Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Prepared by
J.A. Jones Power Delivery, Inc.
Post Office Box 187
Haslet, Texas 76052
Principal Investigator
Dr. M. Ostendorp, P.E.
Prepared for
Electric Power Research Institute
3412 Hillview Avenue
Palo Alto, California 94304
(A) MAKES ANY WARRANTY OR REPRESENTATION WHATSOEVER, EXPRESS OR IMPLIED, (I) WITH RESPECT TO
THE USE OF ANY INFORMATION, APPARATUS, METHOD, PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS REPORT,
INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, OR (II) THAT SUCH USE DOES NOT
INFRINGE ON OR INTERFERE WITH PRIVATELY OWNED RIGHTS, INCLUDING ANY PARTY'S INTELLECTUAL
PROPERTY, OR (III) THAT THIS REPORT IS SUITABLE TO ANY PARTICULAR USER'S CIRCUMSTANCE; OR
(B) ASSUMES RESPONSIBILITY FOR ANY DAMAGES OR OTHER LIABILITY WHATSOEVER (INCLUDING ANY
CONSEQUENTIAL DAMAGES, EVEN IF EPRI OR ANY EPRI REPRESENTATIVE HAS BEEN ADVISED OF THE
POSSIBILITY OF SUCH DAMAGES) RESULTING FROM YOUR SELECTION OR USE OF THIS REPORT OR ANY
INFORMATION, APPARATUS, METHOD, PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS REPORT.
ORDERING INFORMATION
Requests for copies of this report should be directed to the EPRI Distribution Center, 207 Coggins Drive, P.O. Box
23205, Pleasant Hill, CA 94523, (510) 934-4212.
Electric Power Research Institute and EPRI are registered service marks of the Electric Power Research Institute, Inc. EPRI.
POWERING PROGRESS is a service mark of the Electric Power Research Institute, Inc.
Copyright © 1997 Electric Power Research Institute, Inc. All rights reserved.
REPORT SUMMARY
This report documents the 16 full-scale tests that were performed to verify the CASE
methodology for steel pole type transmission structures. Using the CASE method,
utilities can accurately identify lines or line sections that have a high potential to
cascade and, therefore, a reduced level of reliability.
Background
A trend began in the 1950s in the utility industry to place less emphasis on the effect of
unbalanced longitudinal loads caused by failure of line components such as insulators,
shield wires, and conductors. Better manufacturing methods and improved quality
control for these components had significantly reduced the number of transmission line
failures. As a result, it became commonly accepted that these types of failures were very
rare and that damage caused by these events was negligible. Consequently, an
increasing number of new transmission lines were designed and constructed with a low
level of longitudinal resistance to extreme event loads. Since the early 1960s, there have
been numerous documented cases of multiple transmission structure failures. These
longitudinal and transverse cascade failures caused utilities extremely high-economic
losses because they completely destroyed whole sections of transmission lines,
requiring months of repair work.
Objectives
• To develop a method to quantify unbalanced longitudinal loads acting on structures
not adjacent to the insulator, shield wire, or conductor failure.
• To develop a method to assess cascading potential of a transmission line by
considering energy dissipation at successive spans and supports.
• To develop a method to determine effects of upgrading on the cascading potential of
a transmission line.
• To develop a method that assesses cascading potential of a transmission line that is
flexible enough to evaluate the effectiveness of various mitigation methods
Approach
It is not economical for a utility to design, upgrade, or maintain an existing line system
in a manner that provides sufficient strength to withstand high-dynamic loads at every
structure. A successful, economic line design or upgrade requires that the failure of a
limited number of structures—based on the utility’s design philosophy and targeted
iii
reliability levels—is acceptable if the overall system is protected from cascading. EPRI’s
Cascading FAilure RiSk AssEssment (CASE) project is an investigation into the nature
of extreme loads that occur in cascading failures and the corresponding line response.
The CASE investigation focused on effects of a triggering event on a transmission line’s
integrity rather than the cause for initial failure. Developed from analytical and
experimental studies, the advanced CASE method predicts the magnitude of extreme
event longitudinal loads. This report documents the 16 full-scale tests that were
performed to verify the CASE methodology for steel pole type transmission lines. Tests
were performed on a four-span segment of a steel pole transmission line located at
EPRI’s Power Delivery Center in Haslet, Texas.
Results
Test results show that the CASE assessment method accurately predicts unbalanced
longitudinal loads at the first, second and third structures from an initial failure such as
a broken shield wire or conductor in a steel pole line. Additionally, the CASE method
correctly addresses dissipation of energy along the transmission line in the computation
of unbalanced longitudinal loads. The CASE method can quickly determine loads acting
on a transmission line and identify the cascading potential of a line subjected to
different loading conditions. Verification tests of CASE for wood H-Frame type lines is
documented in Volume III of the report. Volume II documents the CASE methodology
and Volume I describes a simplified CASE method.
EPRI Perspective
Industry emphasis has shifted to minimizing costs and maximizing use of existing
facilities to reduce capital spending on upgrades and new construction. Consequently,
the need to effectively apply reduced budgets to minimize system failures and to
extend the life of existing facilities has increased in importance. The primary advantage
of the CASE method is that containment boundaries can be defined or adjusted based
on the importance of a given transmission line to the utility’s operation. Thus,
longitudinal strength of a specific transmission line can now be calibrated to match a
utility’s target reliability level for a minimum cost. Having identified a line’s current
level of risk allows the utility to target system components of the line that are most
critical to maintaining the system’s primary function: delivery of electric power. As a
result, the utility is able to implement cost-effective solutions to minimize outages while
improving power transfer. The advanced CASE method also effectively addresses the
industry need for a verified, uniform method of defining realistic longitudinal loading
at all structures affected by a failure.
