Room Air Conditioner


SERVICE MANUAL

CAUTION
-BEFORE SERVICING THE UNIT, READ THE SAFETY
PRECAUTIONS IN THIS MANUAL.
-ONLY FOR AUTHORIZED SERVICE PERSONNEL.

MODEL : LS-Q076ABL/BBG/BEL/ABG
LS-Q096ABL/BBG/BEL/AEL
LS-Q096ACG/ADG/ADL/BDL
LS-Q096AHG/ABG/ABM/AEM
LS-Q096BAG/BDG
LS-Q096ACL/AAG
LS-Q082BAG/BAM
LS-Q082AAL/ACG/ACL/ACM
LS-H096QNA0
LS-Q096BEG
LS-C082QMA0/QNA0
LS-C096QLA0/QNA0
LS-C096QGL0
LS-H096QGL1
Contents

Details of LG Model Name(2002) .......................................................................................... 3

Details of LG Model Name(2003) .......................................................................................... 4

Functions ................................................................................................................................ 5

Product References .............................................................................................................. 8

Dimensions ........................................................................................................................... 10

Refrigeration Cycle Diagram ............................................................................................... 13

Wiring Diagram..................................................................................................................... 14

Operation Details ................................................................................................................. 15

Display Function .................................................................................................................. 22

Self-diagnosis Function....................................................................................................... 22

Installation ............................................................................................................................ 23

Operation .............................................................................................................................. 34

Disassembly of the parts (Indoor Unit) .............................................................................. 36

2-way, 3-way Valve................................................................................................................ 39

Cycle Troubleshooting Guide.............................................................................................. 46

Electronic Parts Troubleshooting Guide............................................................................ 47

Electronic Control Device.................................................................................................... 54

Schematic Diagram .............................................................................................................. 59

Exploded View and Replacement Parts List...................................................................... 64

-2-
Details of LG Model Name(2002)

1 2 - 3 4 5 6 7 8 9

Code Type Code of Model Meaning

1,2 Type of Airconditioner A~Z LS: LG Split Type Airconditioner

3 Chassis A~Z Name of toll of Unit


Ex. LS-R ➔ S R Chassis
4,5 Capacity(Btu/h) 1~9 Cooling/Heating Capacity
Ex. "09" ➔ 9,000Btu/h

6 Electric Range 1~9 Electric Standard


1 ➔ 115V/60Hz 6 ➔ 220~240V/50Hz
2 ➔ 220V/60Hz 7 ➔ 110V, 50/60Hz
3 ➔ 208~230V/60Hz 8 ➔ 380~415V/50Hz
5 ➔ 200~220V/50Hz 9 ➔ 380~415V/60Hz

7 Serial No. 0~9 Basic A 0


A~Z Plasma Filter B 1
Auto Swing + Plasma Filter C 2
Telephone + LED Display D 3
Telephone + LCD Display E 4
Auto Swing + Plasma Filter + Telephone + LCD F 5
Low Ambient + Ambient/change G 6
Plasma Filter + Low Ambient + Ambient/change H 7
Internet J 8
Auto Swing + Plasma Filter + Oxygen Generator K 9
Auto Swing + Soft Start L Z
Auto Swing + Star Rating M Y
Auto Swing + Star Rating + Plasma Filter N X
Auto Swing + Soft Start + Star Rating P W
Auto Swing + Soft Start + Star Rating 4 + Plasma Q V
Auto Swing + Telephone + LCD R U
Auto Swing + Telephone + LCD + Soft Start S T

8 Cooling/Heating A~Z UNIT R22 HFC R22+AC INV.


HFC+AC HFC+DC
INV. INV.
INDOOR OUTDOOR C/O H/P E/H+C/O E/H+H/P C/O H/P C/O H/P H/P H/P
BASIC BASIC C H X Y F R V N
BASIC GOLD FIN A B 5 6 M P W Y T U
PLASMA GOLD FIN D E 7 8 Q S 1 2
PLASMA BASIC G J - - - - 3 4
GOLD FIN GOLD FIN K L - - - -

9 LG/OEM Brand A~Z L: LG Brand M: 1st OEM Brand


G: 2nd LG Brand N: 2nd OEM Brand

-3-
Details of LG Model Name(2003)~
1 2 - 3 4 5 6 7 8 9 10

Code Type Code of Model Meaning

1 Producing Center, A~Z L: Chang-won R22 N: India


Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia
T: China M: Mexico
K: Turkey R22 V: Vietnam
E: Turkey R410A S: Out Sourcing
H: Thailand

2 Product Type A~Z S: Split Type Air Conditioner

3 Cooling/Heating/Inverter A~Z C: Cooling only V: AC Inverter C/O


H: Heat pump N: AC Inverter H/P
X: C/O + E/Heater Q: DC Inverter C/O
Z: H/P + E/Heater W: DC Inverter H/P

4, 5 Capacity 0~9 Cooling/Heating Capacity


Ex. "09" → 9,000 Btu/h

6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase


A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase
5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase
6: 220-240V/50Hz E: 265V, 60Hz
7: 110V, 50/60Hz F: 200V, 50/60Hz
8: 380-415V/50Hz
9: 380-415V/60Hz

7 Chassis A~Z Name of Chassis of Unit


Ex. LSP → SP Chassis

8 Look A~Z Look,


Color (Artcool Model)

9 Function A~Z Basic A


Basic+4Way B
Plasma Filter C
Plasma Filter+4 Way D
Tele+LCD E
Tele+LCD+Nano plasma+4Way F
Nano Plasma F+(A/changeove)+A/clean+Low A G
Nano Plasma F+(A/changeove)+A/clean+4way+Low A H
Tele+LED+4way I
Internet J
Plasma F+4Way+Oxy generator K
Nano Plasma F+(A/changeove)+A/clean L
Nano Plasma F+(A/changeove)+A/clean+4way M
Nano Plasma F+(A/changeove)+A/clean+PTC N
Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P
Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q
Negative ION+A/Clean R
(Nano)Plasma+Negative ION+A/Clean S
4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U

10 Serial No. 1~9 LG Model Development Serial No.


* ARTCOOL COLOR
R Mirror
W White
B Blue
D Wood
M Metal
C Cherry

-4-
Functions
Indoor Unit

Operation ON/OFF by Remote controller

Sensing the Room Temperature


• Room temperature sensor. (THERMISTOR)

Room temperature control

• Maintains the room temperature in accordance with the Setting Temp.

Starting Current Control


• Indoor fan is delayed for 5 sec at the starting.

Time Delay Safety Control

• Restarting is inhibited for approx. 3 minutes.

Indoor Fan Speed Control


• High, Med, Low, CHAOS, JET COOL

Operation indication Lamps (LED)

--- Lights up in operation


--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Defrost Mode (for Heating Model)
OUTDOOR--- Lights up in compressor operation (for Cooling Model)
PLASMA --- The function illustrates its dynamic mode
by using a multiple lighting system.
( )
--- Linghts up in Telephone Control operation.
PLASMA
Soft Dry Operation Mode
• The function will be operated while in any
• Intermittent operation of fan at low speed. operation mode with selecting the function.
• The function is to be stopped while it is
Sleep Mode Auto Control
operating with selecting the function.
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours. Defrost(Deice) control (Heating)
• Both the indoor and outdoor fan stops dur-
Natural Air Control by CHAOS Logic
ing defrosting.
• The fan is switched to intermittent or irregular operation
• The fan speed is automatically switched from high to low speed. Hot-start Control (Heating)
• The indoor fan stops until the
Airflow Direction Control
evaporator pipe temperature will be reached
• The louver can be set at the desired position or swing at 28°C.
up and down automatically.
-5-
Remote Control
Operation ON/OFF

Operation Mode Selection


Cooling Operation Mode.( ) Auto Operation Mode.( )
(Cooling (Heating
model only) model only) Healthy Dehumidification Operation Mode.( ) Heating Operation Mode.( )
Fan Speed Selection

(Low) (Med) (High) (CHAOS)

Room, Temperature Display

: (High:39°C Low:11°C)
Temperature Setting
TEMPERATURE LOW HIGH

Cooling Down to 18°C Heating Down to 16°C


Up to 30°C Up to 30°C
JET COOL

PLASMA(Optional)
PLASMA

Setting the Time or Timer

Timer Selection
ON OFF
: OFF, ON, OFF ON

Timer Setting
SET

Timer Cancel
CANCEL
: Cancel Sleep Mode, Timer ON or Timer OFF
Sleep Operation
: 1, 2, 3, 4, 5, 6, 7, Off Timer
Airflow Direction Control

Fan Operation Mode


: Fan Operates without cooling or heating.
Horizontal Airflow Direction Control Button(Optional)

Reset

-6-
Remote Control
Operation ON/OFF

Operation Mode Selection


Cooling Operation Mode.( ) Auto Operation Mode.( )
(Cooling (Heating
model only) model only) Healthy Dehumidification Operation Mode.( ) Heating Operation Mode.( )
Fan Speed Selection

(Low) (Med) (High)

Room, Temperature Checking


: (High:39°C Low:11°C)
Temperature Setting
TEMPERATURE LOW HIGH

Cooling Down to 18°C Heating Down to 16°C


Up to 30°C Up to 30°C
JET COOL

PLASMA(Optional)

Setting the Time or Timer

Timer Selection

ON OFF
: OFF, ON, OFF ON
Timer Setting

SET

Timer Cancel
CANCEL
: Cancel Sleep Mode, Timer ON or Timer OFF
Sleep Operation
: 1, 2, 3, 4, 5, 6, 7, Off Timer
Airflow Direction Control

Air Circulation
: Fan Operates without cooling or heating.
Horizontal Airflow Direction Control Button(Optional)

2nd F

Reset

-7-
Product References
LS-Q096BAG, LS-Q096ACG LS-Q096BBG, LS-Q096BEL
LS-Q076BBG LS-Q096ACL, LS-Q096AAL LS-Q096AHG, LS-Q096ABL LS-Q082BAG/BAM
Model Name LS-Q076BEL
LS-Q096ADG, LS-Q096ADL LS-Q096ABG, LS-Q096AEL LS-Q082AAL/ACG LS-H096QNA0
LS-Q076ABL
LS-Q096BDG, LS-Q096BDL LS-Q096ABM, LS-Q096AEM LS-Q082ACL/ACM
LS-Q076ABG
Item Unit LS-Q096AAG LS-Q096BEG

Cooling Capacity 7,000 9,000 9,000 8,000 8,500


Btu/h
Heating Capacity 7,300 - 9,300 - 8,750
Moisture Removal l/h 1.0 1.0 1.0 1.0 1.0
Power Source Ø, V, Hz 1Ø, 220-240V, 50Hz 1Ø, 220-240V, 50Hz 1Ø, 220-240V, 50Hz 1Ø, 220V, 60Hz 1Ø, 220-240V, 50Hz
Indoor 5.9 6 6 6 6
Air Circulation m3/min
Outdoor 20 20 25 20 25
Indoor 34 36 36 36 36
Noise Level dB (A)±3
Outdoor 48 48 48 48 48
Cooling 660 900 900 650 950
Input W
Heating 640 - 870 - 860
Running Cooling 3.0 4.0 3.9 3.0 4.2
A
Current Heating 2.9 - 3.8 - 3.8
E.E.R. Cooling Btu/hW 10.6 10 10 10 8.9
C.O.P Heating 3.3 - 3.13 - 2.8
Indoor 5 5.7 5.7 7.6 8.4
Motor Output W
Outdoor 14 14.5 14.5 18.7 13.6
Dimensions Indoor 824 x 260 x 155 824 x 260 x 155 824 x 260 x 155 824 x 260 x 155 824 x 260 x 155
(W x H x D) mm
Outdoor 525 x 564 x 265 525 x 564 x 265 770 x 540 x 245 525 x 564 x 265 770 x 540 x 245
Indoor 7 7 7 7 7
Net. Weight kg
Outdoor 23 23 33 23 23
Refrigerant g 610(R22) 530(R22) 640(R22) 630(R22) 680(R22)
Airflow Direction Control (Up & Down) O O O O O
Remocon Type L.C.D Wireless L.C.D Wireless L.C.D Wireless L.C.D Wireless L.C.D Wireless
Liquid 1/4" (6.35) 1/4" (6.35) 1/4" (6.35) 1/4" (6.35) 1/4" (6.35)
Service Valve inch(mm)
Gas 3/8" (9.52) 3/8" (9.52) 3/8" (9.52) 3/8" (9.52) 3/8" (9.52)
Sleeping Operation O O O O O
Drain Hose O O O O O
Connecting Cable 0.75mm2 0.75mm2 0.75mm2 0.75mm2 0.75mm2
Power Cord 0.75mm2 0.75mm2 0.75mm2 0.75mm2 0.75mm2

NOTE: Please refer to Label Quality on the product since this specification may be changed for improving
performance

-8-
Model Name LS-C096QLA0
LS-C082QMA0/QNA0 LS-H096QGL1
QNA0/QGL0
Item Unit

Cooling Capacity 9,000 8,000 9,000


Btu/h
Heating Capacity - - 9,300
Moisture Removal l/h 1.0 1.0 1.0
Power Source Ø, V, Hz 1Ø, 220-240V, 50Hz 1Ø, 220V, 60Hz 1Ø, 220-240V, 50Hz
Indoor 6 6 6
Air Circulation m3/min
Outdoor 20 20 25
Indoor 36 36 36
Noise Level dB (A)±3
Outdoor 48 48 48
Cooling 900 650 950
Input W
Heating - - 860
Running Cooling 4.0 3.0 4.2
A
Current Heating - - 3.8
E.E.R. Cooling Btu/hW 10 10 9.5
C.O.P Heating - - 2.8
Indoor 5.7 7.6 8.4
Motor Output W
Outdoor 14.5 18.7 13.6
Dimensions Indoor 824 x 260 x 155 824 x 260 x 155 824 x 260 x 155
(W x H x D) mm
Outdoor 525 x 564 x 265 525 x 564 x 265 770 x 540 x 245
Indoor 7 7 7
Net. Weight kg
Outdoor 23 23 23
Refrigerant g 530(R22) 630(R22) 680(R22)
Airflow Direction Control (Up & Down) O O O
Remocon Type L.C.D Wireless L.C.D Wireless L.C.D Wireless
Liquid 1/4" (6.35) 1/4" (6.35) 1/4" (6.35)
Service Valve inch(mm)
Gas 3/8" (9.52) 3/8" (9.52) 3/8" (9.52)
Sleeping Operation O O O
Drain Hose O O O
Connecting Cable 0.75mm2 0.75mm2 0.75mm2
Power Cord 0.75mm2 0.75mm2 0.75mm2

NOTE: Please refer to Label Quality on the product since this specification may be changed for improving
performance

-9-
Dimensions
(1) Indoor Unit

D
W

Installation plate

MODEL
All Models
DIM Unit

W mm 824

H mm 260

D mm 155

-10-
(2) Outdoor Unit
W L2
L1
D

L3

Gas side
(3-way valve)
H

Liquid side
L5

(2-way valve)
L4

MODEL
7k Heat Pump, 8k Cooling, 9k Cooling

DIM unit
W mm 564
H mm 525
D mm 265
L1 mm 294
L2 mm 66
L3 mm 374
L4 mm 17
L5 mm 270

-11-
(3) Outdoor Unit

W L2
L1
D

L3
H

Gas side
(3-way valve)
L5

Liquid side
L4

(2-way valve)

MODEL
9k Heat Pump
DIM unit
W mm 770
H mm 540
D mm 245
L1 mm 285
L2 mm 65
L3 mm 518
L4 mm 10
L5 mm 100

-12-
Refrigeration Cycle Diagram
(1) Cooling Only Models
INDOOR UNIT OUTDOOR UNIT

LIQUID SIDE

CAPILLARY TUBE

HEAT HEAT
EXCHANGE EXCHANGE
(EVAPORATOR) (CONDENSER)

GAS SIDE
COMPRESSOR

(2) Cooling & Heating Models


INDOOR UNIT OUTDOOR UNIT

CHECK VALVE
LIQUID SIDE (Heating Model only)

VALVE

CAPILLARY TUBE

HEAT HEAT
EXCHANGE EXCHANGE
(EVAPORATOR) (CONDENSER)

GAS SIDE

REVERSING
VALVE
ACCUMU VALVE
LATOR (Heating Model Only)

COMPRESSOR COOLING
HEATING

-13-
Wiring Diagram
(1) Indoor Unit
1. LS-Q076ABL, LS-Q076BBG, LS-Q076BEL 2. LS-Q096AAG, LS-Q096AAL, LS-Q096ACG 3. LS-Q082BAG, LS-Q096ACL, LS-Q082AAL
LS-Q096ABL, LS-Q096ABG, LS-Q066AHG LS-Q096ADL, LS-Q096ADG, LS-Q096BAG LS-Q082ACG, LS-Q082ACL, LS-Q082ACM
LS-Q096AEL, LS-Q096BBG, LS-Q096ABM LS-Q096BAG, LS-Q096BDG, LS-Q096BDL LS-C082QMA0, LS-C082QNA0
LS-Q096AEM, LS-H096QNA0, LS-Q096BEG LS-Q082BAM, LS-C096QGL0, LS-C096QLA0,
LS-C096QNA0, LS-H096QGL1

POWER
AC PWB ASM DC PWB ASM

POWER
POWER

AC PWB ASM. DC PWB ASM. AC PWB ASM. DC PWB ASM.

