Sei sulla pagina 1di 60

png

Substation Automation Products

Bay protection functions REB500


Application Manual
Document ID: 1MRK 505 353-UEN
Issued: March 2016
Revision: A
Product version: 8.2

© Copyright 2016 ABB. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third par-
ty, nor used for any unauthorized purpose.

The software and hardware described in this document is furnished under a license
and may be used or disclosed only in accordance with the terms of such license.

Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered trade-
marks of their respective holders.

Warranty

Please inquire about the terms of warranty from your nearest ABB representative.

ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed prop-
erties. All persons responsible for applying the equipment addressed in this manual
must satisfy themselves that each intended application is suitable and acceptable,
including that any applicable safety or other operational requirements are complied
with. In particular, any risks in applications where a system failure and /or product
failure would create a risk for harm to property or persons (including but not lim-
ited to personal injuries or death) shall be the sole responsibility of the person or
entity applying the equipment, and those so responsible are hereby requested to en-
sure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot be com-
pletely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the
use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communi-
ties on the approximation of the laws of the Member States relating to electromag-
netic compatibility (EMC Directive 2004/108/EC) and concerning electrical
equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in accord-
ance with the product standards EN 50263 and EN 60255-26 for the EMC di-
rective, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Safety information

Dangerous voltages can occur on the connectors, even though the


auxiliary voltage has been disconnected.

Non-observance can result in death, personal injury or substantial


property damage.

Only a competent electrician is allowed to carry out the electrical


installation.

National and local electrical safety regulations must always be fol-


lowed.

The frame of the IED has to be carefully earthed.

Whenever changes are made in the IED, measures should be taken


to avoid inadvertent tripping.

The IED contains components which are sensitive to electrostatic


discharge. Unnecessary touching of electronic components must
therefore be avoided.
Table of contents

Table of contents

Section 1 Introduction................................................................. 3
1.2 This manual .................................................................................... 3
1.3 Intended audience .......................................................................... 3
1.4 Product documentation ................................................................... 3
1.5 Symbols and conventions ............................................................... 4
1.5.1 Symbols..................................................................................... 4
1.5.2 Document conventions............................................................... 4
Section 2 Overview .................................................................... 6
2.1 Functionalities ................................................................................. 6
2.2 Structure of protection function software.......................................... 6
2.2.1 Functional diagram of bay protection REB500 ............................ 7
2.2.2 Label number guide for Figure 1................................................. 8
2.3 Signals............................................................................................ 9
2.3.1 Bay / Station Protection à function overlapping signals.............. 9
2.3.2 Bay protection à function-specific signals ................................ 11
Section 3 Configuring bay protection using HMI500.................... 18
3.1 Integration of bay protection .......................................................... 18
3.2 Configuring the bay protection using HMI500 ................................ 19
3.3 Select Protection Function ............................................................ 19
3.4 Binary signal configuration ............................................................ 23
3.4.2 Configuring binary output signals ............................................. 29
3.4.3 Recording a binary signal as an event ...................................... 32
3.4.4 Disturbance recording of a binary signal ................................... 32
3.5 Protection function settings ........................................................... 32
Section 4 System functions....................................................... 33
4.1 BP Function Monitoring ................................................................. 33
4.2 BP Licenses.................................................................................. 34
4.3 CT grounding ................................................................................ 34
Section 5 Bay protection functions ............................................ 35
5.1 Application / Technical details ....................................................... 35
5.2 Technical additions ....................................................................... 36

Application Manual 1
Bay protection functions REB500
Table of contents

5.2.1 Voltage transformers for bay protection .....................................36


Section 6 BP-Additions to base documentation .......................... 38
6.1 Technical Data ...............................................................................38
6.2 Operation and maintenance ...........................................................46
6.2.1 Maintenance of bay protection functions....................................46
6.2.2 Protection blocking....................................................................46
6.2.3 Protection tripping .....................................................................46
6.3 Commissioning ..............................................................................48
6.3.1 Regulations...............................................................................48
6.3.2 Additional checks for bay protection REB500 ............................48
6.4 Communication ..............................................................................51

2 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 1
Introduction

Section 1 Introduction

1.2 This manual

The manual contains application descriptions, setting guidelines and technical data
for the bay protection functions. It is complementary to the basic Application Man-
ual of REB500.

The manual can be used to find out when and for what purpose a typical protection
function can be used. The manual can also be used when calculating settings.

1.3 Intended audience

This manual addresses the protection and control engineer responsible for plan-
ning, pre-engineering and engineering.

The protection and control engineer must be experienced in electrical power engi-
neering and have knowledge of related technology, such as protection schemes and
communication principles.

1.4 Product documentation

Manual Document number


Product Guide 1MRK 505 352-BEN

Application Manual 1MRK 505 349-UEN

Technical Manual 1MRK 505 350-UEN

Operation Manual 1MRK 500 124-UEN

Commissioning Manual 1MRK 505 351-UEN

Application Manual 1MRK 505 353-UEN


Bay protection Functions
Cyber Security Guideline 1MRK 511 373-UEN

Communication Protocol Manual 1MRK 511 370-UEN


IEC 61850
Communication Protocol Manual, 1MRK 511 371-UEN
IEC 60870-5-103

Application Manual 3
Bay protection functions REB500
Section 1 1MRK 505 353-UEN
Introduction

1.5 Symbols and conventions

1.5.1 Symbols

The electrical warning icon indicates the presence of a hazard which


could result in electrical shock.

The warning icon indicates the presence of a hazard which could re-
sult in personal injury.

The caution icon indicates important information or warning related


to the concept discussed in the text. It might indicate the presence of
a hazard which could result in corruption of software or damage to
equipment or property.

The information icon alerts the reader of important facts and condi-
tions.

The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to under-


stand that under certain operational conditions, operation of damaged equipment
may result in degraded process performance leading to personal injury or death.
Therefore, comply fully with all warning and caution notices.

1.5.2 Document conventions

A particular convention may not be used in this manual.

• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the
push button icons, e.g.:
To navigate the options, use and .

4 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 1
Introduction

• HMI menu paths are presented in bold, e.g.:


Select Main menu/Settings.
• LHMI messages are shown in Courier font, e.g.:
To save the changes in non-volatile memory, select Yes and ….
• Parameter names are shown in italics, e.g.:
The function can be enabled and disabled with the Operation setting.
• The * character after an input or output signal name in the function block
symbol given for a function indicates that the signal must be connected to an-
other function block in the application configuration to achieve a valid applica-
tion configuration.

Application Manual 5
Bay protection functions REB500
Section 2 1MRK 505 353-UEN
Overview

Section 2 Overview

In addition to the station protection (SP) the system includes bay protection func-
tions (BP) applicable for HV and EHV networks. Depending on the requirements
single functions up to system specific line protection arrangements can be config-
ured.

Adding the BP arrangement is made under the “Configurator mode” of HMI500.

2.1 Functionalities

Table 1 Available Bay protection functions


Function REB5000 IEEE / IEC Base L-V2
ANSI No. 61850
Logic LOGIC - - x x

Delay / integrator DELAY - - x x

Distance protection DIST 21 PDIS/PSCH - x

Definite time over and undercurrent protection OCDT 51 PTOC - x

Inverse time overcurrent protection OCINV 51 PTOC - x

Directional overcurrent definite time protection DIROCDT 67 PTOC - x

Directional overcurrent inverse time protection DIROCINV 67 PTOC - x

Inverse time earthfault overcurrent protection I0INV 51N PTOC - x

Peak value over and undercurrent protection OCINST 50 PTOC - x

Definite time over and undervoltage protection OVDT 59/27 PTOV - x

Three phase current plausibility CHKI3PH 46 PTOC - x

Three phase voltage plausibility CHKU3PH 47 PTOV - x

More than one instance of functions is available and may be configured (e.g. two
instances of the OCDT function)

2.2 Structure of protection function software

Figure 1 and the subsequent tables give an overview of the structure of the station
and bay protection functions in a bay unit. These functions are accessed through
so-called BP-input (Bi) and BP output blocks (Bo) which can accommodate up to
20 input and 120 output signals respectively.

6 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 2
Overview

It is to be noted that all signals that are to be mapped to the binary output contacts,
substation automation systems SAS (e.g. IEC 61850 bus) or LEDs first have to be
routed via the BP output block (Bo).

