6.1 Introduction
Air intakes are required for a number of items of equipment which are normally
located in or near plants. Included are internal combustion engines and turbines,
air compressors, inert gas generators, forced draft furnaces, buildings (including
substations) containing unclassified electrical equipment, and boilers. These
equipment items represent an internal source of ignition for any flammable
vapors which might have been pulled in with the air, and the potential for
internal explosion. For this reason, the locations of air intakes in relation to
adjacent equipment must be carefully selected.
6.2.1 For details prescribing design and location of air intakes for buildings
situated within plot limits, refer to SAES-B-014.
6.2.2 For use of unclassified window type air conditioning units and window
type air conditioning units suitable for NEC Class I, Division 2, Group D
atmospheres, refer to SAES-B-014.
6.3.1 Living quarters may not be located on a platform handling crude oil or
gas. Living quarters platforms shall be separated from the other platform
by a minimum of 45 m.
6.3.2 The tie-in platform with production headers and safety shutoff valves
shall be not less than 45 m from the GOSP and/or gas compression
platform(s), and preferably 90 degrees from the prevailing wind.
Page 6 of 32