Sei sulla pagina 1di 5

CONTRACT NO :

LIST
-

PAGE
15NO03-LST-60-003
1 OF 5

PENGADAAN SEMARANG GAS DISTRIBUTION PIPE LINE (CP-16)

INSTRUMENT CABLE SCHEDULE

CLIENT : PT. PERUSAHAAN GAS NEGARA (Persero) Tbk.

CONTRACTOR : KONSORSIUM WIKA - MGP - SGI

PROJECT NAME : PENGADAAN SEMARANG GAS

DISTRIBUTION PIPELINE (CP-16)

LOCATION : SEMARANG

DOCUMENT NO. : 15NO03-LST-60-003

Issued for Bid RP DA DS


Revision By Checked Approved Checked Approved
DATE Status Code
Code ENG. DIP PT. WIKA BUS. DEV
PENGADAAN SEMARANG GAS DISTRIBUTION PIPE LINE (CP-16)

Date :
Rev. 0 INSTRUMENT CABLE SCHEDULE 05/03/2015
15NO03-LST-60-003
Page : 2 of 5

REVISION SHEET

REVISION CODE REVISION CODE REVISION CODE


Page Page Attachment
A B C D 0 1 2 A B C D 0 1 2 A B C D 0 1 2

1
2
3
4
5
PENGADAAN SEMARANG GAS DISTRIBUTION PIPE LINE (CP-16)

Date :
Rev. 0 INSTRUMENT CABLE SCHEDULE 05/03/2015
15NO03-LST-60-003
Page : 3 of 5

COMMENT SHEET

Revision Comment Implementation


Chapter Page Revision Note Remark
Code (Yes/No)
Project : Pengadaan Semarang Gas Distribution Pipeline (CP-16)
Client : PT PERUSAHAAN GAS NEGARA (Persero) Tbk
Document No
Date
: 15NO03-LST-60-003
:-
CABLE SCHEDULE
Rev :-

Core Size Units

Length Units
Cable Type

Core Size
No Cores
Tag No Location_Desc Gland_Size Gland_type

No Pairs
Cable

Length
Addl Item
No Cable No Schedule Service Desription
Description
Remarks
From To From To From To From To

