Sei sulla pagina 1di 14

<<Contents>> <<Index>>

General GCCU MarkII


Gas Chromatograph Computing Unit
Specifications (For GC1000 MarkII)

GS 11B03S02-02E

n General
The GC1000 MarkII process gas chromatograph unit features PC communication, analog hold output, digital I/O,
and communication with a supervisory computer. For analog hold output from the GC1000 MarkII, many signal lines
should be installed between the field and instrument room.
Since the GCCU MarkII can be connected to the GC1000 MarkII via communication and the GCCU MarkII can
output various signals, the number of signal lines to be installed can be reduced.
The GCCU MarkII (Gas Chromatograph Computing Unit) offers such features as analog hold output, analog serial
output, trend output, digital output, digital input, and communication with a supervisory computer.
All parameter setting is executed in the GC1000 MarkII and no setting is required at the GCCU MarkII.

n Schematic Wiring Diagram


Field Instrument room

Communication converter
with explosion-proof
Dedicated maintenance feature *3
communication *1 RS-232-C communication *4 Various outputs *7
K9635JA GCCU MarkII
(Gas
Chromatograph
Power-off signal *2 Computing Unit)
(Analyzer internal
pressure signal) *6
*6

RS-232-C communication *5

GC1000 markII PC *8

F01.ai

*1: 0.5 mm2 or larger 4-pin shielded cable (Phonix terminal type), 1 km or shorter
(or 2-pin shielded cable + 2-or-more-pin cable without shield)
*2: Two lines
*3: An accessory of GC1000 MarkII. The PIN is K9635JB when area class is FM-Y or CSA-Y.
*4: 3-m dedicated cable provided
*5: D-SUB9P (Female) to D-SUB9P (Female) cross cable (commercial item)
*6: JIS Class D independent grounding (grounding resistance of 100Ω or less) or equivalent
*7: Dedicated cable provided
*8: GCMT software (option) can be operated on PC

Yokogawa Electric Corporation GS 11B03S02-02E


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Sep. 2007
Tel.: 81-422-52-5617 Fax.: 81-422-52-6792 2nd Edition Apr.28,2008
<<Contents>> <<Index>> 
n Standard Specifications Analog hold:
Ambient temperature: Analog output : Up to 24 outputs
0 to 50°C 4 to 20 mA DC, load resistance 600Ω or
Installation: lower or 1 to 5 VDC, permissible load
Panel installation resistance 5 kΩ or higher
Power supply: Contact output (stream identification):
100 to 240 VAC, 50/60 Hz 5 outputs (rated load voltage, current: 24
Range of Power fluctuation: V DC, 0.1 A)
85 to 250 VAC, 50/60 Hz ± 3 Hz Contact output (read signal):
Power consumption: 1 output (rated load voltage, current: 24
120 VA V DC, 0.1 A)
Mass: Approx. 10 kg Digital input:
Number of output components: Contact input: 16 inputs (contact rating: 5 V DC or
Max. 24 components/stream higher, 20 mA or higher)
Number of output streams: CAL command (CAL request STD1, 2): 2 inputs
Max. 24 Stream change command (stream change request:
Up to 15 streams): 1 input
● External I/O Range change command (range change request:
Up to 15 components): 1 input
Alarm output: Stream No. code (4 bits Up to 15 streams): 4 inputs
System alarm (level 1, 2; fixed alarms only): Component No. code (4 bits Up to 15 components):
2 contact outputs (Rated load voltage, 4 inputs
current: 24 V DC, 0.1 A) Component list code (4 bits Up to 15 lists): 4 inputs
Component alarm: 1 contact output (Rated load Digital output:
voltage, current: 24 V DC, 0.1 A) Contact output:
NO or NC (open upon power-off for NO) 15 outputs (rated load voltage, current:
Trend output: 24 V DC, 0.1 A)
Analog output : Up to 24 outputs Stream change answerback: 1 output
4 to 20 mA DC, load resistance 600Ω or Range change answerback: 1 output
lower, or 1 to 5 V DC, permissible load CAL change answerback: 1 output
resistance 5 kΩ or higher Analysis completion signal: 1 output
Analog serial: Data byte identification: 2 outputs (2 bits)
Analog output : 1 output Data transmission: 1 output
4 to 20 mA DC, load resistance 600Ω or Component identification, stream identification,
lower, or 1 to 5 V DC, permissible load range identification, data lower byte,
resistance 5 kΩ or higher data upper byte: 8 outputs (8 bits)
Contact output (stream identification): Computer ON/OFF:
5 outputs (rated load voltage, current: 24 Contact output:
V DC, 0.1 A) 1 output (rated load voltage, current: 30
Contact output (component identification): V DC, 50 mA)
5 outputs (rated load voltage, current: 24
V DC, 0.1 A)
Contact output (range identification):
5 outputs (rated load voltage, current: 24
V DC, 0.1 A)
Contact output (interrupt signal):
1 output (rated load voltage, current: 24
V DC, 0.1 A)

