Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
COLLEGE : GNDIT
Acknowledgement
The instrument of acknowledgement will remain out of tune if, I will not
thank Mr. ANKIT MISHRA AND Mr .SONU KUMAR, under whose
worth full guidance I completed my training. With all the knowledge and
skills I have acquired during this period, I hope that I will apply them in a
positive way wherever and whenever possible.
Tarun chauhan
trainee
Contents
1.About TPDDL
1. Organizational Description
2. Organizational Environment
3. Organizational Culture
3.Transformer
-parts of transformer
-protection of a transformer
4.Electric cables
-Characteristic
-types of cables
-Parts of electrical cable
-testing of electrical cable
5 -Circuit breaker
-Protection relays
-Air circuit breaker
-Vacuum circuit breaker
-Sulphur hexafloride(sf6) circuit breaker
6. Revival of cable fault
About TPDDL
ii) Ring main units: In ring main system one ring network of
distributors is fed by more than one feeder. In this case if one feeder is
under fault or maintenance, the ring distributor is still energized by
other feeders connected to it. In this way the supply to the consumers
is not affected even when any feeder becomes out of service. In
addition to that the ring main system is also provided with different
section isolates at different suitable points. If any fault occurs on any
section, of the ring, this section can easily be isolated by opening the
associated section isolators on both sides of the faulty zone.
Fig . Schneider 4 way RMU
iv) Circuit breakers: Similar to the high voltage side where RMU is
used for tripping during fault conditions,air circuit breakers are used
in the low voltage side.
Since the level of voltage is not very high, even the dielectric strength
of air is enough to diminish the arc and hence air is insulating medium
in these breakers.If the fault ocuurs in the distributers, these breakers
trips and supply is disconnected of that distributer.
iii) Service mains: Service mains are the conductors, which connect
the
consumer’s terminals to the distributor.These are tapped from
distributers to supply power to the consumer.
The design of distribution networks starts with a map of the area, the
positions of the roads, streets and buildings and position of
distribution stations. They can be overhead or underground. The
electrical power system equipment’s design is governed by the
electrical and mechanical needs. The electrical design of distribution
facilities is based on the loads that they are to carry safely and the
permissible voltage variation. The configuration has a great effect on
the optimization of the load flow in the system.
TRANSFORMER
A transformer is an electrical device that transfers electrical
energy between two or more circuits through electromagnetic
induction. Electromagnetic induction produces an electromotive
force within a conductor which is exposed to time varying
magnetic fields. Transformers are used to increase or decrease
the alternating voltages in electric power applications.
A varying current in the transformer's primary winding creates a
varying magnetic flux in the transformer core and a varying field
impinging on the transformer's secondary winding. This
varying magnetic field at the secondary winding induces a
varying electromotive force (EMF) or voltage in the secondary
winding due to electromagnetic induction. Making use
of Faraday's Law(discovered in 1831) in conjunction with
high magnetic permeability core properties, transformers can
be designed to efficiently change AC voltages from one voltage
level to another within power networks.
Since the invention of the first constant potential transformer in
1885, transformers have become essential for the
transmission, distribution, and utilization of alternating current
electrical energy.[3] A wide range of transformer designs is
encountered in electronic and electric power applications.
Transformers range in size from RF transformers less than a
cubic centimeter in volume to units interconnecting the power
grid weighing hundreds of tons.
Parts of a transformer
1. Laminated core
2. Windings
3. Insulating Materials
4. Transformer oil
5. Tap changer
6. Conservator
7. Breather
8. Cooling tubes
9. Buchholz Relay
10. Explosion vent
Of the above mentioned, first four can be seen in almost all the
transformers whereas the rest can be found only in
transformers more than 50KVA.
CORE
Core is used to support the windings in the transformer. It also
provides a low reluctance path to the flow of magnetic flux. It is
made up of laminated soft iron core in order to reduce eddy
current loss and Hysteresis loss. The composition of a
transformer core depends on such factors as voltage, current,
and frequency. Diameter of the transformer core is directly
proportional to copper loss and is inversely proportion to the
iron loss. If diameter of the core is decreased, the weight of the
steel in the core is reduced which leads to less core loss of
transformer and the copper loss increase. The vice versa
happen when the diameter is increased.