TAMBAK LOROK OFFTAKE STATION


1 001-PT-01 Type 1 - 1 16 AWG 114,9 M 001-PT-01 AJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PSD Outlet From Other Station Natural Gas To Gas Filter
2 001-PT-02 Type 1 - 1 16 AWG 114,9 M 001-PT-02 AJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PSD Outlet From Other Station Natural Gas To Gas Filter
3 001-PT-03 Type 1 - 1 16 AWG 114,9 M 001-PT-03 AJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PSD Outlet From Other Station Natural Gas To Gas Filter
4 001-PDT-01 Type 1 - 1 16 AWG 112,1 M 001-PDT-01 AJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Gas Filter 3322-F-001A
5 001-PDT-02 Type 1 - 1 16 AWG 107,1 M 001-PDT-02 AJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Gas Filter 3322-F-001B
6 002-AT-01 Type 1 - 1 16 AWG 95,9 M 002-AT-01 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS From Gas Filter To Metering 3322-GM-002 A/B
7 002-AT-02 Type 1 - 1 16 AWG 95,9 M 002-AT-02 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS From Gas Filter To Metering 3322-GM-002 A/B
8 002-AT-03 Type 1 - 1 16 AWG 95,9 M 002-AT-03 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS From Gas Filter To Metering 3322-GM-002 A/B
9 002-AT-04 Type 1 - 1 16 AWG 95,9 M 002-AT-04 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS From Gas Filter To Metering 3322-GM-002 A/B
10 002-AT-05 Type 1 - 1 16 AWG 95,9 M 002-AT-05 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS From Gas Filter To Metering 3322-GM-002 A/B
11 002-AT-06 Type 1 - 1 16 AWG 95,9 M 002-AT-06 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS From Gas Filter To Metering 3322-GM-002 A/B
12 002-FT-01 Type 1 - 1 16 AWG 86,5 M 002-FT-01 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A
13 002-PT-01 Type 1 - 1 16 AWG 86,5 M 002-PT-01 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A
14 002-TT-01 Type 1 - 1 16 AWG 86,5 M 002-TT-01 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A
15 002-FT-02 Type 1 - 1 16 AWG 81,5 M 002-FT-02 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 B
16 002-PT-02 Type 1 - 1 16 AWG 81,5 M 002-PT-02 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 B
17 002-TT-02 Type 1 - 1 16 AWG 81,5 M 002-TT-02 AJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 B
18 3322-FY-01 Type 1 - 1 16 AWG 66,2 M 3322-FY-01 AJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A/B
19 002-PT-03 Type 1 - 1 16 AWG 64,8 M 002-PT-03 AJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A/B
20 3322-PY-02 Type 1 - 1 16 AWG 63,8 M 3322-PY-02 AJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A/B
21 3322-FY-03 Type 1 - 1 16 AWG 61,2 M 3322-FY-03 AJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A/B
22 002-PT-04 Type 1 - 1 16 AWG 59,8 M 002-PT-04 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A/B
23 3322-PY-04 Type 1 - 1 16 AWG 58,4 M 3322-PY-04 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A/B
24 002-PT-05 Type 1 - 1 16 AWG 54,3 M 002-PT-05 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A/B
25 002-PT-06 Type 1 - 1 16 AWG 44,3 M 002-PT-06 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PSD Metering 3322-GM-002 A/B
26 002-PT-07 Type 1 - 1 16 AWG 44,3 M 002-PT-07 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PSD Metering 3322-GM-002 A/B
27 002-PT-08 Type 1 - 1 16 AWG 44,3 M 002-PT-08 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PSD Metering 3322-GM-002 A/B
28 002-TT-03 Type 1 - 1 16 AWG 44,3 M 002-TT-03 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Metering 3322-GM-002 A/B
29 005-AI-01 Type 1 - 1 16 AWG 33,2 M 005-AI-01 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Instrument Air Compressor and Dryer Package
30 005-AI-02 Type 1 - 1 16 AWG 33,2 M 005-AI-02 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog PCS Instrument Air Compressor and Dryer Package
31 007-PT-01 Type 1 - 1 16 AWG 33,2 M 007-PT-01 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog UFD Instrument Air Receiver 3322-V-001
32 007-PT-02 Type 1 - 1 16 AWG 33,2 M 007-PT-02 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog UFD From Air Compressor Packages
33 007-PT-03 Type 1 - 1 16 AWG 33,2 M 007-PT-03 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog UFD From Air Compressor Packages
34 007-PT-04 Type 1 - 1 16 AWG 33,2 M 007-PT-04 AJB3 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Analog UFD From Air Compressor Packages
35 008-LIT-01 Type 1 - 1 16 AWG 29,2 M 008-LIT-01 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Analog UFD Daily Tank For Diesel Engine Generator
36 008-FIT-01 Type 1 - 1 16 AWG 29,2 M 008-FIT-01 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Analog UFD Daily Tank For Diesel Engine Generator
37 008-LT-01 Type 1 - 1 16 AWG 29,2 M 008-LT-01 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Analog UFD Emergency Diesel Generator
38 009-LT-01 Type 1 - 1 16 AWG 29,2 M 009-LT-01 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Analog UFD Daily Tank Diesel Fire Water Pump
39 AJB1 Type 2 - 9 16 AWG 18,7 M AJB1 CONTROL ROOM FIELD CONTROL ROOM 1 1/4" 1 1/4" Type 2 Type 2 Analog PCS Multipair Cable from AJB1 to PCS Marshalling
40 AJB2 Type 3 - 12 16 AWG 18,7 M AJB2 CONTROL ROOM FIELD CONTROL ROOM 1 1/2" 1 1/2" Type 3 Type 3 Analog PCS Multipair Cable from AJB2 to PCS Marshalling
41 AJB2 Type 4 - 13 16 AWG 18,7 M AJB2 CONTROL ROOM FIELD CONTROL ROOM 1 1/2" 1 1/2" Type 3 Type 3 Analog PCS Multipair Cable from AJB2 to PCS Marshalling

