F13.01 digital setting
1: keypad potentiometer
2: AI1
3: Communication
F13.00 PID setting 2 ×
4: Multi-Reference
5: DI7/HI pulse input
6: AI2
7: AI3
F13.01 PID digital setting 0.0~100.0% 50.0% △
0: AI1
1: AI2
2: Communication
3: AI1+AI2
F13.02 PID feedback 4: AI1-AI2 1 ×
5: Max{AI1,AI2}
6: Min{AI1,AI2}
7: DI7/HI pulse input
8: AI3
PID setting
F13.03 0~6000.0 100.0 △
feedbackrange
0: Forward action
F13.04 PID action direction 0 ×
1: Reverse action
Filtering time of PID
F13.05 0.000~10.000s 0.000s △
setting
Filtering time of PID
F13.06 0.000~10.000s 0.000s △
feedback
Filtering time of PID
F13.07 0.000~10.000s 0.000s △
output
F13.08 Proportional gain Kp1 0.0~100.0 1.0 △
F13.09 Integration time Ti1 0.01~10.00s 0.10s △
F13.10 Differential time Td1 0.000~10.000s 0.000s △
F13.11 Proportional gain Kp2 0.0~100.0 1.0 △
F13.12 Integration time Ti2 0.01~10.00s 0.10s △
F13.13 Differential time Td2 0.000~10.000s 0.000s △
0: No switch, determined by
PID setting parameters Kp1, Ti1 and Td1
F13.14 0 ×
feedbackrange 1: Auto switch on the basis of
input offset
- 18 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
2: Switched by terminal
PID parameter
F13.15 switchover 0.0~100.0% 20.0% ×
deviation 1
PID parameter
F13.16 switchover 0.0~100.0% 80.0% ×
deviation 2
F13.17 PID offset limit 0.0~100.0% 0.0% ×
Unit's digit (Whether to stop
integral operation when the
output reaches the limit)
0: Continue integral operation
F13.18 PID integral property 00 ×
1: Stop integral operation
Ten's digit (Integral separated)
0: Invalid
1: Valid
F13.19 PID differential limit 0.0~100.0% 0.5% ×
F13.20 PID initial value 0.0~100.0% 0.0% ×
Holding time of PID
F13.21 0.0~6000.0s 0.0s ×
initial value
PID output frequency lower
PID output frequency limit~100.0%(100.0%
F13.22 100.0% ×
upper limit corresponds to maximum
frequency )
PID output frequency –100.0%~PID output frequency
F13.23 0.0% ×
lower limit upper limit
Detection value of 0.0~100.0%
F13.24 0.0% ×
PID feedback loss 0.0%: Not judging feedback loss
Detection time of
F13.25 0.0~30.0s 1.0s ×
PID feedback loss
Uinit’s digit:PID operation
0: No PID operation at stop
1: PID operation at stop
Ten’s digit:Output limit
0: Do not limit
F13.26 PID operation at stop 000 ×
1: limit
Hundred’s digit:PID digital given
by UP/DOWN
0: Clear to zero when power off
1: Preserve whenpower off
UP/DOWN speed of PID
F13.27 0.0~100% (0.0% valid) 0.0% △
digital given
Group F14: Swing Frequency, Fixed Length ,Wakeup and Count
Dormant frequency (F14.12)~
F14.10 Wakeup frequency 0.00Hz △
Fmax
F14.11 Wakeup delay time 0.0~6000.0s 0.0s △
F14.12 Dormant frequency 0.00~Wakeup frequency 0.00Hz △
F14.13 Dormant delay time 0.0~6000.0s 0.0s △
0: frequency wakeup
F14.14 Wakeup Mode Selection 0 ×
1: pressure wakeup
Dormant Mode 0: frequency dormant
F14.15 0 ×
Selection 1: pressure dormant
0: AI1
Pressure Feedback
F14.16 1: AI2 0 ×
Source
2: DI7/HI Pulse Input
- 19 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
3: AI3
F14.17 Wakeup Pressure 0.0%~Dormant Pressure 10.0% △
F14.18 Dormant Pressure Wakeup Pressure~100.0% 50.0% △
Group U00 Status Monitoring
U00.00 Running frequency 0.00~Fu 0.00Hz ⊙
U00.01 Set frequency 0.00~Fmax 0.00Hz ⊙
U00.02 Output voltage 0~660V 0.0V ⊙