The following diagram gives an overview of the protection function und hardware
blocks of a RE500 bay unit including the possible signal assignments. Table 2 to
Table 4 provide the detailed description of the labeled items.

2.2.1 Functional diagram of bay protection REB500

For the purposes of illustration, the configuration steps described


under Section 3 refer to the functional diagram Figure 1 below and
the herein included label numbers.

Figure 1 Structure and assignment of station and bay protection functions

Application Manual 7
Bay protection functions REB500
Section 2 1MRK 505 353-UEN
Overview

2.2.2 Label number guide for Figure 1


Table 2 Explanations to inputs / outputs
Item No. Name Definition Remark
1 OC input Optocoupler input of bay unit 33 binary inputs per bay unit
2 CR output Relay (contact) output of bay 19 binary outputs per bay unit
unit
3 U, I input Analog input of bay unit Assignment to SP functions is fixed.
Assignment to BP functions is partly
configurable.
4 BP input Logical input of BP part 20 logical inputs per bay unit
5 BP output Logical output of BP part 120 logical outputs per bay unit

Table 3 Explanations to protection function part


Label No. Name Definition Remark
6 SP Station protection part Contains station protection functions
SP function Station protection function Available functions
e.g. BBP, BFP, EFP, ..
7 BP Bay protection part Contains bay protection functions
BP function Bay protection function Available functions
e.g. DIST, OCDT, ..

Table 4 Explanations to signal connections


Label No. Definition Remark
8 OC input assigned to SP function Assignment via software HMI500
e.g. 13710_Start BFP_L1_1
9 SP function assigned to CR output Assignment via software HMI500
e.g. 23105_BFP TRIP
10 OC input assigned to BP input Assignment via software HMI500
e.g. 111205_DIST Ext. Block Dist.
11 BP input assigned to BP function Assignment via software HMI500
e.g. DIST: Ext Blk Dist
12 BP function assigned to BP output Assignment via software HMI500
e.g. DIST: Com Send
13 BP-output assigned to CR output Assignment via software HMI500
e.g. 211880_ DIST Com
14 BP-output assigned to SP function Assignment via software HMI500
e.g. DIST: Trip_DIST à 13785_BP Start
BFP L1L2L3
15 SP-function assigned to BP input Assignment via software HMI500
16 OC-input assigned to SP function and BP Assignment via software HMI500
input e.g. 11530/ 118515_Q0 Open and CB
OPEN
17 SP function and BP output assigned to CR Assignment via software HMI500
output e.g. 21110/ 220815_TRIP
18 Internal connections between BP-functions Assignment via software HMI500
19 Internal connections between SP-functions Automatic assignment done by REB500
ITT-system (ITT = intertripping)

8 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 2
Overview

2.3 Signals

2.3.1 Bay / Station Protection à function overlapping signals

2.3.1.1 Signal designations

The BP/ SP function overlapping (general) signals correspond to the signal num-
bers nomenclature of the station protection system (for details see Technical Man-
ual REB500)

Example: 19205_Block BP (5 digit signal number)

2.3.1.2 Outputs generated by BP and used as SP inputs (default signals)

Table 5 BU_ BP outputs to SP inputs (default signals)


Signal Description
11120_BP External TRIP This is the tripping signal generated by bay protection of
REB500. It trips faults on a line with the aid of the REB500
tripping contact. Tripping thus takes account of the busbar
configuration at the time. The signal is activated by the bay
protection directly and does not therefore appear as binary
input signal.
11125_BP External TRIP BB zone This is a tripping signal generated by the bay protection of
REB500 which is used to trip the entire bus zone to which the
fbay is connected. The tripping command is applied to all the
bay units of the bus zone and sections of busbars intercon-
nected by an isolator (intertripping).
13210_BP Block BFP This signal is directly activated by the bay protection and
doesn’t therefore appear as a binary input signal. The opera-
tion of the breaker failure protection of the corresponding
feeder is blocked. When the blocking signal is cancelled and
providing a starting signal is present and current is flowing, the
timers start again at t = 0.
13610_BP Trip transfer Reserved for the special application “trip transfer”.
This signal is directly activated by the bay protection unit and
does not therefore appear as a binary input signal.
13761_BP Start BFP L1L2L3_5 This signal is functionally identical to signal "13760_Start BFP
L1L2L3_5", but it is directly activated by the bay protection and
does not therefore appear as a binary input signal.
13770..13780_BP Start BFP Lp Breaker failure protection with phase-selective starting (p = 1,
2 or 3). The breaker failure protection timer starts when this
signal is activated by BP functions and the BFP measures a
current in the corresponding phase. This signal is directly
activated by the bay protection and does not therefore appear
as a binary input signal.
13785_BP Start BFP L1L2L3 Breaker failure protection with three-phase starting. The
breaker failure protection timer starts when this signal is acti-
vated and the BFP measures a current in any phase.
This signal is directly activated by the bay protection and does
not therefore appear as a binary input signal.

Application Manual 9
Bay protection functions REB500
Section 2 1MRK 505 353-UEN
Overview

Signal Description
13790_BP External start BFP Breaker failure protection with three-phase starting. The
breaker failure protection timer starts when this signal is acti-
vated regardless of the current measurement.
This signal is directly activated by the bay protection and does
not therefore appear as a binary input signal.
13797_BP Start BFP L0 Breaker failure protection with L0 - starting. The breaker failure
protection timer starts when this signal is activated by BP
functions and the BFP measures a current in the neutral sys-
tem. This signal is directly activated by the bay protection and
does not therefore appear as a binary input signal.
16760_BP Global Start DR Starts those disturbance recorders in the bay units that are
configured. The signal ‘Central start DR’ in the bay units must
be configured. This signal is directly activated by the BP unit
and does not therefore appear as a binary input signal.

2.3.1.3 General inputs to BP

Table 6 BU_ Inputs to BP


Signal Description
19205_Block BP The BP output signals of the respective bay unit are blocked.
(Internal processing of the functions continues and therefore
measurements and signals continue to be displayed on the
local HMI.)
19600_Activation BP ParSet_1 The protection functions and settings assigned to parameter
set 1 are active. They remain active after the signal has been
reset.
19605_Activation BP ParSet_2 The protection functions and settings assigned to parameter
set 2 are active. They remain active after the signal has been
reset.
19610_Activation BP ParSet_3 The protection functions and settings assigned to parameter
set 3 are active. They remain active after the signal has been
reset.
19615_Activation BP ParSet_4 The protection functions and settings assigned to parameter
set 4 are active. They remain active after the signal has been
reset.

Table 7 CU_ Inputs to BP


Signal Description
39205_Block BP The bay protection output signals are blocked throughout the
system (internal processing of the functions continues and
therefore measurements and signals continue to be displayed
on the local HMI).

10 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 2
Overview

2.3.1.5 General outputs from BP

Table 8 BU_ Output signals from BP


Signal Description
29405_BP blocked Signals that the outputs of the bay protection functions are
blocked (either the bay concerned or throughout the system).
29410_BP partial blocked Signals certain bay protection functions are blocked
(Signal must be set explicitly in the bay protection).
29600 ParaSet_1 active Signals that parameter set 1 is active (activated via the station
bus or an input signal).
29605 ParaSet_2 active Signals that parameter set 2 is active (activated via the station
bus or an input signal).
29610 ParaSet_3 active Signals that parameter set 3 is active (activated via the station
bus or an input signal).
29615 ParaSet_4 active Signals that parameter set 4 is active (activated via the station
bus or an input signal).

Table 9 CU_ Output signals from BP


Signal Description
49405_BP blocked Signals that the outputs of the bay protection functions are
blocked (either individual bays or throughout the system).
49410_BP partial blocked Signals that certain bay protection output signals in specific
bays or throughout the entire system are blocked (Must be
configured together with the corresponding BU output signal
29410_BP partial blocked).

