DEEP SEA ELECTRONICS AUTO MAINS


FAILURE
CONTROLLER
FEATURES DESCRIPTION cont’d
055-015 Issue 1
¾ Automatically senses Selected timers and alarms can AM 16/01/06
mains (utility) failure and be altered by the customer from
starts the backup the front panel.
generator.
Alterations to the system are
¾ Clear, backlit LCD display made using the 810 interface
to show the status of the and a PC. This interface also
load switches, and mains provides real time diagnostic
(utility) supply as well as to facilities.
indicate alarm conditions
should they occur. It is also possible to monitor and
control the system via PC up to SPECIFICATION
¾ Integral, configurable
100metres (111 yards) from the DC Supply:
starting and stopping 8V to 35V Continuous.
controller.
timers. Able to survive 0V for 50mS, providing
supply was at least 10V before dropout
¾ Configurable inputs and Easy push button control and supply recovers to 5V. This is
Operation of the module is via achieved without the need for internal
outputs to help meet batteries.
increasing demand within pushbutton controls mounted on
the front panel with Max. Operating Current:
the industry. 180mA at 12V. 190mA at 24V
STOP/RESET, MANUAL,
¾ Comprehensive PC TEST, AUTO and START Max. Standby Current:
configuration, monitoring 145mA at 12V. 150mA at 24V
pushbuttons. The first four
and control including true pushbuttons feature LED Generator Input Range:
PC mimic of the module 35V(L-N) to 277V(L-N) AC (+20%)
‘selected’ indications. A further 50Hz - 60Hz (min 15V AC)
fascia. pushbutton provides LCD
DISPLAY SCROLL function. Mains Sensing Input Range:
¾ Selected field adjustable 35V(L-N) to 277V(L-N) AC (+20%)
parameters configurable Instrumentation and Alarms 50Hz - 60Hz (min 15V AC)
from the fascia. The 720 module provides Auxiliary outputs:
metering and alarm facilities Solid state
2.4A DC at supply voltage.
DESCRIPTION via the LCD display and
includes the following Fuel / Start outputs:
The Model 720 is an Automatic instrumentation displays, Solid state
3.4A DC at supply voltage.
Mains Failure Control Module. accessed via the DISPLAY
The module is used to monitor SCROLL pushbutton: Generator C.T.
5A secondary 0.5VA
a mains supply and
automatically start a standby Mains Volts (L1-N, L2-N, L3-N) Operating Temperature Range:
Mains Volts (L1-L2, L2-L3, L3-L1) -30°C to +70°C
generator set. The module
also provides indication of Generator frequency Dimensions:
Engine speed 209mm x 146mm x 30.3mm
operational status and fault (8.23” x 5.75” x 1.08”)
conditions, automatically Generator Volts (L1-N)
Generator current (L1, L2, L3) Panel cutout:
shutting down the genset and 182mm x 137mm
indicating failures by means of Engine oil pressure (7.17” x 5.39”)
an LCD display, and Engine coolant temperature Maximum panel thickness - 8mm (0.3”)
appropriate flashing LED on Hours run counter Deep Sea Electronics reserve the right to change
the front panel. Battery Volts specification without prior notice.

Deep Sea Electronics Plc. Deep Sea Electronics inc.


Highfield House, Hunmanby Industrial Estate, North Yorkshire. 3230 Williams Avenue
YO14 0PH. ENGLAND Rockford, IL 61101-2668. U.S.A.
Tel:+44 (0)1723 890099. Phone: +1 (815) 316-8706
Fax: +44 (0)1723 893303. Fax: +1 (815) 316-8708
Email: sales@deepseaplc.com Email: dsesales@deepseausa.com
Web: www.deepseaplc.com Web: www.deepseausa.com
CASE
DIMENSIONS

Panel Cutout : 182mm x 137mm (7.17” x 5.39”)


TYPICAL WIRING DIAGRAM