CN-TH
CN-ACDC1

CN-ACDC2
CN-ACDC1

CN-ACDC2

CN-L/R CN-U/D CN-TH


CN-L/R CN-U/D CN-TH

TRIAC TRIAC THERMISTOR

CN-AC/DC

CN-AC/DC
OR THERMISTOR OR THERMISTOR
GN/YL GN/YL
MOTOR MOTOR

BR(BK/Plained)
BL(WH/Ribbed)
BR(BK/Plained)
BL(WH/Ribbed)

BK STEP BK STEP

CN-U/D
MOTOR STEP
MOTOR TRIAC
CN-MOTOR CN-MOTOR OR MOTOR
BR YL BR YL

BR(BK/Plained)
BL(WH/Ribbed)
STEP STEP MOTOR
MOTOR MOTOR BK
SH-CAPA SH-CAPA

CN-L/R
CN-MOTOR STEP
BR YL MOTOR

CN-CONT CN-12V CN-HVB


CN-CONT CN-12V CN-HVB

GN/YL
RD AIR RD AIR
T/BOARD H.V. T/BOARD H.V.
ASM. BK CLEAN ASM. BK CLEAN CN-TAB1
CN-TAB T-BLOCK (PLASMA) CN-TAB T-BLOCK (PLASMA) SH-CAPA
BK BK BK BK RD AIR
BK BK S/W1 4 3 BK BK S/W1 FUSE H.V.
4 3 4 3 250V T2A ASM BK CLEAN
1(L) 2(N)
1(L) 2(N)

(PLASMA)

1(L) 2(N)
RY-COMP FUSE BK BK RY-COMP FUSE BK BK BK
BK BK RY-COMP
250V T2A BK BK S/W2 250V T2A S/W2 BK SAFETY S/W1

GN/YL CN-DISP GN/YL CN-DISP BK


RY-4WAY T/BLOCK
3

BK SAFETY S/W2
4

RY-FAN CN-DISP

GN/YL
GN/YL
GN/YL

BR
DISPLAY PWB ASM. DISPLAY PWB ASM.

BL
BR

SW(FORCE)
RD

BL
BR

BK
BL

DISPLAY PWB ASM


TO OUTDOOR UNIT
TO OUTDOOR UNIT TO OUTDOOR UNIT
INDOOR WIRING DIAGRAM P/No : 3854A20238H INDOOR WIRING DIAGRAM P/No : 3854A20238J INDOOR WIRING DIAGRAM 3854A20142B

(2) Outdoor Unit


1. LS-Q076ABL, LS-Q076ABG, 2. LS-Q096AAG, LS-Q096AAL, 3. LS-Q096ABL, LS-Q096AEL, 4. LS-H096QNA0, LS-H096QNA0
LS-Q076BBG LS-Q096ACG, LS-Q096ADL, LS-Q096ABG, LS-Q096AHG,
LS-Q076BEL LS-Q096ADG, LS-Q096ACL LS-Q096BBG, LS-Q096BEL
LS-Q096BAG, LS-Q096BDG, LS-Q096ABM, LS-Q096AEM,
LS-Q096BDL LS-Q082BAG, LS-Q096BEG
LS-Q096ABM, LS-Q082AAL
LS-Q082BAM, LS-Q082ACG,
LS-Q082ACL, LS-Q082ACM
LS-C082QMA0, LS-C082QNA0
LS-C096QCL0, LS-C096QLA0
LS-C096QNA0, LS-H096QGL1

BL BL PTC GN/YL FAN


CAPACITOR CAPACITOR COMP MOTOR
RD H C F RD RD H C F RD C S R BL BL
R S R S
COMP COMP BL CAPACITOR
BL BK BL
OLP

BL H C F

RD BL YL
C C
GN/YL GN/YL
BR BR BR RD BL
BK(RD)
REVERSING
VALVE

OLP FAN OLP FAN RD


REVERSING

MOTOR MOTOR
VALVE

BL
BR(YL) YL
BR BK YL
YL

1
1 2 3

BR BL GN/YL BK(RD) YL
BR BL GN/YL BK RD BR BL GN/YL TERMINAL
1(L) 2(N) 3 4 BLOCK
PILLAR PILLAR
1(L) 2(N) 3 4 TERMINAL
1(L) 2(N) TERMINAL

BR BL GN/YL BK RD
BR BL GN/YL BK RD BR BL GN/YL

BLACK GRAY BLACK

TO INDOOR UNIT
TO INDOOR UNIT TO INDOOR UNIT

OUTDOOR WIRING DIAGRAM OUTDOOR WIRING DIAGRAM OUTDOOR WIRING DIAGRAM


3854AR2262E 3854AR2262F 3854A30077D

-14-
Operation Details
1. MAIN UNIT FUNCTION
• DISPLAY
1) C/O Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)

Sleep Timer Indicator


• ON while in sleep timer mode, OFF when sleep timer cancel or appliance operation pause.

Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.

Comp. Running Incidator


• While in appliance operation, ON while in outdoor unit compressor running, OFF while in compressor off.

2) H/P Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)

Sleep Timer Indicator


• ON while in sleep timer mode, OFF when sleep timer cancel or appliance operation pause.

Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.

Defrost Indicator
• OFF except when hot start during heating mode operation or while in defrost control.

■ Cooling Mode Operation


• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp ➲ Setting Temp+0.5°C
Compressor OFF Temp ➲ Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote control. While in compressor
not running, operating with the low airflow speed regardless of the setting.

■ Healthy Dehumidification Mode


• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp ➲ 25°C
24°C ≤ Intake Intake Air Temp<26°C ➲ Intake Air Temp-1°C
18°C ≤ Intake Intake Air Temp<24°C ➲ Intake Air Temp-0.5°C
Intake Air Temp<18°C ➲ 18°C

-15-
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidifica-
tion operation and 4-min compressor off repeat.
Compressor ON Temp. ➲ Setting Temp+0.5°C
Compressor OFF Temp. ➲ Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

■ Heating Mode Operation


• When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below
the setting temp, the compressor is turned on.
Compressor ON Temp. ➲ Setting Temp.
Compressor OFF Temp. ➲ Setting Temp.+3°C
• While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it
operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper-
ates with Super-Low(while in sleep mode, with the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
• If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temp.
• While in defrost control, both of the indoor and outdoor fans are turned off.

■ Defrost Control
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing,
reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
• After 40 min heating mode operation, at 4 min interval, whether to carry out defrost control or not and the time
of defrost control are determined according to the following conditions.
1) While in heating mode operation, the maximum of the indoor pipe temperature is measured and it is com-
pared with the present indoor pipe temperature to get the difference of the indoor pipe temperatures (=the
maximum temperature of indoor pipe ? the present temperature of indoor pipe), according to which, whether
to carry out defrost control or not is determined.
2) According to the need of defrost control shown above and the elapsed time of heating mode operation at that
moment, the defrost control time is determined.
3) When the determined time of defrost control is below 7 min, heating mode operation continues without carry-
ing out defrost control. According to the procedure stated above, the determination is made again. When the
defrost control time is 7 min or longer, defrost control is then carried out.
• While in defrost control, the minimum temp of the indoor pipe is measured and it is compared with the present
temp of the indoor pipe to get the difference of the indoor pipe temperatures (=the present temperature of the
indoor pipe ? the minimum temperature of the indoor pipe). When the difference is 5°C or higher, defrost con-
trol is completed and heating mode operation is carried out.
• While in defrost control, if the defrost time determined before the start of defrost control is completed, defrost
control stops and heating mode operation is carried out regardless of the above condition.
• When the indoor pipe temp is 42°C or above, defrost control is not carried out even if the condition is one of
the defrost conditions above.
• While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.

-16-
■ Fuzzy Operation (C/O Model)
• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting
temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp + 0.5°C
Compressor OFF Temp ➲ Setting Temp + 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp ➲ 25°C
24°C ≤ Intake Air Temp < 26°C ➲ Intake Air Temp + 1°C
22°C ≤ Intake Air Temp < 24°C ➲ Intake Air Temp + 0.5°C
18°C ≤ Intake Air Temp < 22°C ➲ Intake Air Temp
Intake Air Temp<18°C ➲ 18°C

• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the
temperature.

■ Fuzzy Operation (H/P Model)


• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C ≤ Inatake Air Temp ➲ Fuzzy Operation for Cooling
21°C ≤ Inatake Air Temp<24°C ➲ Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C ➲ Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

1) Fuzzy Operation for Cooling


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor
is turned on.
Compressor ON Temp ➲ Setting Temp +0.5°C
Compressor OFF Temp ➲ Setting Temp + 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C≤ Intake Air Temp ➲ 25°C
24°C≤ Intake Air Temp<26°C ➲ Intake Air Temp + 1°C
22°C≤ Intake Air Temp<24°C ➲ Intake Air Temp + 0.5°C
18°C≤ Intake Air Temp<22°C ➲ Intake Air Temp
Intake Air Temp<18°C ➲ 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the tem-
perature.

-17-
2) Fuzzy Operation for Dehumidification
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor
is turned on.
Compressor ON Temp ➲ Setting Temp + 0.5°C
Compressor OFF Temp ➲ Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp ➲ 25°C
24°C ≤ Intake Air Temp<26°C ➲ Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C ➲ Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C ➲ Intake Air Temp
Intake Air Temp<18°C ➲ 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.

3) Fuzzy Operation for Heating


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp
Compressor OFF Temp ➲ Setting Temp + 3°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C≤Intake Air Temp ➲ Intake Air Temp + 0.5°C
Intake Air Temp<20°C ➲ 20°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.

■ Airflow Speed Selection


• The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow
speed selection key on the remote control.

■ On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.

-18-
■ Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.

■ Off-Timer ↔ On-Timer Operation


• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is
carried out according to the set time.

■ Sleep Timer Operation


• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli-
ance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C. After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the
low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.

■ Chaos Swing Mode


• By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are
fixed to the desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.

< Cooling Mode > < Heating Mode >


CLOSED CLOSED

7° 7°

OPEN OPEN

■ Chaos Natural Wind Mode


• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.

-19-
■ Jet Cool Mode Operation (C/O Model)
• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

■ Jet Cool Mode Operation (H/P Model)


• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other
mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

■ Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.
Heat pump Model
Cooling Model
Room Temp. ≥ 24°C 21°C ≤ Room Temp. < 24°C Room Temp. < 21°C
Operating mode Cooling Cooling Healthy Dehumidification Heating
Indoor FAN Speed High High High High
Setting Temperature 22°C 22°C 23°C 24°C

• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.

■ Test operation
• During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem-
perature and resets in 18±1 minutes.
• During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, open the front panel upward and Press the power button let it be pressed for
about 3 seconds.
• If you want to stop the operation, re-press the button.
■ Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.

■ Air Cleaner Operation


• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.

-20-
■ Remote Control Operation Mode
• When the remote control is selected by the slide switch on the main unit, the appliance operates according to
the input by the remote control.

■ Protection of the evaporator pipe from frosting


• If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool-
ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor
evaporator pipe from frosting.
• When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the
outdoor fan is turned on according to the condition of the room temperature.

■ Buzzer Sounding Operation


• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
• When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the
remote control signal cannot be received.

-21-
Display Function
1. Heating Model 2. Cooling Model

Operation Indicator Operation Indicator

• Cooling, Soft Dry, Fan, Heating • Cooling, Soft Dry, Fan

Sleep Timer Indicator Sleep Timer Indicator

• Sleep Mode • Sleep Mode

Timer Indicator Timer Indicator

• Timer Mode • Timer Mode

Defrost Indicator Compressor Indicator OUTDOOR

• Hot-start, Defrost

PLASMA Indicator PLASMA PLASMA Indicator PLASMA

• PLASMA Mode • PLASMA Mode

Self-diagnosis Function
Error Error Display LED
Error contents SVC check point
Code (Indoor body operation LED)
• Indoor room temperature
(once) thermistor open/short • Indoor Thermistor
1
• Indoor pipe temperature assembly check
3sec 3sec 3sec thermistor open/short.

-22-
Installation

1. Installation of indoor, Outdoor unit

1) Selection of the best location • Select a place so that the warm air and noise from the
1. Indoor unit air conditioner do not disturb neighbors.
More than 10 cm
• Do not have any heat or steam near the unit. More than 10 cm
• Select a place where there are no obstacles in front of
the unit.
• Make sure that condensation drainage can be conve-
niently routed away.
Do not install near a doorway.
• Ensure that the space around the left and right of the
More than 70 cm
unit is more than "A". The unit should be installed as
high on the wall as possible, allowing a minimum of
2) Piping length and elevation
"B" from ceiling.
• Use a stud finder to locate studs to prevent unneces- Pipe Size Standard Max. Max. Additional
Capacity
sary damage to the wall. Length Elevation Length Refrigerant
(Btu/h) GAS LIQUID (m) B (m) A (m) (g/m)
More than "B" 3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20
7k~14k
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
More than "A"
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30
30k~38k
3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50

Indoor unit
Outdoor unit

More than 2.3m


More than "B" A
A
CAUTION
Indoor unit B B Outdoor unit
Install the indoor unit on the wall where the height
from the floors more than 2.3 meters.

Clearance(cm)
Grade I
A B Outdoor unit
7K~28K 10 5
30K~38K 30 12
Oil trap A
2. Outdoor unit
• If an awning is built over the unit to prevent direct sun- Indoor unit
B
light or rain exposure, make sure that heat radiation
from the condenser is not restricted.
• Ensure that the space around the back and sides is
more than 10cm. The front of the unit should have
If case more than 5m
more than 70cm of space.
CAUTION
• Do not place animals and plants in the path of the
warm air. • Capacity is based on standard length and maximum
• Take the air conditioner weight into account and select allowance length is on the basis of reliability.
a place where noise and vibration are minimum. • Oil trap should be installed every 5~7 meters.

-23-
3) How to fix installation plate 4) Drill a hole in the wall
The wall you select should be strong and solid enough • Drill the piping hole with a ø70mm hole core drill. Drill
to prevent vibration the piping hole at either the right or the left with the
hole slightly slanted to the outdoor side.
1. Mount the installation plate on the wall with four
type A screws. If mounting the unit on a concrete
wall, use anchor bolts. WALL
• Mount the installation plate horizontally by aligning Indoor Outdoor
the centerline using a level.

Installation Plate

(3/16"~5/16")
5-7mm
Type "A" screw

2. Measure the wall and mark the centerline. It is


also important to use caution concerning the
location of the installation plate-routing of the
wiring to power outlets is through the walls typi-
cally. Drilling the hole through the wall for piping
connections must be done safely.

C
Installation plate
D

Ø70mm
A
Ø70mm

Left rear piping Right rear piping

CHASSIS Distance (mm)


(Grade) A B C D
SJ 90 20 80 20
SL, SK 45 40 80 20
SQ 75 12 80 12
SR 0 40 20 40
ST 105 0 210 0

Installation plate
B
D

C E A

Right rear piping Ø70mm


Left rear piping

CHASSIS Distance (mm)


(Grade) A B C D E
SM 180 115 - 115 50
SN 180 115 195 115 -

-24-
2. Flaring Work and Connection of Piping

1) Flaring work 4. Flaring work


• Firmly hold copper pipe in a die in the dimension
Main cause for refrigerant leakage is due to defect in
shown in the table above.
the flaring work. Carry out correct flaring work using the
following procedure.
Handle

"A"
1. Cut the pipes and the cable. Bar
Bar
• Use the piping kit accessory or pipes purchased locally. Yoke
• Measure the distance between the indoor and the
outdoor unit. Cone
• Cut the pipes a little longer than the measured
Copper pipe
distance.
• Cut the cable 1.5m longer than the pipe length. Clamp handle
Red arrow mark

Copper • Carry out flaring work using flaring tool as shown


pipe 90° Slanted Uneven Rough below.