TR-107087-V4
Interest Categories Keywords
Overhead planning, analysis & design Cascade failures
Overhead construction, O&M Transmission line failures
Overhead transmission
Transmission lines
iv
ABSTRACT
In this study, 16 full-scale dynamic tests were performed to determine the magnitude
and dynamic characteristics of the unbalanced longitudinal loads generated in extreme
failure events caused by broken insulators, broken shield wires, and broken conductors.
Tests were performed on a four-span, single circuit, transmission line segment
supported by steel single poles. The tests were part of the Electric Power Research
Institute’s (EPRI) ‘Cascading Failure Risk Assessment’ (CASE) project. The CASE
project constituted an investigation into the nature of the extreme loads that cause
cascading failures and the corresponding line response. The goals of this investigation
were:
• Determine the magnitude and dynamic characteristics of the conductor and shield
wire tensions of each phase in the first, second, and third span from the initial
failure.
• Develop scale factors to amplify static wire tensions to produce an effect at the first,
second, and third structure from the initial failure that accurately simulates the
dynamic characteristics.
The investigation showed that unbalanced longitudinal load predictions by the CASE
assessment method compare well with measured full-scale test values and values
published by other researchers. It was determined that impact factors and
corresponding unbalanced longitudinal loads are primarily a function of the span-sag
ratio, the span-insulator ratio, and the structural flexibility.
v
CONTENTS
1 INTRODUCTION .......................................................................................................1-1
1.1 Background.........................................................................................................1-2
1.2 Objectives ...........................................................................................................1-3
1.3 Past Research ....................................................................................................1-3
2 TEST DESCRIPTION................................................................................................2-1
2.1 Test Structure ....................................................................................................2-1
2.2 Line Segment.....................................................................................................2-5
2.3 Conductor and Shield Wire................................................................................2-5
2.4 Test Cases.........................................................................................................2-6
3 INSTRUMENTATION ................................................................................................3-1
3.1 Load Cells ..........................................................................................................3-1
3.2 Data Acquisition .................................................................................................3-1
3.3 Data Reduction ..................................................................................................3-2
4 TEST RESULTS........................................................................................................4-1
4.1 Conductor and Shield Wire Tension ..................................................................4-1
4.2 Unbalanced Longitudinal Loads.........................................................................4-4
4.3 Reactions ...........................................................................................................4-6
4.4 Longitudinal Load Impact Factors......................................................................4-7
vii
5.4 Longitudinal Load Impact Factors......................................................................5-2
8 REFERENCES ..........................................................................................................8-1
viii
LIST OF FIGURES
Figure 2-1 Steel Pole Test Structure - 'Vertical' Phase Configuration ..........................2-3
Figure 2-2 Steel Pole Test Structure - 'Delta' Phase Configuration ..............................2-4
Figure 2-3 View of Second and Third Test Structure....................................................2-5
Figure 3-1 Location of Test Line Load Cells .................................................................3-2
Figure 4-1 Longitudinal Load Impact Factors at the First Structure from the
Failure - Test .........................................................................................................4-8
Figure 4-2 Longitudinal Load Impact Factors at the Second Structure from the
Failure - Test .........................................................................................................4-8
Figure 4-3 Longitudinal Load Impact Factors at the Third Structure from the
Failure - Test .........................................................................................................4-9
Figure 5-1 Longitudinal Load Impact Factors at the First Structure from the
Failure - CASE.......................................................................................................5-3
Figure 5-2 Longitudinal Load Impact Factors at the Second Structure from the
Failure - CASE.......................................................................................................5-3
Figure 5-3 Longitudinal Load Impact Factors at the Third Structure from the
Failure - CASE.......................................................................................................5-4
Figure 6-1 Longitudinal Load Impact Factors at the First Structure from the
Failure ...................................................................................................................6-1
Figure 6-2 Longitudinal Load Impact Factors at the Second Structure from
the Failure .............................................................................................................6-2
Figure 6-3 Longitudinal Load Impact Factors at the Third Structure from the
Failure ...................................................................................................................6-3
Figure 6-4 Longitudinal Load Impact Factors at the First Structure vs. Span/Sag
Ratio ......................................................................................................................6-4
Figure 6-5 Longitudinal Load Impact Factors at the Second Structure vs. Span/Sag
Ratio ......................................................................................................................6-4
Figure 6-6 Longitudinal Load Impact Factors at the Third Structure vs. Span/Sag
Ratio ......................................................................................................................6-5
ix
Figure 6-7 Longitudinal Load Impact Factors at the First Structure vs. Span/Insulator
Ratio ......................................................................................................................6-6
Figure 6-8 Longitudinal Load Impact Factors at the Second Structure vs. Span/Insulator
Ratio ......................................................................................................................6-6
Figure 6-9 Longitudinal Load Impact Factors at the Third Structure vs. Span/Insulator
Ratio ......................................................................................................................6-7
x
LIST OF TABLES
xi
UTS ...................................................................................................................... A-7
Table A-13 Tension Summary - Broken Upper Conductor, Long Insulator, 25%