U00.03 Output current 0.0~3000.0A 0.0A ⊙
U00.04 Output power -3000.0~3000.0kW 0.0kW ⊙
Estimated Motor
U00.05 0~60000rm 0rm ⊙
Speed
U00.06 Bus voltage 0~1200V 0V ⊙
U00.07 Synchronous Frequency 0.00~Fu 0.00Hz ⊙
U00.08 PLC step 1~15 1 ⊙
Program Operation
U00.09 0.0~6000.0s(h) 0.0s(h) ⊙
Time
U00.10 PID set 0~60000 0 ⊙
U00.11 PID feedback 0~60000 0 ⊙
Status of DI1~DI5
U00.12 DI5 DI4 DI3 DI2 DI1 00000 ⊙
digital input terminal
Status of DI6~DI7
U00.13 DI7 DI6 00 ⊙
digital input terminal
Status of digital output
U00.14 R2 R1 Y2 Y1 0000 ⊙
terminal
U00.15 AI1 input 0.0~100.0% 0.0% ⊙
U00.16 AI2 input 0.0~100.0% 0.0% ⊙
U00.17 AI3 input -100.0~100.0% 0.0% ⊙
Keypad potentiometer
U00.18 0.0~100.0% 0.0% ⊙
input
U00.19 HI input 0.00~100.00kHz 0.00kHz ⊙
U00.20 AO1 output 0.0~100.0% 0.0% ⊙
U00.21 AO2 output 0.0~100.0% 0.0% ⊙
U00.22 HO output 0.00~100.00kHz 0.00kHz ⊙
U00.23 Temperature of inverter -40.0℃~120.0℃ 0.0℃ ⊙
Accumulative power-on
U00.24 0~65535min 0min ⊙
time
Accumulative running
U00.25 0~6553.5min 0.0min ⊙
time
Cumulative power-on
U00.26 0~65535h 0h ⊙
time
U00.27 Cumulative running time 0~65535h 0h ⊙
U00.28 Count value 0~65535 0 ⊙
U00.29 Length value 0~65535m 0m ⊙
U00.30 Linear speed 0~65535m/min 0m/Min
U00.31 Output torque 0.0~300.0% 0.0% ⊙
Motor temperature by
U00.32 -40℃~200℃ 0℃ ⊙
PTC
Speed detected by
U00.33 0~60000rpm 0rpm ⊙
encoder
U00.34 Encoder lines 0~65535 0 ⊙
U00.35 Power dissipation 0~65535kWh 0kWh ⊙
U00.36 VDI1~VDI5 input state VDI5 VDI4 VDI3 VDI2 VDI1 00000 ⊙
- 20 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
VDO1~VDO5 output
U00.37 VDO5 VDO4 VDO3 VDO2 VDO1 00000 ⊙
state
Group U01 Fault Record
Err00: No fault
Err01: Accel overcurrent
Err02: Decel overcurrent
Err03: Constant-speed
overcurrent
Err04: Accel overvoltage
Err05: Decel overvoltage
Err06: Constant-speed
overvoltage
Err07: Bus undervoltage
Err08: Short circuit
Err09: Power input phase loss
Err10: Power output phase loss
Err11: Motor overload
Err12: Inverter overload
Err13: External equipment fault
Err14: Module overheat
Err15: EEPROM read/write fault
Err16: Motor auto-tuning
cancelled
Err17: Motor auto-tuning fault
U01.00 Current Fault Type Err18: Communication overtime 0 ⊙
error
Err19: PID feedback loss
Err20: Continuous running time
reached
Err21: Parameter upload fault
Err22: Parameter download
fault
Err23: Braking unit fault
Err24: Module temperature
detection disconnection
Err25: Load becoming 0
Err26: With-wave current limit
fault
Err27: Inverter soft-start relay is
off
Err28: Software
versioncompatibility fault
Err29: Instantaneous
overcurrent
Err30: Instantaneous
overvoltage
Running frequency
U01.01 when the latest fault 0.00~Fu 0.00Hz ⊙
occurred
Output current when the
U01.02 0.0~3000.0A 0.0A ⊙
latest fault occurred
Bus voltage when the
U01.03 0~1200V 0V ⊙
latest fault occurred
Cumulative running time
U01.04 when the latest fault 0~65535h 0h ⊙
occurred
- 21 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
U01.05 Code of previous fault Same as U01.00 0 ⊙
Running frequency
U01.06 when previous fault 0.00~Fu 0.00Hz ⊙
occurred
Output current when
U01.07 0.0~3000.0A 0.0A ⊙
previous fault occurred
Bus voltage when
U01.08 0~1200V 0V ⊙
previous fault occurred