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
<<Contents>> <<Index>> 
● External I/O Signal Timing
(1) Trend output
Analog serial output, Analog hold output
Completion N-th stream Completion (N+1)-th stream
of calibration of calibration
7.5 x M (s)
5 to 10s 7.5s
Trends 0 to 24 M-th
First Second Third Fourth component First
component component component compt (including component
Analog output: 1 output operation)
*
(Serial Component identification (5 bits)
output): Range identification *
1 output Stream identification (5 bits) * 4s 2s

Interrupt signal: 1 output

Analog output: 24 outputs


(Hold
output): Read signal: 1 output *
24 outputs
Stream identification (5 bits) *

*: Final analysis value in previous output


F02.ai

(2) Digital I/O (for a supervisory computer)


(a) Output timing

First component Second component


3 to 4s 3 to 4s 3 to 4s
Component identification
Control byte *

+ Stream identification
Data lower byte
Range signal + Data upper byte 1 to 2s

Data transmission
(interrupt signal) 1 to 2s

Data bytes
Component Data lower Range signal
identification +
+ byte
Data upper byte
Stream
identification
*: For the answerback signal, see “Digital input.” F03.ai

Note: The output timing of the analysis completion signal is the end of sequence.
Analysis completion signal
2s

Sequence end F03-1.ai

(b) Input timing and answerback output timing


Command

1s or longer

Calibration, 1s or longer *2
stream change, Command
or range change
2s

Answerback *1 F04.ai
*1: Answerback is output for each command when the command is accepted, regardless of command execution.
*2: At least a 1-second interval is required between requests.

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Feb.21,2011-02
<<Contents>> <<Index>> 
(3) Correspondence of alarm between GCCU MarkII and GC1000 MarkII
The GC1000 MarkII alarms are output as System alarm when Digital output is selected.
(a) System alarm (Level 1)
The following GC1000 MarkII alarms are output as Level 1 alarm from GCCU MarkII.

No. MESSAGE Alarm Overview No. MESSAGE Alarm Overview


1 SYS ERR System error 30 TMP HIGH ERR Temp. protection unit activated
2 DATA CS ERR Data checksum error 36 ELEC PRESS DOWN Electric room pressure drop
3 DRAM ERR DRAM error C-OVEN PRESS Programmed-temp. oven inner
37
4 EXCP ERR Exceptional interruption error DOWN pressure drop
5 BUS ERR Bus error I-OVEN PRESS Isothermal oven inner pressure
38
DOWN drop
6 CARD ID ERR Card ID error
39 PURGING Purging is in progress.
7 WDOG TIMER ERR Watchdog timer error
Detector 1 card A/D calibration
8 FPGA ERR FPGA error 41 DET1 A/D ERR
error
A/D calibration error in various Detector 2 card A/D calibration
9 A/D ERR
cards 42 DET2 A/D ERR
error
11 START BUFF ERR Start-to store-chromatogram 43 DET1 FLAME OUT Detector 1 flame extinguished
12 BUFF FULL ERR Chromatogram storage area full 44 DET2 FLAME OUT Detector 2 flame extinguished
13 WRITE DATA ERR EEPROM write error DET1 CURRENT Detector 1 (TCD) current flowing
Isothermal oven or programmed- 45
ERR exceeds the rated value.
21 TMP CTL ERR temp. oven cannot control DET2 CURRENT Detector 2 (TCD) current flowing
temperature. 46
ERR exceeds the rated value.
Programmed-temp. oven temp. 47 CAR1 PRESS DOWN CAR 1 pressure drop
22 C-OVEN COM ERR
controller communication error
48 CAR2 PRESS DOWN CAR 2 pressure drop
Programmed-temp. oven temp.
23 C-OVEN COM OVER 51 EPC COM ERR EPC communications error
error
24 I-OVEN COM OVER Isothermal oven temp. error 52 CAR1 PRES OVER Carrier 1 pressure too high
25 LSV1 TEMP OVER LSV1 high-temp. error 53 CAR2 PRES OVER Carrier 2 pressure too high
26 LSV2 TEMP OVER LSV2 high-temp. error 54 HYD1 PRES OVER Hydrogen 1 pressure too high
Detector 1 (FID, FPD) high-temp. 55 HYD2 PRES OVER Hydrogen 2 pressure too high
27 DET1 TMP OVER
error 56 AIR1 PRES OVER Air 1 pressure too high
28 DET2 TMP OVER Detector 2 (FID) high-temp. error 57 AIR2 PRES OVER Air 2 pressure too high
29 TMP SENSOR ERR Temp. sensor disconnected