2.3.2 Bay protection à function-specific signals

2.3.2.1 Signal designations of binary inputs and outputs

The signal range of REB500 is expanded for the bay protection functions. The BP
function-specific signal can be identified by a 6 digit signal number

Example:

Signal 211105_DIST_Trip CB L1

Table 10 Signal numbers nomenclature


211105 DIST Trip CB L1

6 Digit signal number Protection function Signal designation

Application Manual 11
Bay protection functions REB500
Section 2 1MRK 505 353-UEN
Overview

Table 11 Signal numbers nomenclature


Digit 1 Digit 2,3 Digit 4 Digit 5,6
Category Protection Signal function Sequence
function number
1 BU_in 11 DIST 1 TRIP 05

2 BU_out 12 OCDT 2 Block command 10

3 CU_in 13 OCINV 3 Tripping signal 15

4 CU_out 14 DIROCDT 4 Blocking signal 20

5 System 15 DIROCINV 5 Bus image etc.

16 OVTD 6 Control

21 I0INV 7 Start

24 CHKI3PH 8 General alarm

25 CHKU3PH

26 OCINST

2.3.2.2 Signal designations of BP internal signals

Each BP function provides a set of internal input and output signals. They can be
mapped to binary inputs (optocoupler) and outputs (contacts) of the bay unit by us-
ing the corresponding binary inputs and output signals.

Example:

BP internal Signal Designation of binary input signal


Trip CB L1 211105_DIST TRIP CB L1

2.3.2.3 Binary input signals of BP

Table 12 BU_ Logic input signals


BP int. Signal Designation of binary input sig. Description
Block 122205_LOGIC Block Input for blocking LOGIC function
Binary Input 1 122805_LOGIC Binary Input 1 Logic input 1
Binary Input 2 122810_LOGIC Binary Input 2 Logic input 2
Binary Input 3 122815_LOGIC Binary Input 3 Logic input 3
Binary Input 4 122820_LOGIC Binary Input 4 Logic input 4

Table 13 BU_ Delay input signals


BP int. Signal Designation of binary input sig. Description
Block 123205_DELAY Block Input for blocking of DELAY function
Binary Input 123805_DELAY Binary Input Input to be delayed

12 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 2
Overview

Table 14 BU_ DIST input signals


BP int. Signal Designation of binary input sig. Description
Ext Blk Dist 111205_DIST Ext. Block Dist. Input for disabling the distance protection func-
tion.
Ext Blk PSB 111215_DIST Ext. Blk. PSB Input for blocking the power-swing function
Ext Blk O/C 111220_DIST Ext. Block O/C Input the backup overcurrent function
ExtBlkSOTF 111225_DIST Ext. Block SOTF Input for blocking the tripping condition for the
switch-onto-fault logic
ExtBlkHF 111230_DIST Ext. Block HF Input for blocking a received PLC signal (con-
trolled, for example, by a sensitive E/F scheme
using the same PLC channel
ExtBlock Z1 111235_DIST Ext. Block Z1 Input for blocking measurement in the first zone
Manual close 111505_DIST Manual Close Circuit breaker manual close command
Isol Open 111510_DIST Isolator Open Isolator open signal for activating the ‘short-zone’
logic and protection (T section in 1½ breaker
schemes)
ChgMeasDir 111605_DIST Change Meas. Input for changing the direction of measurement
Dir.
DeadLine 111805_DIST Deadline Line de-energized signal (auxiliary contact on the
circuit-breaker when the VTs are on the busbar)
ZExtension 111810_DIST Zextension External zone extension control signal
Zone extension
Com Rec 111815_DIST Com Rec Input for PLC signal from the remote station
Com Fail 111820_DIST Com Fail Input for PLC failure signal

Table 15 BU_ OCDT input signals


BP int. Signal Designation of binary input sig. Description
Block 112205_OCDT Block Input for blocking OCDT

Table 16 BU_ OCINV input signals


BP int. Signal Designation of binary input sig. Description
Block 113205_OCINV Block Input for blocking of OCINV

Table 17 BU_ DIROCDT input signals


BP int. Signal Designation of binary input sig. Description
Block 114205_DIROCDT Block Input for Blocking of DIROCDT
Receive 114805_DIROCDT Receive PLC receive signal

Table 18 BU_ DIROCINV input signals


BP int. Signal Designation of binary input sig. Description
Block 115205_DIROCINV Block Input for blocking of DIROCINV
Receive 115805_DIROCINV Receive PLC receive signal

Application Manual 13
Bay protection functions REB500
Section 2 1MRK 505 353-UEN
Overview

Table 19 BU_ I0INV input signals


BP int. Signal Designation of binary input sig. Description
Block 121205_I0INV Block Input for blocking of I0INV

Table 20 BU_ OCINST input signals


BP int. Signal Designation of binary input sig. Description
Block 126205_OCINST Block Input for blocking of OCINST

Table 21 BU_ OVDT input signals


BP int. Signal Designation of binary input sig. Description
Block 116205_OVDT Block Input for blocking of OVTD

Table 22 BU_CHKI3PH input signals


BP int. Signal Designation of binary input sig. Description
Block 124205_CHKI3PH Block Input for blocking of CHKI3PH

Table 23 BU_ CHKU3PH input signals


BP int. Signal Designation of binary input sig. Description
Block 125205_CHKU3PH Block Input for blocking of CHKU3PH

2.3.2.4 Binary output signals of BP

Table 24 BU_ LOGIC output signals


BP int. Signal Designation of binary output sig. Description
Binary output 222805_LOGIC Binary Output Logic signal (output from logic)
Binary output 222810_LOGIC BINARY OUT- Trip signal (output from trip logic)
PUT

Table 25 BU_ DELAY output signals


BP int. Signal Designation of binary output sig. Description
Trip 223105_DELAY TRIP Trip signal
Start 223705_DELAY Start Start signal

Table 26 BU_ DIST output signals


BP int. Signal Designation of binary output sig. Description
Trip CB L1 211105_DIST TRIP CB L1 Circuit-breaker L1 phase trip
This signal is disabled while a blocking signal is
being applied with the exception of a trip by the
backup over-current protection.

14 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 2
Overview

BP int. Signal Designation of binary output sig. Description


Trip CB L2 211110_DIST TRIP CB L2 Circuit-breaker L2 phase trip
This signal is disabled while a blocking signal is
being applied with the exception of a trip by the
backup over-current protection.
Trip CB L3 211115_DIST TRIP CB L3 Circuit-breaker L3 phase trip
This signal is disabled while a blocking signal is
being applied with the exception of a trip by the
backup over-current protection.
Trip CB 211305_DIST TRIP CB General circuit-breaker tripping signal. This
signal is disabled while a blocking signal is being
applied with the exception of a trip by the backup
overcurrent protection.
Trip L1L2L3 211310_DIST Trip L1L2L3 General tripping signal. This signal is not disa-
Trip L1L2L3 211315_DIST Trip L1L2L3 Aux bled while a blocking signal is being applied.
Aux
Trip CB 3P 211320_DIST Trip CB 3ph Three-phase trip signal. This signal is disabled
while a blocking signal is being applied with the
exception of a trip by the backup overcurrent
protection.
Trip CB 1P 211325_DIST Trip CB 1ph Single-phase trip signal. This signal is disabled
while a blocking signal is being applied with the
exception of a trip by the backup overcurrent
protection.
Trip O/C 211330_DIST Trip O/C Backup overcurrent trip signal.
Trip SOTF 211335_DIST Trip SOTF Switch-onto-fault trip signal.
Trip Com 211340_DIST Trip Com Signal for tripping either enabled by the receipt
of a permissive signal or the non-receipt of a
blocking signal. (This signal is disabled while a
blocking signal is being applied.)
Trip Stub 211345_DIST Trip Stub 'Short-zone’ protection trip signal.
Dist Blocked 211405_DIST Blocked Signal indicating that the distance protection is
blocked.
DelDistBlk 211410_DIST Del Blocked Signal delayed by 12 s indicating that the dis-
tance protection is blocked.
Start 211705_DIST Start L1+L2+L3 General distance protection starting signal (OR
L1+L2+L3 logic for all starting signals excepting ‘weak
infeed').
Start L1L2L3 211710_DIST Start L1L2L3 General distance protection starting signal (OR
Start L1L2L3 211715_DIST Start L1L2L3 Aux logic for all starting signals including ‘weak in-
Aux feed').
Start L1 211720_DIST Start L1 Distance protection L1 phase starting signal
Start L1 Aux 211725_DIST Start L1 Aux (including ‘weak infeed').
Start L2 211730_DIST Start L2 Distance protection L2 phase starting signal
Start L2 Aux 211735_DIST Start L2 Aux (including ‘weak infeed').
Start L3 211740_DIST Start L3 Distance protection L3 phase starting signal
Start L3 Aux 211745_DIST Start L3 Aux (including ‘weak infeed').
Start L0 211750_DIST Start E Distance protection E/F starting signal (U0 or I0).
Start L0 Aux 211755_DIST Start E Aux Only generated together with a phase starter.
Start I0 211760_DIST Start I0 Neutral current starting signal (I0).
Start U0 211765_DIST Start U0 Neutral voltage starting signal (U0).
Start OC 211770_DIST Start O/C Overcurrent starting signal.
Start SOFT 211780_DIST Start SOTF Enabling signal for the switch-onto-fault protec-
tion.