Cumulative running time
U01.09 when previous fault 0~65535h 0h ⊙
occurred
Before-previous fault
U01.10 Same as U01.00 0 ⊙
code
Running frequency
U01.11 when before-previous 0.00~Fu 0.00Hz ⊙
fault occurred
Output current when
U01.12 before-previous fault 0.0~3000.0A 0.0A ⊙
occurred
Bus voltage when
U01.13 before-previous fault 0~1200V 0V ⊙
occurred
Cumulative running time
U01.14 when before-previous 0~65535h 0h ⊙
fault occurred
H00 group: multi-pumps constant pressure water supply
Special purpose 0: Invalid
H00.00 0 ×
inverter function enable 1: Valid
0: fixed variable-frequency
pumps mode
H00.01 Work modes selection 0 ×
1: 2 variable-frequency pumps
cycle mode
Frequency for add Frequency for reduce
H00.02 50.00Hz △
pumps pumps~max frequency
Frequency for reduce 0.00Hz~frequency for add
H00.03 5.00Hz △
pumps pumps
Pressure tolerance for
H00.04 0.0~100.0% 0.0% △
add pumps
Pressure tolerance for
H00.05 0.0~100.0% 0.0% △
reduce pumps
H00.06 Added pumps delay 0.0~300.0s 20.0s △
H00.07 Reduced pumps delay 0.0~300.0s 15.0s △
Time for added pumps
H00.08 0.0~300.0s 1.0s △
speed arrival max
Time for reduced
H00.09 0.0~300.0s 1.0s △
pumps zero-flow
H00.10 Switching time 0.1~10.0s 1.0s ×
Unit: No.1 pump status
0:Spare
1:Enable
Decade: No.2 pump status(same
H00.11 Pumps Status with unit) 00011 △
Hundreds: No.3 pump
status(same with unit)
Kilobit: No.4 pump status(same
with unit)
- 22 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
Myriabit: No.5 pump status(same
with unit)
0:fixed order
H00.12 Timing rotate or not 1:start first stop first 0 ×
2:timing rotate
H00.13 Gap of timing rotate 1~60000Min 240Min ×
Inverter action selection
when adding or 0:Inverter stop
H00.14 reducing pump in 0 ×
single-variable pump 1:Inverter not stop
mode
R1A R2A
24V R S T KA1 KA2
PLC R1C R2C
FWD DI1 R1A
REV DI2 R1C
Default Value FR200H
DI3 R2A KM1 KM2 KM3 KM4
Q2
DI4 R2C
Q3
DI5
Q4 DI6 24V
Q5 DI7 Y1 KA1
COM
Y2 KA2
10V
Given
AI1
Feedback
AI2
GND U V W
M5 M4 M3 M2 M1
- 23 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
Fixed variable-frequency pumps mode parameters setting instructions
F04.02=9(external default
F01.01=6 (PID preset) F02.00=1 (external terminals)
input)
F05.00=31(No.2 F05.01=32 (No.3 F05.02=33(No.4
power-frequency pump) power-frequency pump) power-frequency pump)
F05.03=34(No.5 F13.00=2 (AI1 Pressure F13.02=1AI2(Pressure
power-frequency pump) Preset) Feedback)
H00.01=0(single-variable
pump, multi-power H00.11=1111(all pumps start)
frequency pump)
Note: in case of using 2 pumps or 3 pumps, set parameter (H00.11 pump status) corresponding to set
the un-usage pump to be 0, the pump stops.
1: 2 variable-frequency pumps cycle mode
Water supply system doesn’t fix a certain pump as variable-frequency pump, when system pressure is
insufficient, the running variable-frequency pump firstly switch to grid-power frequency running, and
then variable-frequency enable the next new pump, the pump is the new variable-frequency pump.
When the system has too much pressure, power-frequency pump stops. The same moment at most
only one pump work as variable-frequency pump, another one work on power-frequency, (can control
2*variable-frequency pumps work in cycle). Wirings refer to Figure 3-2.