Also a level 1 alarm is output when GC1000 MarkII is powered down. Because GCCU MarkII recognizes that GC1000
MarkII has no power if it does not get any data from GC1000 MarkII within 1 min, so this alarm occurs when the com-
munication is cut due to wiring problem.
Note that no alarm is output when the contact is used as NC.

(b) System alarm (Level 2)


The following GC1000 MarkII alarms are output as Level 2 alarm from GCCU MarkII.
No. MESSAGE Alarm Overview No. MESSAGE Alarm Overview
151 C-OVEN TMP VAR Programmed-temp. oven 168 DEV OUT Invalid coefficient of variation
ERR temperature deviation error 169 TAIL OUT Invalid tailing coefficient
152 I-OVEN TMP VAR Isothermal oven temperature
Pressure deviation error in car-
ERR deviation error 171 CAR1 PR VAR ERR
rier gas 1
153 LSV1 TMP VAR ERR LSV1 temperature deviation
172 CAR2 PR VAR ERR Pressure deviation error in
error
carrier gas 2
154 LSV1 TMP VAR ERR LSV2 temperature deviation
173 FUEL1 PR VAR ERR Pressure deviation error in
error
combustion hydrogen 1
155 DET1 TMP VAR ERR Detector 1 (FID, FPD)
174 FUEL2 PR VAR ERR Pressure deviation error in
temperature deviation error
combustion hydrogen 2
156 DET2 TMP VAR ERR Detector 2 (FID) temperature
175 AIR1 PR VAR ERR Pressure deviation error in
deviation error
auxiliary air 1
158 OVERRIDE Under override
176 AIR2 PR VAR ERR Pressure deviation error in
161 C-OVER Calibration out of range auxiliary air 2
162 C-REPT Calibration repetition failure 181 ANABUS SEND ERR ANABUS send error
163 C-COEF Invalid calibration coefficient 182 ANABUS RCV ERR ANABUS receive error
166 CONC OUT Concentration abnormal 183 DUAL ETHE ERR Wrong def. of dual Ethernet
167 RT OUT Retention time out

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
<<Contents>> <<Index>> 
(c) Component alarm
The concentration alarm which is set in GC1000 MarkII
as concentration alarm is output as “ Component
alarm” from GCCU MarkII.

No. MESSAGE Alarm Overview


166 CONC OUT Concentration anbormal

● Analog Output Code Table for Supervi-


sory Computer
(1) Analog Serial Output
(a) Component identification: 5 bits (b) Stream identification: 5 bits

Pin symbol Pin symbol


Component Stream No. 6 2
No. 12 7 5 4 3
11 10 8 (MSB) (LSB)
(MSB) (LSB)
1 0 0 0 0 1 1 0 0 0 0 1
2 0 0 0 1 0 2 0 0 0 1 0
3 0 0 0 1 1 3 0 0 0 1 1
4 0 0 1 0 0 4 0 0 1 0 0
5 0 0 1 0 1 5 0 0 1 0 1
6 0 0 1 1 0
6 0 0 1 1 0
7 0 0 1 1 1
7 0 0 1 1 1
8 0 1 0 0 0
8 0 1 0 0 0
9 0 1 0 0 1
10 0 1 0 1 0 9 0 1 0 0 1
11 0 1 0 1 1 10 0 1 0 1 0
12 0 1 1 0 0 11 0 1 0 1 1
13 0 1 1 0 1 12 0 1 1 0 0
14 0 1 1 1 0 13 0 1 1 0 1
15 0 1 1 1 1 14 0 1 1 1 0
16 1 0 0 0 0 15 0 1 1 1 1
17 1 0 0 0 1
16 1 0 0 0 0
18 1 0 0 1 0
17 1 0 0 0 1
19 1 0 0 1 1
18 1 0 0 1 0
20 1 0 1 0 0
21 1 0 1 0 1 19 1 0 0 1 1
22 1 0 1 1 0 20 1 0 1 0 0
23 1 0 1 1 1 21 1 0 1 0 1
24 1 1 0 0 0 22 1 0 1 1 0
23 1 0 1 1 1
24 1 1 0 0 0