Application Manual 15
Bay protection functions REB500
Section 2 1MRK 505 353-UEN
Overview

BP int. Signal Designation of binary output sig. Description


Start O/C 211785_DIST Start OC Backup overcurrent start signal.
Start UZ 211790_DIST Start UZ Underimpedance starting signal.
Start 1ph 211805_DIST Start 1ph Indicates that the distance protection was started
by a single phase.
Delay >= 2 211810_DIST Delay >= 2 Signal for starting in Zone 2 or higher.
Delay 1 211815_DIST Delay 1 Signal for starting in Zone 1.
Delay 2 211820_DIST Delay 2 Signal for starting in Zone 2.
Delay 3 211825_DIST Delay 3 Signal for starting in Zone 3.
Delay 4 211830_DIST Delay 4 Signal for starting in Zone 4 (excepting when
Zone 4 is being used as an overreaching zone).
Delay Def 211835_DIST Delay Def Signal for starting in the final zone.
Meas Main 211840_DIST Meas Main Measurement by the distance function (Zones 1,
2, 3, 4 or the final zone).
Meas 211845_DIST Meas Oreach Measurement in the distance protection over-
Oreach reach zone.
Meas Fward 211850_DIST Meas Fward Measurement by the distance protection in the
forwards direction.
Meas Bward 211855_DIST Meas Bward Measurement by the distance protection in the
reverse direction (reverse zone).
Weak Infeed 211860_DIST Weak Infeed Tripping by the ‘weak infeed’ function.
Power Swing 211865_DIST Power Swing Power-swing blocking function picked up.
VTSup 211870_DIST VT Sup VT supervision picked up.
VTSup Delay 211875_DIST VT Sup Delay Delayed operation of the VT supervision after
12 s.
Com Send 211880_DIST Com Send Signal generated when a transfer trip signal is
transmitted.
Com Boost 211885_DIST Com Boost Signal for boosting PLC transmitting power.
Freq dev 211890_DIST Freq Dev Signal indicating a deviation of the memory
voltage frequency.

Table 27 BU_ OCDT output signals


BP int. Signal Designation of binary output sig. Description
Trip 212105_OCDT TRIP Trip signal
Start 212705_OCDT Start Start signal

Table 28 BU_ OCINV output signals


BP int. Signal Designation of binary output sig. Description
Trip 213105_OCINV TRIP Trip signal
Start 213705_OCINV Start Start signal

Table 29 BU_ DIROCDT output signals


BP int. Signal Designation of binary output sig. Description
Trip 214105_DIROCDT TRIP Trip signal.
Start 214705_DIROCDT Start Start signal.
Start L1 214710_DIROCDT Start L1 L1 phase start signal

16 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 2
Overview

Start L2 214715_DIROCDT Start L2 L2 phase start signal


Start L3 214720_DIROCDT Start L3 L3 phase start signal
MeasFwd 214805_DIROCDT MeasFwd Signals measurement in the forwards direction.
MeasBwd 214810_DIROCDT MeasBwd Signals measurement in the backwards direc-
tion.

Table 30 BU_ DIROCINV output signals


BP int. Signal Designation of binary output sig. Description
Trip 215305_DIROCINV TRIP Trip signal.
Start 215705_DIROCINV Start Start signal.
Start L1 215710_DIROCINV Start L1 L1 phase start signal
Start L2 215715_DIROCINV Start L2 L2 phase start signal
Start L3 215720_DIROCINV Start L3 L3 phase start signal
MeasFwd 215805_DIROCINV MeasFwd Signals measurement in the forwards direction.
MeasBwd 215810_DIROCINV MeasBwd Signals measurement in the backwards direc-
tion.

Table 31 BU_ I0INV output signals


BP int. Signal Designation of binary output sig. Description
Trip 221105_I0INV TRIP Trip signal
Start 221705_I0INV Start Start signal

Table 32 BU_ OCINST output signals


BP int. Signal Designation of binary output sig. Description
Trip 226105_OCINST TRIP Trip signal
Start 226705_OCINST Start Start signal

Table 33 BU_ OVDT output signals


BP int. Signal Designation of binary output sig. Description
Trip 216105_OVDT TRIP Trip signal
Start 216705_OVDT Start Start signal

Table 34 BU_ CHKI3PH output signals


BP int. Signal Designation of binary output sig. Description
Trip 224605_CHKI3PH Picked Up Trip signal

Table 35 BU_ CHKU3PH output signals


BP int. Signal Designation of binary output sig. Description
Trip 225605_CHKU3PH Picked Up Trip signal

Application Manual 17
Bay protection functions REB500
Section 3 1MRK 505 353-UEN
Configuring bay protection using HMI500

Section 3 Configuring bay protection using HMI500

3.1 Integration of bay protection

The REB500 bay models include no bay protection functionality. The integration
of the bay protection (variant V-L2) takes place under the setfile engineering dur-
ing the “Import a Bay Model” process.

The dialogue “Bay model import options” enables the selection of the BP variant
V-L2. After pressing the OK button, the respective bay is imported to the single-
line diagram and the selected BP variant (comprising the “V-L2 set” of BP func-
tions) is available for further configuration.

Figure 2 Selection the import option “Bay protection and “Variant””

For detailed information about the setfile engineering refer the REB500 Engineer-
ing Manual Section “single-line diagram”

The setfile engineering and the integration of the Bay protection re-
quires that the HMI500 is started under der “Configurator Mode”.
After that, the configuration details can also be adjusted under the
“Operator Mode”.

18 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 3
Configuring bay protection using HMI500

3.2 Configuring the bay protection using HMI500

To configure and set the bay protection function, open the HMI500 menu “Set-
tings” and select the menu item “Bay protection”.

Figure 3 Settings / Bay protection Configuration


Table 36 “Bay protection – Configuration” - buttons
Button Function
Continue Opens the dialogue “Select Protection Function” of a selected bay and
thus the BP configuration.
Instead of “Continue” button, simply double click a unit line
Copy Copies the BP configuration of a selected bay
Paste Pastes the copied BP configuration to a selected bay
Delete configuration Delete the BP configuration of the selected bay

3.3 Select Protection Function

This dialog is divided into the following parts:

The protection functions available for configuration are listed on the left (in the
form of buttons). Its content is determined by the already selected Bay protection
variant (see Section 3.2).

The protection functions used for configuration are listed on the right. The first is
always the binary output function “BP output” (see Figure 4).

Application Manual 19
Bay protection functions REB500
Section 3 1MRK 505 353-UEN
Configuring bay protection using HMI500

Figure 4 Select Protection Functions

Table 37 Select Protection Function – used BP Functions


Menu item Description
No. Unique instance number of the BP function
Func. Symbol representing the BP function of the instance
Description User specific description of the BP function of the instance
P1..P4 Parameter set in which the protection function occurs. Switching between
parameter sets is accomplished using the binary input signals 19600_x,
19605_x, 19610_x and 19615_x
x = “Activation BP ParSet 1..4”
Copy of Instance No. of the original function, where the instance is a copy of a func-
tion that already exists.

If the number of function instances exceeds the size of the display area, a scroll bar
automatically appears on the right. The maximum number of instances per bay unit
is limited to 128.

There are a number of tabs, which can be selected in this part of the dialog. The
first tab (ParSet 1..4) lists all the functions. It has to be selected to change functions
and determine the instances where they occur. The tabs ParSet 1 to ParSet 4 list
the functions configured for a particular parameter set and are merely for infor-
mation.

Creating instances of protection functions

An instance of a protection function is created by selecting it in the list on the left


of the dialog using the left mouse button and while keeping the button depressed
dragging it onto the area of the first tab (ParSet 1..4) (drag and drop). It is not pos-
sible to ‘drop’ the function while the symbol is being shown. The instance of

20 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 3
Configuring bay protection using HMI500

the protection function is created when the mouse cursor changes to an arrow and
the mouse button is released.