Outside diameter
mm inch mm
Ø6.35 1/4 0~0.5
Ø9.52 3/8 0~0.5
2. Burr removal
Ø12.7 1/2 0~0.5
• Completely remove all burrs from the cut cross sec-
Ø15.88 5/8 0~1.0
tion of pipe/tube.
Ø19.05 3/4 1.0~1.3
• Put the end of the copper tube/pipe in a downward
direction as you remove burrs in order to avoid drop-
5. Check
ping burrs into the tubing.
• Compare the flared work with figure below.
Pipe • If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
Reamer

Smooth all round


Point down Inside is shiny without scratches

= Improper flaring =

3. Putting nut on
• Remove flare nuts attached to indoor and outdoor Inclined Surface Cracked Uneven
damaged thickness
unit, then put them on pipe/tube having completed Even length
burr removal. all round

(not possible to put them on after flaring work)


Flare nut

Copper tube

-25-
2) Connection of piping Indoor 3. Tape the tubing, drain hose, and the connecting
cable. Be sure that the drain hose is located at the
• Preparing the indoor unit's piping and drain hose for
lowest side of the bundle. Locating at the upper
installation through the wall.
side can cause drain pan to overflow inside the
• Remove the plastic tubing retainer(see illustration
unit.
below) and pull the tubing and drain hose away from
chassis.
• Replace the plastic tubing holder in the original posi-
tion.

Loop

Connecting Gas side


cable piping
Tubing holder Liquid side
Drain hose piping
CAUTION
NOTE: If the drain hose is routed inside the room,
When install, make sure
insulate the hose with an insulation material* so that
that the remaining parts
dripping from "sweating"(condensation) will not damage
must be removed clearly
furniture or floors.
so as not to damage the
*Foamed polyethylene or equivalent is recommended.
piping and drain hose,
especially power cord 4. Indoor unit installation
and connecting cable. • Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the instal-
For right rear piping lation plate.) Ensure that the hooks are properly seat-
ed on the installation plate by moving it left and right.
1. Route the indoor tubing and the drain hose in the
direction of rear right.
Connecting
cable

Drain hose
Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
4. Connecting the pipings to the indoor unit and drain
hose to drain pipe.
Drain hose • Align the center of the pipes and sufficiently tighten
the flare nut by hand.
2. Insert the connecting cable into the indoor unit
from the outdoor unit through the piping hole.
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy
Indoor unit tubing Flare nut Pipes
connection later.

-26-
• Tighten the flare nut with a wrench. • Wrap the area which accommodates the rear piping
housing section with vinyl tape.

Open-end wrench (fixed) Indoor


Connection
pipe unit pipe
Flare nut Vinyl tape Wrap with vinyl tape
(wide)
Connection pipe
Wrench

Indoor unit tubing Connecting cable

Outside diameter Torque Pipe


mm inch kg.m
Ø6.35 1/4 1.8 Vinyl tape(narrow)
Ø9.52 3/8 4.2
Ø12.7 1/2 5.5
Ø15.88 5/8 6.6 • Bundle the piping and drain hose together by wrap-
Ø19.05 3/4 6.6 ping them with vinyl tape for enough to cover where
they fit into the rear piping housing section.
• When extending the drain hose at the indoor unit,
install the drain pipe. Wrap with vinyl tape

Pipe

Drain pipe
Vinyl tape(wide)
Drain hose

Indoor unit drain hose


For left rear piping
Vinyl tape(narrow)
Adhesive
1. Route the indoor tubing and the drain hose to the
required piping hole position.
5. Wrap the insulation material around the connecting
portion.
• Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there is no gap.

Plastic bands Insulation material

2. Insert the piping, drain hose, and the connecting


cable into the piping hole.

Connecting cable

Drain pipe

-27-
3. Insert the connecting cable into the indoor unit. Outside diameter Torque
• Don't connect the cable to the indoor unit. mm inch kg.m
• Make a small loop with the cable for easy connection Ø6.35 1/4 1.8
later. Ø9.52 3/8 4.2
Ø12.7 1/2 5.5
4. Tape the drain hose and the connecting cable. Ø15.88 5/8 6.6
• Connecting cable Ø19.05 3/4 6.6

• When extending the drain hose at the indoor unit,


install the drain pipe.

Drain hose

5. Indoor unit installation Indoor unit drain hose


• Hang the indoor unit from the hooks at the top of the Vinyl tape (narrow)
installation plate. Adhesive
• Insert the spacer etc. between the indoor unit and the
installation plate and separate the bottom of the 7. Wrap the insulation material around the con-
indoor unit from the wall. necting portion.
• Overlap the connection pipe heat insulation and the
indoor unit pipe heat insulation material. Bind them
Indoor unit together with vinyl tape so that there is no gap.
Spacer
Plastic bands Insulation material

Installation plate
8cm

6. Connecting the pipings to the indoor unit and the


drain hose to drain pipe. • Wrap the area which accommodates the rear piping
• Align the center of the pipes and sufficiently tighten housing section with vinyl tape.
the flare nut by hand.

Connection Indoor
pipe unit piping

Vinyl tape Wrap with vinyl tape


Indoor unit tubing Flare nut Pipes (wide)

• Tighten the flare nut with a wrench.


Pipe
Open-end wrench (fixed)
Vinyl tape(narrow)

Flare nut Connecting cable

Connection pipe
Wrench

Indoor unit tubing

-28-
• Bundle the piping and drain hose together by wrap- 3) Connection of the pipes-Outdoor
ping them with cloth tape over the range within which
they fit into the rear piping housing section.
1. Align the center of the pipings and sufficiently
Pipe tighten the flare nut by hand.
Drain hose
Vinyl tape(narrow)

Wrap with
vinyl tape(wide)

8. Reroute the pipings and the drain hose across the


2. Finally, tighten the flare nut with torque wrench
back of the chassis.
until the wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on
the wrench.
Outside diameter Torque
mm inch kg.m
Piping for
passage through Ø6.35 1/4 1.8
piping hole Ø9.52 3/8 4.2
9. Set the pipings and the drain hose to the back of Ø12.7 1/2 5.5
the chassis with the tubing holder. Ø15.88 5/8 6.6
• Hook the edge of tubing holder to tap on chassis and Ø19.05 3/4 6.6
push the bottom of tubing holder to be engaged at the Outdoor unit
Gas side piping
bottom of chassis. (Bigger diameter)

Liquid side
piping
(Smaller
diameter)

Tubing holder Torque wrench

10. Indoor unit installation LS-Q096ABL


• Remove the spacer.
• Ensure that the hooks are properly seated on the
installation plate by moving it left and right.

Outdoor unit Gas side piping


(Bigger Dia.)

Connecting
cable
Liquid side piping
(Smaller Dia.)

Drain hose Torque wrench

Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
LS-Q096AAL

-29-
3. Connecting The Cable Between Indoor Unit and Outdoor Unit

1) Connect the cable to the Indoor unit.


• Connect the cable to the indoor unit by connecting the wires to the terminals on the control board in
dividually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and
the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
CAUTION
• When installing, refer to the circuit diagram on the The power cord connected to the "A" unit should be
Control Box of Indoor Unit. complied with the following specifications
• When installing, refer to the wiring diagram on the (Type "B" approved by HAR or SAA).
Control Cover Inside Outdoor Unit.

CAUTION
(mm2)
• The above circuit diagram is subject to change with-
NORMAL Grade
out notice. CROSS
• Be sure to connect wires according to the wiring dia- 5k~9K 12k~14k 18k 24k~28k 30k, 32k 36k, 38k
-SECTIONAL
gram. AREA 0.75 1.0 1.5 2.5 2.5 5.5
• Connect the wires firmly, so that not to be pulled out Unit(A) Indoor Indoor Indoor Indoor Outdoor Outdoor
easily. Cable Type(B) H05VV-F H05VV-F H05VV-F H05VV-F H05RN-F H05RN-F
• Connect the wires according to color codes by refer-
The power connecting cable connected to the indoor
ring the wiring diagram.
and outdoor unit should be complied with the following
specifications
(Type "B" approved by HAR or SAA).

CAUTION
If a power plug is not to be used, provide a circuit breaker
between power source and the unit as shown below.
Main power source NORMAL
CROSS-SECTIONAL
(mm2) AREA 0.75mm2
NORMAL Grade
Circuit Breaker CROSS
Air 5k~9k 12k~14k 18k 24k~28k
Use a circuit -SECTIONAL
Conditioner
breaker or time AREA 0.75 1.0 1.5 2.5
delay fuse. Cable Type(B) H07RN-F H07RN-F H07RN-F H07RN-F

(mm2)
Grade
NORMAL CROSS
30k, 32k 36k, 38k
-SECTIONAL AREA
0.75 0.75
Cable Type(B) H07RN-F H07RN-F

-30-
2) Connect the cable to the outdoor unit Outdoor unit
Terminal block
1. Remove the control cover from the unit by loos- (Pillar terminal)
ening the screw. Connecting
cable
Connect the wires to the terminals on the control
board individually. Holder for
Over connecting
5mm cable
2. Secure the cable onto the control board with the Cover control
cord clamp.

3. Refix the control cover to the original position


with the screw.
LS-Q096AAL
4. Use a recognized circuit breaker "A"
between the power source and the unit. Outdoor unit
A disconnecting device to adequately disconnect Terminal block
all supply lines must be fitted. (Pillar terminal)
Over 5mm
Holder for
Grade power supply
Circuit cord
Breaker 7k~14k 18k 24k~28k 30k, 32k 36k, 38k
(A)
Cover control
15 20 30 30 40

Connecting cable

LS-Q096ABL

CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness. (Refer to page 30))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal
function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an
air gap contact separation of at least 3mm in each active(phase) conductors.

-31-
4. Checking the Drainage and Forming the Pipings

1) Checking the drainage 2) Form the piping


1. To remove the front panel from the indoor unit. 1. Form the piping by wrapping the connecting por-
• Set the air direction louvers up-and-down to the posi- tion of the indoor unit with insulation material and
tion(horizontally) by hand. secure it with two kinds of vinyl tapes.
• Remove the securing screws that retain the front pan- • If you want to connect an additional drain hose, the
el. Pull the lower left and right sides of the grille end of the drain outlet should be routed above the
toward you and lift it off. ground. Secure the drain hose appropriately.

2. In cases where the outdoor unit is installed below


the indoor unit perform the following.
• Tape the piping, drain hose and connecting cable from
down to up.
• Secure the tapped piping along the exterior wall using
Pull the right and
the left side. saddle or equivalent.

Seal small openings


around pipings with a
2. To check the drainage. gum type sealer.
• Pour a glass of water on the evaporator.
• Ensure the water flows through the drain hose of the Taping Taping
indoor unit without any leakage and goes out the drain Drain Drain hose
hose
exit.

Pipings Pipings
Connecting Connecting
cable cable
LS-Q096AAL LS-Q096ABL

Trap is required to prevent water


from entering into electrical parts.

3. In cases where the Outdoor unit is installed above


the Indoor unit perform the following.
• Tape the piping and connecting cable from down to up.
• Secure the taped piping along the exterior wall. Form
3. Drain piping a trap to prevent water entering the room.
• The drain hose should point downward for easy drain • Fix the piping onto the wall by saddle or equivalent.
flow.
Seal a small opening
Downward slope
around the pipings
with gum type sealer.
Trap

• Do not make drain piping.


Accumulated
Do not raise
drain water
Air Tip of drain hose
Less than
dipped in water
50mm gap Trap
Water Water Water
Waving
leakage leakage leakage Ditch

-32-
5. Test Running

1. Check that all tubing and wiring have been properly


connected. Intake temperature
2. Check that the gas and liquid side service valves are
fully open. Discharge air

1. Prepare remote control


1. Remove the battery cover
by pulling it according to the
arrow direction. Discharge
temperature
2. Insert new batteries making
sure that the (+) and (–) of 4. For reference; the gas side pressure of optimum con-
battery are installed correctly. dition is as below.(Cooling)
3. Reattach the cover by
pushing it back into position. Outside ambient The pressure of the gas side
Refrigerant
TEMP. service valve.

NOTE: R-22 35°C (95°F) 4~5kg/cm2G(56.8~71.0 P.S.I.G.)


• Use 2 AAA(1.5volt) batteries. Do not use recharge-
able batteries. NOTE: If the actual pressure is higher than shown, the
• Remove the batteries from the remote control if the system is most likely over-charged, and charge
system is not going to be used for a long time. should be removed. If the actual pressure are
lower than shown, the system is most likely
2. Settlement of outdoor unit undercharged, and charge should be added.
• Anchor the outdoor unit with a bolt and nut(ø10mm) The air conditioner is now ready for use.
tightly and horizontally on a concrete or rigid mount.
• When installing on the wall, roof or rooftop, anchor the PUMP DOWN
mounting base securely with a nail or wire assuming This is performed when the unit is to be relocated
the influence of wind and earthquake. or the refrigerant circuit is serviced.
• In the case when the vibration of the unit is conveyed Pump Down means collecting all refrigerant in the
to the hose, secure the unit with an anti-vibration outdoor unit without loss in refrigerant gas.
bushing.
CAUTION:
Bolt Be sure to perform Pump Down procedure with the
unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to
the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge
the air from the manifold hose using the refrigerant
Tubing connection
gas.
3. Evaluation of the performance 3. Close the liquid side service valve(all the way in).
Operate unit for 15~20 minutes, then check the system 4. Turn on the unit's operating switch and start the
refrigerant charge: cooling operation.
1. Measure the pressure of the gas side service valve. 5. When the low-pressure gauge reading becomes 1
2. Measure the temperature of the intake and discharge to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the
of air. gas side valve stem and then quickly turn off the
3. Ensure the difference between the intake tempera- unit. At that time, Pump Down has been completed
ture and the discharge is more than 8°C(46°F) (Cool- and all refrigerant gas will have been collected in
ing) or (Heating). the outdoor unit.

-33-
Operation
Name and Function-Remote Control
The remote control transmits the signals to the system.

1 START/STOP BUTTON
Operation starts when this button is pressed and stops
Remote Control when the button is pressed again.

2 OPERATION MODE SELECTION BUTTON


Used to select the operation mode.
Signal transmitter
ROOM TEMPERATURE SETTING BUTTONS
3 Used to select the room temperature.
INDOOR FAN SPEED SELECTOR
4 Used to select fan speed in four steps
low, medium, high and CHAOS.
JET COOL
5 Used to start or stop the speed
cooling. (Speed cooling operates
5 6 super high fan speed in cooling mode.)
CHAOS SWING BUTTON
4 1 6 Used to stop or start louver movement and set the
3 desired up/down airflow direction.
ON OFF
7 10 ON/OFF TIMER BUTTONS
8 11 7 Used to set the time of starting and stopping operation.
SET CANCEL
9 12 TIME SETTING BUTTONS
2
PLASMA
13
8 Used to adjust the time.

15 14 TIMER SET/CANCEL BUTTONS


9 Used to set the timer when the desired time is obtained
and to cancel the Timer operation.
SLEEP MODE AUTO BUTTON
Flip-up door 10 Used to set Sleep Mode Auto operation.
(opened)
AIR CIRCULATION BUTTON
11 Used to circulate the room air without cooling or heat-
Operation Mode ing.
ROOM TEMPERATURE CHECKING BUTTON
Cooling Operation 12 Used to check the room temperature.
Auto Operation PLASMA(OPTION)
13 Used to start or stop the plasma-purification function.
Healthy Dehumidification Operation RESET BUTTON
14 Used prior to resetting time or after replacing batteries.
Heating Operation
HORIZONTAL AIRFLOW DIRECTION CONTROL BUT-
15 TON (NOT ON ALL MODELS)
• Cooling Model( ), Heat Pump Model( )
Used to set the desired horizontal airflow direction.

-34-
Name and Function-Remote Control
The remote control transmits the signals to the system.

1 START/STOP BUTTON
Operation starts when this button is pressed and stops
when the button is pressed again.
Remote Control
2 OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
Signal transmitter
3 ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.

4 INDOOR FAN SPEED SELECTOR


Used to select fan speed in four steps low, medium, high
and CHAOS.

5 JET COOL
Used to start or stop the speed cooling. (Speed cooling
operates super high fan speed in cooling mode.)
5 1
CHAOS SWING BUTTON
6 6
Used to stop or start louver movement and set the desired
3 up/down airflow direction.
ON/OFF TIMER BUTTONS
4 7 Used to set the time of starting and stopping operation.
2 10
CANCEL
9 TIME SETTING BUTTONS
7 ON OFF SET 8
11 Used to adjust the time.
12
8 9 TIMER SET/CANCEL BUTTON
13 14 Used to set the timer when the desired time is obtained
and to cancel the Timer operation.
15 16
SLEEP MODE AUTO BUTTON
10
Used to set Sleep Mode Auto operation.

11 AIR CIRCULATION BUTTON


Flip-up door Used to circulate the room air without cooling or heating.
(opened)
ROOM TEMPERATURE CHECKING BUTTON
12
Used to check the room temperature.
Operation Mode
13 PLASMA(OPTIONAL)
Cooling Operation Used to start or stop the plasma-purification function.

