Boiler start up

description Range / action Remarks


1. Vacom Feed steam valve , Manual Auto / open Visual check (valve should be
valve open at boiler start up)
2. Boiler steam valve open
3. condensate tank level Tank level 30%~50% If the level low the pump will not
run./burner will not run
4. Diesel tank level Tank level 30%~90% If the level low burner will not
run
5. Boiler feed pump suction & Open
discharge valves
6. Burner suction valve. Open
7. Water box controller , air vent Open / close For 1min , until you observe
(two valves) water coming from drain header
located under boiler skid.

8. feed pump Switch on


9. burner Switch on Burner will start work.

Boiler monitoring :
description Range / action Remarks
1. boiler blow down valve Open / close Every 8hours open blow down
valve for 5sec , be careful
- blowdown water is
pressurize and hot.
- Slowly open/close to
avoid and shock for the
boiler
2. Boiler pressure 20~60 psig any higher pressure , shutdown
the boiler.

Boiler shutdown:
Check list :

description Range / action Remarks


1. feed pump Switch off
2. burner Switch off

3. burner suction valve close