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
<<Contents>> <<Index>> 
(c) Range identification: 5 bits (2) Analog Hold Output
Stream identification: 5 bits
Pin symbol
Component
No. 17 13 Pin symbol
16 15 14
(MSB) (LSB) Stream No. 15 11
14 13 12
1 0 0 0 0 1 (MSB) (LSB)
2 0 0 0 1 0 1 0 0 0 0 1
3 0 0 0 1 1 2 0 0 0 1 0
4 0 0 1 0 0 3 0 0 0 1 1
5 0 0 1 0 1 4 0 0 1 0 0
6 0 0 1 1 0 5 0 0 1 0 1
7 0 0 1 1 1 6 0 0 1 1 0
8 0 1 0 0 0 7 0 0 1 1 1
9 0 1 0 0 1 8 0 1 0 0 0
10 0 1 0 1 0 9 0 1 0 0 1
11 0 1 0 1 1 10 0 1 0 1 0
12 0 1 1 0 0 11 0 1 0 1 1
13 0 1 1 0 1 12 0 1 1 0 0
14 0 1 1 1 0 13 0 1 1 0 1
15 0 1 1 1 1 14 0 1 1 1 0
16 1 0 0 0 0 15 0 1 1 1 1
17 1 0 0 0 1 16 1 0 0 0 0
18 1 0 0 1 0 17 1 0 0 0 1
19 1 0 0 1 1 18 1 0 0 1 0
20 1 0 1 0 0 19 1 0 0 1 1
21 1 0 1 0 1 20 1 0 1 0 0
22 1 0 1 1 0 21 1 0 1 0 1
23 1 0 1 1 1 22 1 0 1 1 0
24 1 1 0 0 0 23 1 0 1 1 1
24 1 1 0 0 0

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
<<Contents>> <<Index>> 
● Digital I/O Code Table for Supervisory (d) Stream identification: 4 bits
Computer
Pin symbol
(1) Digital Output Stream No. 8 5
7 6
(a) Control byte (MSB) (LSB)
Data byte identification code: 2 bits 1 0 0 0 1
2 0 0 1 0
Pin symbol
3 0 0 1 1
12 11
(MSB) (LSB) 4 0 1 0 0
Component identification + Stream 5 0 1 0 1
0 0
identification 6 0 1 1 0
Data lower byte 0 1 7 0 1 1 1
Range signal + Data upper byte 1 0 8 1 0 0 0
9 1 0 0 1
(b) Data byte
Data output 10 1 0 1 0
11 1 0 1 1
Upper 4 bits Lower 8 bits 12 1 1 0 0
MSB LSB MSB LSB 13 1 1 0 1
100 % 1 0 0 0 0 0 0 0 0 0 0 0 14 1 1 1 0
0% 0 0 0 0 0 0 0 0 0 0 0 0 15 1 1 1 1

(c) Component identification: 4 bits (e) Range identification: 4 bits


Pin symbol Pin symbol
Component
No. 4 1 Range No. 4 1
3 2 3 2
(MSB) (LSB) (MSB) (LSB)
1 0 0 0 1 1 0 0 0 1
2 0 0 1 0 2 0 0 1 0
3 0 0 1 1 3 0 0 1 1
4 0 1 0 0 4 0 1 0 0
5 0 1 0 1 5 0 1 0 1
6 0 1 1 0 6 0 1 1 0
7 0 1 1 1 7 0 1 1 1
8 1 0 0 0 8 1 0 0 0
9 1 0 0 1 9 1 0 0 1
10 1 0 1 0 10 1 0 1 0
11 1 0 1 1 11 1 0 1 1
12 1 1 0 0 12 1 1 0 0
13 1 1 0 1 13 1 1 0 1
14 1 1 1 0 14 1 1 1 0
15 1 1 1 1 15 1 1 1 1