Windings
There are two windings wound over the transformer core which
are insulated from each other. Windings consists of several
turns of copper coils bundled together an each bundles are
connected in series to form a winding.
Windings can be classified in two different ways.
a) Based on the input and output supply
b) Based on the voltage range
Based on the supply
Based on the supply the windings are classified into
a) Primary windings
It is the winding to which the input voltage is applied.
b) And secondary windings.
It is the winding to which the output voltage is applied.
Based on the voltage range
Based on the voltage the windings can be classified as follows
a) High voltage winding
High voltage windings are made up of copper coil. The number
of turns in it is the multiple of the number of turns in the low
voltage windings. It has copper coils thinner than that of the low
voltage windings.
b) Low voltage windings
Low voltage winding has lesser number of turns than that of the
high voltage windings. It is made up of the thick copper
conductors. This is because the current in the low voltage
windings is higher than that of high voltage windings.
Transformer can be supplied from either LV or HV windings
based on the requirement.
Insulating materials
Insulating papers and card boards are used in transformers of
to isolate primary and secondary winding from each other and
from transformer core. Transformer oil is also a insulating
material.
Windings are made of copper due to the following reasons.
High conductivity
1. Minimizes amount of copper needed for winding (volume &
weight of winding)
2. Minimizes losses
High ductility
1. Easy to bend conductors into tight winding around core thus
minimizes amount of copper and volume of winding
Transformer oil
Transformer oil performs two important functions of insulation
as well as cooling for the core and coil assembly. Core and
windings of the transformer must be completely immersed in
the oil. Normally hydrocarbon mineral oils are used as
transformer oil. Oil contamination is a serious problem because
it robs its dielectric properties and renders it useless as an
insulating medium.
Conservator
Tap changer
The output voltage may vary according to the input voltage and
the load. During loaded conditions the voltage on the output
terminal fall and during off load conditions the output voltage
increases. In order to balance the voltage variations tap
changers are used. Tap changers can be either on load tap
changer or off load tap changer. In on load tap changers the
tapping can be changed without isolating the transformer from
the supply and in off load tap changers it is done after
disconnecting the transformer. Automatic tap changers are also
available.
Cooling tubes
There are various parts of a cable to be taken care of during construction. The
power cable mainly consists of
1. Conductor
2. Insulation
3. LAY for Multi core cables only
4. Bedding
5. Beading/Armouring (if required)
6. Outer Sheath
Conductor
Conductors are the only power carrying path in a power cable.
Conductors are of different materials. Mainly in cable industry
we use copper (ATC, ABC) and aluminium conductors for power
cables. There are different types of conductor as Class 1: solid,
Class 2 stranded, Class 5 flexible, Class 6 Extra flexible (Mostly
used for cords and welding) etc. Conductor sizes are identified
with conductor resistance.
Insulation
The insulation provided on each conductor of a cable by mainly
PVC (Poly Vinyl Chloride), XLPE (Cross linked Poly ethylene),
RUBBER (Various Types of Rubber). Insulating material is
based on operating temperature.
Cores are identified by colour coding by using different colours
on insulation or by number printing on cores
Armouring
There are mainly G.I. WIRE ARMOURING, G.I. STEEL STRIP
armouring. It is done by placing G.I. WIREs, GI or STEEL
STRIPs one by one on inner sheath. Armouring is a process
which is done mainly for providing earthing shield to the
current carrying conductors as well as it is also used for
earthing purpose of the cable for safety. When there is any
insulation failure in the conductor, the fault current gets
enough paths to flow through the armour if it is properly
earthed. Providing extra mechanical protection and strength to
cable an important added advantage of armouring. In MINING
CABLES it is done for conductance
Beading
ANNEALED TINNED COPPER WIRE, NYLON BRAID, COTTON
BRAID are mainly used for this purpose. Braiding is the process
which gives high mechanical protection to cable and also used
for earthing purpose. Significance of braiding is it is more
flexible in comparison to armouring.
Outer Sheath
This is outermost cover of the cable normally made of PVC
(Poly Vinyl Cloride), RUBBER (Various Types of Rubber) and
often the same material as the bedding. It is provided over the
armour for overall mechanical, weather, chemical and electrical
protection. Outer sheath is protection offered to cable not
much electrically but more mechanically.