UTS ...................................................................................................................... A-8
Table A-14 Unbalanced Loads - Broken Upper Conductor, Long Insulator, 25%
UTS ...................................................................................................................... A-8
Table A-15 Normalized Tensions - Broken Upper Conductor, Long Insulator, 25%
UTS ...................................................................................................................... A-9
Table A-16 Normalized Loads - Broken Upper Conductor, Long Insulator, 25%
UTS ...................................................................................................................... A-9
Table A-17 Tension Summary - Broken Ground Wire, Short Insulator, 25%
UTS .................................................................................................................... A-10
Table A-18 Unbalanced Loads - Broken Ground Wire, Short Insulator, 25%
UTS .................................................................................................................... A-10
Table A-19 Normalized Tensions - Broken Ground Wire, Short Insulator, 25%
UTS .................................................................................................................... A-11
Table A-20 Normalized Loads - Broken Ground Wire, Short Insulator, 25%
UTS .................................................................................................................... A-11
Table A-21 Tension Summary - Broken Upper Conductor, Short Insulator, 25%
UTS .................................................................................................................... A-12
Table A-22 Unbalanced Loads - Broken Upper Conductor, Short Insulator, 25%
UTS .................................................................................................................... A-12
Table A-23 Normalized Tensions - Broken Upper Conductor, Short Insulator, 25%
UTS .................................................................................................................... A-13
Table A-24 Normalized Loads - Broken Upper Conductor, Short Insulator, 25%
UTS .................................................................................................................... A-13
Table A-25 Tension Summary - Broken Ground Wire, Short Insulator, 15%
UTS .................................................................................................................... A-14
Table A-26 Unbalanced Loads - Broken Ground Wire, Short Insulator, 15%
UTS .................................................................................................................... A-14
Table A-27 Normalized Tensions - Broken Ground Wire, Short Insulator, 15%
UTS .................................................................................................................... A-15
Table A-28 Normalized Loads - Broken Ground Wire, Short Insulator, 15%
UTS .................................................................................................................... A-15
xii
Table A-29 Tension Summary - Broken Upper Conductor, Short Insulator, 15%
UTS .................................................................................................................... A-16
Table A-30 Unbalanced Loads - Broken Upper Conductor, Short Insulator, 15%
UTS .................................................................................................................... A-16
Table A-31 Normalized Tensions - Broken Upper Conductor, Short Insulator, 15%
UTS .................................................................................................................... A-17
Table A-32 Normalized Loads - Broken Upper Conductor, Short Insulator, 15%
UTS .................................................................................................................... A-17
Table B-1 Normalized Tensions - Broken Ground Wire, Long Insulator, 15%
UTS ...................................................................................................................... B-2
Table B-2 Normalized Unbalanced Loads - Broken Ground Wire, Long Insulator,
15% UTS .............................................................................................................. B-2
Table B-3 Normalized Tensions - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... B-3
Table B-4 Normalized Unbalanced Loads - Broken Upper Conductor, Long Insulator,
15% UTS .............................................................................................................. B-3
Table B-5 Normalized Tensions - Broken Ground Wire, Long Insulator, 25%
UTS ...................................................................................................................... B-4
Table B-6 Normalized Unbalanced Loads - Broken Ground Wire, Long Insulator,
25% UTS .............................................................................................................. B-4
Table B-7 Normalized Tensions - Broken Upper Conductor, Long Insulator, 25%
UTS ...................................................................................................................... B-5
Table B-8 Normalized Unbalanced Loads - Broken Upper Conductor, Long Insulator,
25% UTS .............................................................................................................. B-5
Table B-9 Normalized Tensions - Broken Ground Wire, Short Insulator, 25%
UTS ...................................................................................................................... B-6
Table B-10 Normalized Unbalanced Loads - Broken Ground Wire, Short Insulator,
25% UTS .............................................................................................................. B-6
Table B-11 Normalized Tensions - Broken Upper Conductor, Short Insulator, 25%
UTS ...................................................................................................................... B-7
Table B-12 Normalized Unbalanced Loads - Broken Upper Conductor, Short
Insulator, 25% UTS .............................................................................................. B-7
Table B-13 Normalized Tensions - Broken Ground Wire, Short Insulator, 15%
UTS ...................................................................................................................... B-8
xiii
Table B-14 Normalized Unbalanced Loads - Broken Ground Wire, Short Insulator,
15% UTS .............................................................................................................. B-8
Table B-15 Normalized Tensions - Broken Upper Conductor, Short Insulator,
15% UTS .............................................................................................................. B-9
Table B-16 Normalized Unbalanced Loads - Broken Upper Conductor, Short
Insulator, 15% UTS .............................................................................................. B-9
Table C-1 Tension Summary - Broken Middle Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-2
Table C-2 Unbalanced Loads - Broken Middle Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-2
Table C-3 Normalized Tensions - Broken Middle Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-3
Table C-4 Normalized Loads - Broken Middle Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-3
Table C-5 Tension Summary - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-4
Table C-6 Unbalanced Loads - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-4
Table C-7 Normalized Tensions - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-5
Table C-8 Normalized Loads - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-5
Table C-9 Tension Summary - Broken Middle Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-6