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
<<Contents>> <<Index>> 
(2) Digital Input (c) Range No. code: 4 bits
(a) Stream No. code: 4 bits (specified component list No. code)

Pin symbol Pin symbol


Range
Stream No. 8 5 17 14
7 6 signal No. 16 15
(MSB) (LSB) (MSB) (LSB)
1 0 0 0 1 1 0 0 0 1
2 0 0 1 0 2 0 0 1 0
3 0 0 1 1 3 0 0 1 1
4 0 1 0 0 4 0 1 0 0
5 0 1 0 1 5 0 1 0 1
6 0 1 1 0 6 0 1 1 0
7 0 1 1 1 7 0 1 1 1
8 1 0 0 0 8 1 0 0 0
9 1 0 0 1 9 1 0 0 1
10 1 0 1 0 10 1 0 1 0
11 1 0 1 1 11 1 0 1 1
12 1 1 0 0 12 1 1 0 0
13 1 1 0 1 13 1 1 0 1
14 1 1 1 0 14 1 1 1 0
15 1 1 1 1 15 1 1 1 1

(b) Component No. code: 4 bits Note: 1: Short, 0: Open

Pin symbol ● I/O Circuit


Component
No. 13
12 11
10 (1) Contact Output Circuit
(MSB) (LSB) Alarm, Analog serial, Analog hold, Digital, Computer
1 0 0 0 1 ON/OFF
2 0 0 1 0
Inner 5 V
3 0 0 1 1
4 0 1 0 0
L
5 0 1 0 1
6 0 1 1 0
7 0 1 1 1
8 1 0 0 0
9 1 0 0 1
10 1 0 1 0
11 1 0 1 1 COM
12 1 1 0 0
Rated load Voltage, current: 24 V DC, 0.1 A
13 1 1 0 1
14 1 1 1 0 (2) Contact Input Circuit
Digital input
15 1 1 1 1
+5V

COM
Clock generator

Contact input: OFF signal 100 kΩ or higher


ON signal 200 Ω or lower
Contact Ratings: 5 V DC, 20 mA or higher
No-voltage contact

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
<<Contents>> <<Index>> 
n Model and Suffix Codes
Option
Model Suffix code Description
code
GCCU ••••••••••••••••••••••••••••••••••••••••••••• •••••••••••••••• Gas Chromatograph Computing Unit
Installation -P •••••••••••••••• Panel installation
Trend output * 0 •••••••••••••••• None
1 •••••••••••••••• 1 to 4 outputs (4 to 20 mA DC)
2 •••••••••••••••• 5 to 8 outputs (4 to 20 mA DC)
3 •••••••••••••••• 9 to 12 outputs (4 to 20 mA DC)
4 •••••••••••••••• 13 to 16 outputs (4 to 20 mA DC)
5 •••••••••••••••• 17 to 20 outputs (4 to 20 mA DC)
6 •••••••••••••••• 21 to 24 outputs (4 to 20 mA DC)
A •••••••••••••••• 1 to 4 outputs (1 to 5 V DC)
B •••••••••••••••• 5 to 8 outputs (1 to 5 V DC)
C •••••••••••••••• 9 to 12 outputs (1 to 5 V DC)
D •••••••••••••••• 13 to 16 outputs (1 to 5 V DC)
E •••••••••••••••• 17 to 20 outputs (1 to 5 V DC)
F •••••••••••••••• 21 to 24 outputs (1 to 5 V DC)
Anlog hold output * 0 •••••••••••••••• None
1 •••••••••••••••• 1 to 4 outputs (4 to 20 mA DC)
2 •••••••••••••••• 5 to 8 outputs (4 to 20 mA DC)
3 •••••••••••••••• 9 to 12 outputs (4 to 20 mA DC)
4 •••••••••••••••• 13 to 16 outputs (4 to 20 mA DC)
5 •••••••••••••••• 17 to 20 outputs (4 to 20 mA DC)
6 •••••••••••••••• 21 to 24 outputs (4 to 20 mA DC)
A •••••••••••••••• 1 to 4 outputs (1 to 5 V DC)
B •••••••••••••••• 5 to 8 outputs (1 to 5 V DC)
C •••••••••••••••• 9 to 12 outputs (1 to 5 V DC)
D •••••••••••••••• 13 to 16 outputs (1 to 5 V DC)
E •••••••••••••••• 17 to 20 outputs (1 to 5 V DC)
F •••••••••••••••• 21 to 24 outputs (1 to 5 V DC)
Analog serial output * 0 •••••••••••••••• None
1 •••••••••••••••• Provided (4 to 20 mA DC)
A •••••••••••••••• Provided (1 to 5 V DC)
Communication output 0 •••••••••••••••• None
Digital output * 0 •••••••••••••••• Alarm only
1 •••••••••••••••• Contact input answerback and analysis completion signal
2 •••••••••••••••• Bit parallel output
Digital input 0 •••••••••••••••• None
1 •••••••••••••••• Provided (External contact)
2 •••••••••••••••• Provided (Internal SW)
Power supply -N •••••••••••••••• 100 to 120 V AC (for GC1000E/T/S/D)
-2 •••••••••••••••• 200 to 240 V AC (for GC1000E/T/S/D)
-C •••••••••••••••• 100 to 120 V AC (for GC1000C/W)
-4 •••••••••••••••• 200 to 240 V AC (for GC1000C/W)
Language and attached software N •••••••••••••••• Japanese language, attached software not provided
P •••••••••••••••• Japanese language, attached software provided
E •••••••••••••••• English language, attached software not provided
F •••••••••••••••• English language, attached software provided
Option /MCMP For 2-streams and 150-components