Assigning protection functions to parameter sets

Every instance of a protection function can be assigned to a particular parameter


set. The REB500 runs the protection functions in the currently selected parameter
set. The active parameter set is changed by setting the appropriate binary input on
the bay unit.

Figure 5 Parameter set assignment

To assign the instance of a protection function to a parameter set, simply check the
corresponding box using the left mouse button.

Using the context menu

To open the context menu for a particular protection function, first select the func-
tion by clicking the left mouse button on its symbol and then clicking the right
mouse button.

Figure 6 Content menu

Table 38 Content menu dialogues


Menu item Description
Copy Creates a copy of the protection function according to the following rules:
• A copy cannot be in the same parameter set as the original.

• The input signals of a copy are the same as those of the original and
cannot be changed.

• Only defined parameters of a copy can be configured. All other param-


eters are taken from the original.

Application Manual 21
Bay protection functions REB500
Section 3 1MRK 505 353-UEN
Configuring bay protection using HMI500

Menu item Description


Delete The instance of the specific protection function is deleted together with all the
settings that the user has made up to that point.
If the function being deleted has connections to other protection functions, an
error message appears instructing you to first delete the connections.

Thus an instance can only be deleted after all its interconnections have been
deleted.
Properties This opens a dialog with all the function’s settings. Double clicking on the
function’s symbol opens the same dialog.

Status indicator

On the left of each instance number and function symbol there is a status indicator
which signals the validity of the parameters entered.

Figure 7 Status indication of BP Function

Green indicates that the configuration is correct and valid while red indicates that
the setting procedure has not been completed. This generally means in the case of a
single-phase function that an analog channel has not yet been assigned to it.

The “Bay protection” dialog cannot be closed by clicking on “OK” until all the sta-
tus indicators are green.

Statistical evaluation

Double clicking with the right mouse button with the cursor in the dialog below the
area of the tabs opens a window with statistics and status information on the bay
protection functions.

Figure 8 Area below tabs – sensitive for selection of statistical evaluation

The version number of the bay protection configuration module is shown in the
bottom left-hand corner.

22 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 3
Configuring bay protection using HMI500

Figure 9 Status indication of BP Function

Table 39 Status indication of BP Function – Mode


Dialogue tem Description
Configuration The dialog is in the protection function configuration or setting mode.

Measurements The dialog was started in the measurement display mode.

Test Not implemented in this version.

Read- Write The user can edit and save settings.

Read- only The user cannot edit settings.

Table 40 Status indication of BP Function – Statistics


Dialogue item Description
Configured functions Number of instances created by the user for this bay unit. The maximum
number is 128.
Available parame- The number of memory locations available for protection function settings
ters in the entire system.
Used parameters Number of protection function settings used by the present bay unit.

3.4 Binary signal configuration

3.4.1.1 Configuring binary input signals

Each Bay protection function has a defined number of binary inputs. These are de-
scribed for each of the protection functions in Section 2.3.2.3. .

Application Manual 23
Bay protection functions REB500
Section 3 1MRK 505 353-UEN
Configuring bay protection using HMI500

In the dialogs for setting protection functions, a binary input is described in plain
text and has a button for configuration.

Figure 10 Setting binary input signal – e.g. OCDT Blocking input

The following signals can be assigned to the binary inputs of each


BP function:

BP internal

• outputs from an another BP function (see 3.4.1.2)


• General inputs to BP (see 2.3.1.3)
• Signal status “Always FALSE” or “Always TRUE”

BP external (see 3.4.1.4)

• Binary input signals (from optocoupler inputs)


• Predefined outputs of a station protection function

24 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 3
Configuring bay protection using HMI500

3.4.1.3 Assignment of ‘BP internal’ input signals

Click the left mouse button on the status button of the desired signal to open the di-
alog “Select Binary Input” for configuring the status of the particular binary input
signal.

The dialog has two tabs, the first of which (“TRUE / FALSE”) provides facility for
setting the input status to “Always True”, OR “Always False”. This is a permanent
assignment, without the involvement of an output signal of another function.

Figure 11 Configuring binary inputs (TRUE / FALSE)

The second tab “Output from Function” enables the output of an existing instance
of a protection function to be connected to the particular signal input.

The “Output from Function” tab lists all the protection function instances set for
the particular bay unit together with the unique number of the instance. Upon se-
lecting a protection function in the list on the left by clicking the left mouse button
on it, its binary output signals appear on the right of the dialog.

Application Manual 25
Bay protection functions REB500
Section 3 1MRK 505 353-UEN
Configuring bay protection using HMI500

Figure 12 Configuring binary inputs (Output from other BP function)

Table 41 “Output from Function”- dialogue / Column designations


Dialogue tem Description
Channel Unique No. of the output signal

Inv Check this box to invert the signal

Signal text Output signal name

Location of ‘BP internal’ input signals within the BP function dia-


gram see Figure 1, Label No. 18.

3.4.1.4 Assignment ‘BP external’ input signals

The system automatically creates an instance “BP Binary Input”. It thus always
heads the list of instances.

If you select “BP Binary Input”, the right-hand half of the dialog presents two tabs
“Default” and “General purpose”.

26 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 3
Configuring bay protection using HMI500

Default

The “Default” tab lists station protection default outputs (see Figure 13). Any bina-
ry input of a BP function can be linked to these to enable the exchange of signals
between station protection and the bay protection sections (e.g. signal
21105_External TRIP).

Figure 13 Configuring binary inputs (“Default” à Output from SP function)

Location of input signals from ‘SP function’within the BP func-


tion diagram see Figure 1, Label No. 15.

General Purpose

The “General Purpose” tab provides facility for defining up to 20 user signals. To
this end, select a signal number with the left mouse button. A text field appears in
which the user can write a signal name (see Figure 14).

The signal name entered must conform to REB500 signal conventions (see Section
2.3.2.1). The Section 2.3.2.3 provides a list of all signals available for “General
Purpose” inputs.

Application Manual 27
Bay protection functions REB500
Section 3 1MRK 505 353-UEN
Configuring bay protection using HMI500

Example:

Signal name under the BP function Designation of binary input signals to be entered under
“General Purpose”
Ext Blk Dist 111205_DIST Ext. Block Dist.

Figure 14 Configuring binary inputs (General purpose)

Location of ‘BP internal’ input signals within the BP function dia-


gram see Figure 1, Label No. 11.

Once defined, signals can be assigned to an optocoupler input by selecting the


menu “Configuration/ Binary module/ Inputs”.

Location of ‘Binary module’ input signals within the BP function


diagram see Figure 1, Label No. 10.

28 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 3
Configuring bay protection using HMI500

3.4.2 Configuring binary output signals

Each REB500 bay protection function has a defined number of binary output sig-
nals. These are described for each of the protection functions in Section 2.3.2.4. In
the dialogs for setting protection functions, a binary output signal is described in
plain text and has a field, which lists the input signals assigned to the respective
output.

Figure 15 BP output signal assignment

The list shows the input signals assigned to the respective output. For each signal
in the list, the instance number and an abbreviation of the function are given.

Table 42 BP output signal assignment


Example Description
09 Instance of BP function
OR Symbol representing the BP function of the instance
Binary Inp 2 Binary input 2 of OR function

Output signals are assigned when configuring either the binary out-
put function (see Section 3.4.2.1) or bay protection input signal
function (see Section 3.4.1.1).

3.4.2.1 Exception: Binary output function

The binary output function has to be included in all sets of parameters and that is
why the function is automatically selected for all of them and the setting cannot be
changed by the user.

Figure 16 Parameter set assignment of BP outputs (fixed allocation)

Application Manual 29
Bay protection functions REB500
Section 3 1MRK 505 353-UEN
Configuring bay protection using HMI500

The configuration of the binary output function is basically the same as for the oth-
er protection functions. Open the configuration dialog by double clicking with the
left mouse button on the symbol or via the context menu.

The signals of the binary output function are divided into two groups for “De-
fault” and “General purpose” outputs.

Default

The default groups are signals which are exchanged between bay
and station protection functions (e.g. distance protection trip for
starting the breaker failure protection). The station protection input
signals (see Table 5) are all predefined and can’t be changed.
Choice of the bay protection output signals (“General Purpose”, see
Figure 18), on the other hand, is unrestricted.

Figure 17 BP output (Default)

The signals assigned under the default group do not reduce the
number of BP output channels (total of 120).