Mainly above 6 sq mm cables are called power cables but it
depends upon the use of cable. For PVC power cables we use
IS:1554 and for XLPE power cables we use IS:7098 and for
Rubber based power cables we use IS:9968 and other relevant
specifications. Power cables are defined by voltage grade and
nominal cross sectional area.
Phasing Test:
The correct phasing of all LV circuits shall be checked at all
positions where the LV cables are terminated into fuse bases
and where any LV cable is run from point to point.
This test shall be performed with an instrument designed for
the purpose. Mains frequency voltage of 240 Volts is not
acceptable for this test.
The neutral conductor shall be connected to the earth stake
for this test.
resistance values of the test leads.
Circuit breaker
1. DIFFERENTIAL RELAY: -
DIFFERENTIAL RELAY
Vacuum circuit breakers (VCB)
Vacuum circuit breakers are used mostly for low and medium
voltages. Vacuum interrupters are developed for up to 36 kV
and can be connected in series for higher voltages. The
interrupting chambers are made of porcelain and sealed. They
cannot be open for maintenance, but life is expected to be
about 20 years, provided that the vacuum is maintained.
Because of the high dielectric strength of vacuum, the
interrupters are small. The gap between the contacts is about 1
cm for 15 kV interrupters, 2 mm for 3 kV interrupters.
Fig. Vacuum interrupter
EARTHING OF A SYSTEM
Why ground?
Poor grounding not only contributes to unnecessary downtime, but a
lack of good grounding is also dangerous and increases the risk of
equipment failure. Without an effective grounding system, we could
be exposed to the risk of electric shock, not to mention
instrumentation errors, harmonic distortion issues, power factor
problems and a host of possible intermittent dilemmas. If fault
currents have no path to the ground through a properly designed and
maintained grounding system, they will find unintended paths that
could include people.
Grounding electrodes are used to ground the system. Ground rods are
generally made of highly conductive/low resistance material such as
steel or copiice of a ground system:
1. Diameter of the ground electrode.
Increasing the diameter of the ground electrode has very little
effect in lowering the resistance. For example, you could double the
diameter of a ground electrode and your resistance would only
decrease by 10 %.
2. Number of ground electrodes.
Another way to lower ground resistance is to use multiple
ground electrodes. In this design, more than one electrode is driven
into the ground and connected in parallel to lower the resistance. For
additional electrodes to be effective,
the spacing of additional rods need to be at least equal to the depth of
the driven rod. Without proper spacing of the ground electrodes, their
spheres of influence will intersect and the resistance will not be
lowered.
3. Ground system design.
Simple grounding systems consist of a singleground electrode driven
into the ground. The use of a single ground electrode is the most
common form of grounding and can be found outside your home or
place of business. Complex
grounding systems consist of multiple ground rods, connected, mesh
or grid networks, ground plates, and ground loops. These systems are
typically installed at power generating substations, central offices, and
cell tower sites.
REVIVAL OF FAULTY CABLES
1.CABLE TESTING
To locate a fault in the cable ,the cable must first be
tested for faults .Cable testing is therefore usually
performed first in cable fault location .During the
cable test ,flash –overs are generated at the weak
points in the cable ,which can then be localised.
2.PRE-LOCATION
Pre location is used to determine the fault
distance.There is mainly a method for this.
. Transient method
In the transient method ,a breakdown is triggered
at the cable fault.This effects a low resistance short
circuit for a few milliseconds.This in turn produces two
travelling waves defusing in opposite directions .These
waves are reflected at the cable ends so that they then
travel toward each other again in the direction of the
cable fault . The waves are unable to pass because of
the arc produced by the short circuit, so they are
therefore reflected back again as with the pulse
reflection method,which due to the burning short
circuit result in a reversal of polarity.There are various
ways to decouple and analyse these transients.
3.ROUTE TRACING AND PIN POINTING
Route tracing is used to determine where the faulty
cable lies and pinpointing is the process of determining
the exact position of the cable fault.
4.FAULT CONVERSION
After the cable fault is identified and located,it is then
possible to burn it inusing burner devices, in other
words to convert it from a low-resistive to a high-
impedance fault.