14 HORIZONTAL AIRFLOW DIRECTION CONTROL


Auto Operation BUTTON (NOT ON ALL MODELS)
Used to set the desired horizontal airflow direction.
Healthy Dehumidification Operation
15 RESET BUTTON
Used prior to resetting time or after replacing batteries.
Heating Operation
2nd F Button
16
• Cooling Model( ), Heat Pump Model( ) Used prior to using modes printed in blue at the bottom of
buttons.

-35-
Disassembly of the parts (Indoor unit)

Warning :
Disconnect the unit from power supply before making
any checks.
Be sure the power switch is set to “OFF”.

To remove the Grille from the Chassis.


• Set the up-and-down air discharge louver to open
position (horizontally) by finger pressure.
• Remove the securing screws.
• To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it
straight upward.

Display
P.C.B
Conductor
1. Before removing the control box, be sure to Sensor
take out the wire screwed at the other end. Conductor
Motor
Conductor

Step Motor
Earth Conductor
Conductor

Earth
Conductor

-36-
2. To remove the Control Box.
• Remove securing screws.
• Pull the control box out from the chassis careful-
ly.
Caution label

3. To remove the Discharge Grille.


• Unhook the discharge grille and pull the dis-
charge grille out from the chassis carefully.

4. To remove the Evaporator.


• Remove 3 screws securing the evaporator(at the
left 2EA in the Eva Holder, at the right 1EA).

Caution label
When repair, do not damage the Caution
label.

-37-
• Unhook the tab on the right inside of the chassis
at the same time, slightly pull the evaporator
toward you until the tab is clear of the slot.

5. To remove the Motor Cover


• Remove 2 securing screw.
• Pull the motor cover out from the chassis
carefully.

Motor cover

6. To remove the Cross-Flow Fan


• Loosen the screw securing the cross-flow fan to
the fan motor (do not remove).
• Lift up the right side of the cross-flow fan and the
fan motor, separate the fan motor from the
cross-flow fan.

• Remove the left end of the cross-flow fan from


the self-aligning bearing.

-38-
2-way, 3-way Valve

2-way Valve (Liquid Side) 3-way Valve (Gas Side)

Valve cap
Hexagonal wrench (4mm) Open position
Flare nut Flare nut Closed position
Open position
Pin
Closed position
To To
piping piping Service Service
connection connection port cap port
To outdoor unit To outdoor unit

Works Shaft position Shaft position Service port

Closed Closed Closed


Shipping
(with valve cap) (with valve cap) (with cap)

Air purging Open Closed Open


1. (Installation) (counter-clockwise) (clockwise) (push-pin or with
vacumm pump)

Open Open Closed


Operation
(with valve cap) (with valve cap) (with cap)

Pumping down Closed Open Open


2. (Transfering) (clockwise) (counter-clockwise) (connected manifold
gauge)

Evacuation Open Open Open


3. (Servicing) (with charging
cylinder)

Gas charging Open Open Open


4. (Servicing) (with charging
cylinder)
Pressure check Open
5. (Servicing) Open Open (with charging cylinder)

Gas releasing Open


6. Open Open (with charging cylinder)
(Servicing)

-39-
1. Air purging
Required tools : hexagonal wrench, adjustable The air in the indoor unit and in the piping must be
wrench, torque wrenches, wrench to purged. If air remains in the refrigeration pipes, it will
hold the joints, and gas leak detec- affect the compressor, reduce to cooling capacity, and
tor. could lead to a malfunction.

The additional gas for air purging has been charged


in the outdoor unit.
However, if the flare connections have not be done
correctly and there gas leaks, a gas cylinder and the
charge set will be needed.

Indoor unit Liquid side


Open Outdoor unit
2-way
valve

Gas side

Clsed
3-way
valve

Service port nut:


Be sure, using a torque wrench to tighten the service port nut (after using the service port), so that it prevents the
gas leakage from the refrigeration cycle.
* CAUTION : Do not leak the gas in the air during Air purging.

• Procedure
(6) Set the 3-way valve to the back seat.
(1) Recheck the piping connections.
(7) Mount the valve stem nuts to the 2-way and 3-
(2) Open the valve stem of the 2-way valve coun- way valves.
terclockwise approximately 90°, wait 10 sec-
onds, and then set it to closed position. (8) Check for gas leakage.
– Be sure to use a hexagonal wrench to operate – At this time, especially check for gas leakage
the valve stem. from the 2-way and 3-way valve’s stem nuts,
and from the service port nut.
(3) Check for gas leakage.
– Check the flare connections for gas leakage. Caution
(4) Purge the air from the system. If gas leakage are discovered in step (3) above,
– Set the 2-way valve to the open position and take the following mesures :
remove the cap from the 3-way valve’s service If the gas leaks stop when the piping connections
port. are tightened further, continue working from step (4).
– Using the hexagonal wrench to press the valve If the gas leaks do not stop when the connections
core pin, discharge for three seconds and then are retightened, repair the location of the leak, dis-
wait for one minute. Repeat this three times. charge all of the gas through the service port, and
(5) Use torque wrench to tighten the service port then recharge with the specified amount of gas
nut to a torque of 1.8kg.cm. from a gas cylinder.

-40-
2. Pumping down

Indoor unit Liquid side


Open Outdoor unit
2-Way
valve

Gas side

Closed
3-Way
valve

Lo
CLOSE CLOSE

Purge the air

• Procedure
(1) Confirm that both the 2-way and 3-way valves (6) Operate the air conditioner at the cooling
are set to the open position. cycle and stop it when the gauge indicates
– Remove the valve stem caps and confirm that 1kg/cm2g.
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate (7) Immediately set the 3-way valve to the closed
the valve stems. position.
– Do this quickly so that the gauge ends up indi-
(2) Operate the unit for 10 to 15 minutes. cating 3 to 5kg/cm2g.

(3) Stop operation and wait for 3 minutes, then (8) Disconnect the charge set, and mount the 2-
connect the charge set to the service port of way and 3-way valve’s stem nuts and the ser-
the 3-way valve. vice port nut.
– Connect the charge hose with the push pin to – Use torque wrench to tighten the service port
the service port. nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.

(5) Set the 2-way valve to the closed position.

-41-
1) Re-air purging
(Re-installation)

Indoor unit Liquid side


Closed Outdoor unit
2-Way
valve

Gas side

Closed
3-Way
valve

Gas cylinder

Lo
R22 OPEN CLOSE

• Procedure
(1) Confirm that both the 2-way valve and the 3- (6) Disconnect the charge set and the gas cylin-
way valve are set to the closed position. der, and set the 2-way and 3-way valves to the
open position.
(2) Connect the charge set and a gas cylinder to – Be sure to use a hexagonal wrench to operate
the service port of the 3-way valve. the valve stems.
– Leave the valve on the gas cylinder closed.
(7) Mount the valve stem nuts and the service
(3) Air purging. port nut.
– Open the valves on the gas cylinder and the – Use torque wrench to tighten the service port
charge set. Purge the air by loosening the flare nut to a torque of 1.8 kg.m.
nut on the 2-way valve approximately 45° for 3 – Be sure to check for gas leakage.
seconds then closing it for 1 minute; repeat 3
times. * CAUTION:
– After purging the air, use a torque wrench to Do not leak the gas in the air during Air Purg-
tighten the flare nut on the 2-way valve. ing.

(4) Check for gas leakage.


– Check the flare connections for gas leakage.

(5) Discharge the refrigerant.


– Close the valve on the gas cylinder and dis-
charge the refrigerant until the gauge indicates
3 to 5 kg/cm2g.

-42-
2) Balance refrigerant of the 2-way, 3-way valves
(Gas leakage)

Indoor unit Liquid side


Outdoor unit
2-Way
valve Open

Gas side

3-Way
valve Open

Lo
OPEN CLOSE

• Procedure (3) Open the valve (Lo side) on the charge set
and discharge the refrigerant until the gauge
(1) Confirm that both the 2-way and 3-way valves indicates 0 kg/cm2G.
are set to the back seat. – If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not run-
(2) Connect the charge set to the 3-way valve’s ning is higher than 1 kg/cm2G), discharge the
port. refrigerant until the gauge indicates 0.5 to 1
– Leave the valve on the charge set closed. kg/cm2G. if this is the case, it will not be neces-
– Connect the charge hose with the push pin to sary to apply a evacuatin.
the service port. – Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.

-43-
3. Evacuation
(All amount of refrigerant leaked)

Indoor unit Liquid side


Outdoor unit
2-Way
valve Open

Gas side

3-Way
valve Open

Vacuum pump
Lo
OPEN CLOSE

• Procedure (4) Disconnect the charge hose from the vacuum


pump.
(1) Connect the vacuum pump to the charge set’s – Vacuum pump oil.
center hose If the vacuum pump oil becomes dir ty or
depleted, replenish as needed.
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).

(3) Close the valve (Lo side) on the charge set,


turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).

-44-
4. Gas Charging
(After Evacuation)

Indoor unit Liquid side


Open Outdoor unit
2-Way
valve

Gas side

Open
3-Way
Check valve valve
Charging
cylinder

Lo
(1) OPEN CLOSE

• Procedure
\

(1) Connect the charge hose to the charging


This is different from previous procedures.
cylinder.
Because you are charging with liquid refrigerant
– Connect the charge hose which you dis-con-
from the gas side, absolutely do not attempt to
nected from the vacuum pump to the valve at
charge with larger amounts of liquid refrigerant
the bottom of the cylinder.
while operating the air conditioner.
– If you are using a gas cylinder, also use a scale
and revers the cylinder so that the system can
be charged with liquid. (4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
(2) Purge the air from the charge hose. – Stopping partway will allow the gas to be dis-
– Open the valve at the bottom of the cylinder charged.
and press the check valve on the charge set to – If the system has been charged with liquid
purge the air. (Be careful of the liquid refriger- refrigerant while operating the air conditioner
ant). The procedure is the same if using a gas turn off the air conditioner before disconnecting
cylinder. the hose.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant. (5) Mount the valve stem nuts and the service
– If the system can not be charged with the spec- port nut.
ified amount of refrigerant, it can be charged – Use torque wrench to tighten the service port
with a little at a time (approximately 150g each nut to a torque of 1.8 kg.m.
time) while operating the air conditioner in the – Be sure to check for gas leakage.
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure (pumping down-pin).

-45-
Cycle Troubleshooting Guide

Trouble analysis

1. Check temperature difference between intake and discharge air and operating current.

Temp. difference : approx. 0°C


• All amount of refrigerant leaked
Current : less than 80% of
out. Check refrigeration cycle.
rated current

Temp. Difference • Refrigerant leakege


Temp. difference : approx. 8°C
Current : less than 80% of Clog of refrigeration cycle
rated current Defective compressor

Operating Current Temp. difference : less than 8°C


Current : over the reated • Excessive amount of refrigerant
current

Temp. difference : over 8°C • Normal

Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower tem-
perature difference is larger.

2. Check temperature and pressure of refrigeration cycle.

Suction pressure Temperature


(Compared with (Compared with Cause of Trouble Description
the normal value) the normal valve)

Defective compressor Current is low.


High
Defective 4-way reverse valve
Higher
Excessive amount of High pressure does not quickly
Normal refrigerant rise at the beginning of
operation.

Insufficient amount of Current is low.


Lower Higher refrigerant (Leakage)
Clogging Current is low.

Notice :
1. The suction pressure is usually 4.5~6.0 kg/cm2G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.

-46-
Electronic Parts Troubleshooting Guide
1. Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power

(After 10 seconds)

Turn on Main Power

Does "beeping" sound is made from the Indoor Unit?

NO YES

Check the voltage of power(About AC 220V, 60Hz) Primarily, the operating condition of Micom is OK.
(About AC 220/240V, 50Hz)

• Main power's voltage


• Voltage applied to the unit
• Connecting method of Indoor/Outdoor connecting
cable Check each load(Indoor/Outdoor Fan Motor, Com-
• Check PWB Assembly pressor, Stepping Motor) and contacting
- Fuse condition of related connector
- Pattern damage
- Varistor(ZNR01J)

Check the connection housing for contacting

• Connector related to CN-TAB1, RY-COMP NO.3


• Connector related to CN-MOTOR
• Connector contacting of Outdoor Fan/Compressor
• Display PWB Assembly Check

Main PCB Board Operation Check


Items Content Remedy
• SMPS Transformer
(Indoor unit)
- Input Voltage - About AC220V/240V±10% - Check the power voltage • Replace Trans
- Output Voltage(ZD02D) - About DC12V

• IC04D(7805) Output • DC +5V • Replace IC04D


(Indoor/Outdoor unit)

• IC01A(KIA7036, Reset IC) • Voltage of Micom No. 2, • Replace faulty parts


X01(8MHz) (DC +4.5V over) and Soldering condition.

-47-
2. The product is not operate with the remote control.

Turn on Main Power

While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.

When the compressor stopped Indoor Fan is driven by a low speed.


At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the
low speed by force.)

Cause by the remote control Caused by other parts except the remote control

When the mark( ) is displayed in LCD screen, replace


Check the contact of CN-DISP1 connector.
battery.

Check the connecting circuit between the remote controller


Check Display PWB Assembly
MICOM (No. ) - R17(2Ω) - IR LED - TR - R16(2.2KΩ).
- Voltage between CN DISP1 - : DC +5V

Check point

• Check the connecting circuit between CN-DISP1 2 -


R01L(5.1K) - C01L(680pF) - MICOM PIN 43
• Check Receiver Assembly

-48-
3. Compressor/Outdoor Fan are unable to drive.

Turn on Main Power

Operate "Cooling Mode( )" by setting the desired temperature of the


remote controller is less than one of the indoor temperature by 1°C at least.

When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.

Check the sensor for indoor temperature is attached as close as to be


effected by the temperature of Heat Exchanger(EVA).

When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.

• Check the related circuit of RY-FAN.


• Check the indoor temperature sensor is disconnected or not(About 10kΩ / at 25°C).

Check Relay(RY - COMP) for driving compressor.

• When the power(About AC220V/240V) is applied to the connecting wire


terminal support transferred to compressor, PWB Assembly is normal.
• Check the circuit related to the relay.
Check point COMP ON COMP OFF
Between Micom(No.
DC5V DC0V
62) and GND
Between IC01M(No. 14) Below DC 1V
About DC12V
and GND (app)

Turn off Main Power

• Check the electrical wiring diagram of outdoor side.


• Check the abnormal condition for the component of Compressor/Out-
door Fan Motor.
• Check the "open" or "short" of conmecting wires between indoor and
outdoor.

-49-
4. When indoor Fan does not operate.

Turn off Main power

Check the connection of CN-MOTOR

Check the Fan Motor

Check the Fuse(AC250V/T2A)

Check the related circuit of indoor Fan Motor.

• The pin NO 58 of Micom, and the part for driving TRIAC(the input and
output signal of IC01M, PIN NO 7, 10)
• Check the pattern
• Check the TRIAC
- TRIAC Open: Indoor Fan Motor never operate
- TRIAC short: Indoor Fan Motor always operates in case of ON or OFF.

Turn ON Main Power

Check the TRIAC high speed operation by remote control.


(The Indoor Fan Motor is connected)

The voltage of PIN NO 1(orange) and 3(yellow) of CN-MOTOR.

About AC 180V over About AC 50V over

TRIAC is not damaged TRIAC Check

-50-
5. When Vertical Louver does not operate.

• Confirm that the Vertical Louver is normally geared with the shaft of
Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with
hands Normal

• Check the connecting condition of CN-U/D Connector


• Check the soldering condition(on PWB) of CN-U/D Connector

Check the operating circuit of the Vertical Louver

• Confirm that there is DC +12V between pin (RED) of CN-U/D and


GND.
• Confirm that there is a soldering short at following terminals.
- Between 60 , 61 , 62 and 63 of MICOM
- Between , , and of IC01M
- Between , , and of IC01M

If there are no problems after above checks

• Confirm the assembly conditions that are catching and interfering parts
in the rotation radial of the Vertical Louver

-51-
6. When Heating does not operate

Turn ON Main Power

Operate “Heating Mode( )” by setting the desired temperature of the


remote control is higher than one of the indoor temperature by 2°C at
least.

In heating Mode, the indoor fan operates in case the pipe temperature
is higher than 28°C.

Check the connector of intake and pipe sensor(thermistors)

• Check the related circuit of RY-4WAY


• Check the indoor room temperature is disconnected or not (about
10KΩ/at 25°C).
• Check the indoor pipe temperature is disconnected or not (about
5KΩ/at 25°C).