Table C-10 Unbalanced Loads - Broken Middle Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-6
Table C-11 Normalized Tensions - Broken Middle Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-7
Table C-12 Normalized Loads - Broken Middle Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-7
Table C-13 Tension Summary - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-8
Table C-14 Unbalanced Loads - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-8
xiv
Table C-15 Normalized Tensions - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-9
Table C-16 Normalized Loads - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... C-9
Table C-17 Tension Summary - Broken Middle Conductor, Long Insulator, 25%
UTS .................................................................................................................... C-10
Table C-18 Unbalanced Loads - Broken Middle Conductor, Long Insulator, 25%
UTS .................................................................................................................... C-10
Table C-19 Normalized Tensions - Broken Middle Conductor, Long Insulator, 25%
UTS .................................................................................................................... C-11
Table C-20 Normalized Loads - Broken Middle Conductor, Long Insulator, 25%
UTS .................................................................................................................... C-11
Table C-21 Tension Summary - Broken Upper Conductor, Long Insulator, 25%
UTS .................................................................................................................... C-12
Table C-22 Unbalanced Loads - Broken Upper Conductor, Long Insulator, 25%
UTS .................................................................................................................... C-12
Table C-23 Normalized Tensions - Broken Upper Conductor, Long Insulator, 25%
UTS .................................................................................................................... C-13
Table C-24 Normalized Loads - Broken Upper Conductor, Long Insulator, 25%
UTS .................................................................................................................... C-13
Table C-25 Tension Summary - Broken Outside Insulator, Unguyed, Long Insulator,
25% UTS ............................................................................................................ C-14
Table C-26 Unbalanced Loads - Broken Outside Insulator, Unguyed, Long Insulator,
25% UTS ............................................................................................................ C-14
Table C-27 Normalized Tensions - Broken Outside Insulator, Unguyed, Long
Insulator, 25% UTS ............................................................................................ C-15
Table C-28 Normalized Loads - Broken Outside Insulator, Unguyed, Long Insulator,
25% UTS ............................................................................................................ C-15
Table C-29 Tension Summary - Broken Upper Conductor, Short Insulator, 25%
UTS .................................................................................................................... C-16
Table C-30 Unbalanced Loads - Broken Upper Conductor, Short Insulator, 25%
UTS .................................................................................................................... C-16
Table C-31 Normalized Tensions - Broken Upper Conductor, Short Insulator,
25% UTS ............................................................................................................ C-17
xv
Table C-32 Normalized Loads - Broken Upper Conductor, Short Insulator, 25%
UTS .................................................................................................................... C-17
Table D-1 Normalized Tensions - Broken Middle Conductor, Long Insulator, 15%
UTS ...................................................................................................................... D-2
Table D-2 Normalized Unbalanced Loads - Broken Middle Conductor, Long
Insulator, 15% UTS .............................................................................................. D-2
Table D-3 Normalized Tensions - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... D-3
Table D-4 Normalized Unbalanced Loads - Broken Upper Conductor, Long
Insulator, 15% UTS .............................................................................................. D-3
Table D-5 Normalized Tensions - Broken Middle Conductor, Long Insulator, 15%
UTS ...................................................................................................................... D-4
Table D-6 Normalized Unbalanced Loads - Broken Middle Conductor, Long
Insulator, 15% UTS .............................................................................................. D-4
Table D-7 Normalized Tensions - Broken Upper Conductor, Long Insulator, 15%
UTS ...................................................................................................................... D-5
Table D-8 Normalized Unbalanced Loads - Broken Upper Conductor, Long
Insulator, 15% UTS .............................................................................................. D-5
Table D-9 Normalized Tensions - Broken Middle Conductor, Long Insulator, 25%
UTS ...................................................................................................................... D-6
Table D-10 Normalized Unbalanced Loads - Broken Middle Conductor, Long
Insulator, 25% UTS .............................................................................................. D-6
Table D-11 Normalized Tensions - Broken Upper Conductor, Long Insulator, 25%
UTS ...................................................................................................................... D-7
Table D-12 Normalized Unbalanced Loads - Broken Upper Conductor, Long
Insulator, 25% UTS .............................................................................................. D-7
Table D-13 Normalized Tensions - Broken Middle Conductor, Short Insulator, 25%
UTS ...................................................................................................................... D-8
Table D-14 Normalized Unbalanced Loads - Broken Middle Conductor, Short
Insulator, 25% UTS .............................................................................................. D-8
Table D-15 Normalized Tensions - Broken Upper Conductor, Short Insulator, 25%
UTS ...................................................................................................................... D-9
Table D-16 Normalized Unbalanced Loads - Broken Upper Conductor, Short
Insulator, 25% UTS .............................................................................................. D-9
xvi
1
INTRODUCTION
Deregulation and competition have changed the electric power industry business
environment. The emphasis has shifted to minimizing costs and maximizing the use of
existing facilities to reduce the capital spending on upgrades and new construction.
Consequently, the need to effectively apply reduced budgets to minimize system
failures and to extend the life of existing facilities has increased in importance.
It is not economical for a utility to design, upgrade, or maintain an existing line system
in a manner that provides sufficient strength to withstand the high dynamic loads at
each structure. A successful and economic line design or upgrade requires that the
failure of a limited number of structures is acceptable if the overall system is protected
from cascading. The acceptable number of structural failures should be determined
based on the utility’s design philosophy and targeted reliability levels.
