MITIGATING CONDENSATION

WITHIN ENCLOSURES
preventing damage and ensuring OPTIMAL LIFE FOR ENCLOSED ELECTRICAL
AND ELECTRONIC EQUIPMENT
Electrical and electronic equipment, as well as components, are typically housed in an
electrical enclosure designed to provide protection from the external environment.
However, even with a sealed enclosure the introduction of moisture and water can
result from a variety of circumstances. Once inside the enclosure, this water can
accumulate—from small droplets on the components themselves to large puddles in
the base of the enclosure. To address this concern, users employ a variety of methods
intended to eliminate condensation and remove moisture. Yet, even small amounts of
remaining moisture and liquid can result in costly damage to components, shorten the While some enclosures are specifically
built to protect against washdown, high-
expected life cycle and affect overall component performance. In order to better protect
pressure spray may penetrate around
components from condensation, a new, all-encompassing solution is needed—one that sealed components and gaskets in many
is effective, inexpensive and can be used in almost any industry. enclosures.

History dangerous occurrences of arcing and In wet or humid applications and


Condensation results when moist air is sparking. In order to ensure optimal life environments, moisture enters an
cooled or comes into contact with a cool expectancy of components, companies enclosure when the enclosure’s door is
surface that is at or below its saturation should take several precautions to help opened for service or maintenance
point, also called its dew point. At this prevent these harmful conditions. purposes. Since internal components
temperature air can no longer hold all the generate heat within the enclosure, the
moisture, and water vapor condenses into Challenge warmed air inside can hold even more
moisture droplets on available surfaces. Although complete condensation moisture. When the enclosure surfaces
When temperatures are below freezing, prevention is ideal, the circumstances cool to the dew point as a result of
the water vapor condenses into frost. that lead to its incidence are difficult to shutdown, lower evening temperatures or
avoid. Condensation can stem from lower outside air temperatures caused by
Various problems result when conden- numerous sources in many environments a cool rain and other circumstances,
sation forms on sensitive electrical and and applications. For example, in indoor condensation forms. Large temperature
electronic devices inside an enclosure. washdown applications, it is possible for variations between the inside and outside
Corrosion is one of the inherent troubles high-pressure spray with soap lubricants of the enclosure can also result in
of moisture because it causes increased to penetrate around sealed components pressure differences that may create a
electrical resistance, which in turn and gaskets. Plus, in cases where conduit vacuum and draw water through the
generates additional heat and contributes or pipe fittings aren’t sealed properly, fittings and/or component and gasket
to decreased and inconsistent component condensation may form in the pipe or seals. The best way to combat these
performance. In addition, corrosion can conduit and drain directly into the harmful occurrences is by using a device
lead to rusting of critical electrical enclosure. Even with best practices— to rid both the enclosure and the housed
components, increasing the risk of leaks happen. components of condensation. Finding an
circuits shorting out, as well as effective yet affordable solution, however,
has proved problematic.

EQUIPMENT PROTECTION MitigatING ENCLOSURE Condensation white paper


MITIGATING CONDENSATION WITHIN ENCLOSURES

Previous Solutions— heat sensitive components. Another Enclosure Ratings


and Shortcomings partial solution involves utilizing fans to The National Electrical Manufacturers
Several methods have been employed to increase airflow, which makes it more Association (NEMA), Underwriters
prevent harmful corrosion on enclosure difficult for condensation to form on Laboratories Inc. (UL) and Canadian
walls and equipment. While some surfaces. Yet even with this method, if Standards Association (CSA) are
methods are low-cost and low-tech, the temperature reaches dew point, standard-writing organizations commonly
others are extremely sophisticated and condensation will form in locations recognized in North America. Their
costly. Equipment operators may where air movement is minimal. ratings are based on similar application
attempt to rid enclosures of moisture by descriptions and expected performance.
simply wiping them down with towels. The use of hazardous location-style
However, in addition to being drains and breathers provide the UL and CSA require enclosure testing by
inconvenient, this method is usually only functionalities of draining and pressure qualified evaluators. They also send site
partially effective. Operators often wipe equalization, but these devices are simply inspectors to ensure that manufacturers
standing water from the bottom of an certified for hazardous location adhere to prescribed manufacturing
enclosure but not from the sensitive requirements, which are not the same as methods and material specifications.
components themselves. UL 508A and CSA 22.3 enclosure NEMA does not require independent
standards. They typically will not pass a testing and leaves compliance entirely
When water pooling in the enclosure Type 4 water hose down test, designed to up to the manufacturer.
bottom occurs, some users drill a small ensure that water will be kept out of an
hole in the bottom of the enclosure and enclosure. Plus, these drains and However, keep in mind that an enclosure
mount the enclosure at a slant to direct breathers do not address the problem of rating can only be as high as the ratings
water towards the opening. While this condensation on components and related of its enclosed components. This makes
method can be an effective way to drain performance and corrosion issues. it critical to ensure both the enclosure
the enclosure, it doesn’t address the and components are properly rated for
issue of moisture on the components Air conditioners or Vortex coolers can be the application requirements.
themselves, and it allows humid air and employed to maintain temperatures
water to re-enter through the very holes within a specified range, as well as
that were created to rid the enclosure of remove moisture from the inside of the
water—creating a continuous cycle of enclosure. Due to physical A/C sizes and
condensation. Even more importantly, filter maintenance requirements or the
any holes in an enclosure not filled with requirement of obtaining compressed air
an appropriately rated device, which is for a Vortex cooler, these solutions are
approved by applicable UL or CSA often impractical and cost-prohibitive for
standards, negate the enclosure’s NEMA many enclosure applications. In a
Type ratings. situation where there is a lot of moisture
in an enclosure and the A/C or Vortex
Other lower cost methods work on the cooler drops the temperature rapidly—
principle of maintaining the internal possibly to the dew point or below before
temperature above the dew point switching off—condensation of
temperature to prevent air within the remaining moisture on the internal
enclosure from reaching its dew point. components and enclosure walls is
Examples include light bulbs and possible. The same is true of heating
An electronic moisture removal device
heaters, which can also employ and cooling device combinations used in within the enclosure can be utilized to
thermostat or humidity controls for applications with varying temperature remove water vapor from the internal
more sophisticated monitoring. Still, ranges, such as those subject to a wide enclosure air, preventing condensation
range of temperature extremes or from forming on the enclosure walls and
higher temperatures allow more components.
moisture in the air inside the enclosure seasonal climate changes.
To rid enclosures of pooled water, a one-way
and may cause detrimental effects to drain is needed that is properly rated for the
enclosure. The device should be designed
to allow water to drain out, while preventing
water and contaminants from reentering
from the outside.