Check the DC voltage on the PWB ASSEMBLY

• The details of check are as followings


• Comp Relay. • Outdoor fan Relay

Check point Comp ON Comp OFF Check point Fan ON Fan OFF

Between Micom Between Micom


DC 5V DC 0V DC 5V DC 0V
(NO.59) and GND (NO.53) and GND

Between IC01M Between IC02M


Below DC 1V About DC Below DC 1V About DC 12V
(NO.11) and GND (NO.12) and GND
12V

• 4 way Relay

Check point 4 way ON 4 way OFF

Between Micom
DC 5V DC 0V
(NO.51) and GND

Between IC02M
Below DC 1V About DC 12V
(NO.11) and GND

-52-
Turn off Main Power

• Check the electrical wiring diagram of outdoor side.


• Check the abnormal condition for the component of Compressor/Out-
door Fan Motor, 4 way.
• Check the "open" or "short" of connecting wires between indoor and
outdoor.

-53-
Electronic Control Device
(1) MAIN P.W.B ASSEMBLY (AC PART)
• TOP VIEW • BOTTOM VIEW

(1) MAIN P.W.B ASM (AC)


• COOLING MODEL • HEAT PUMP MODEL

-54-
(2) MAIN P.W.B ASSEMBLY (DC PART)
• TOP VIEW • BOTTOM VIEW

• TOP VIEW • BOTTOM VIEW

-55-
• TOP VIEW • BOTTOM VIEW

6871A20164

6871A20216

6871A20217

6871A20218
6871A20219
6871A20220

-56-
(3) DISPLAY ASSEMBLY

– 6871A20194
TOP VIEW

BOTTOM VIEW

– 6871A30009
TOP VIEW

BOTTOM VIEW

– 6871A20227
TOP VIEW

BOTTOM VIEW

-57-
– 6871A20390
TOP VIEW

BOTTOM VIEW

– 6871A20391
TOP VIEW
C01A
88SEG

BOTTOM VIEW

C01A

-58-
TELEPHONE-CONTROL MODEL ONLY
Schematic Diagram

-59-
Cooling Model
• LED TYPE

-60-
Cooling Model
• HVB TYPE(PLASMA)

-61-
• LED TYPE

Option

STEPPING MOTOR
(LEFT/RIGHT)
DC PART
BL PK YL OR RD TELE (OPTION)
2 3 4 5 1
Heat Pump Model

2 3 4 5 1 C01H
CN-L/R 1uF DC250V

ZD04H~ZD05H ZD04H ZD05H R01H


6.2K/1W
3.9V, 1/2W D01H~D04H 5V 5V
1N4004
5V 5V
C04H
Q02M 1uF
7 R07H 16V
KTC2016 100K OP1 MICOM
STEPPING MOTOR INDOOR FAN 12V CN-PHONE R02H 10K PIC16C54CR
6.2K PC01H
TLP621BL 18
(UP/DOWN) ZD01H 1/4W 1 RA1 TX
6 R01T C01T 3 3 R04H RA2
1 4 R08H 17
COMP C02T 1.5KE56A 2 RA0 RX
CN-U/D 1K 104 2 R19H 4.7K 2K RA3
102 2 2 2.7 1/2W
ZNR01 RY-HOOK 16
HR93F,5V C03H 2 3 OP2 OSC1
5 BSP351L
BL G6A-234P,5V 22uF 10K R01B
5 5 + 50V 3

FAN
1 Q03M R06H T0CLK 1M

4WAY
1 1 15
C03T R18H 2222A 27 OSC2
PK 4 2.7 1/2W R03H R05H 4
102 RST MCLR
4 4 D01T 7.5K 27 5V OSC01B
Q03T Q04T 5V 5 CST-4.00MGW
1N4148 VSS
16 15 14 13 12 11 10 9 A104S CN-TEL 14
YL 3 C104S 6
VDD
3 3 BD RB0 13 Q0
IC02M D01M RB7
C01X
DE 7 0.01uF
KID65004AF 1N4004 RB1 12 Q1
OR 2 5V DSO 8 RB6 50V
R01M RB2
2 2 11 Q2
1 2 3 4 5 6 7 8 4.7K DE RB5
+ C09H
1 1uF 10 Q3
9 RB4
63V Q01M RB3
HVB OUT C3198Y
C02H
RD 9 8 0.1uF/50V
1 1
Q02T Q01T R12H
12V 1K R16H IC-DTMF 5V
A104S C104S C05H 5V R14H R13H 100K
IC01M 0.01uF R15H 750 270 ZD02H HT9170B
100V (ST9170)
10K 2
6 8 VN
KID65004AF BD - 18
VDD
OP-AMP 7
LM358 R17H C02X
5
+ 4 C08H 51K 0.1uF
0.15uF ZD03H C11H T1 3 17 50V
0.1uF TRANS GS RI
R02E,20 63V 50V
5V 1 16
VP
R09H EST
CN-TELE C06H 4
1K ZD02H~ZD03H VREF R01X
0.1uF/50V
DISPLAY BZ01E 5.1V, 1/2W 100K
5V R01E 7
X1
3 + C01D DSO
1K PKM13EPY-4002 15
20K 100uF/25V DV
5V 8
1 X2 14 Q3
R02F 2 D3
R01L 5.1K OSC02B
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 CST-3.58M 13 Q2
Q01T D2
5V A104S TX
2 B 1 5 12 Q1
1 1 1 1 5V 1 48 NC D1
Z Q02T
R02L,1K 6 11
S/W(FORCE) C104S NC Q0
2 D0
3 47 receiver 5V 9
2 2 2 2 C02L VSS 10
NEC DE
+ OE
220uF SD 3 46 C01L 5V
LED1 Operation R01G 220 10V UPD780023AGC-C 680pF/50V C01T R02A
4 4 45 0.001uF R01T 4.7K
3 3 3 3 50V 1K 5V
R01A
1K 1
Sleep R02G 220 5 INT1 44 5V RST 3
LED2 5 RX 3.6V IC01A
4 4 4 4 R07D D01T KIA7036P
6 INT0 43 1N4148 Q04T C02T C01A + R03A 2
12K A104S 10uF 100
Q01C 0.001uF
LED3 Timer R03G 220 Q03T 50V 50V
6 7 Vss1 42 KTC3198-Y INT C104S
5 5 5 5 2SC5343
8 X1 41 R01B R06D
LED4 Defrost R04G 220 7 1M 56K
6 6 6 6 9 Vss0 X2 40
9 8 5V 10 Vdd0 39
5V OSC01B
Vcc 7 7 7 7 receiver CSTS0800MG03-T2 R02A,20K
C01A C04C 11 38 5V
104 CRTL8.00MSOT 5V
IC01G 103 37 C03C 1
GND 8 8 8 8 12
KID65004AF 103 3 IC01A
13 RESET 36 3.6V KIA7036P
Vout S7136
14 A AVdd 35 C01A 2
V A 0.01
RECEIVER 15 d V AVref 34 5V 50V
d s
16 1 s 33
17 18 1920 21 22 23 24 25 26 27 28 29 30 31 32

CN-TH ROOM-TH
5V 4 4
R04H R02H
6.2K 12.1K 3 3
1% 1%
5V 2 2
20K 20K PIPE-TH
1 G Vcc 8 R01P R02P
2012 2012 1 1
Option 2 A2 WP
7

-62-
5V R05H
3 A1 SCL 6
10K
CN-HVB 4 A0 SDA 5

EEPROM
3 3 R22H
CAT24WC01J

2 2 R23H
HVB R14H
R24H
1 1 5V R21H~R26H
R13H 12.1K, 1%
R25H
R11H~R14H R12H
R26H
20K 2012
R11H
3 3 R21H
5V
2 1 2 2 OJ1H OJ2H OJ3H OJ4H
1 1 HVB OUT
CN-CONT OR6H OR5H OR4H OR3H OR2H OR1H
Hi Med Low O/L F2 F1
3 3
2 1 2 2
L2
1 1 12V
10nH
CN-12V 5V INT 4WAY FAN COMP 12V INDOOR FAN

+ C02C
220uF
10V/SD

CN-ACDC2 8 7 6 5 4 3 2 1

AC PART
CN-ACDC 1 2 3 4 5 6 7 8 INDOOR
CN-MOTOR FAN
MOTOR
INT 3 3
12V INDOOR FAN
R03J
680 2 2 SH-CAPACITOR
5V 12V 12V
1
1/2W
RY-COMP 12V 5 1 1
RY-4WAY R04J 2
12V 560 4
1/4W 3
RY-FAN T2 R01J
INDOOR FAN TR01J 120, 1/2W
IC01J
TLP762JF TRAICS ZNR02J
SM1L43 TVR10561 C03J
T1 METAL FILM
100nF/275V/436D

IC04D L1 D01A D01B R02J TERMINAL BOARD


S78DL05L 1W 12V C03D D05D IN4007
ZBF503D NTC SCK-102 IN4007 100,1/2W
681 SMPS 1N4007 OUTDOOR
O I
5V 7805 FAN MOTOR
D07D
UG2D D01C D01D 12V 1 1 12V
C07D C06D R03D + 5V 5 5
C04D SD01D IN4007 IN4007 4
103 330 39 NF01J
470/35V/SD STO2D-200 R05D FUSE RY-COMP 2 3 RY-COMP 4 4
25V 25V SD 1/6W 15mH/1A 3
R04D 300K 250V/T2A
27k 1/4W 6 6 4-WAY
+ C09D C08D 1/6W 3216
+
220 103 C01D INT C02J C01J
8 9 2 2
ZNR01J 2(N)
10V SD 25V D 5 4.7uF METAL FILM METAL FILM TVR10561
1 4 1 47nM/275V/435D 100nM/275V/436D 4 1 1
R02D 450V/SD 4 11 12 1(L)
IC02D EN 4 3 COMPRESSOR
20K TLP421(V4 BL) D08D
1/6W R06D
2 3 LL4148 13 15 1
BP 1 IC01D 2 300K RY-COMP
3 1/4W 3 4
C02D IC03D G4A-1A-E-LG
TNY266P RY-4WAY
ZD02D C05D 104 TLP421(V4 BL) L
S 2 G5N-1A(G5NB-1A)
BZX55C11 472M 50V 3 4 1 1
N
DC LOW DC HIGH DC HIGH DC LOW DC HIGH RY-FAN CN-TAB1
G5N-1A(G5NB-1A)
VOLTAGE GND VOLTAGE GND VOLTAGE GND VOLTAGE GND VOLTAGE GND
AC220~240V
50/60Hz
Option
• HVB TYPE

STEPPING MOTOR
(LEFT/RIGHT)
DC PART
BL PK YL OR RD TELE (OPTION)
2 3 4 5 1

2 3 4 5 1 C01H
CN-L/R 1uF DC250V
Heat Pump Model

ZD04H~ZD05H ZD04H ZD05H R01H


6.2K/1W
3.9V, 1/2W D01H~D04H 5V 5V
1N4004
5V 5V
C04H
Q02M 1uF
7 R07H 16V
KTC2016 100K OP1 MICOM
STEPPING MOTOR INDOOR FAN 12V CN-PHONE R02H 10K PIC16C54CR
6.2K PC01H
TLP621BL 18
(UP/DOWN) ZD01H 1/4W 1 RA1 TX
6 R01T C01T 3 3 R04H RA2
1 4 R08H 17
COMP C02T 1.5KE56A 2 RA0 RX
CN-U/D 1K 104 2 R19H 4.7K 2K RA3
102 2 2 2.7 1/2W
ZNR01 RY-HOOK 16
HR93F,5V C03H 2 3 OP2 OSC1
5 BSP351L
BL G6A-234P,5V 22uF 10K R01B
5 5 + 50V 3

FAN
1 Q03M R06H T0CLK 1M

4WAY
1 1 15
C03T R18H 2222A 27 OSC2
PK 4 2.7 1/2W R03H R05H 4
102 RST MCLR
4 4 D01T 7.5K 27 5V OSC01B
Q03T Q04T 5V 5 CST-4.00MGW
1N4148 VSS
16 15 14 13 12 11 10 9 A104S CN-TEL 14
YL 3 C104S 6
VDD
3 3 BD RB0 13 Q0
IC02M D01M RB7
C01X
DE 7 0.01uF
KID65004AF 1N4004 RB1 12 Q1
OR 2 5V DSO 8 RB6 50V
R01M RB2
2 2 11 Q2
1 2 3 4 5 6 7 8 4.7K DE RB5
+ C09H
1 1uF 10 Q3
9 RB4
63V Q01M RB3
HVB OUT C3198Y
C02H
RD 9 8 0.1uF/50V
1 1
Q02T Q01T R12H
12V 1K R16H IC-DTMF 5V
A104S C104S C05H 5V R14H R13H 100K
IC01M 0.01uF R15H 750 270 ZD02H HT9170B
100V (ST9170)
10K 2
6 8 VN
KID65004AF BD - 18
VDD
DISPLAY OP-AMP
LM358
7
R17H C02X
5
+ 4 C08H 51K 0.1uF
0.15uF ZD03H C11H T1 3 17 50V
0.1uF TRANS GS RI
R02E,20 63V 50V
5V 1 16
VP
R09H EST
CN-TELE C06H 4
1K ZD02H~ZD03H VREF R01X
0.1uF/50V
CN-DISP1 BZ01E 5.1V, 1/2W 100K
R01E 7
X1
3 + C01D DSO
R17H 1K PKM13EPY-4002 15
100uF/25V DV
1 1 1 1 7 5V 8
X2 14 Q3
LED4 2 D3
OUTDOOR R16H 6 R01L 5.1K OSC02B
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 CST-3.58M 13 Q2
2 2 Q01T D2
LED3 2 2 5V A104S TX
B 1 5 12 Q1
R15H 1 48 NC D1
3 4 TIMER 5 Q02T
Z R02L,1K 6
NC 11
3 3 3 3 C104S Q0
2 D0
47 receiver 5V 9
R14H VSS 10
4 NEC DE
OE
4 4 4 4 3 46 C01L 5V
UPD780023AGC-C 680pF/50V C01T R02A
R13H 3 4 45 0.001uF R01T 4.7K
50V 1K 5V
LED2 5 5 5 5 R01A
A B C 1K 1
5 INT1 44 5V RST 3
SLEEP R12H 2 RX 3.6V IC01A
R07D D01T KIA7036P
6 6 6 6 6 INT0 43 1N4148 Q04T C02T C01A + R03A 2
LED1 12K A104S 10uF 100
Q01C 0.001uF
OPERATION R11H 1 Q03T 50V 50V
7 Vss1 42 KTC3198-Y INT C104S
7 7 7 7
9 8 R01B 2SC5343
5V 8 X1 41 R06D
2 1 R11H~R17H C04C 1M 56K
220 1/8W IC01G 9 Vss0 X2 40
CN-DISP2
KID65004AF 5V 10 Vdd0 39 OSC01B
8 8 8 8 103 CSTS0800MG03-T2 R02A,20K
11 38 5V 5V
CRTL8.00MSOT
12 37 C03C 1
7 7 7 7 receiver 103 3 IC01A
Q13G Force 13 RESET 36 3.6V KIA7036P
KRA107S
6 6 6 6 20K A 35 S7136
14 AVdd C01A 2
R02F V A 0.01
5 5 5 5 15 d V AVref 34 5V
Q12G 50V
KRA107S d s
4 4 4 4 5V 16 1 s 33

Vcc Q11G
17 18 1920 21 22 23 24 25 26 27 28 29 30 31 32
3 3 3 3
KRA107S
GND
C01A
Vout 104 2 2 2 2 CN-TH ROOM-TH
5V 5V
RECEIVER 1 1 1 1 Force + C02L
4 4
SW(FORCE) R04H R02H
220uF SD 6.2K 12.1K 3 3
10V 1% 1%
5V 2 2
20K 20K PIPE-TH
1 G Vcc 8 R01P R02P
2012 2012 1 1
Option 2 A2 WP
7

-63-
5V R05H
3 A1 SCL 6
10K
CN-HVB 4 A0 SDA 5

EEPROM
3 3 R22H
CAT24WC01J

2 2 R23H
HVB R14H
R24H
1 1 5V R21H~R26H
R13H 12.1K, 1%
R25H
R11H~R14H R12H
R26H
20K 2012
R11H
3 3 R21H
5V
2 1 2 2 OJ1H OJ2H OJ3H OJ4H
1 1 HVB OUT
CN-CONT OR6H OR5H OR4H OR3H OR2H OR1H
Hi Med Low O/L F2 F1
3 3
2 1 2 2
L2
1 1 12V
10nH
CN-12V 5V INT 4WAY FAN COMP 12V INDOOR FAN

