Time dependent analysis of a simply supported beam with a single tendon. The duration of the first stage is 30
days, the shuttering is removed on 7th day and the DL & PS loads are applied on the first day of construction
stage. The beam is jacked from one (left, Node 1) end.

Calculation of Jacking Force


Maximum Jack Pressure shall not exceed 90% of 0.1% Proof Stress. 0.1% of proof stress shall be taken as
equal to 85% of minimum UTS.
Proof Stress is the one that will cause a permanent deformation

Loss Calculation
Friction Loss

Slip Loss
Relaxation Loss
Short Term Relaxation
The loss of Pre-stress due to relaxation is related to the
jacking force in the cables. The recommended value of
jacking force should be in the range of 0.5fpu to 0.8fpu as
per Clause 8, Page 11, IRC:18 - 2000.

Long Term Relaxation


For calculation of stress in service condition long term relaxation loss value occuring
at about 0.5x10e6, hours shall be considered, which is 3times the1000hrs value.(IRC:18, CL.11.4)

Creep Loss

Fibre stress due to PS

Fibre stress due to SW

Net stress

Strain
Maturity at 7days
Maturity at 30days
The creep straiin for the corresponding maturity of concrete as per IRC:18-2000 ; Table 2 ; Page 16
For 66% maturity = 6.54 e-4 /10mpa
For 100% maturity = 4.00 e-4 /10mpa
Net strain = 6.54e-4 - 4.0e-4 = 2.04e-4/10mpa
Loss due to creep

Long Term creep loss

Shrinkage Loss
The shrinkage strain for the correxponding maturity of concrete as per IRC 18-2000; Table 3 ; Page 17
Strain due to residual shrinkage for 7 days = 3.5e-4
Strain due to residual shrinkage for 28 days = 1.9e-4
Net strain = 3.5e-4 - 1.9e-4
Short Term shrinkage Loss

Long Term shrinkage Loss

Creep +Shrinkage
Input / Output Quantities Notation Value Unit
Beam Dimension L 20.000 m
B 0.500 m
H 1.200 m
No. of Cables 1.000
No of Strands 19.000
Strand Dia 12.700 mm
Area of 1 Strand 98.170 mm2
Area of Cable Ac 1875.300 mm2
Tendon Type
Duct Dia. Ø 85.000 mm
Ultimate Tensile Strength fpu 1860.000 N/mm2
Yield Strength fy 1581.000 N/mm2
Young's Modulus of Steel Es 195000.000 N/mm2
Young's Modulus of Concrete Ec 34000.000 N/mm2
Moduler Ratio m 5.735
Relaxation Coefficient 0.025
Curveture Friction Factor μ 0.200
Wobble Friction Factor k 0.002 Per m
Anchorage Slip 6.000 mm
Bond Type
Compressive strength of concrete at 28days fck 45.000 N/mm2

0.1% of Proof Stress 1581.000 N/mm2


Maximum Jacking Stress 1422.900 N/mm2
%age of UTS that should be used for JackingStress 76.500
Hence Jacking Stress 1422.900 N/mm2
Jacking Force P 266.836 Ton

α 0.032

Residual Force after Friction Loss at node no. 5 253.114 Ton


Friction Loss at node no. 5 13.722 Ton

lset 17882.520 mm
lset 17.883 m
Friction + Slip Loss 24.539 Ton
Only Slip Loss 10.817 Ton
Residual Force after Friction & Slip Loss at node no. 5 242.297 Ton
Short Term Relaxation Loss 66709.109 N
Short Term Relaxation Loss 6.671 Ton

1000 hrs relaxation 7.410 Ton


Long Time Relaxation 22.230 Ton

e 0.320
P/A 4.447 N/mm2
M/Z 7.116 N/mm2
P/A +M/Z 11.563 N/mm2
m 72.200 Ton-m
M/Z 6.017 N/mm2
5.546 N/mm2

66.5 %
101.0 %

6.54E-05 mpa
4.00E-05 mpa
2.54E-05 mpa
5.15 Ton

8.11 Ton

3.50E-04
1.90E-04
1.60E-04
5.85 Ton

6.95 Ton

11.00 Ton
Note

As per the Standard


As per the Standard
Internal Post-tension

UTS
85% of UTS

Low Relaxation (Clause 11.4, Table 4A, Page 17, IRC:18 - 2000

Bonded

0.1% of Proof Stress = (85% of UTS)


Maximum Jacking Force = 90% of (85% of UTS)
(Maximum Jacking Force / UTS)*100
(76.5% of maximum jacking stress) Used in standard calculations

Px  Po  e  (   kx )

Little deviation is due to inaccuracy in manual calculation of Alpha value

Slip will occur at the end where jacking is done i.e. node 1
Clause 11.4, Table 4A, Page 17, IRC:18-2000
20m Width: 0.5m

0 0.5 m
-0.16
-0.32 1.2m

5m 5m 5m 5m