Sei sulla pagina 1di 2

ES-SS07F

For Fire Protection Applications


Job Name Contractor Approval

Job Location Engineer Approval

Contractors P.O. No. Representative

Series SS07F
Stainless Steel Single Detector Check Valves
Sizes: 4" 10" (100 250mm)
Series SS07F Stainless Steel Single Detector Check Valves are designed to detect any leakage or unauthorized use of water from fire sprinkler systems. During times of minimal water flow, the valve clapper remains closed so that the water flows through a bypass meter (optional). When fire flow is required, the increased demand will open the clapper to allow full flow.
SS07F 4", 6"

Features
Lightest weight in the industry reduces shipping and handling costs Non-corrosive stainless steel construction eliminates pin holes and voids associated with epoxy coated valves Can be installed in horizontal/vertical positions Optional meter bypass assembly (specify GPM or CFM). Required to detect leakage or theft of water Optional sized bypass tappings available
SS07F 8", 10"

Standards
Flange bolt pattern and hole diameter in accordance with ANSI B16.5 Class 125/AWWA C207 Class D. Body nameplate provides nominal size, direction of flow, psi rating, year of manufacture and approval marks.

Specifications
The valve body shall be formed, welded units, in 300 series stainless steel. The valve shall be hydrostatically tested in excess of 700psi. Valve construction shall eliminate any possibility of defects such as sand pits and blow holes which may occur in casting. All linkage parts shall be stainless steel. Each valve shall be individually tested before shipping. All 8" and 10" valve sizes shall be equipped with lifting lugs. Valve shall be Watts Regulator Company Series SS07F.

Approvals

(8" & 10" sizes only)

Materials
Body: 300 Series stainless steel Linkage Parts: stainless steel
IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES FOR LOCAL INSTALLATION REQUIREMENTS

Pressure Temperature
Maximum Working Pressure: 175psi (12.06 bar) Temperature Range: 33F-110F (5C-43C)

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

Capacities
*Head loss at the UL rated flow

kPa psi 69 10 55 Pressure Loss 41 28 14 0 8

4" (100mm)

kPa psi 69 10 55 Pressure Loss 41 28 14 0 8 6 4 2 0 0 0 500 1900

6" (150mm)

6 4 2 0 0 0 200 760 400 1520 600 2280 Flow Rate 800 3040 1000 3800 1200 gpm 4560 lpm

1000 3800 Flow Rate

1500 5700

2000 gpm 7600 lpm

kPa psi 69 10 55 Pressure Loss 41 28 14 0 8

8" (200mm)

kPa psi 69 10 55 Pressure Loss 41 28 14 0 8 6 4 2 0 0 0 1000 3800

10" (250mm)

6 4 2 0 0 0 500 1900 1000 3800 1500 2000 5700 7600 Flow Rate 2500 9500 3000 gpm 11400 lpm

2000 7600

3000 11400

4000 15200

5000 gpm 19000 lpm

Flow Rate

Dimensions Weights
Sizes: 4", 6" E T K B D B D E L S L S K R Sizes: 8", 10" T R

SIZE (DN)

DIMENSIONS

WEIGHTS

B
in. mm in. mm in.

D
mm in.

E
mm

K (NPT)
in.
1 2 3 4

L
in. mm in.

R
mm in.

S
mm in.
5 8 11 16

T
mm

less Bypass
lb. kg.

with Bypass
lb. kg.

mm

4" 6" 8" 10"

100 150 200 250

111/2 131/2 151/2 171/2

292 343 394 445

41/2 51/2 63/4 8

114 127/8 140 17 171 211/4 203 281/4

327 432 540 718

/ / 2 2

13 19 51 51

161/2 221/2 261/2 36

419 572 673 914

8 101/2 121/4 141/2

203 9 267 11 311 131/2 368 16

229 279 343 406

/ / 11/16 11/16

16 17 17 17

30 65 143 163

13.6 29.5 64.9 73.9

35 70 153 173

15.9 31.8 69.3 78.5

Backflow Prevention Products

USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca Watts, 2008

ES-SS07F 0830