+ C02C
220uF
10V/SD

CN-ACDC2 8 7 6 5 4 3 2 1

AC PART
CN-ACDC 1 2 3 4 5 6 7 8 INDOOR
CN-MOTOR FAN
MOTOR
INT 3 3
12V INDOOR FAN
R03J
680 2 2 SH-CAPACITOR
5V 12V 12V
1
1/2W
RY-COMP 12V 5 1 1
RY-4WAY R04J 2
12V 560 4
1/4W 3
RY-FAN T2 R01J
INDOOR FAN TR01J 120, 1/2W
IC01J
TLP762JF TRAICS ZNR02J
SM1L43 TVR10561 C03J
T1 METAL FILM
100nF/275V/436D

IC04D L1 D01A D01B R02J TERMINAL BOARD


S78DL05L 1W 12V C03D D05D IN4007
ZBF503D NTC SCK-102 IN4007 100,1/2W
681 SMPS 1N4007 OUTDOOR
O I
5V 7805 FAN MOTOR
D07D
UG2D D01C D01D 12V 1 1 12V
C07D C06D R03D + 5V 5 5
C04D SD01D IN4007 IN4007 4
103 330 39 NF01J
470/35V/SD STO2D-200 R05D FUSE RY-COMP 2 3 RY-COMP 4 4
25V 25V SD 1/6W 15mH/1A 3
R04D 300K 250V/T2A
27k 1/4W 6 6 4-WAY
+ C09D C08D 1/6W 3216
+
220 103 C01D INT C02J C01J
8 9 2 2
ZNR01J 2(N)
10V SD 25V D 5 4.7uF METAL FILM METAL FILM TVR10561
1 4 1 47nM/275V/435D 100nM/275V/436D 4 1 1
R02D 450V/SD 4 11 12 1(L)
IC02D EN 4 3 COMPRESSOR
20K TLP421(V4 BL) D08D
1/6W R06D
2 3 LL4148 13 15 1
BP 1 IC01D 2 300K RY-COMP
3 1/4W 3 4
C02D IC03D G4A-1A-E-LG
TNY266P RY-4WAY
ZD02D C05D 104 TLP421(V4 BL) L
S 2 G5N-1A(G5NB-1A)
BZX55C11 472M 50V 3 4 1 1
N
DC LOW DC HIGH DC HIGH DC LOW DC HIGH RY-FAN CN-TAB1
G5N-1A(G5NB-1A)
VOLTAGE GND VOLTAGE GND VOLTAGE GND VOLTAGE GND VOLTAGE GND
AC220~240V
50/60Hz
Exploded View and Replacement Parts List
1. Indoor Unit
135312

152313
135314

152302

131410 733010

359011
267110

342800
159830

135311

159901

268712 346810
249951 35211B
354212 135516

TYPE B 249951 TYPE A


352150 263230
268714-2
268714-1
146811-2
146811-1
268714-1 264110 264110
266090 268714-2
266090

W0CZZ
W6640 263230 263232

-64-
Parts List(Indoor)
PART No.
LOCATION No. DESCRIPTION REMARKS
LS-Q076ABL LS-Q076BBG LS-Q076BEL
131410 CHASSIS ASSEMBLY 3141A20006A 3141A20006B 3141A20006A R
135311 GRILLE ASSEMBLY, DISCHARGE(INDOOR) 3531A10127A 3531A10127E 3531A10127E R
135312 GRILLE ASSEMBLY, FRONT(INDOOR) 3531A20101B 3531A20103B 3531A20101E R
135314 GRILLE ASSEMBLY, INLET SUB 3531A20100B 3531A20102D 3531A20100C R
135516 COVER ASSEMBLY, MOTOR 3551A20050H 3551A20050H 3551A20050H R
146811 MOTOR ASSEMBLY, STEP 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH), A/C 5230A10005A 5230A10005A 5230A10005A R
152313 FILTER ASSEMBLY, DEODORIZER 5231AR2412T 5231A30001C 5231A30001C R
159830 AIR CLEANER ASSEMBLY - 5983A10009B 5983A10009D R
159901 VANE, HORIZONTAL 5990A10005A 5990A10005A 5990A10005A R
4995A20199R 4995A20199T 4995A20199T
249951 CONTROL BOX ASSEMBLY, INDOOR R
(4995A20257J) 4995A20257K) 4995A20257K)
263230 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A 6323A20004A R
6411A20013D 6411A20013D 6411A20013D
264110 POWER CORD ASSEMBLY R
(6411A20026D) (6411A20026D) (6411A20026D)
266090 H.V ASSEMBLY - 6609A10003J 6609A10003J R
6711A20010B
267110 REMOTE CONTROLLER ASSEMBLY 6711A20010F 6711A20010F R
(6711A20067G)
6871A20194A 6871A20227D 6871A20227D
268712 PWB(PCB) ASSEMBLY, DISPLAY R
(6871A20194F) (6871A20227G) (6871A20227G)
6871A20163A 6871A20163A 6871A20163A
268714-1 PWB(PCB) ASSEMBLY, MAIN(AC) R
(6871A20272J) (6871A20272J) (6871A20272J)
6871A20218Q 6871A20225L 6871A20225L
268714-2 PWB(PCB) ASSEMBLY, MAIN(DC) R
(6871A20310B) (6871A20310C) (6871A20310C)
342800 BEARING 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY, INDOOR 4681A20062D 4681A20062D 4681A20062D R
352150 HOSE ASSEMBLY, DRAIN 5251AR2575F 5251AR2575F 5251AR2575F R
354211 EVAPORATOR ASSEMBLY, BENDING 5421A10025C 5421A10025C 5421A10025G R
359011 FAN ASSEMBLY, CROSS FLOW 5901A20007B 5901A20007B 5901A20007B R
35211B TUBE ASSEMBLY, TUBING 5211AR7066P 5211AR7066P 5211AR7066P R
733010 PLATE ASSEMBLY, INSTALL 3301A10003A 3301A10003A 3301A10003A R
W0CZZ CAPACITOR, DRAWING 3H01487A 3H01487A 3H01487A R
W6640 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20283A 6871A20283A 6871A20283A R

NOTE) * Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
1) TYPE A : ~2002
2) TYPE B : 2003~

-65-
Parts List(Indoor)

LOCATION PART No.


DESCRIPTION REMARKS
No. LS-Q096ABL LS-Q096BBG LS-Q096BEL LS-Q096AEM LS-Q096BEG
131410 CHASSIS ASSEMBLY 3141A20006A 3141A20006B 3141A20006A 3141A20006A 3141A20006A R
135311 GRILLE ASSEMBLY, DISCHARGE(INDOOR) 3531A10127A 3531A10127E 3531A10127E 3531A10232J 3531A10127R R
135312 GRILLE ASSEMBLY, FRONT(INDOOR) 3531A20101B 3531A20103B 3531A20101E 3531A10167C 3531A10225E R
135314 GRILLE ASSEMBLY, INLET SUB 3531A20100B 3531A20102D 3531A20100C 3531A20142A 3531A20102X R
135516 COVER ASSEMBLY, MOTOR 3551A20050H 3551A20050H 3551A20050H 3551A20050H 3551A20050H R
146811 MOTOR ASSEMBLY, STEP 4681A20055A 4681A20055A 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH), A/C 5230A10005A 5230A10005A 5230A10005A 5230A10005A 5230A10005A R
152313 FILTER ASSEMBLY, DEODORIZER 5231AR2412T 5231A30001C 5231A30001C - 5231A30001C R
159830 AIR CLEANER ASSEMBLY - 5983A10009B 5983A10009D - 5983A10009B R
159901 VANE, HORIZONTAL 5990A10005A 5990A10005A 5990A10005A 5990A10005A 5990A10005A R
4995A20199H 4995A20199J 4995A20199J
249951 CONTROL BOX ASSEMBLY, INDOOR 4995A20257G 4995A20257S R
(4995A20257B) (4995A20257D) (4995A20257D)
263230 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A 6323A20004A 6323A20004K 6323A20004K R
6411A20013D 6411A20013D 6411A20013D
264110 POWER CORD ASSEMBLY 6411A20026E 6411A20026E R
(6411A20026D) (6411A20026D) (6411A20026D)
266090 H.V ASSEMBLY - 6609A10003J 6609A10003J - 6609A10003N R
6711A20010B 6711A20010F 6711A20010F
267110 REMOTE CONTROLLER ASSEMBLY 6711A20012M 6711A20083G R
(6711A20067G) (6711A20067J) (6711A20067J)
6871A20194A 6871A20227D 6871A20227D
268712 PWB(PCB) ASSEMBLY, DISPLAY 6871A20390C 6871A20227G R
(6871A20194F) (6871A20227G) (6871A20227G)
6871A20163A 6871A20163A 6871A20163A
268714-1 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20272A 6871A20272A R
(6871A20272A) (6871A20272A) (6871A20272A)
6871A20218H 6871A20225N 6871A20225N
268714-2 PWB(PCB) ASSEMBLY, MAIN(DC) 6871A20310G 6871A20310J R
(6871A20310G) (6871A20310J) (6871A20310J)
342800 BEARING 4280A20004A 4280A20004A 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY, INDOOR 4681A20062A 4681A20062A 4681A20062A 4681A20062A 4681A20062A R
352150 HOSE ASSEMBLY, DRAIN 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F 5211AR7066P R
354212 EVAPORATOR ASSEMBLY, BENDING 5421A10025B 5421A10025B 5421A10025E 5421A10025E 5251AR2575F R
359011 FAN ASSEMBLY, CROSS FLOW 5901A20007B 5901A20007B 5901A20007B 5901A20007B 5421A10025E R
35211B TUBE ASSEMBLY, TUBING 5211AR7066P 5211AR7066P 5211AR7066P 5211AR7066P 5901A20007B R
733010 PLATE ASSEMBLY, INSTALL 3301A10003A 3301A10003A 3301A10003A 3301A10003A 3301A10003A R
W0CZZ CAPACITOR, DRAWING 3H01487A 3H01487A 3H01487A 3H01487A 3H01487A R
W6640 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20283A 6871A20283A 6871A20283A 6871A20283A 6871A20283A R

NOTE) * Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
1) TYPE A : ~2002
2) TYPE B : 2003~

-66-
Parts List(Indoor)
LOCATION PART No.
DESCRIPTION REMARKS
No. LS-Q096AHG LS-Q096ACG LS-Q096BAG LS-Q096ACL LS-Q096AAG
131410 CHASSIS ASSEMBLY 3141A20006B 3141A20006B 3141A20006B 3141A20006B 3141A20006A R
135311 GRILLE ASSEMBLY, DISCHARGE(INDOOR) 3531A10127H 3531A10127H 3531A10127H 3531A10127H 3531A10127P R
135312 GRILLE ASSEMBLY, FRONT(INDOOR) 3531A20103H 3531A20103A 3531A20103J 3531A20101K 3531A20103U R
135314 GRILLE ASSEMBLY, INLET SUB 3531A20102H 3531A20102A 3531A20102J 3531A20100H 3531A20102A R
135516 COVER ASSEMBLY, MOTOR 3551A20050H 3551A20050E 3551A20050E 3551A20050E 3551A20050E R
146811 MOTOR ASSEMBLY, STEP 4681A20055A 4681A20055A 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH), A/C 5230A10005A 5230A10005A 5230A10005A 5230A10005A 5230A10005A R
152313 FILTER ASSEMBLY, DEODORIZER - - 5231A30001C 5231AR2412T - R
159830 AIR CLEANER ASSEMBLY - - 5983A10009B - - R
159901 VANE, HORIZONTAL 5990A10005A 5990A10005A 5990A10005A 5990A10005A 5990A10005A R
4995A20199H 4995A20199A 4995A20199Z
249951 CONTROL BOX ASSEMBLY, INDOOR 4995A20232A 4995A20257A R
(4995A20257B) (4995A20257A) (4995A20257C)
263230 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A 6323A20004A 6323A20004A 6323A20004L R
6411A20013D 6411A20013D 6411A20013D 6411A20013D 6411A20026D R
264110 POWER CORD ASSEMBLY
(6411A20026D) (6411A20026D) (6411A20026D)
266090 H.V ASSEMBLY - - 6609A10003J 6609A10003J - R
6711A20010B 6711A20010A 6711A20010E
267110 REMOTE CONTROLLER ASSEMBLY 6711A20010A 6711A20067E R
(6711A20067G) (6711A20067E) (6711A20067H)
6871A20194A 6871A20194A 6871A20227D
268712 PWB(PCB) ASSEMBLY, DISPLAY 6871A20390A 6871A20294F R
(6871A20390C) (6871A20390C) (6871A20227G)
6871A20163A 6871A20163B 6871A20163B 6871A20272B
268714-1 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20163B R
(6871A20272A) (6871A20272K) (6871A20272K) (6871A20283B)
6871A20218H 6871A20218A 6871A20225P
268714-2 PWB(PCB) ASSEMBLY, MAIN(DC) 6871A20218A 6871A20310E R
(6871A20310G) (6871A20310E) (6871A20310H)
342800 BEARING 4280A20004A 4280A20004A 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY, INDOOR 4681A20062A 4681A20062A 4681A20062A 4681A20062A 4681A20062A R
352150 HOSE ASSEMBLY, DRAIN 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F R
354211 EVAPORATOR ASSEMBLY, BENDING 5421A10025B 5421A10025B 5421A10025B 5421A10025B 5421A10025A R
359011 FAN ASSEMBLY, CROSS FLOW 5901A20007B 5901A20007B 5901A20007B 5901A20007B 5901A20007B R
35211B TUBE ASSEMBLY, TUBING 5211AR7066P 5211AR7066P 5211AR7066P 5211AR7066P 5211AR7066P R
733010 PLATE ASSEMBLY, INSTALL 3301A10003A 3301A10003A 3301A10003A 3301A10003A 3301A10003A R
W0CZZ CAPACITOR, DRAWING 3H01487A 3H01487A 3H01487A 3H01487A 3H01487A R
263232 CABLE, FLAT - - - 6850A90001C - R
W6640 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20283B 6871A20283B 6871A20283B - 6871A20283B R

NOTE) * Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
1) TYPE A : ~2002
2) TYPE B : 2003~

-67-
Parts List(Indoor)

LOCATION PART No.


DESCRIPTION REMARKS
No. LS-Q096ABG LS-Q076ABG LS-Q082BAG LS-Q082BDL LS-N096QNA0
131410 CHASSIS ASSEMBLY 3141A20006A 3141A20006A 3141A20006A 3141A20006A 3141A20006A R
135311 GRILLE ASSEMBLY, DISCHARGE(INDOOR) 3531A10127A 3531A10127A 3531A10127E 3531A10127A 3531A10127P R
135312 GRILLE ASSEMBLY, FRONT(INDOOR) 3531A20101B 3531A20101B 3531A20103J 3531A20101T 3531A10194K R
135314 GRILLE ASSEMBLY, INLET SUB 3531A20100B 3531A20100B 3531A20102J 3531A20100R 3531A20153K R
135516 COVER ASSEMBLY, MOTOR 3551A20050H 3551A20050H 3551A20050E 3551A20050E 3551A20050H R
146811 MOTOR ASSEMBLY, STEP 4681A20055A 4681A20055A 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH), A/C 5230A10005A 5230A10005A 5230A10005A 5230A10005A 5230A10005C R
152313 FILTER ASSEMBLY, DEODORIZER 5231AR2412T 5231AR2412T 5231A30001C 5231A30001C - R
159830 AIR CLEANER ASSEMBLY - - 5983A10009B 5983A10009B - R
159901 VANE, HORIZONTAL 5990A10005A 5990A10005A 5990A10005A 5990A10005A 5990A10005A R
4995A20199H 4995A20199R
249951 CONTROL BOX ASSEMBLY, INDOOR 4995A20199W 4995A20199L 4995A20257T R
(4995A20257B) (4995A20257J)
263230 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A 6323A20004A 6323A20004A 6323A20004K R
6411A20013D 6411A20013D
264110 POWER CORD ASSEMBLY 6411A20013D 6411A20013D 6411A20026E R
(6411A20026D) (6411A20026D)
266090 H.V ASSEMBLY - - 6609A10003J 6609A10003J - R
6711A20010B 6711A20010B
267110 REMOTE CONTROLLER ASSEMBLY 6711A20010E 6711A20010E 6711A20028B R
(6711A20067G) (6711A20067G)
6871A20194A 6871A20194A
268712 PWB(PCB) ASSEMBLY, DISPLAY 6871A20391C 6871A20391C 6871A20194F R
(6871A20194F) (6871A20194F)
6871A20163A 6871A20163A
268714-1 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20163B 6871A20163B 6871A20272R R
(6871A20272A) (6871A20272J)
6871A20218H 6871A20218Q
268714-2 PWB(PCB) ASSEMBLY, MAIN(DC) 6871A20235A 6871A20225P 6871A20310G R
(6871A20310G) (6871A20310B)
342800 BEARING 4280A20004A 4280A20004A 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY, INDOOR 4681A20062A 4681A20062D 4681A20062E 4681A20062A 4681A20062A R
352150 HOSE ASSEMBLY, DRAIN 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F 5211AR7066P R
354211 EVAPORATOR ASSEMBLY, FINAL 5421A10025B 5421A10025C 5421A10025A 5421A10025F 5251AR2575F R
359011 FAN ASSEMBLY, CROSS FLOW 5901A20007B 5901A20007B 5901A20007B 5901A20007B 5421A10025B R
35211B TUBE ASSEMBLY, TUBING 5211AR7066P 5211AR7066P 5211AR7066P 5211AR7066P 5901A20007B R
733010 PLATE ASSEMBLY, INSTALL 3301A10003A 3301A10003A 3301A10003A 3301A10003A 3301A10003A R
W0CZZ CAPACITOR, DRAWING 3H01487A 3H01487A 3H01487A 3H01487A 3H01487A R
263232 CABLE, FALT 6850A90001C 6850A90001C 6850A90001C 6850A90001C - R
W6640 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20283A 6871A20283A - - 6871A20283A R
NOTE) * Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
1) TYPE A : ~2002
2) TYPE B : 2003~