Location of ‘BP default’ output signals within the BP function di-


agram see Figure 1, Label No. 14.

30 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 3
Configuring bay protection using HMI500

General Purpose

The “General Purpose” tab provides facility for defining up to 120 output signals.

Figure 18 BP output (General purpose)

Location of “BP general purpose” output signals within the BP


function diagram see Figure 1, Label No. 12.

Edit (used for both “Default” and “General purpose” signals

Click on the respective “Edit” button to assign a “Default” or “General purpose”


signal. This opens the dialog “Select binary input”. The remaining procedure is the
same as described for binary input signals (see Section 3.4.1.4).

Only bay protection output signals that are configured to a BP


Output Channel can be assigned to an output relay of the bay unit
by selecting the menu “Configuration/ Binary module/ Outputs”.
Section 2.3.2.4 provides a list of available bay protection output
signals.

Location of Binary module’ output signals within the BP function


diagram see Figure 1, Label No. 13.

Application Manual 31
Bay protection functions REB500
Section 3 1MRK 505 353-UEN
Configuring bay protection using HMI500

3.4.3 Recording a binary signal as an event

Only bay protection binary signals can be configured to be recorded as events that
are also configured via menu “Configuration/ Binary module” (output signals do
not necessarily have to be assigned to output relays).

3.4.4 Disturbance recording of a binary signal

Binary output signals generated by bay protection functions can be configured for
disturbance recording, providing they are configured in the “General purpose” dia-
log for the binary output function (see Figure 18).

Binary input signals of the bay protection functions can be configured for disturb-
ance recording, providing they are configured in the “General purpose” dialog for
the binary input function (see Figure 14) and also as a binary input via the HMI500
menu “Configuration/Binary module/Inputs” menu.

3.5 Protection function settings

The appropriate dialog for setting a protection function is opened by double click-
ing the left mouse button on the respective symbol or via the context menu.

Figure 19 Protection function settings

The settings in the dialog for each protection function are described in detail in
Section 5.

32 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 4
System functions

Section 4 System functions

4.1 BP Function Monitoring

The BP function monitoring (measurement of primary system values) is made un-


der the “Operator mode”. The bay units licensed to include bay protection are listed
in the overview dialog. To view the measurements, select a bay unit and click on
the “Continue” button or more directly, simply double click on the desired bay unit
using the left mouse button. The “Select function” dialog with a list of bay protec-
tion functions and measurements available in the particular bay unit appears. Select
the desired function either by double clicking on it or selecting and clicking on the
'Open function' button.
The protection function measurement is automatically refreshed. Close the dialog
either by clicking on 'OK' or 'Cancel'.

Figure 20 Bay protection measurements

The primary system values are needed, for example, for checking
the measuring direction of the distance protection function while
commissioning the protection.

Application Manual 33
Bay protection functions REB500
Section 4 1MRK 505 353-UEN
System functions

4.2 BP Licenses

The menu “Configuration / BP Licences” provides an overview of licensed and


configured protection function groups for each bay unit is shown.

Figure 21 licensed BP function groups

4.3 CT grounding

The location at which the CT neutrals are grounded (line or busbar side) is of con-
sequence to directional protection functions (Distance protection DIST, Directional
overcurrent definite time protection DIROCDT and Directional overcurrent inverse
time protection DIROCINV).

The following table lists the functions with provision for configuring the location
of the CT neutral ground:

Table 43 CT grounding setting


Protection function Provision for configuring the CT ground?
Distance protection yes

Directional overcurrent definite time protection no

Directional overcurrent inverse time protection no

The default setting for the last two functions is busbar side, but if a Distance pro-
tection function has been configured, its setting (line or busbar side) applies for the
directional overcurrent functions as well.

34 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 5
Bay protection functions

Section 5 Bay protection functions

5.1 Application / Technical details

For detailed information about application and technical details of the bay protec-
tion functions refer to Users Guide REB500/ REB500sys 1MRB520292-Uen Sec-
tion 12 as follows:

Bay protection Function Section


Logic 12.15

Delay / integrator 12.16

DIST Distance protection 12.2

OCDT Definite time over and undercurrent protection 12.3

OCINV Inverse time overcurrent protection 12.4

DIROCDT Directional overcurrent definite time protection 12.5

DIROCINV Directional overcurrent inverse time protection 12.6

I0INV Inverse time earthfault overcurrent protection 12.7

OCINST Peak value over and undercurrent protection 12.17

OVDT Definite time over and undervoltage protection 12.8

CHKI3PH Three phase current plausibility 12.11

CHKU3PH Three phase voltage plausibility 12.12

Application Manual 35
Bay protection functions REB500
Section 5 1MRK 505 353-UEN
Bay protection functions

5.2 Technical additions

5.2.1 Voltage transformers for bay protection

The HMI500 “Settings/Voltage transformers/Overview” tab opens a dialog with


the list of all voltage transformers in the single-line diagram with their labels, bay
labels primary and secondary rated voltages.

In the “Details” view the description can be edited in the input field “Markings”.
The ratio is determined by the primary and secondary ratings entered in the “Trans-
former ratio” input field. The VT input is a single winding, which is suitable for all
the main VT secondary ratings, the effective voltage being set via HMI500 to ei-
ther 100 V or 200 V. Other voltages are accommodated by appropriately setting the
scaling factor.

This menu item appears only if voltage transformers have been fitted.

Figure 22 Settings/Voltage transformers

36 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 5
Bay protection functions

5.2.1.2 Star point setting for bay protection

If a REB500 bay unit includes bay protection functionality with 3-


phase voltage measurement, the mode of VT connection
“3Phase_Star” is mandatory.

Setting example for BP applications

• VT data:

UN primary = 220 kV / √3

UN secondary = 110 V / √3

Connection to REB500: 3 phases_star (mandatory connection)

• Settings made in HMI500

VT connection: 3 phases_star (mandatory setting)

Primary voltage: 220,000 V

Secondary voltage: 100 V

Scaling factor: 1.1

5.2.1.3 Scaling factor setting for bay protection

The scaling factor only applies to the voltage functions and not to
distance protection.

Application Manual 37
Bay protection functions REB500
Section 6 1MRK 505 353-UEN
BP-Additions to base documentation

Section 6 BP-Additions to base documentation

6.1 Technical Data

The following information about bay protection functionality applies in addition to


the Product Guide of REB500.

Table 44 Logic
Function/ Parameter Range/ Value Accuracy

· Logic for 4 binary inputs with the following 3 configurations: - -


1. OR gate
2. AND gate
3. Bistable flip-flop with 2 set and 2 reset inputs (both OR
gates), resetting takes priority
· 4 independent parameter sets
All configurations have an additional blocking input. Provision for inverting all inputs.

Table 45 Delay/ integrator


Function/ Parameter Range/ Value Accuracy

• Pick-up or reset time 0 to 300 s in steps of 0.01 s -

• Integration yes/no -

· For delaying pick-up or reset or for integrating 1 binary signal


· Provision for inverting the input
· 4 independent parameter sets

38 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 6
BP-Additions to base documentation

Table 46 Distance Protection 21 (PDIS)


Function/ Parameter Range/ Value

• Impedance measurement -300 to 300 W/ph in steps of 0.01 W/ph


• Zero-sequence current compensation 0 to 8 in steps of 0.01,
-180° to +90° in steps of 1°

• Mutual impedance for parallel circuit lines 0 to 8 in steps of 0.01,


-90° to +90° in steps of 1°

• Time step setting range 0 to 10 s in steps of 0.01 s

• Underimpedance starters -999 to 999 W/ph in steps of 0.1 W/ph

• Overcurrent starters 0.5 to 10 IN in steps of 0.01 IN

• Min. operating current 0.1 to 2 IN in steps of 0.01 IN

• Back-up overcurrent 0 to 10 IN in steps of 0.01 IN

• Neutral current criterion 0.1 to 2 IN in steps of 0.01 IN

• Neutral voltage criterion 0 to 2 UN in steps of 0.01 UN

• Low-voltage criterion for detecting, for example, a weak infeed 0 to 2 UN in steps of 0.01 UN

VT supervision
• NPS/neutral voltage criterion 0.01 to 0.5 UN in steps of 0.01 UN
• NPS/neutral current criterion 0.01 to 0.5 IN in steps of 0.01 IN

Operating times of the distance protection function (including tripping relay)