*: If “1 to 6” or “A to F” is selected for trend output, “0” is selected for analog hold output.
If “1 to 6” or “A to F” is selected for analog hold output, “0” is selected for trend output.
If “1” or “A” is selected for analog serial output, “0” or “1” is selected for digital output.
If “2” is selected for digital output, “0” is selected for analog serial output.

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E May 10,2010-01
<<Contents>> <<Index>> 10
n Pin Connections
K9635JA
GC1000 MarkII ( or K9635JB) GCCU MarkII
Note
9 :SD+ 1:SDA CN1 CN11 CN1
10:SD- 2:SDB CN2
7 :RD+ 3:RDA CN3
8 :RD- 4:RDB CN4
Shield CN5
13:12V+ 5:12V+ CN2 CN6
14:12V- 6:12V- CN7
CN8
CN9
Power L Power L Power L
supply N supply N supply N
G G G

JIS Class D JIS Class D JIS Class D


independent grounding independent grounding independent grounding
(grounding resistance (grounding resistance (grounding resistance of 100Ω or less) or equivalent
of 100Ω or less) of 100Ω or less)
or equivalent or equivalent Connected to the PC. F05.ai

CN1 to CN3 are D-sub 25-pin female connectors and CN4 to CN11 are D-sub 9-pin male connectors. Dedicated
cables are attached for CN1 to CN9 and CN11. Dedicated cables for CN1 to CN9 are connected by using the crimped
terminal for M4. The dedicated cable for CN11 is a D-sub 9-pin cross cable. The crimped terminal for M4 are used for
the wiring of the power supply.
The connections of CN1 to CN11 pins are shown below.
Note: The shield is used for SD in case of 2 core shield cable. 6 core shield cable also can be used.

● CN1
1:System alarm (level 1)
2:System alarm (level 2)
3:Component alarm
4:Stream change answerback
5:Range change answerback
Provided when digital output 1 is selected
6:CAL command answerback
7:Analysis completion signal
8:
9:Digital common (for No.1 to 8)
10:Read signal
11: LSB
12:
Provided when analog hold output is selected.
13: Stream identification signal
CN1
14:
15: MSB
16:
17:
18:Digital common (for No.10 to 17)
19:Computer OFF
20:Computer ON
21:Computer common
22:
23:
24:
25:
26:Cable shield