-68-
Parts List(Indoor)
LOCATION PART No.
DESCRIPTION REMARKS
No. LS-Q096AEL LS-Q096ADG LS-Q096ADL LS-Q096BDG LS-Q096ABM
131410 CHASSIS ASSEMBLY 3141A20006A 3141A20006B 3141A20006A 3141A20006B 3141A20006B R
135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A10127A 3531A10127A 3531A10127A 3531A10127E 3531A10127P R
135312 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A20101B 3531A20103A 3531A20101A 3531A20103J 3531A10167F R
135314 GRILLE ASSEMBLY,INLET SUB 3531A20100B 3531A20102A 3531A20100A 3531A20102J 3531A20142D R
135516 COVER ASSEMBLY,MOTOR 3551A20050H 3551A20050E 3551A20050E 3551A20050E 3551A20050H R
146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH),A/C 5230A10005A 5230A10005A 5230A10005A 5230A10005A 5230A10005A R
152313 FILTER ASSEMBLY,DEODORIZER - - - 5231A30001C - R
159830 AIR CLEANER ASSEMBLY - - - 5983A10009B - R
159901 VANE,HORIZONTAL 5990A10005A 5990A10005A 5990A10005A 5990A10005A 5990A10005A R
4995A20232C 4995A20199A 4995A20232B 4995A20199L
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20257B R
(4995A20257G) (4995A20257A) (4995A20257A) (4995A20257C)
263230 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A 6323A20004C 6323A20004C 6323A20004K R
6411A20013T 6411A20013D 6411A20013T 6411A20013D
264110 POWER CORD ASSEMBLY 6411A20026D R
(6411A20026E) (6411A20026D) (6411A20026D) (6411A20026D)
266090 H.V ASSEMBLY - - - 6609A10003J - R
6711A20028B
267110 REMOTE CONTROLLER ASSEMBLY 6711A20010A 6711A20028A 6711A20010E 6711A20010B R
(6711A20067S)
6871A20194A 6871A20194A 6871A20194A 6871A20227D
268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20194F R
(6871A20390C) (6871A20390C) (6871A20390C) (6871A20391G)
6871A20163A 6871A20163B 6871A20163B 6871A20163B
268714-1 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20272A R
(6871A20272A) (6871A20272K) (6871A20272K) (6871A20272K)
6871A20218H 6871A20218A 6871A20218A 6871A20225P
268714-2 PWB(PCB) ASSEMBLY,MAIN(DC) 6871A20310G R
(6871A20310G) (6871A20310E) (6871A20310E) (6871A20310H)
342800 BEARING 4280A20004A 4280A20004A 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY,INDOOR 4681A20062A 4681A20062A 4681A20062A 4681A20062A 4681A20062A R
352150 HOSE ASSEMBLY,DRAIN 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F R
354211 EVAPORATOR ASSEMBLY,BENDING 5421A10025E 5421A10025F 5421A10025F 5421A10025F 5421A10025B R
359011 FAN ASSEMBLY,CROSS FLOW 5901A20007B 5901A20007B 5901A20007B 5901A20007B 5901A20007B R
35211B TUBE ASSEMBLY,TUBING 5211AR7066P 5211AR7066P 5211AR7066P 5211AR7066P 5211AR7066P R
733010 PLATE ASSEMBLY,INSTALL 3301A10003A 3301A10003A 3301A10003A 3301A10003A 3301A10003A R
W0CZZ CAPACITOR,DRAWING 3H01487A 3H01487A 3H01487A 3H01487A 3828A20243C R
263232 CABLE,FLAT - - - 6850A90001C 3H01487A R
W6640 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20283A 6871A20283B 6871A20283B 6871A20283B 6871A20283A R

NOTE) * Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
1) TYPE A : ~2002
2) TYPE B : 2003~

-69-
Parts List(Indoor)
LOCATION PART No.
DESCRIPTION REMARKS
No. LS-Q082BAM LS-Q082AAL LS-Q082ACG LS-Q082ACL LS-Q082ACM
131410 CHASSIS ASSEMBLY 3141A20006B 3141A20006B 3141A20006A 3141A20006A 3141A20006A R
135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A10127R 3531A10127A 3531A10127A 3531A10127A 3531A10127A R
135312 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A10167G 3531A20101R 3531A20103G 3531A20101K 3531A10167H R
135314 GRILLE ASSEMBLY,INLET SUB 3531A20142E 3531A20100P 3531A20102G 3531A20100H 3531A20142F R
135516 COVER ASSEMBLY,MOTOR 3551A20050E 3551A20050E 3551A20050E 3551A20050E 3551A20050E R
146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH),A/C 5230A10005A 5230A10005A 5230A10005A 5230A10005A 5230A10005A R
152313 FILTER ASSEMBLY,DEODORIZER 5231A30001C - 5231AR2412T 5231AR2412T 5231AR2412T R
159830 AIR CLEANER ASSEMBLY 5983A10009C - - - - R
159901 VANE,HORIZONTAL 5990A10005A 5990A10005A 5990A10005A 5990A10005A 5990A10005A R
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20257N 4995A20232N 4995A20232R 4995A20232R 4995A20232R R
263230 THERMISTOR ASSEMBLY 6323A20004L 6323A20004C 6323A20004C 6323A20004C 6323A20004C R
264110 POWER CORD ASSEMBLY 6411A20015H 6411A20015B 3H03671F 3H03671F 3H03671F R
267110 REMOTE CONTROLLER ASSEMBLY 6711A20069B 6711A20069A 6711A20067V 6711A20067V 6711A20067V R
268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20391G 6871A20390A 6871A20390A 6871A20390A 6871A20390A R
268714-1 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20272K 6871A20163B 6871A20163B 6871A20163B 6871A20163B R
268714-2 PWB(PCB) ASSEMBLY,MAIN(DC) 6871A20310D 6871A20218V 6871A20218V 6871A20218V 6871A20218V R
342800 BEARING 4280A20004A 4280A20004A 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY,INDOOR 4681A20062E 4681A20062E 4681A20062E 4681A20062E 4681A20062E R
352150 HOSE ASSEMBLY,DRAIN 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F R
354211 EVAPORATOR ASSEMBLY,FINAL 5421A10025A 5211AR7066P 5421A10025A 5421A10025A 5421A10025A R
359011 FAN ASSEMBLY,CROSS FLOW 5901A20007B 5421A10025A 5901A20007B 5901A20007B 5901A20007B R
35211B TUBE ASSEMBLY,TUBING 5211AR7066P 5901A20007B 5211AR7066P 5211AR7066P 5211AR7066P R
733010 PLATE ASSEMBLY,INSTALL 3301A10003A 3301A10003A 3301A10003A 3301A10003A 3301A10003A R
W0CZZ CAPACITOR,DRAWING 3H01487A 3H01487A 3H01487A 3H01487A 3H01487A R
W6640 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20283B - - - - R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

-70-
Parts List(Indoor)
LOCATION PART No.
DESCRIPTION REMARKS
No. LS-C082QMA0 LS-C082QNA0 LS-C096QGL0
131410 CHASSIS ASSEMBLY 3141A20006A 3141A20006A 3141A20006A R
135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A10232B 3531A10232B 3531A10232B R
135312 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A21013A 3531A21021A 3531A21013A R
135314 GRILLE ASSEMBLY,INLET SUB - - - R
135516 COVER ASSEMBLY,MOTOR 3551A20099F 3551A20099F 3551A20099F R
146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH),A/C 5230A10005A 5230A10005A 5230A10005A R
152313 FILTER ASSEMBLY,DEODORIZER 5231A20032E 5231A20032E 5231A20032E R
159830 AIR CLEANER ASSEMBLY - - - R
159901 VANE,HORIZONTAL 5990A10005A 5990A10005A 5990A10005A R
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20232R 4995A20232R 4995A20232R R
263230 THERMISTOR ASSEMBLY 6323A20004C 6323A20004C 6323A20004C R
264110 POWER CORD ASSEMBLY 3H03671F 3H03671F 3H03671F R
266090 H.V ASSEMBLY - - - R
267110 REMOTE CONTROLLER ASSEMBLY 6711A20067V 6711A20067V 6711A20067V R
268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20390A 6871A20390A 6871A20390A R
268714-1 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20163B 6871A20163B 6871A20163B R
268714-2 PWB(PCB) ASSEMBLY,MAIN(DC) 6871A20218V 6871A20218V 6871A20218V R
342800 BEARING 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY,INDOOR 4681A20062E 4681A20062E 4681A20062E R
35211B TUBE ASSEMBLY,TUBING 5211A21046H 5211A21046H 5211A21046H R
352150 HOSE ASSEMBLY,DRAIN 5251AR2575F 5251AR2575F 5251AR2575F R
354211 EVAPORATOR ASSEMBLY,FINAL 5421A10038A 5421A10038A 5421A10038A R
359011 FAN ASSEMBLY,CROSS FLOW 5901A20007E 5901A20007E 5901A20007E R
733010 PLATE ASSEMBLY,INSTALL 3301A10003A 3301A10003A 3301A10003A R
W0CZZ CAPACITOR,DRAWING 3H01487A 3H01487A 3H01487A R
263232 CABLE,FLAT - - - R
W6640 PWB(PCB) ASSEMBLY,SUB 6871A20283B 6871A20283B 6871A20283B R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

-71-
Parts List(Indoor)
LOCATION PART No.
DESCRIPTION REMARKS
No. LS-C096QLA0 LS-C096QNA0 LS-H096QGL1
131410 CHASSIS ASSEMBLY 3141A20006A 3141A20006C 3141A20006A R
135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A10127P 3531A10127X 3531A10127R R
135312 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A21014E 3531A21021B 3531A20103B R
135314 GRILLE ASSEMBLY,INLET SUB - - 3531A20102D R
135516 COVER ASSEMBLY,MOTOR 3551A20050E 3551A20050E 3551A20050H R
146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH),A/C 5230A10005A 5230A10005A 5230A10005A R
152313 FILTER ASSEMBLY,DEODORIZER 5231A20032E 5231A20032E 5231A20032C R
159830 AIR CLEANER ASSEMBLY - - 5983A10009V R
159901 VANE,HORIZONTAL 5990A10005A 5990A10005A 5990A10005A R
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20424B 4995A20424B 4995A20257U R
263230 THERMISTOR ASSEMBLY 6323A20004L 6323A20004L 6323A20004K R
264110 POWER CORD ASSEMBLY 6411A20043C 6411A20043C 6411A20026D R
266090 H.V ASSEMBLY - - 6609A10003N R
267110 REMOTE CONTROLLER ASSEMBLY 6711A20067E 6711A20067E 6711A20077L R
268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20194F 6871A20194F 6871A20227G R
268714-1 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20272K 6871A20272K 6871A20272A R
268714-2 PWB(PCB) ASSEMBLY,MAIN(DC) 6871A20310E 6871A20310E 6871A20310M R
342800 BEARING 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY,INDOOR 4681A20062L 4681A20062L 4681A20062L R
35211B TUBE ASSEMBLY,TUBING 5211A21046H 5211A21046H 5211A21046H R
352150 HOSE ASSEMBLY,DRAIN 5251AR2575F 5251AR2575F 5251AR2575F R
354211 EVAPORATOR ASSEMBLY,FINAL 5421A10038A 5421A10038A 5421A10038G R
359011 FAN ASSEMBLY,CROSS FLOW 5901A20007E 5901A20007E 5901A20007E R
733010 PLATE ASSEMBLY,INSTALL 3301A10003A 3301A10003A 3301A10003A R
W0CZZ CAPACITOR,DRAWING 3H01487A 3H01487A 3H01487A R
263232 CABLE,FLAT - - - R
W6640 PWB(PCB) ASSEMBLY,SUB 6871A20283B 6871A20283B 6871A20283A R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

-72-
2. Outdoor unit

437210

552111 437212

552102
554031

435511

559010 546810

W0CZZ

649950
552116
567502

552202
554160

561410
550140 552203-1
552203-2

430410

-73-
Parts List(Outdoor)
PART No.
LOCATION No. DESCRIPTION REMARKS
LS-Q076ABL LS-Q076BBG LS-Q076BEL LS-Q076ABG
437210 GRILLE ASSEMBLY, FRONT(OUTDOOR) 3531AR2512R 3531AR2512R 3531AR2512R 3531AR2512R R
546810 MOTOR ASSEMBLY, OUTDOOR 4681A20004F 4681A20004F 4681A20004F 4681A20004F R
430410 BASE ASSEMBLY, WELD[OUTDOOR] 3041AR2415K 3041AR2415K 3041AR2415K 3041AR2415K R
435511 COVER ASSEMBLY, CONTROL(OUTDOOR) 4994AR3492B 4994AR3492B 4994AR3492B 4994AR3492B R
437212 PANEL ASSEMBLY, REAR(OUTDOOR) 3530AR0058C 3530AR0058C 3530AR0058C 3530AR0058C R
550140 ISOLATOR, COMP 4H00982E 4H00982E 4H00982E 4H00982E R
552102 TUBE, CAPILLARY BEND 5210A30151L 5210A30151L 5210A30151L 5210A30151L R
552111 TUBE ASSEMBLY, CAPILLARY 5211A30082S 5211A30082S 5211A30082S 5211A30082S R
552116 TUBE ASSEMBLY, REVERSING 5211A30095C 5211A30095C 5211A30095C 5211A30095C R
552202 VALVE, REVERSING 5220AR3084A 5220AR3084A 5220AR3084A 5220AR3084A R
552203-1 VALVE, SERVICE 2H02479F 2H02479F 2H02479F 2H02479F R
552203-2 VALVE, SERVICE 2A00393M 2A00393M 2A00393M 2A00393M R
554031 CONDENSER ASSEMBLY, BENT 5403AR2475L 5403AR2475L 5403AR2475L 5403AR2475L R
554160 COMPRESSOR SET 2520UKYP2CA 2520UKYP2CA 2520UKYP2CA 2520UKYP2CA R
559010 FAN ASSEMBLY, PROPELLER 5900AR1266A 5900AR1266A 5900AR1266A 5900AR1266A R
561410 COIL ASSEMBLY, REVERSING VALVE 3A02028G 3A02028G 3A02028G 3A02028G R
567502 O.L.P 6750U-L014A 6750U-L014A 6750U-L014A 6750U-L014A R
649950 CONTROL BOX ASSEMBLY, OUTDOOR 4995A20031A 4995A20031A 4995A20031A 4995A20031A R
W0CZZ CAPACITOR, DRAWING 6120AR2194H 6120AR2194H 6120AR2194H 6120AR2194H R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

-74-
Outdoor unit

437210

437212

554031

435301
435511

546810

552102-2
559010

649950
552201
552111
552102-1 552116
W0CZZ

552202

567502

561410

554160
447910

550140 552203-1

430410
552203-2

-75-
Parts List(Outdoor)

LOCATION PART No.