42 3322-ZSC-001 Type 5 2 - 16 AWG 117,2 M 3322-ZSC-001 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PSD Outlet From Other Station Natural Gas To Gas Filter
43 3322-ZSO-001 Type 5 2 - 16 AWG 117,2 M 3322-ZSO-001 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PSD Outlet From Other Station Natural Gas To Gas Filter
44 3322-SV-001 Type 5 2 - 16 AWG 117,2 M 3322-SV-001 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PSD Outlet From Other Station Natural Gas To Gas Filter
45 002-ZSC-01 Type 5 2 - 16 AWG 89,4 M 002-ZSC-01 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
46 002-ZSO-01 Type 5 2 - 16 AWG 89,4 M 002-ZSO-01 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
47 002-SV-01A Type 5 2 - 16 AWG 89,4 M 002-SV-01 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
48 002-SV-01B Type 5 2 - 16 AWG 89,4 M 002-SV-01 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
49 002-ZSC-02 Type 5 2 - 16 AWG 83,7 M 002-ZSC-02 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
50 002-ZSO-02 Type 5 2 - 16 AWG 83,7 M 002-ZSO-02 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
51 002-SV-02A Type 5 2 - 16 AWG 83,7 M 002-SV-02 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
52 002-SV-02B Type 5 2 - 16 AWG 83,7 M 002-SV-02 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
53 002-ZSC-03 Type 5 2 - 16 AWG 84,4 M 002-ZSC-03 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 B
54 002-ZSO-03 Type 5 2 - 16 AWG 84,4 M 002-ZSO-03 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 B
55 002-SV-03A Type 5 2 - 16 AWG 84,4 M 002-SV-03 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 B
56 002-SV-03B Type 5 2 - 16 AWG 84,4 M 002-SV-03 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 B
57 002-ZSC-04 Type 5 2 - 16 AWG 78,7 M 002-ZSC-04 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 B
58 002-ZSO-04 Type 5 2 - 16 AWG 78,7 M 002-ZSO-04 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 B
59 002-SV-04A Type 5 2 - 16 AWG 78,7 M 002-SV-04 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 B
60 002-SV-04B Type 5 2 - 16 AWG 78,7 M 002-SV-04 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 B
61 002-ZSC-05 Type 5 2 - 16 AWG 80 M 002-ZSC-05 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A/B
62 002-ZSO-05 Type 5 2 - 16 AWG 80 M 002-ZSO-05 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A/B
63 002-SV-05A Type 5 2 - 16 AWG 80 M 002-SV-05 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A/B
64 002-SV-05B Type 5 2 - 16 AWG 80 M 002-SV-05 DJB1 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A/B
65 002-ZSC-021 Type 5 2 - 16 AWG 92,8 M 002-ZSC-021 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
66 002-ZSO-021 Type 5 2 - 16 AWG 92,8 M 002-ZSO-021 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
70 002-ZSO-023 Type 5 2 - 16 AWG 80,5 M 002-ZSO-023 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A
71 002-ZSC-024 Type 5 2 - 16 AWG 78 M 002-ZSC-024 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A/B
72 002-ZSO-024 Type 5 2 - 16 AWG 78 M 002-ZSO-024 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 A/B
73 002-ZSC-025 Type 5 2 - 16 AWG 75,5 M 002-ZSC-025 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 B
74 002-ZSO-025 Type 5 2 - 16 AWG 75,5 M 002-ZSO-025 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Metering 3322-GM-002 B
75 3322-ZSC-006 Type 5 2 - 16 AWG 69,4 M 3322-ZSC-006 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PSD Metering 3322-GM-002 A/B
76 3322-ZSO-006 Type 5 2 - 16 AWG 69,4 M 3322-ZSO-006 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PSD Metering 3322-GM-002 A/B
77 3322-SV-006 Type 5 2 - 16 AWG 69,4 M 3322-SV-006 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PSD Metering 3322-GM-002 A/B
78 3322-ZSC-007 Type 5 2 - 16 AWG 64,4 M 3322-ZSC-007 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PSD Metering 3322-GM-002 A/B
79 3322-ZSO-007 Type 5 2 - 16 AWG 64,4 M 3322-ZSO-007 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PSD Metering 3322-GM-002 A/B
80 3322-SV-007 Type 5 2 - 16 AWG 64,4 M 3322-SV-007 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PSD Metering 3322-GM-002 A/B
81 002-ZSC-031 Type 5 2 - 16 AWG 45,6 M 002-ZSC-031 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS From Metering 3322-GM-002 A/B
82 002-ZSO-031 Type 5 2 - 16 AWG 45,6 M 002-ZSO-031 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS From Metering 3322-GM-002 A/B
83 002-UA-01 Type 5 2 - 16 AWG 48,6 M 002-UA-01 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Odorizer Package
84 002-FI-01 Type 5 2 - 16 AWG 48,6 M 002-FI-01 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Odorizer Package
85 002-XL-01 Type 5 2 - 16 AWG 48,6 M 002-XL-01 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Odorizer Package
86 002-LI-01 Type 5 2 - 16 AWG 48,6 M 002-LI-01 DJB2 FIELD JUNCTION BOX 1/2" 1/2" Type 1 Type 1 Digital PCS Odorizer Package
87 005-AC-LCP-1 Type 6 6 - 16 AWG 51,9 M 005-AC-LCP-1 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PCS Instrument Air Compressor and Dryer Package
88 005-AC-LCP-2 Type 6 6 - 16 AWG 51,9 M 005-AC-LCP-2 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PCS Instrument Air Compressor and Dryer Package
89 005-PSHL-001 Type 5 2 - 16 AWG 51,9 M 005-PSHL-001 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PSD/mcc Air Compressor Packages To Instrument Air Dryer Packages
90 005-XA-05 Type 5 2 - 16 AWG 51,9 M 005-XA-05 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PCS Air Compressor Packages To Instrument Air Dryer Packages
91 005-XA-06 Type 5 2 - 16 AWG 51,9 M 005-XA-06 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PCS Air Compressor Packages To Instrument Air Dryer Packages
92 009-MCC-P1A Type 7 10 - 16 AWG 68,8 M 009-MCC-P1A CONTROL ROOM ELECTRICAL ROOM CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PCS Deep Well Pump
93 009-MCC-P1B Type 7 10 - 16 AWG 43,3 M 009-MCC-P1B CONTROL ROOM ELECTRICAL ROOM CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PCS Deep Well Pump
94 009-MCC-P2 Type 7 10 - 16 AWG 70,1 M 009-MCC-P2 CONTROL ROOM ELECTRICAL ROOM CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PCS Electrical Fire Water PumpDiesel Engine Fire Water Pump
95 009-MCC-P3 Type 7 10 - 16 AWG 70,1 M 009-MCC-P3 CONTROL ROOM ELECTRICAL ROOM CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PCS Electrical Jockey Fire Water Pump
96 009-MCC-P4 Type 7 10 - 16 AWG 70,1 M 009-MCC-P4 CONTROL ROOM ELECTRICAL ROOM CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PCS Diesel Engine Fire Water Pump
97 009-LS-01 Type 5 2 - 16 AWG 49,8 M 009-LS-01 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital UFD Fire Water Tank 3322-T-003
98 009-LSHL-01 Type 5 2 - 16 AWG 14,5 M 009-LSHL-01 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital UFD Daily Water Tank
99 009-PSHL-001 Type 5 2 - 16 AWG 49,8 M 009-PSHL-001 CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Digital PSD Diesel Engine Fire Water Pump
100 DJB1 Type 9 46 - 16 AWG 18,7 M DJB1 CONTROL ROOM JUNCTION BOX CONTROL ROOM 2" 2" Type 4 Type 4 Digital PCS Multicore Cable from DJB1 to PCS Marshalling
101 DJB2 Type 8 44 - 16 AWG 18,7 M DJB2 CONTROL ROOM JUNCTION BOX CONTROL ROOM 2" 2" Type 4 Type 4 Digital PCS Multicore Cable from DJB2 to PCS Marshalling