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
<<Contents>> <<Index>> 11
● CN2
There are two types of connections depending on the specifications:
(1) Pattern 1
Provided when digital output 2 is selected.
11:LSB
Data byte identification code
12:MSB
10:Data transmission
9:Digital common (for No.1 to 8)
1: LSB<MSB> LSB<MSB> LSB<MSB>
2: Component
identification Range identification signal
3: signal
4: MSB<LSB> MSB<LSB>
Data lower byte
5: LSB<MSB> LSB<MSB>
6: Stream
identification Data upper byte
CN2 7: signal
8: MSB<LSB> MSB<LSB> MSB<LSB>
18:Digital common (for No.10 to 17)
19:
20:
21:
22:
23:
24:
25: < >:Specification for GC6
26:Cable shield

(2) Pattern 2
Provided when analog serial output is selected.
1:Interrupt signal
2: LSB
3:
4: Stream identification signal
5:
6: MSB
7: LSB
8:
9:Digital common (for No.1 to 8)
10: Component identification signal
11:
12: MSB
13: LSB
CN2
14:
15: Range identification signal
16:
17: MSB
18:Digital common (for No.10 to 17)
19:
20:
21:
22:
23:
24:
25:
26:Cable shield

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
<<Contents>> <<Index>> 12
● CN3
Provided when digital input is selected.
1:CAL command STD1
2:CAL command STD2
3:Stream change request
4:Range change request
5: LSB
6:
Stream No. code
7:
8: MSB
9:Digital common (for No.1 to 8)
10: LSB
11:
Component No. code
12:
13: MSB
CN3
14: LSB
15:
Component list No. code
16:
17: MSB
18:Digital common (for No.10 to 17)
19:
20:
21:
22:
23:
24:
25:
26:Cable shield

● CN4 to CN9
Provided when analog hold output, analog serial output, or trend output is selected. CN4 to CN9 are provided depend-
ing on the number of outputs.
1:Analog output 1+ Provided if analog 1:Analog output 13+
2:Analog output 1– serial output is 2:Analog output 13–
selected.
3:Analog output 2+ 3:Analog output 14+
4:Analog output 2– 4:Analog output 14–
CN4 5:Analog output 3+ CN7 5:Analog output 15+
6:Analog output 3– 6:Analog output 15–
7:Analog output 4+ 7:Analog output 16+
8:Analog output 4– 8:Analog output 16–
10:Cable shield 10:Cable shield

1:Analog output 5+ 1:Analog output 17+


2:Analog output 5– 2:Analog output 17–
3:Analog output 6+ 3:Analog output 18+
4:Analog output 6– 4:Analog output 18–
CN5 5:Analog output 7+ CN8 5:Analog output 19+
6:Analog output 7– 6:Analog output 19–
7:Analog output 8+ 7:Analog output 20+
8:Analog output 8– 8:Analog output 20–
10:Cable shield 10:Cable shield

1:Analog output 9+ 1:Analog output 21+


2:Analog output 9– 2:Analog output 21–
3:Analog output 10+ 3:Analog output 22+
4:Analog output 10– 4:Analog output 22–
CN6 5:Analog output 11+ CN9 5:Analog output 23+
6:Analog output 11– 6:Analog output 23–
7:Analog output 12+ 7:Analog output 24+
8:Analog output 12– 8:Analog output 24–
10:Cable shield 10:Cable shield

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
<<Contents>> <<Index>> 13
● CN11
Connect to CN1 on the communication converter (K9635JA or K9635JB).

n External Dimensions
(1) GCCU MarkII
Unit: mm

50 or more (wiring space)

470
228 20 450

8 9 10 11
COMPUTING UNIT
COMPUTING UNIT MODEL GCCU
SUFFIX

SUPPLY
100 ~ 240 V AC
4 5 6 7 50/60Hz
AMB TEMP
0 TO 50 °C
190

STYLE
NO.
20 KGC

Made in Japan

1 2 3
L N

2 to 12 (panel thickness)

Panel cut More than 60


220 ±0.5
172 ±0.5
More than 80

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
<<Contents>> <<Index>> 14
(2) Communication Converter (K9635JA/K9635JB)
233 Unit: mm
218
203

126
110
96

4.5
11.5
4-ø4.5 Mounting holes

57 MODEL
NO.

GCCU (RS-232C) Shield M4


1.6

D-SUB 9P Socket GC COM. , D/I 12 V Power supply M4


(MALE)
PC (RS-232C)
D-SUB 9P Socket (MALE)

All Rights Reserved. Copyright © 2007, Yokogawa Electric Corporation GS 11B03S02-02E Apr.28,2008-00
Subject to change without notice.

Potrebbero piacerti anche