In this study, 16 full-scale dynamic tests were performed to determine the magnitude
and characteristics of the unbalanced longitudinal loads generated in extreme failure
events caused by broken insulators, broken shield wires, and broken conductors. Tests
were performed on a four-span, single circuit, transmission line segment supported by
steel poles. The tests were part of the Electric Power Research Institute’s (EPRI)
‘Cascading Failure Risk Assessment’ (CASE) project. The CASE project constituted an
1-1
Introduction
investigation into the nature of the extreme loads caused by cascading failures and the
corresponding line response. The goals of the CASE project were to identify and/or
develop a method to predict extreme event longitudinal load magnitudes and to assess
the cascading potential of a line when subjected to such loads.
1.1 Background
Starting in the 1950’s, a trend began in the utility industry to place less emphasis on the
effect of unbalanced longitudinal loads caused by the failure of line components such as
insulators, shield wires, and conductors. Better manufacturing methods and improved
quality control in the production of these components in the preceding years had
significantly reduced the number of failures observed on transmission lines. As a result
of these improvements, it became commonly accepted that these types of failures were
very rare and that the damage caused by these events was negligible.
Indicative of the general perception at the time, P.P. Bonar (1) stated in 1958 that “...the
incidence of conductor failures on overhead lines is now much reduced because of
improved materials and design and erection techniques...”. Similarly, E. Comellini (2)
indicated in an earlier publication that “...that the failure of these elements should not
be considered in tower design...” while a 1960 AIEE survey (3) conducted concluded
that “...the possibility of a broken conductor in these days of large conductors, lightning
shielding, and fast relaying is so remote that it is uneconomical to design for broken
conductors...”.
Attempting to minimize the cost of line construction, the industry’s focus shifted to
designing transmission line structures to primarily resist transverse and longitudinal
forces caused by wind and ice loading on the conductors and shield wires. The
consensus of the industry centralized on the belief that it was uneconomical to design
transmission structures to withstand extreme event loads. Consequently, an increasing
number of new transmission lines were designed and constructed with negligible
longitudinal resistance to extreme event loads.
Since the early 1960’s there have been numerous documented cases of multiple
transmission structure failures that can be directly related to the lack of nationally
recognized or mandated design provisions for longitudinal strength. Records indicate
at least 28 different cascading failures nationwide over a time period of 35 years
resulted in a loss of more than 3000 transmission structures. At an average cost of only
thirty thousand dollars for each transmission structure, the amount of damage easily
approaches a few hundred million dollars. While it is true that a number of these
cascading failures were triggered by component failures as a result of significant wind
or ice loads, it is apparent that a sizable amount of these cascades occurred under
normal loading conditions. Consequently, it is evident that variations in the design of
1-2
Introduction
transmission lines exist which give rise to systems that may or may not be able to resist
extreme loading events.
1.2 Objectives
• Determine the magnitude and dynamic characteristics of the conductor and shield
wire tensions of each phase in the first, second, and third span from the initial
failure.
• Develop scale factors to amplify static wire tensions to produce an effect at the first,
second, and third structure from the initial failure that accurately simulates the
dynamic characteristics.
Despite the loss of many miles of transmission lines as a result of cascading failures
limited research has been performed to determine the nature of the unbalanced
longitudinal loads acting on the support structures. Most tests performed consisted of
full-scale tests on existing transmission lines and scale model investigations and focused
on obtaining impact loads on the structure adjacent to the failure. Therefore, limited
information has been published on the loads acting on the subsequent structures in the
line due to the initial failure event.
Haro (4), Govers (5), and Peyrot (6) conducted full-scale tests on existing transmission
lines. Haro’s tests were performed on semi-flexible steel and wood H-Frames with
Copper and ACSR conductors. Parameters varied in Haro’s study included span and
insulator length, initial tensions, and the number of spans. Govers performed tests on
full-scale and scale model transmission lines. Parameters varied included span and
1-3
Introduction
insulator length, type of conductor, type of structure, number of spans, and initial
tensions. Peyrot’s full-scale tests were performed on rigid steel lattice towers with
Copper-Bronze and ACSR conductors. Parameters investigated included the type of
conductor, the length of the insulators, and the initial tension.
Govers (5), Ferry-Borges (7), Mozer (8), and Kempner (9) performed extensive tests on
scale models of transmission lines. Parameters varied by the investigators included the
conductor type, insulator length, tower stiffness, span length, initial tension, and the
number of spans. Based on these tests, it was determined that line parameters affecting
peak unbalanced loads are:
• Initial Tension
• Span Length
• Insulator Length
• Tower Flexibility
• Catenary Constant
• Number of Spans
Govers (5), Ferry-Borges (7), Mozer (8) used the results of their research to develop
design aids and analysis tools capable of predicting the magnitude of the unbalanced
longitudinal loads at the first structure from the initial failure. While the unbalanced
load predictions made by all three researchers compare well with full-scale test results
at the first structure from the initial failure, little or no effort was made to identify or
quantify the reduction in the unbalanced load along the line due to the dissipation of
energy.
Kempner (9) performed extensive tests on scale models to identify both unbalanced
load magnitudes and the reduction in energy along the line thus creating the notion of
containment of a cascading failure by allowing the first structure to fail. Results of the
tests were used to develop design aids capable of predicting the magnitude of the
unbalanced longitudinal load for tangent and dead end structures.