• minimum 20 ms
• typical 25 ms

(see also isochrones


• Figure 23)
Typical reset time 35 ms

VT-MCB auxiliary contact requirements


• Operation time <15 ms

· Five measuring stages with polygonal impedance characteristic forward and backward
· All values of settings referred to the secondaries, every zone can be set independently of the others
· 4 independent parameter sets

Accuracies Value

Amplitude error ±5% for U/UN >0.1

Phase error ±2° for U/UN >0.1

Applicable for current time constants between 40 and 150 ms

For details about distance protection operating times see Figure 23

Application Manual 39
Bay protection functions REB500
Section 6 1MRK 505 353-UEN
BP-Additions to base documentation

Figure 23 Distance protection operating times

40 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 6
BP-Additions to base documentation

Table 47 Definite time over and undercurrent protection 51 (PTOC/PTUC)


Function/ Parameter Range/ Value

• Pick-up current 0.2 to 20 IN in steps of 0.01 IN

• Delay 0.02 to 60 s in steps of 0.01 s

Reset ratio:
• overcurrent >94% (for max. function)
• undercurrent <106% (for min. function)

• Max. operating time without delay 60 ms

• Inrush restraint (optional):


• pick-up setting 0.1 I2h/I1h

· Over- and undercurrent detection


· Single or three-phase measurement with detection of the highest, respectively lowest phase current
· 2nd harmonic restraint for high inrush currents
· 4 independent parameter sets

Accuracies Value

Accuracy of the pick-up setting (at f N) ±5%

Table 48 Inverse time overcurrent protection 51 (PTOC)


Function/ Parameter Range/ Value

Inverse time characteristic t = k1 / ((I/IB)C - 1)


(acc. to B.S. 142, IEC 60255-3 with extended setting range):
• normal inverse • c = 0.02
• very inverse • c=1
• extremely inverse • c=2
• long time inverse • c=1

• or RXIDG characteristic t = 5.8 - 1.35 x·ln(I/IB)

• Number of phases 1 or 3

• Base current IB 0.04 to 2.5 IN in steps of 0.01 IN

Pick-up current Istart 1 to 4 IB in steps of 0.01 IB

Min. time setting tmin 0 to 10 s in steps of 0.1 s

k1 setting 0.01 to 200 s in steps of 0.01 s

· Single or three-phase measurement with detection of the highest phase current


· 4 independent parameter sets

Application Manual 41
Bay protection functions REB500
Section 6 1MRK 505 353-UEN
BP-Additions to base documentation

Table 49 Directional overcurrent definite time protection 67 (PTOC)


Function/ Parameter Range/ Value

• Current 0.02 to 20 IN in steps of 0.01 IN

• Angle -180° to +180° in steps of 15°

• Delay 0.02 to 60 s in steps of 0.01 s

• Wait time 0.02 to 20 s in steps of 0.01 s

• Memory duration 0.2 to 60 s in steps of 0.01 s

• Voltage input range 0.005 to 2 UN

• Voltage memory range <0.005 UN

• Response time without delay 65 ms

· Directional overcurrent protection with detection of power flow direction


· Back-up protection
· 4 independent parameter sets
· Three-phase measurement
· Suppression of DC and HF components
· Definite time characteristic
· Voltage memory for near faults
· Selectable response when power direction no longer valid (trip or block)

Accuracies Classes/ Value

• Accuracy of pick-up value ±5%

• Accuracy of angle measurement (at 0.97…1.03 fN) ±5°

• Reset ratio 95%

42 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 6
BP-Additions to base documentation

Table 50 Directional overcurrent inverse time protection 67 (PTOC)


Function/ Parameter Range/ Value

• Current 0.02 to 20 IN in steps of 0.01 IN

• Angle -180° to +180° in steps of 15°

Inverse time characteristic t = k1 / ((I/IB)C - 1)


(acc. to B.S. 142, IEC 60255-3 with extended setting range):
• normal inverse • c = 0.02
• very inverse • c=1
• extremely inverse • c=2
• long time inverse • c=1

• t-min 0 to 20 in steps of 0.01

• IB-value 0.04 to 2.5 IN in steps of 0.01 IN

• Wait time 0.02 to 20 s in steps of 0.01 s

• Memory duration 0.2 to 60 s in steps of 0.01 s

• Voltage input range 0.005 to 2 UN

• Voltage memory range <0.005 UN

• Response time without delay 60 ms

· Directional overcurrent protection with detection of power flow direction


· Back-up protection
· 4 independent parameter sets
· Three-phase measurement
· Suppression of DC and HF components
· Inverse time characteristic
· Voltage memory for near faults
· Selectable response when power direction no longer valid (trip or block)

Application Manual 43
Bay protection functions REB500
Section 6 1MRK 505 353-UEN
BP-Additions to base documentation

Table 51 Inverse time earthfault overcurrent protection 51N (PTOC)


Function/ Parameter Range/ Value

Inverse time characteristic t = k1 / ((I/IB)C - 1)


(acc. to B.S. 142, IEC 60255-3 with extended setting range):
• normal inverse • c = 0.02
• very inverse • c=1
• extremely inverse • c=2
• long time inverse • c=1

• or RXIDG characteristic t = 5.8 - 1.35 x·ln(I/IB)

• Number of phases 1 or 3

• Base current IB 0.04 to 2.5 IN in steps of 0.01 IN

• Pick-up current Istart 1 to 4 IB in steps of 0.01 IB

• Min. time setting tmin 0 to 10 s in steps of 0.1 s

• k1 setting 0.01 to 200 s in steps of 0.01 s

• Response time without delay 60 ms

· Neutral current measurement (derived externally or internally)


· 4 independent parameter sets

Table 52 Peak value over and undercurrent protection 50 (PTOC/PTUC)


Function/ Parameter Range/ Value

• Current 0.1 to 20 IN in steps of 0.1 IN

• Delay 0 to 60 s in steps of 0.01s

• Max. trip time with no delay (at f N) for max. function £30 ms
• Max. trip time with no delay (at f N) for min. function £60 ms

· Maximum or minimum function (over- and undercurrent)


· Single or three-phase measurements
· Wide frequency range (0.04 to 1.2 f N)
· Peak value evaluation

Accuracies Value

Accuracy of the pick-up value (at 0.2 to 1.1 f N) ±5%

• Reset ratio for max. function • >90%


• Reset ratio for min. function • <110%

44 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 6
BP-Additions to base documentation

Table 53 Definite time over and undervoltage protection 59/27 (PTUV/PTOV)


Function/ Parameter Range/ Value

• Pick-up voltage 0.01 to 2.0 UN in steps of 0.01 UN

• Delay 0.02 to 60 s in steps of 0.01 s

• Max. operating time without delay 60 ms

· Over- and undervoltage detection


· Single or three-phase measurement with detection of the highest, respectively lowest phase voltage
· 4 independent parameter sets

Accuracies Value

Accuracy of the pick-up setting (at f N) ±2% or ±0.005 UN

• Reset ratio (U ³ 0.1 UN) •


• overvoltage • >95%
• undervoltage • <106

Table 54 Three phase current plausibility 46 (PTOC)


Function/ Parameter Range/ Value

• Pick-up differential for sum of internal summation current 0.05 to 1.00 IN in steps of 0.05 IN

• Amplitude compensation for summation CT -2.00 to +2.00 in steps of 0.01

• Delay 0.1 to 60 s in steps of 0.1 s

· Determination of the sum and phase sequence of the 3 phase currents


· 4 independent parameter sets

Accuracies Value

Accuracy of the pick-up setting at rated frequency ±2% IN in the range 0.2 to 1.2 IN

• Reset ratio ³90% whole range

Table 55 Three phase voltage plausibility 47 (PTUV)


Function/ Parameter Range/ Value

• Pick-up differential for sum of internal summation voltage 0.05 to 1.2 UN in steps of 0.05 UN

• Amplitude compensation for summation VT -2.00 to +2.00 in steps of 0.01

• Delay 0.1 to 60 s in steps of 0.1 s

· Determination of the sum and phase sequence of the 3 phase voltages


· 4 independent parameter sets

Accuracies Value

Accuracy of the pick-up setting at rated frequency ±2% UN in the range 0.2 to 1.2 UN

• Reset ratio >95% (at U > 0.1 UN or I > 0.1 IN)

Application Manual 45
Bay protection functions REB500
Section 6 1MRK 505 353-UEN
BP-Additions to base documentation

6.2 Operation and maintenance

The following information about bay protection functionality applies in addition to


the Operation Manual of REB500.

