Single and Dual Duct

VAV Controllers
VAV Series

Description
The VAV Series of controllers are an easy and
unique approach to operating a wide variety of VAV
terminal units. The integrated actuators, internal

programs make these BACnet Application

installations.

Easy to install Just mount the controller, wire it

and temperature sensors. A VAV controller


automatically detects sensors as they are connected

Simple, menu driven setup The controllers feature


simple, menu driven setup choices. No special

to choose applications, enter setpoints, set network Specifications


Inputs and outputs
be set by using only an VAV-CO sensor which All inputs and outputs for VAV Series controllers
can be installed as the permanent room sensor or
temporarily connected as a technician’s service tool. programming.
Inputs
The VAV Series of
Sensors are automatically detected
controllers are ideal for new installations or
Inputs accept industry-standard 10K ohm
thermistors sensors.
Input overvoltage protection up to 24 volts AC,
reheat continuous.
Series or parallel fan control 12-bit analog-to-digital conversion
Single or dual duct application

Native BACnet All models are BACnet Application Triac outputs


Optically isolated triac output.
BACnet MS/TP network. Device instance, MAC Maximum switching 24 volts AC at 1.0 ampere
address, and baud rate are set from an VAV-CO for each output
Maximum for controller is 3.0 amperes.

Easy system integration For VAV controller Analog outputs


installations that are part of a BACnet building Short-circuit protected
automation system, the controllers provide system Output voltage 0–10 volts DC
diagnostic indicators. Through the MS/TP network, 30 mA per output, 30 mA total for all analog
the controllers signal demands for higher static duct outputs
pressure, cooler or warmer supply air, and when to 12–bit analog–to–digital conversion
start air handler units.

Specifications and design subject to change without notice.


Specifications
Air flow sensor features Operating Sequences
The following VAV Series models are supplied with
(0-500 Pa) measurement range. Internally linearized factory included programs.
and temperature compensated. VAV-CO
Model VAV-CO is supplied with inputs, outputs,
Span accuracy 4.5% of reading. and sequences of operation for the following
Zero point accuracy 0.0008 in. H2O/0.2 Pa at functions.
25° C Single duct heating and cooling VAV
Barbed connections for 1/4 inch FR tubing. Automatic heating/cooling changeover including
Actuator features morning warmup
All models of VAV Series controllers include an Occupancy setback—requires VAV-STAT-MO
integrated actuator. System diagnostic indicators
Torque 40 in-lb. (4.5 N•m)
Angular Rotation 0 to 95° VAV-FPR and VAV-DPF
Adjustable end stops Models VAV-FPR and VAV-DPF are supplied with
at 45 and 60° rotation inputs, outputs, and sequences of operation for the
Motor Timing following functions.
VAV-CO 90 sec./90°at 60 Hz Single duct heating and cooling VAV
VAV-FPR and 108 sec./90° at 50 Hz
VAV-DDP staged reheat
Series and parallel fan control
VAV-DPF 60 sec./90°at 60 Hz
Automatic heating/cooling changeover including
Shaft size morning warmup
Directly mounts on 3/8 to 5/8 inch (9.5 to 16 mm) Discharge air temperature limiting
round or 3/8 to 7/16 inch (9.5 to 11 mm) square Occupancy setback—requires VAV-STAT-MO
Actuator position feedback for true damper
positioning (VAV-DPF only)
System diagnostic indicators
6.53 in.
166 mm 4.89 in.
124 mm

ON CTS
VAV-DDP
1 2
Model VAV-DDP is supplied with inputs, outputs,
and sequences of operation for the following
functions.
4.25 in.
108 mm Dual-duct VAV heating and cooling
Occupancy setback—requires VAV-STAT-MO
System diagnostic indicators

Uses VAV-TPS-DDS for secondary damper control


0.77 in.
19 mm
BACnet communication
6.00 in.
Integrated peer-to-peer BACnet MS/TP network
152 mm
communications.
Network speed from 9600 to 76,800 baud
2.14 in.
54 mm
Meets or exceeds ANSI/ASHRAE BACnet
1.92 in.
49 mm Controllers.
Installation Accessories
Supply voltage 24 volts AC (–15%, +20%), Airflow sensors
50-60 Hz, 5 VA,
Class 2 only
Weight 13.2 ounces (376 grams) tubing adaptor is required. Each kit includes 6’ of
Case material plastic tucing.
retardant plastic
Environmental limits VAV-KIT-04 Velocity sensor probe for 4” duct
Operating 32 to 120° F (0 to 49° C) VAV-KIT-06 Velocity sensor probe for 6” duct
Shipping –40 to 140° F (–40 to 60° C) VAV-KIT-08 Velocity sensor probe for 8” duct
Humidity 0-95% relative humidity VAV-KIT-10 Velocity sensor probe for 10” duct
(non-condensing)
Regulatory VAV digital sensors
UL 916 Energy Management Equipment VAV-STAT VAV sensor and digital display
BACnet Testing Laboratory listed as Application
VAV-STAT VAV sensor and digital display
CE compliant with motion sensor
SASO PCP Registration KSA R-103263
FCC Class B, Part 15, Subpart B and complies VAV discrete temperature sensors
with Canadian ICES-003 Class B VAV-SEN Temperature sensor with RJ-45
connector
VAV-SEN-SP Temperature sensor with rotary
This device complies with part 15 of the FCC Rules.
setpoint dial, RJ-45 connector
Operation is subject to the following two conditions:
VAV-SEN-SP-O Temperature sensor with rotary
(1) This device may not cause harmful interference,
and (2) this device must accept any interference
RJ-45 connector
received, including interference that may cause
undesired operation.
Dual duct actuator
VAV-TSP-DDS
(required for dual duct)

Ordering information
Model description Model number
BACnet ASC: VAV Cooling/Heating, 40 in-lbs, 90 sec actuator VAV-CO

BACnet ASC: VAV Fan and Reheat, 40 in-lbs, 90 sec actuator VAV-FPR

BACnet ASC: VAV Dual Duct, 40 in-lbs, 90 sec actuator VAV-DDP

BACnet ASC: VAV Fan and Reheat, Position, 40 in-lbs, 60 sec actuator VAV-DPF
Controller selection guide

Single duct heating

90 second rotation

60 second rotation
Time proportional
Dual duct heating

True damper
DAT limiting

1,2,3 staged
and cooling

and cooling

Modulating

positioning
Floating

Parallel
reheat

reheat

reheat

reheat

Series
fan

fan
Models
VAV-CO

VAV-FPR

VAV-DDP

JSVAV-DPF

Sensor selection guide


For sensor details see the data sheet for each sensor model.

Configuration
Setpoint dial
Temperature

Balancing
Override

Setpoint
buttons

Motion

display
Digital
button
sensor

sensor

tool

tool
Model
VAV-STAT

VAV-STAT-MO

VAV-SEN

VAV-SEN-SP

VAV-SEN-SP-O

Jackson Systems
5418 Elmwood Avenue
Indianapolis, IN 46203
888.652.9663
www.jacksonsystems.com
info@jacksonsystems.com
© 2014 Jackson Systems. LLC 08-1105-080814