MitigatING ENCLOSURE Condensation white paper 2


MITIGATING CONDENSATION WITHIN ENCLOSURES

Finally, a purge system that uses steel. Non-metallic vent drains provide a
pressurized dry air to maintain positive cost-effective and corrosion-resistant
pressure on the inside of an enclosure certified solution for removing liquids
prevents external moisture and dust that can be used on mild steel,
from entering the enclosure, helps to aluminum, non-metallic and even some
reduce moisture within the enclosure stainless steel enclosures. For stainless
itself and keeps components on the steel applications, including outdoor,
inside of the enclosure dry. The supply of food, beverage, water and petroleum,
dry air required by these units, however, the 304 stainless steel vent drain
can be expensive and difficult to acquire. provides the aesthetics and performance
Although this method helps prevent The versatile H2OMIT Vent Drain is available that these applications require.
condensation, it is a costly solution and in corrosion-resistant non-metallic material
may not be a practical option for many or encased in 304 stainless steel. For retrofit applications of enclosures
applications—leaving a demand for a already installed, the UL- and CSA-
new, affordable and effective A Comprehensive Solution from certified 508 Type 4/4X vent drain is easily
condensation solution. Hoffman: H2OMIT™ Condensation installed by drilling a hole in the enclosure
Solution System bottom or screwing directly into a ½-inch
A Solution that Works conduit hub. The thermoelectric
Hoffman’s H2OMIT™ Condensation
A comprehensive solution is needed to dehumidifier can be installed on an
Solution System utilizes two components
ensure that water will be removed from interior back or side panel if space is
to assure reliable performance and
the enclosure, while still maintaining the available. Otherwise, this device is
realize the capabilities previously
enclosure’s integrity and environmental designed so that it can be installed on the
described. The vent drain device functions
Type rating. A drainage device that enclosure bottom, directly above a vent
to equalize pressure and reduce the
equalizes pressure and allows accum- drain, so it doesn’t require panel space.
harmful effects of a temperatureinduced
ulated water to drain out, while preventing vacuum—that could pull water and
water and contaminants from re-entering The thermolelectric dehumidifier
moisture into the enclosure—in addition
and maintaining UL and CSA enclosure combined with the UL- and CSA-rated
to providing a one way drain. As
certification, delivers this solution. vent drain provide a comprehensive
condensation accumulates and pools, it
protection solution, effectively and
exits the enclosure and vent drain by the
With the certified drain, humid air can cost-efficiently combating damage to
force of gravity. From the outside, water
still enter the enclosure when the door is electrical and electronic parts due to
and contaminants are blocked from entry
open. However, when used in combination condensation and ensuring maximum
with a mechanical shut-off.
with an internal moisture-removing life expectancy and performance of
device, a total system solution is internal components.
By incorporating Hoffman’s thermoelectric
achieved—one that provides a continuous dehumidifier, water vapor can be removed
method of protection for the components (pulled out) of the internal enclosure air.
and enclosure. This system solution This process affords users a way to
removes internal enclosure moisture, continuously remove and dry internal
controls condensation, reduces corrosion, enclosure air, and in doing so, control
drains pooled liquid and helps maintain condensation on components and
optimal internal component expected life enclosure walls. This moisture is then
and performance. collected and directed to the vent drain
device for expulsion from the enclosure.

The vent drain, which is approximately


2-inches long and 1¼-inches in
diameter, is available in corrosion- The H2OMIT Thermolelectric Dehumidifier
resistant non-metallic polyester and Vent Drain work to remove water vapor
material or encased in 304 stainless from the air and rid it from the enclosure
for a comprehensive moisture removal and
elimination solution.