102 3322-GC-003A Type 10 - - - AWG 114,6 M 3322-GC-003A CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 From Gas Filter To Metering 3322-GM-002 A/B
103 3322-GC-003B Type 10 - - - AWG 114,6 M 3322-GC-003B CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 From Gas Filter To Metering 3322-GM-002 A/B
104 002-FQYI-01 Type 10 - - - AWG 15 M 002-FQYI-01 CONTROL ROOM CONTROL ROOM CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Metering 3322-GM-002 A
105 002-FQYI-02 Type 10 - - - AWG 15 M 002-FQYI-02 CONTROL ROOM CONTROL ROOM CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Metering 3322-GM-002 B
106 Power Cable GC3A Type 11 2 - 14 AWG 114,6 M Power Cable GC3A CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 From Gas Filter To Metering 3322-GM-002 A/B
107 Power Cable GC3B Type 11 2 - 14 AWG 114,6 M Power Cable GC3B CONTROL ROOM FIELD CONTROL ROOM 1/2" 1/2" Type 1 Type 1 From Gas Filter To Metering 3322-GM-002 A/B
108 Power Cable FQYI1 Type 11 2 - 14 AWG 15 M Power Cable FQYI1 CONTROL ROOM CONTROL ROOM CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Metering 3322-GM-002 A
109 Power Cable FQYI2 Type 11 2 - 14 AWG 15 M Power Cable FQYI2 CONTROL ROOM CONTROL ROOM CONTROL ROOM 1/2" 1/2" Type 1 Type 1 Metering 3322-GM-002 B