1-4
2
TEST DESCRIPTION
A total of 16 full-scale dynamic tests were performed at the EPRI Power Delivery
Center in Haslet, Texas. Tests were performed on a four-span segment of a steel pole
transmission line. The tests simulated the failure of an insulator, shield wire, or
conductor. Testing started in November 1995 and concluded in January 1996.
The structure used in the full-scale dynamic tests was a 100-ft. single circuit, twelve
sided, tapered steel pole as shown in Figure 2-1 and Figure 2-2. Tests were performed
for a ‘Vertical’ and ‘Delta’ phase configuration. The single shield wire was attached
directly to the top of each steel pole supported by standard wire hardware. Conductors
were supported by 10-ft. long, tapered steel cross-arms. The steel cross-arms used in
the tests had rectangular cross-sections and were attached to the steel pole via two
threaded rods.
Insulators used on the test structure were porcelain units. Tests were performed for
two different insulator lengths. The ‘Long Insulator’ configuration consisted of 18
porcelain suspension units while the ‘Short Insulator’ configuration consisted of 9 units.
The length of the long and short insulator configuration was 10 ft. and 5 ft.,
respectively.
Four test structures were less than 5 years old while an additional pole was newly
purchased. A thorough inspection of all test structures revealed that the structures
were in very good condition without any noticeable defects. Steel poles had 3/16 inch
thick walls with a top and ground line diameter of 8.5 inches and 22 inches,
respectively.
Dead end structures were guyed with 3/8 inch diameter EHS steel wire. Both, front
and back guys were used on each dead end and connected to separate guy anchors.
Guy angles ranged from 15° to 30° measured from the longitudinal direction and 45° to
60° measured from the vertical direction. In cases where guys were installed, guys were
tensioned to approximately 2500 pounds.
2-1
Test Description
Test structures were embedded directly into 2-ft. diameter holes drilled to a depth of 10
feet. To accelerate the construction, holes were back-filled with standard polymer based
expansion foam rather than with the displaced soil. Continued inspection of the
foundation ground line after completion of each test indicated that the expansion foam
did not work very well when subjected to torsional loads. Steel poles permanently
rotated within the foundation socket and had to be realigned before each test.
2-2
Test Description
Figure 2-1
Steel Pole Test Structure - 'Vertical' Phase Configuration
2-3
Test Description
Figure 2-2
Steel Pole Test Structure - 'Delta' Phase Configuration
2-4
Test Description
Figure 2-3
View of Second and Third Test Structures
The line segment traversed the ground in an east to west orientation. The first dead
end structure (DE_1) was located at the western end of the test line while the second
dead end (DE _2) was located at the eastern end. The first (ST_1), second (ST_2), and
third (ST_3) structure were located at 1000-ft. intervals from DE_1. There were neither
horizontal nor vertical line angles within the line segment.
2-5
Test Description
A total of 16 dynamic tests were performed on the test line. The test cases simulated the
failure of conductors or shield wires. Table 2-1 shows a summary description of all
tests. The ‘Broken Conductor’ load case simulated the failure of the conductor (physical
separation) on any phase of the span. Failure of the conductor resulted in large
unbalanced loads acting on the two adjacent structures. Similarly, the ‘Broken Shield
Wire’ load case simulated the failure of one of the shield wires.
Table 2-1
Summary of Extreme Event Test Cases
Critical parameters varied in the tests consisted of the structural stiffness, the insulator
length, and the tension in both shield wires and conductors in addition to varying the
location of the initial failure. Previous investigations had shown that the magnitude of
the unbalanced load was significantly influenced by the span/insulator ratio (i.e., span
length divided by insulator length), the span/sag ratio (i.e., span length divided by the
wire sag), and the structural flexibility of the wire supports (i.e., unit deflection divided
by unit load).
2-6
3
INSTRUMENTATION
Load cells were located in each conductor and shield wire phase of the test line
segment. Additionally, load cells were placed in each insulator string. Figure 3-1
shows the location of each load cell in each span. Furthermore, transducers were used
to measure the ambient temperature, relative humidity, and atmospheric pressure.
Tension load cells were used to monitor the loads in each conductor and shield wire in
each of the 16 dynamic tests. Additionally, load cells were located at each insulator
string of S_1, S_2, and S_3 structures resulting in a total of 25 load cells. The tension
load cells are fully weatherproof and temperature compensated for temperatures
ranging from -20°F to 120°F. Load cells used to measure tensions in the shield wires
had a full-scale load range of 12-kip; load cells used in the conductors had a full-scale
load range of 25-kip; and load cells used in the insulator strings had a full-scale load
range of 50-kip.
Tension load cells in the first span were located 10 ft. to the left of the S_1 structure
while load cells in the second span were located 10 ft. to the right. Load cells in the
third span were located 10 ft. to the right of structure S_2 and load cells in the fourth
span were located 10 ft. to the right of structure S_3. Insulator load cells were located in
the top of each insulator string at structures S_1, S_2, and S_3.
Each load cell was calibrated before and after the tests at the PDC with a hydraulic,
100-kip MTS test machine. The calibration data (i.e., calibration constants and offsets)
were used during the tests to determine the load cell readings. Correlation of the pre-
and post-test calibrations indicated that the load cells used in the tests had errors of less
than 1% of the full-scale load range.
