Sei sulla pagina 1di 1

E3001.e technical data E2001.e/E3001.

e
Rating (kVA) 5 10 15 20 30 40 50 60 80 100 120 160 200
Nominal power (kW) 4 8 12 16 24 32 40 48 64 80 96 128 160 Features and benefits
Input
OBuilt-in
inverter transformer for DC-AC
Input voltage 380/400/415 (optional 208/480) Vac 3-phase ±10%, 50/60 Hz ±10%
galvanic separation
Input THDi 27% 6p, 12% 12p, 6% THD filter +12p
Bypass input voltage 200/208/220 or 380/400/415 (optional 480) Vac ±20% OIGBT, PWM controlled inverter for high
(adjustable according to inverter output voltage) efficiency and low output THD
Battery OSupport vented/sealed lead acid
DC voltage available DC bus voltages vary with requested output AC voltages and rating batteries and Ni-Cd batteries
(see the table below)
OStandard configurations for
110 Vdc (90÷160 Vdc range)
200÷220 Vac - cost-effective, short lead time solutions
220 Vdc (180÷300 Vdc range)
Output voltage
110 Vdc (90÷160 Vdc range) 220 Vdc (180÷300 OHigh personalization grade
380÷415 Vac
220 Vdc (180÷300 Vdc range) Vdc range)
OFront accessibility for easy maintenance
Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable
Operating battery voltage Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable O16-bitmicroprocessor control for
Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable best-in-class performance and reliability
Output ODigitalcontrol panel and mimic display,
Nominal voltage 200/208/220/380/400/415 (optional 480) Vac 3-phase for signals, alarms, meters and history
Frequency 50/60 Hz (selectable), ± 0.001 Hz free running, ±2 Hz synchronized with mains events continuous monitoring
Voltage regulation ±1% static; ±5% dynamic (80% load change), <40 ms recovery time OComprehensive set of communication
Overload capacity 125% for 10 min; 150% for 1 min; 200% for 100 ms options for total remote monitoring of
Harmonic Distortion THDv <2% linear load; <5% non-linear load equipment operation
System OInput transformer protected by MCCB
Isolation Floating battery; input/output isolation available with additional bypass transformer for AC-DC galvanic separation and SCR
Dimensions WxD (mm) Height is 2100 mm, width and depth vary with input voltage and rating rectifier for reliable operation in all
(see the table below) mains conditions.
Rating (kVA) 5 10 15 20 30 40 50 60 80 100 120 160 200

110 Vdc 800x800 1400x800 1600x800


2000 2000 2400
- - - Main options
x800 x1000 x1000
OBypass
line isolation transformer &
Input voltage 1400 2400 AC/AC voltage regulator
1200 x800* 1600 x800* 2400 2000 2000 2400
220 Vdc 800x800 1400x800 OAdditional RFI filters
x800 /1200 x800 /1600 x800 x800¨ x1000¨ x1000¨
x800¨ x800¨
OCustomized input and output voltage
Maximum weight (kg) 460 520 620 670 750 850 950 1150 1250 1400 1520 1680 1970 OActiveparallel redundant, hot-standby
Cooling Forced ventilation and load-sync configuration
Efficiency 88%
OAC earth fault monitoring and alarm
Colour RAL 7035
OFan
monitoring and alarm and
Protection degree (IEC 60529) IP20 (other options)
redundant ventilation
* 208 Vac ¨400 Vac
OTop cable entry
E2001.e and E3001.e technical data OSpace heaters and panel lighting
Environmental
OAnalogue meters and lamps on front
Operating temperature -10 °C ÷ +40 °C
Storage temperature -20 °C ÷ +70 °C
panel for immediate visualisation
Altitude <2000 m (derating according to EN 62040-3) OCustomisable status and alarm LED set
Audible noise at 1meter (dBA) <65÷75
OSpecialpainting and protection degree
Options Associated battery cabinets and distribution panels; bypass isolation transformer and AC/AC voltage stabilizer;
12 pulse bridge; THD filters; built-in battery breaker; timed battery charging; external battery breakers in up to IP54
standard or Eex-d wall-mounted box; battery thermal probe; parallel redundant, hot-standby, load-sync;
AC and DC earth fault alarm; fan monitoring and alarm; redundant ventilation; additional RFI filters; top cable entry OAmbient temperature up to +55 °C.
User Interface
Front panel LCD display, LED mimic, keyboard. Customisable status and alarms LED set
Connectivity SPDT contact relay card, RS232 serial port
Optional: RS485 ModBus-RTU serial port, ModBus to PROFIBUS DP adapter, Ethernet SNMP/WEB
adapter, remote monitoring software, up to 2 additional SPDT contact relay cards

Higher ratings on request

Potrebbero piacerti anche