6.2.1 Maintenance of bay protection functions

Before checking the bay protection functions, consider the possible effect of, for
example, secondary injection on other protection functions such as the busbar and
breaker failure protection functions.

Where there is doubt, block the station protection functions by ap-


plying the input signal “31205_Block SP” to the central unit.

6.2.2 Protection blocking

This section lists the indications and signals which occur when the bay protection
is blocked.

Table 56 BP blocked, central unit and bay units


HMI text LEDs Event
BP blocked Green lit, yellow CU: “49405_BP blocked” active
flashes until button BU: “29405_BP blocked” active
on the local HMI
pressed

6.2.3 Protection tripping

This section lists the indications and signals which occur when the bay protection
trips.

Table 57 BP tripped, central unit


HMI text LEDs Event
Date Time Green lit, CU: None
DIST trip red lit
Feeder name
Date Time Green lit, CU: None
OCTD trip red lit
Feeder name
Date Time Green lit, CU None
OCINV trip red lit
Feeder name
Date Time Green lit, CU: None
I0INV trip red lit
Feeder name
Date Time Green lit, CU: None

46 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 6
BP-Additions to base documentation

HMI text LEDs Event


OVSTD trip red lit
Feeder name
Date Time Green lit, CU: None
DIROCDT trip red lit
Feeder name
Date Time Green lit, CU: None
DIROCINV trip red lit
Feeder name
Date Time Green lit, CU: None
OCINST trip red lit
Feeder name

Table 58 BP tripped, bay unit


HMI text LEDs Event
Date Time Green lit, BU: 2111xx_DIST TRIP CB Ly
DIST trip red lit
Feeder name
Date Time Green lit, BU: 212105_OCDT TRIP
OCDT trip red lit
Feeder name
Date Time Green lit, BU: 213105_OCINV TRIP
OCINV trip red lit
Feeder name
Date Time Green lit, BU: 221105_I0INV TRIP
I0INV trip red lit
Feeder name
Date Time Green lit, BU: 216105_OVSTD TRIP
OVSTD trip red lit
Feeder name
Date Time Green lit, BU: 214105_DIROCDT TRIP
DIROCDT trip red lit
Feeder name
Date Time Green lit, BU: 215305_DIROCINV TRIP
DIROCINV trip red lit
Feeder name
Date Time Green lit, BU: 226105_ OCINST TRIP
OCINST trip red lit
Feeder name
Date Time Green lit, BU: 224605_CHKI3PH Picked up
CHKI3PH trip red lit
Feeder name
Date Time Green lit, BU: 225605_CHKU3PH Picked up
CHKU3PH trip red lit
Feeder name

Application Manual 47
Bay protection functions REB500
Section 6 1MRK 505 353-UEN
BP-Additions to base documentation

6.3 Commissioning

The following information about bay protection functionality applies in addition to


the Commissioning Manual of REB500.

6.3.1 Regulations

DANGER: Note that when commissioning REB500 the analogue


input signals act on the bay protection functions as well as the sta-
tion functions. Especially when the commissioning subsequently
(e.g. following additions to the system), care must be taken to pre-
vent part of the system which are already in operation from mal-
operating. Corresponding precautions must be taken (interrupting
tripping circuits, blocking system functions, disabling auxiliary
tripping relays).

6.3.2 Additional checks for bay protection REB500

The following checks described below are necessary to commission the bay protec-
tion function (in addition to the function test of REB500 station protection).

6.3.2.1 Commissioning a new station without any HV

When commissioning a new station or a station, which is not energized, the busbar
and breaker failure protection functions and the bay protection functions (line pro-
tection) can be commissioned separately, although certain tests do overlap and
should be coordinated to save time.

Note also that, for example, injecting current in the analog input of one feeder can
trip other feeders via the intertripping logic. This can, however, be prevented by
taking the appropriate precautions (interrupting tripping circuits, blocking station
protection functions or blocking tripping relays).

48 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 6
BP-Additions to base documentation

6.3.2.2 Additions to an existing station

When adding bay protection to an existing station more checks have to be carried
out than is the case of a REB500 with only station protection. To avoid any risk of
the station protection functions (BBP, BFP and EFP) being affected and possibly
mal operating when performing the additional checks, the following procedure is
recommended. The basic philosophy is to check the bay unit on its own first (with-
out the rest of the REB500 system). This is done in the stand-alone bay unit mode
and requires that the setfile be loaded in the bay unit to be extended beforehand as
follows:

Step 1

Interrupt the optical fiber link between the central unit and the by unit to be com-
missioned.

Step 2

Switch on the auxiliary supply to the new bay unit.

Step 3

Appropriately update the setfile of the REB500 in question to include the new bay
unit (activate the feeder) and download it to the new bay unit. The setfile must
include all the settings needed for the new bay unit.

Step 4 (Check of the analogue inputs)

Refer to REB500 Commissioning Manual Sections “Checking the analog inputs


(CTs)” and “Checking the analog inputs (VTs)”.

Measuring the start values of BP functions (e.g. distance protection function) is un-
necessary, because they are fully processed by the software and any error would be
detected by the self-supervision function. However, it is normal to measure the re-
actances of the various distance measuring zones. This may be omitted if a suitable
test set is not available.

Step 5 (Check the binary inputs and outputs)

Refer to REB500 Commissioning Manual Sections “Checking the binary input sig-
nals”, “Checking the aux. contacts of isolators and circuit breakers” and “Checking
the binary output signals”.

Step 6

Block the REB500 system (e.g. using “Block output relays” on the central unit).

Application Manual 49
Bay protection functions REB500
Section 6 1MRK 505 353-UEN
BP-Additions to base documentation

Step 7

Download the updated setfile to the central unit.

This requires that the PC running HMI500 be connected either directly to the cen-
tral unit or a bay unit, which is already operational.

WARNING: On no account connect the optical fiber link to the


new bay unit before the setfile has been successfully downloaded to
the central unit.

Step 8

• Switch off the bay unit


• Connect the optical fiber cable going to the central unit
• Switch on the bay unit

Step 9

Perform the busbar protection through-fault stability check (Refer to REB500


Commissioning Manual Sections “Checking protection stability”)

Step 10

Check the direction of the distance protection function with load current. This is
achieved by measuring real and apparent power in L1 phase.

The real and apparent power measurements of all the directional functions can be
viewed by selecting the HMI500 menu “View/BP function monitoring”. The di-
rection “Forwards” or “Backwards” is also displayed for both real and apparent
power as soon as a valid measurement has been made.

The display is influenced by the setting ‘CT Neutral’ “Line side/Busbar side” for
the distance protection function. The default setting of ‘CT Neutral’ for the dis-
tance protection function is CTs grounded on the busbar side.

Note the following with respect to busbar protection:

The side on which the CTs are grounded is of no consequence for the busbar pro-
tection and does not therefore have a setting. What is important, however, is that
the grounding of all the CTs on the busbars is the same (and have the same winding
sense), otherwise the differential current will not be correct.

Where this is not the case, the connections to the corresponding CT inputs on the
respective bay units must be reversed (current phase-angle rotated by 180°).

In the feeders in which the current direction has been rotated in the bay unit by
180°, the setting parameter 'CT Neutral' of the distance function must also be re-
spectively corrected to correspond to actual earthing direction of the CT.

50 Application Manual
Bay protection functions REB500
1MRK 505 353-UEN Section 6
BP-Additions to base documentation

Step 11

Restore REB500 to normal operation.

6.4 Communication

The Communication Protocol Manuals describe the communication protocols sup-


ported by the IED with a focus on vendor-specific implementations.

The communication signal engineering extends the basic signal engineering of BP


described in the present Application Manual. The cross reference list (see Table
59) reflects the relationship between the Application Manual for BP and the rele-
vant sections of the Communication Protocol Manuals.

Table 59 Cross references


Item Topic see present Application Manual for BP Communication Protocol Manual / Section

1 Logical output signals Figure 1 à Item No. 5 IEC61850 / Bay protection specific signals

2 Configuring binary output signals Section 3.4.2 IEC61850 / Bay protection specific signals

Application Manual 51
Bay protection functions REB500
Contact us

1MRK 505 353-UEN A © Copyright 2016 ABB, All rights reserved.


ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation

Potrebbero piacerti anche