All data acquisition was performed using a 486 personal computer equipped to collect
data on up to 64 channels at frequencies of up to 1000 Hz. Each load cell signal was
amplified at the load cell before being transmitted through shielded co-axial cable to the
data acquisition system. Data was collected at 60 Hz. for 30 seconds on 32 channels (i.e.,
3-1
Instrumentation
29 load cells, temperature, relative humidity, and atmospheric pressure). Data was
acquired analog, passed through an analog to digital converter, and filtered to remove
any high frequency noise above 50 Hz.
Once the data was filtered all measurements were stored in binary format in the data
acquisition system. Upon completion of each test, the data was backed up to removable
storage media and subsequently converted to ASCII format. Converted files were then
stored separately to be reduced and analyzed.
Figure 3-1
Location of Test Line Load Cells
ASCII data files were processed to determine statistical parameters such as average
value, median value, standard deviation, coefficient of variation, and maximum and
minimum value. Additionally, the data was processed to determine tensions prior to
and after the failure (i.e., initial and residual tensions). Last, results of the data
reduction were summarized in an ASCII summary file and time history plots of each
channel were stored in a graphics language print file.
3-2
Instrumentation
A second data reduction module was used to produce time histories of the unbalanced
longitudinal loads at each conductor and shield wire phase of each structure.
Additionally, time histories of the unbalanced reactions were extracted at each
structure. Last, results of the secondary data reduction were summarized in a different
ASCII summary file and time history plots of each of the unbalanced longitudinal loads
and reactions were stored in a graphics language print file.
3-3
4
TEST RESULTS
Data obtained in each test included the shield wire, conductor, and insulator tension
time histories. Table 4-1 shows the test summary of a particular configuration. The
summary includes a description of the test configuration, the type of failure simulated,
date and time of the experiment, and the observed outcome of the test. Tables shown in
sections 4.1 through 4.3 are used to illustrate the results of the data reduction for a
single test case. Test information on all 16 dynamic tests can be found in Appendix A of
this report.
Table 4-1
Dynamic Test Summary Table
Configuration 1 1/0/00
25% UTS 0:00:00
Long Insulators
No Pods
Test Broken Ground Wire (D1204A.001)
Shield wire, conductor, and insulator tensions were monitored throughout each test.
Table 4-2 shows a statistical summary of all measurements recorded for this particular
configuration. Of special interest to the evaluation of the transient data are the average
values before and after the test (i.e., initial and static residual tensions) and the peak
amplitudes of the transient response.
Table 4-2 shows that tensions in the conductors and shield wire for this particular
configuration were approximately 7900 lb. and 3400 lb. prior to the test. Target tensions
were 7875 lb. and 3850 lb. at 60ºF. However, small differences in the instrumentation
offset and a different ambient temperature typically induced slight differences in the
tensions measured prior to the test. Consequently, measured tensions were normalized
to eliminate these effects. Additionally, in order to facilitate comparisons of the
different test configurations, measured tensions were normalized with respect to the
4-1
Test Results
target tensions. Table 4-3 shows normalized shield wire, conductor, and insulator
tensions for the broken shield wire test described in Table 4-1.
Table 4-2
Shield Wire, Conductor and Insulator Tension Summary - Test Data
Test results were processed to calculate the average tension in the shield wire and
conductors before and after each test for each load cell (i.e., initial and residual wire
tension). Both initial and residual static wire tensions have been used in previous
investigations to define load impact factors. Load impact factors were defined to
produce equivalent static loads for a transmission structure with load and deflection
characteristics comparable to actual dynamic loads observed in tests.
4-2
Test Results
In addition, data was processed to identify maximum and minimum response values in
each load cell time history for each test. Maximum and minimum response values were
used to determine the upper and lower limit of the tension changes in each span for
each wire. Peak to peak data ranges were then correlated to standard deviations.
Similar to the data in Table 4-2, test results were processed to calculate the normalized
average tension in the shield wire and conductors before and after each test for each
load cell (i.e., normalized initial and residual wire tension). Normalized wire tensions
from all tests were correlated and compared to values published by previous
investigators.
Table 4-3
Normalized Shield Wire, Conductor and Insulator Tension Summary - Test Data
4-3
Test Results
Again, data was processed to identify normalized maximum and minimum response
values in each load cell time history for each test. Normalized maximum and minimum
response values were used to determine the upper and lower limit of the tension
changes in each span for each wire. Peak to peak data ranges were then correlated to
normalized standard deviations.
Unbalanced longitudinal loads were calculated based on the measured tension time
histories for each particular configuration. Unbalanced loads were calculated at each
structure for each phase and shield wire. Table 4-4 shows a summary of the unbalanced
longitudinal loads acting on the first, second, and third structure for the broken shield
wire test configuration described in Table 4-1.
Table 4-4
Unbalanced Longitudinal Load Summary - Test Data
Unbalanced loads were corrected to eliminate the effect of slight load imbalances prior
to the test. Table 4-5 shows a summary of all unbalanced loads on the first, second, and
third structure for the particular test configuration as a result of the shield wire failure.
Maximum and minimum unbalanced longitudinal loads are shown for each shield wire
and conductor phase. Finally, the table summarizes the net unbalanced shield wire and
conductor loads acting on each structure.