R1A R2A
24V R S T KA1 KA2
PLC R1C R2C
FWD DI1 R1A
REV DI2 R1C
Default Value
DI3
FR200H
R2A KM1 KM2 KM3 KM4
Q1
DI4 R2C
Q2
DI5
COM 24V
Y1 KA1
10V Y2 KA2
Given
AI1
Feedbac
AI2
k U V W
GND
M2 M1
- 24 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
pumps pumps
Pressure tolerance for
H00.04 0.0~100.0% 0.0% △
add pumps
Pressure tolerance for
H00.05 0.0~100.0% 0.0% △
reduce pumps
H00.06 Added pumps delay 0.0~300.0s 20.0s △
H00.07 Reduced pumps delay 0.0~300.0s 15.0s △
Add pumps: running frequency≥H00.02 set value, feedback pressure<set pressure-pressure
tolerance, and last the delay time set by H00.06, meet the terms of add pumps, add pump.
Reduce pumps: running frequency≤H00.03 set value, feedback pressure>set pressure+pressure
tolerance, and last the delay time set by H00.07, meet the terms of reduce pumps, reduce pump.
Time for added pumps
H00.08 0.0~300.0s 1.0s △
speed arrival max
Time for reduced pumps
H00.09 0.0~300.0s 1.0s △
zero-flow
Time for added pumps speed arrival max: when command for adding pumps being sent, a
delay(H00.08 parameters) been start, which makes the pump arrive at its rated speedbefore start
another pump(avoid shaking).
Time for reduced pumps zero-flow: when command for adding pumps being sent, a delay(H00.09
parameters) been start, which makes the pump can stop effectively before stop another pump(avoid
shaking).
H00.10 Switching time 0.1~10.0s 1.0s ×
This function mainly use for protection inverter and AC power supply from short-circuited, which
caused by contactor action delay when a motor switched from variable frequency to power frequency.
Set the shortest time larger than the total of relay action time and contactor action time, generally
the contactor action from connect to disconnect takes longer time than switch from disconnect to
connect, please operate on longer time.
Unit: No.1 pump status
0:spare
1:start
Decades: No.2 pump status
(same with unit)
H00.11 Pump status Hundreds: No.3 pump status 00011 △
(same with unit)
Thousands: No.4 pump
status(same with unit)
Myriabit: No.5 pump
status(same with unit)
Spare: Control terminals DI1~DI7 are multi-functional terminals, which define their functions by
setting the value of F04.00~F04.03. Repeat definition is allowed, one of the re-defined
terminals valid, the function valid. 51~54 is special functions for constant pressure water
supply, instructions as below: 51~54:No.1~No.4 pumps status.
Start: When function of DI1~DI7 terminal defined as 51~54, terminals valid, then the corresponding
pumps allowed to run, if terminals invalid, and F04.00~F04.03 corresponding pumps status
selected to be 1: start, then the pumps allowed to run, if selected to be 0: spare, then the
pumps not allowed to run.
0:fixed order
H00.12 Timing rotate or not 1:start first stop first 0 ×
2:timing rotate
0: fixed order: start the pumps from small to large.
1: start first stop first: firstly start the running time shortest one when add pumps, firstly stop the
running time longest one when reduce pumps.
2: timing rotate:(1)Single variable pump, with assisted pump switched, timing rotate. When 2 pcs or
more than 2 pcs assisted pumps running at the same time, if system meets the term of reduce
pumps, the firstly started pump will stop first; if the one of them keep running more than H00.13
(timing rotate gap), the assisted pump stops, and start the pump with longest stop time. (2) Multi
- 25 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
variable pump, with assisted pump, with timing rotate. Start current variable pump, when the
running frequency higher than frequency for add pumps, start H00.06 delay, if the frequency
still higher than frequency for add pumps after the delay, then start the other assisted pump.
When variable pump keep running within a certain time, no need to start assisted pumps, if the
time ,more than timing rotate time set by H00.12, then stop the current variable pump, switch
the assisted pump to variable pump.
H00.13 Gap of timing rotate 1~60000Min 240Min ×
Single variable mode: when parts of power-frequency motor running, water supply system under
stable, to avoid parts of motor keep running in a long time, timing rotate time set for limit the longest
running time.
Multi variable mode: when only variable pumps running, and keep running time more than set timing
rotate time, then stop the current running pump and switch to another variable pump.
0:Inverter stop
In single-varialble pump mode, when adding or reducing pump , inverter will stop.
1: inverter not stop
In single-varialble pump mode, when adding or reducing pump , inverter will not stop.
- 26 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
FR200H inverter provides a number of warning information and protection, when a fault occurs,
the protective function is activated, the inverter will stop output, inverter fault relay contact, and in the
inverter displays the fault code on the display panel. Before seeking service user can press the
self-examination tips in this section, analyze problems, and identify solutions. If the problem still
cannot be excluded, seek services, or contact the dealer you purchase the driver with my company.