DESCRIPTION REMARKS
No. LS-Q096ACG LS-Q096BAG LS-Q096ACL LS-Q082BAG LS-Q096ABM LS-H096QNA0
430410 BASE ASSEMBLY, WELD[OUTDOOR] 3041AR2415K 3041AR2415K 3041AR2415K 3041AR2415E 3041A20008K 3041A20016A R
435301 GRILLE, DISCHARGE 3530A20006B 3530A20006B 3530A20006B 3530A20006B 3530A20006B 3530A10059D R
435511 COVER ASSEMBLY, CONTROL(OUTDOOR) 4994AR3492B 4994AR3492B 4994AR3492B 4994AR3492B 3551A30023E 3551A30023Q R
437210 PANEL ASSEMBLY, FRONT(OUTDOOR) 3531AR2512R 3531AR2512R 3531AR2512R 3531AR2512R 3721A20027A 3721A20060B R
437212 PANEL ASSEMBLY, REAR(OUTDOOR) 3530AR0058B 3530AR0058B 3530AR0058B 3530AR0058B 3721A20026B 3721A20059A R
447910 BARRIER ASSEMBLY, OUTDOOR - - - - - 4971A30002B R
546810 MOTOR ASSEMBLY, OUTDOOR 4681A20004F 4681A20004F 4681A20004F 4681A20068A 4681A20004J 4791A20011A R
550140 ISOLATOR, COMP 4H00982E 4H00982E 4H00982E 4H00982E 4H00982E 4681A20004F R
5210A21341A
552102-1 TUBE, CAPILLARY BEND 5424AR3582H 5424AR3582H 5424AR3582H 5424AR3582C 4H00982E R
5424AR7208M
552102-2 TUBE,CAPILLARY BEND - - - - - 5210A20595F R
552111 TUBE ASSEMBLY, CAPILLARY 5211A30275D 5211A30275D 5211A30275D 5211A30337A 5211A20117E 5211A20133Z R
552116 TUBE ASSEMBLY, REVERSING - - - - 5211A20116C 5211A21027B R
552201 VALVE, CHECK - - - - 3H01552F - R
552202 VALVE, REVERSING - - - - 5220AR3084A 5220AR3084E R
552203-1 VALVE, SERVICE 2H02479F 2H02479F 2H02479F 2H02479F 2H02479H 2H02479N R
552203-2 VALVE, SERVICE 2A00393U 2A00393U 2A00393U 2A00393U 2A00393U 2A00393Z R
554031 CONDENSER ASSEMBLY, BENT 5403AR2870F 5403AR2870M 5403AR2870F 5403AR2870P 5403A20028H 5403A20059B R
554160 COMPRESSOR SET 5416A20013L 5416A20013L 5416A20013L 5416A20013J 5416A20013C 5417A20012H R
559010 FAN ASSEMBLY, PROPELLER 5900AR1266A 5900AR1266A 5900AR1266A 5900AR1266A 5901A10004A 5900AR1266A R
561410 COIL ASSEMBLY, REVERSING VALVE - - - - 3A02028Y 3A02028Y R
567502 O.L.P 6750A30001C 6750A30001C 6750A30001C 6750A30001C 6750A30001C 6750A30001C R
649950 CONTROL BOX ASSEMBLY, OUTDOOR 4995AR2566B 4995AR2566B 4995AR2566B 4995AR2566E 4995A20083F 4995A10032J R
W0CZZ CAPACITOR, DRAWING 2H01451P 2H01451P 2H01451P 2H01451P 2H01451P 2H01451P R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

-76-
Parts List(Outdoor)
LOCATION PART No.
DESCRIPTION REMARKS
No. LS-Q096ABL LS-Q096BBG LS-Q096BEL LS-Q096AHG LS-Q096ABG LS-Q096AEM
430410 BASE ASSEMBLY, OUTDOOR 3041A20008K 3041A20008K 3041A20008K 3041A20008K 3041A20008K 3041A20008K R
435511 COVER ASSEMBLY, CONTROL(OUTDOOR) 3551A30023E 3551A30023E 3551A30023E 3551A30023E 3551A30023E 3551A30023E R
437210 PANEL ASSEMBLY, FRONT(OUTDOOR) 3721A20027A 3721A20027A 3721A20027A 3721A20027A 3721A20027A 3721A20027A R
437212 PANEL ASSEMBLY, REAR(OUTDOOR) 3721A20026B 3721A20026B 3721A20026B 3721A20026B 3721A20026B 3721A20026B R
447910 BARRIER ASSEMBLY, OUTDOOR 4791A30002B 4791A30002B 4791A30002B 4791A30002B 4791A30002B 4791A30002B R
546810 MOTOR ASSEMBLY, OUTDOOR 4681A20004J 4681A20004J 4681A20004J 4681A20004J 4681A20004J 4681A20004J R
550140 ISOLATOR, COMP 4H00982E 4H00982E 4H00982E 4H00982E 4H00982E 4H00982E R
552111 TUBE ASSEMBLY, CAPILLARY 5211A20117C 5211A20117C 5211A20117C 5211A20117C 5211A20117C 5211A20117E R
552116 TUBE ASSEMBLY, REVERSING 5211A20116A 5211A20116A 5211A20116A 5211A20116A 5211A20116A 5211A20116C R
552201 VALVE, CHECK 3H01552F 3H01552F 3H01552F 3H01552F 3H01552F 3H01552F R
552202 VALVE, REVERSING 5220AR3084A 5220AR3084A 5220AR3084A 5220AR3084A 5220AR3084A 5220AR3084A R
552203-1 VALVE, SERVICE 2H02479H 2H02479H 2H02479H 2H02479H 2H02479H 2H02479H R
552203-2 VALVE, SERVICE 2A00393U 2A00393U 2A00393U 2A00393U 2A00393U 2A00393U R
552102-1 TUBE,CAPILLARY BEND - - - - - 5210A21341A R
552102-2 TUBE,CAPILLARY BEND - - - - - 5424AR7208M R
554031 CONDENSER ASSEMBLY, BENT 5403A20028H 5403A20028H 5403A20028H 5403A20028B 5403A20028B 5403A20028H R
554160 COMPRESSOR 5416A20013C 5416A20013C 5416A20013C 5416A20013C 5416A20013C 5416A20013C R
559010 FAN ASSEMBLY, PROPELLER 5901A10004A 5901A10004A 5901A10004A 5901A10004A 5901A10004A 5901A10004A R
561410 COIL ASSEMBLY, REVERSING VALVE 3A02028Y 3A02028Y 3A02028Y 3A02028Y 3A02028Y 3A02028Y R
567502 O.L.P - - - - - 6750A30001C R
649950 CONTROL BOX ASSEMBLY, OUTDOOR 4995A20083F 4995A20083F 4995A20083F 4995A20083F 4995A20083F 4995A20083F R
W0CZZ CAPACITOR, DRAWING 2H01451P 2H01451P 2H01451P 2H01451P 2H01451P 2H01451P R
435301 GRILLE, DISCHARGE 3530A20006B 3530A20006B 3530A20006B 3530A20006B 3530A20006B 3530A20006B R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

-77-
Parts List(Outdoor)

LOCATION PART No.


DESCRIPTION REMARKS
No. LS-Q096BDG
LS-Q096AEL LS-Q096ADG LS-Q096ADL LS-Q096AAG LS-Q096BEG
LS-Q096BDL
430410 BASE ASSEMBLY,OUTDOOR 3041A20008K 3041AR2415K 3041AR2415K 3041AR2415K 3041AR2415K 3041A20008K R
435301 GRILLE,DISCHARGE - - - - - 3530A20006B R
435301 GRILLE,DISCHARGE 3530A20006B 3530A20006B 3530A20006B 3530A20006B - - R
435511 COVER ASSEMBLY,CONTROL(OUTDOOR) 3551A30023E 4994AR3492B 4994AR3492B 4994AR3492B 4994AR3492B 3551A30023E R
437210 PANEL ASSEMBLY,FRONT(OUTDOOR) 3721A20027A 3531AR2512R 3531AR2512R 3531AR2512R 4994AR3492B 3721A20027A R
437212 PANEL ASSEMBLY,REAR(OUTDOOR) 3721A20026B 3530AR0058B 3530AR0058B 3530AR0058B 3530AR0058B 3721A20026B R
447910 BARRIER ASSEMBLY,OUTDOOR - - - - - 4791A30002B R
546810 MOTOR ASSEMBLY,OUTDOOR 4681A20004J 4681A20004F 4681A20004F 4681A20004F 4681A20004F 4681A20004J R
550140 ISOLATOR,COMP 4H00982E 4H00982E 4H00982E 4H00982E 4H00982E 4H00982E R
552102-1 TUBE,CAPILLARY BEND 5210A21341A 5424AR3582H 5424AR3582H 5424AR3582H 5424AR3582H 5210A21341A R
552102-1 TUBE,CAPILLARY BEND 5424AR7208M - - - - 5424AR7208M R
552111 TUBE ASSEMBLY,CAPILLARY 5211A20117C 5211A30275D 5211A30275D 5211A30275D 5211A30275D 5211A20117E R
552116 TUBE ASSEMBLY,REVERSING 5211A20116A - - - - 5211A20116C R
552201 VALVE,CHECK 3H01552F - - - - 3H01552F R
552202 VALVE,REVERSING 5220AR3084A - - - - 5220AR3084A R
552203-1 VALVE,SERVICE 2H02479H 2H02479F 2H02479F 2H02479F 2H02479F 2H02479H R
552203-2 VALVE,SERVICE 2A00393U 2A00393U 2A00393U 2A00393U 2A00393U 2A00393U R
554031 CONDENSER ASSY,BENT 5403A20028H 5403AR2870M 5403AR2870M 5403AR2870M 5403AR2870M 5403A20028H R
554160 COMPRESSOR 5416A20013C 5416A20013L 5416A20013L 5416A20013L 5416A20013L 5416A20013C R
559010 FAN ASSEMBLY,PROPELLER 5901A10004A 5900AR1266A 5900AR1266A 5900AR1266A 5900AR1266A 5901A10004A R
561410 COIL ASSEMBLY,REVERSING VALVE 3A02028Y - - - - 3A02028Y R
567502 O.L.P 6750A30001C 6750A30001C 6750A30001C 6750A30001C 6750A30001C 6750A30001C R
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995A20083F 4995AR2566F 4995AR2566F 4995AR2566F 4995AR2566F 4995A20083F R
W0CZZ CAPACITOR,DRAWING 2H01451P 2H01451P 2H01451P 2H01451P 2H01451P 2H01451P R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

-78-
Parts List(Outdoor)
LOCATION PART No.
DESCRIPTION REMARKS
No. LS-Q082BAM LS-Q082AAL LS-Q082ACG LS-Q082ACL LS-Q082ACM
430410 BASE ASSY,WELD[OUTDOOR] 3041AR2415E 3041AR2415E 3041AR2415E 3041AR2415E 3041AR2415E R
435511 COVER ASSEMBLY,CONTROL(OUTDOOR) 4994AR3492B 4994AR3492B 4994AR3492B 4994AR3492B 4994AR3492B R
437210 GRILLE ASSEMBLY,FRONT(OUTDOOR) 3531AR2512R 3531AR2512R 3531AR2512R 3531AR2512R 3531AR2512R R
437212 PANEL ASSEMBLY,REAR(OUTDOOR) 3530AR0058B 3530AR0058B 3530AR0058B 3530AR0058B 3530AR0058B R
546810 MOTOR ASSEMBLY,OUTDOOR 4681A20068A 4681A20068A 4681A20068A 4681A20068A 4681A20068A R
550140 ISOLATOR,COMP 4H00982E 4H00982E 4H00982E 4H00982E 4H00982E R
552102-1 TUBE,CAPILLARY BEND 5424AR3582C 5424AR3582C 5424AR3582C 5424AR3582C 5424AR3582C R
552102-2 TUBE,CAPILLARY BEND - - - - - R
552111 TUBE ASSY,CAPILLARY 5211A30337A 5211A30337A 5211A30337A 5211A30337A 5211A30337A R
552203-1 VALVE,SERVICE 2H02479F 2H02479F 2H02479F 2H02479F 2H02479F R
552203-2 VALVE,SERVICE 2A00393U 2A00393U 2A00393U 2A00393U 2A00393U R
554031 CONDENSER ASSEMBLY,BENT 5403AR2870P 5403AR2870P 5403AR2870H 5403AR2870H 5403AR2870H R
554160 COMPRESSOR 5416A20013J 5416A20013J 5416A20013J 5416A20013J 5416A20013J R
559010 FAN ASSEMBLY,PROPELLER 5900AR1266A 5900AR1266A 5900AR1266A 5900AR1266A 5900AR1266A R
567502 O.L.P 6750A30001D 6750A30001D 6750A30001D 6750A30001D 6750A30001D R
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995AR2566E 4995AR2566E 4995AR2566E 4995AR2566E 4995AR2566E R
W0CZZ CAPACITOR,DRAWING 6120AR2194G 6120AR2194G 6120AR2194G 6120AR2194G 6120AR2194G R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

-79-
Parts List(Outdoor)
LOCATION PART No.
DESCRIPTION REMARKS
No. LS-C082QMA0 LS-C082QNAO LS-C096QGL0
430410 BASE ASSY,WELD[OUTDOOR] 3041AR2415E 3041AR2415E 3041AR2415K R
435301 GRILLE,DISCHARGE - - - R
435511 COVER ASSEMBLY,CONTROL(OUTDOOR) 4994AR3492B 4994AR3492B 4994AR3492B R
437210 GRILLE ASSEMBLY,FRONT(OUTDOOR) 3531AR2512R 3531AR2512R 3531AR2512R R
437212 PANEL ASSEMBLY,REAR(OUTDOOR) 3530AR0058B 3530AR0058B 3530AR0058B R
546810 MOTOR ASSEMBLY,OUTDOOR 4681A20068K 4681A20068K 4681A20004F R
550140 ISOLATOR,COMP 4H00982E 4H00982E 4H00982E R
552102 TUBE,CAPILLARY BEND 5424AR3582C 5424AR3582C 5424AR3582H R
552102-1 TUBE,CAPILLARY BEND - - - R
552102-2 TUBE,CAPILLARY BEND - - - R
552111 TUBE ASSY,CAPILLARY 5211A30337A 5211A30337A 5211A30275D R
552116 TUBE ASSY,REVERSING - - - R
552201 VALVE,CHECK - - - R
552202 VALVE,REVERSING - - - R
552203-1 VALVE,SERVICE 2H02479F 2H02479F 2H02479F R
552203-2 VALVE,SERVICE 2A00393U 2A00393U 2A00393U R
554031 CONDENSER ASSEMBLY,BENT 5403AR2870H 5403AR2870H 5403AR2870M R
554160 COMPRESSOR 5416A20013J 5416A20013J 5416A20013L R
559010 FAN ASSEMBLY,PROPELLER 5900AR1266A 5900AR1266A 5900AR1266A R
561410 COIL ASSY,REVERSING VALVE - - - R
567502 O.L.P 6750A30001D 6750A30001D 6750A30001C R
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995AR2566N 4995AR2566N 4995AR2566F R
W0CZZ CAPACITOR,DRAWING 6120AR2194G 6120AR2194G 2H01451P R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

-80-
Parts List(Outdoor)
LOCATION PART No.
DESCRIPTION REMARKS
No. LS-C096QLA0 LS-C096QNA0 LS-H096QGL1
430410 BASE ASSY,WELD[OUTDOOR] 3041AR2415K 3041AR2415K 3041A20016A R
435301 GRILLE,DISCHARGE - - 3530A10059G R
435511 COVER ASSEMBLY,CONTROL(OUTDOOR) 4994AR3492B 4994AR3492B 3551A30023Q R
437210 GRILLE ASSEMBLY,FRONT(OUTDOOR) 3531AR2512R 3531AR2512R 3720A10171A R
437212 PANEL ASSEMBLY,REAR(OUTDOOR) 3530AR0058B 3530AR0058B 3720A10172A R
546810 MOTOR ASSEMBLY,OUTDOOR 4681A20004F 4681A20004F 4681A20121A R
550140 ISOLATOR,COMP 4H00982E 4H00982E 4H00982E R
552102 TUBE,CAPILLARY BEND 5424AR3582H 5424AR3582H 5210A20595F R
552102-1 TUBE,CAPILLARY BEND - - - R
552102-2 TUBE,CAPILLARY BEND - - - R
552111 TUBE ASSY,CAPILLARY 5211A30275D 5211A30275D 5211A20133Z R
552116 TUBE ASSY,REVERSING - - 5211A21027B R
552201 VALVE,CHECK - - - R
552202 VALVE,REVERSING - - 5220AR3084E R
552203-1 VALVE,SERVICE 2H02479F 2H02479F 2H02479P R
552203-2 VALVE,SERVICE 2A00393U 2A00393U 5220A20040A R
554031 CONDENSER ASSEMBLY,BENT 5403AR2870M 5403AR2870M 5403A20059F R
554160 COMPRESSOR 5416A20013L 5416A20013L 5416A20013L R
559010 FAN ASSEMBLY,PROPELLER 5900AR1266A 5900AR1266A 5900AR1266A R
561410 COIL ASSY,REVERSING VALVE - - 3A02028Y R
567502 O.L.P 6750A30001C 6750A30001C 6750A30001C R
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995AR2566F 4995AR2566F 4995A10032J R
W0CZZ CAPACITOR,DRAWING 2H01451P 2H01451P 2H01451P R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

-81-
April, 2004
P/No.: 3828A20178A Printed in Korea