- 28 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
1: The cable connecting the
AC drive and the motor is 1: Eliminate external faults.
faulty. 2: Check whether the motor
Power output 2: The AC drive's three-phase Three-phase winding is
Err10
phase loss outputs are unbalanced when normal.
the motor is running. 3: Contact the agent or
3: The drive board is faulty. Frecon.
4: The module is faulty.
1: F11-17 is set improperly. 1: Set F11-17 correctly.
2: The load is too heavy or 2: Reduce the load and
locked-rotor occurs on the check the motor and the
Err11 Motor overload
motor. mechanical condition.
3: The AC drive model is of too 3: Select an AC drive of
small power class. higher power class.
1: The load is too heavy or 1: Reduce the load and
locked-rotor occurs on the check the motor and
Err12 Inverter overload motor. mechanical condition.
2: The AC drive model is of too 2: Select an AC drive of
small power class. higher power class.
External 1: External fault signal is input
Err13 Reset the operation.
equipment fault via DI.
1: The ambient temperature is 1: Lower the ambient
too high. temperature.
2: The air filter is blocked. 2: Clean the air filter.
3: The fan is damaged. 3: Replace the damaged
Err14 Module overheat 4: The thermally sensitive fan.
resistor of the module is 4: Replace the damaged
damaged. thermally sensitive resistor.
5: The inverter module is 5: Replace the inverter
damaged. module.
EEPROM The EEPROM chip is Replace the main control
Err15
read/write fault damaged. board.
Since the identification
Motor auto-tuning Press STOP / RST key to
Err16 process, press STOP / RST
cancelled reset
key
1: the motor and the inverter 1: check the connection
output terminals are not between the inverter and
Motor auto-tuning connected motor
Err17
fault 2: The motor does not 2: The motor is disengaged
disengage the load load
3: The electrical fault 3: Check the motor
1: The PC is not working
1: Check the PC Connection
properly
Communication 2: Check the communication
2: The communication line is
Err18 overtime cable
not normal
error 3: The communication
3: F15 set communication
parameters are set correctly
parameters set incorrectly
Check the PID feedback
PID feedback PID feedback set value is less
Err19 signal or set to an
loss than F13.24
appropriate value F13.24
- 29 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
Continuous
Set the running time to reach reference F05.14
Err20 running time
this function Description
reached
1: Is not installed or is not
1: a copy of the card is
plugged parameter copy card
properly installed
Parameter upload 2: Parameter copy card
Err21 parameters
fault anomalies
2: for technical support
3: The control board
3: for technical support
abnormalities
1: Is not installed or is not
1: A copy of the card is
plugged parameter copy card
properly installed
Parameter 2: Parameter copy card
Err22 parameters
download fault anomalies
2: For technical support
3: The control board
3: For technical support
abnormalities
1: The brake line failure or 1: Check the brake unit,
damage the brake pipe replace the brake pipe
Err23 Braking unit fault
2: An external braking resistor 2: Increasing the braking
is too small resistor
Module
temperature The temperature sensor
Err24 For technical support
detection failure or cable break
disconnection
Check that the load is
The AC drive running current disconnected or the setting
Err25 Load becoming0
is lower than F11.22 F11-22 and F11-23 is
correct.
1: The load is too heavy or 1: Reduce the load and
locked rotor occurs on the check the motor and
With-wave
Err26 motor. mechanical condition.
current limit fault
2: The AC drive model is of too 2: Select an AC drive of
small power class. higher power class.
1: Check the grid voltage
Inverter soft-start 1: The grid voltage is too low
Err27 2: Demand for technical
relay is off 2: Rectifier module failure
support
1: The upper and lower
transmission module
Software version re-upload module
Err28 parameters in the parameter
compatibility fault parameters to pass down
version of the control panel
version mismatch.
1. Inverter output circuit being 1. Troubleshooting
grounded or short-circuit; peripheral problems;
2. The acceleration and 2. To increase the
deceleration time is too short; acceleration time;
Instantaneous 3. Manually torque boost or 3. Adjust the manually
Err29
overcurrent V/F curve not appropriate; torque boost or V/F curve;
4. Voltage too low; 4. Adjust the voltage to
5. Start the running motor; normal range;
6. Sudden-load in the acce 5. Select RPM track start or
process; start after motor stopped;
- 30 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
7. Model selection of inverter 6. Cancel sudden-load;
power is too small. 7. Select the inverter with
larger power.
- 31 -
FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
- 32 -