4-4
Test Results
Table 4-5
Normalized Unbalanced Longitudinal Load Summary - Test Data
Table 4-6
Unbalanced Reaction Summary - Test Data
4-5
Test Results
4.3 Reactions
Similar to the unbalanced longitudinal load summary, unbalanced reaction forces were
calculated based on the measured tension time histories for each particular
configuration. Unbalanced reaction forces were calculated at each structure. Table 4-6
shows a summary of the unbalanced reaction forces at the first, second, and third
structure for the broken shield wire test configuration described in Table 4-1.
Unbalanced reaction forces were corrected to eliminate the effect of slight load
imbalances prior to the test. Table 4-7 shows a summary of the unbalanced reactions for
the particular test configuration. Also, maximum and minimum unbalanced reactions
are summarized. Last, based on the peak reactions observed during the test, the table
summarizes the maximum strength demand imposed on the first, second, and third
structure as a result of the shield wire failure. The maximum strength demand is
defined as the ratio of the maximum observed reaction force (i.e., Mmax, Tmax, or Vmax)
divided by ultimate strength of the transmission support structure (i.e., Mu, Tu, or Vu).
Table 4-7
Normalized Unbalanced Reaction Summary - Test Data
4-6
Test Results
Based on test results, longitudinal load impact factors were determined for the first,
second, and third structure. Longitudinal load impact factors (LLIF) are defined in this
document as the ratio of the peak unbalanced tension (PUT) divided by the initial
tension (IT) of the conductor or shield wire prior to failure (i.e., LLIF = PUT/IT).
Therefore, the peak unbalanced tension can also be expressed as the product of the
longitudinal load impact factor and the initial tension for a particular conductor or
shield wire.
Figure 4-1 shows longitudinal load impact factors for the first structure away from the
initial failure as a function of the normalized weight span of the catenary. Impact
factors at the first structure were calculated for all 16 tests and averaged at each distinct
weight span ratio. Thus, Figure 4-1 shows the average longitudinal load impact factor
for each of the normalized weight spans in all 16 tests. The normalized weight span of
a catenary wire is directly proportional to the span/sag ratio and is defined as the
square root of the weight span divided by the initial tension prior to failure.
Figure 4-2 shows longitudinal load impact factors for the second structure from the
initial failure as a function of the normalized weight span of the catenary. Again,
impact factors for all 16 tests were calculated and averaged at each distinct weight span
ratio. A closer examination of the differences between Figure 4-1 and Figure 4-2 shows
a significant reduction in the magnitude of the longitudinal load impact factors from
the first structure to the second structure. Based on the data, impact factors at the first
structure vary uniformly and are about 30% higher than impact factors observed at the
second structure at all normalized weight span ratios.
Similarly, Figure 4-3 shows longitudinal load impact factors for the third structure from
the initial failure. As before, impact factors for all 16 tests were calculated and
averaged at each distinct weight span ratio. As expected, an examination of Figure 4-2
and Figure 4-3 also shows a significant reduction in the magnitude of the longitudinal
load impact factors from the second to the third structure. Longitudinal load impact
factors at the second structure also vary uniformly and are about 30% higher than
impact factors observed at the third structure at all normalized weight span ratios.
4-7
Test Results
Figure 4-1
Longitudinal Load Impact Factors at the First Structure from the Failure - Test
Figure 4-2
Longitudinal Load Impact Factors at the Second Structure from the Failure - Test
4-8
Test Results
Figure 4-3
Longitudinal Load Impact Factors at the Third Structure from the Failure - Test
4-9
5
CASCADING FAILURE RISK ASSESSMENT (CASE)
Similar to the tests, data obtained in each CASE assessment included the shield wire,
conductor, and insulator tension time histories. Tables shown illustrate the results of
the cascading failure risk assessment (CASE) method and show predictions made by
the method for the same test configuration discussed in Section 4. CASE predictions for
all 16 test conditions can be found in Appendix B of this report.
Shield wire, conductor, and insulator tensions were extracted from each CASE
assessment. Results from the CASE analysis were processed to calculate the
normalized average tension in the shield wires and conductors before and after the
initiating failure for each load cell (i.e., normalized initial and residual wire tension).
Normalized wire tensions from all CASE assessments were correlated and compared to
test results published by previous investigators. Axial loads in the insulators were
normalized with respect to the target conductor tensions.
Predictions made by the CASE methodology display similar magnitudes and dynamic
characteristics than values observed in the full-scale test. However, it is quite apparent
that the normalized tensions in any of the other wires vary very little and do not
compare well with predictions made by the CASE assessment methodology. This
apparent discrepancy has been traced to the difference between the calculated stiffness
based on idealized boundary conditions and material properties and the actual stiffness
observed in full-scale tests with real boundary conditions and material properties.
Unbalanced longitudinal loads were calculated based on the calculated tension time
histories for each particular configuration. Unbalanced loads were calculated at each
structure for each phase and shield wire. Table 5-1 shows a summary of the
unbalanced longitudinal loads acting on the first, second, and third structure.
5-1
Cascading Failure Risk Assessment (CASE)
5.3 Reactions
Similar to the unbalanced longitudinal load summary, unbalanced reaction forces were
calculated based on the measured tension time histories for each particular
configuration at each structure. Predicted unbalanced reaction forces compared
favorably with measured values.
Table 5-1
Normalized Unbalanced Longitudinal Load Summary - CASE
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 0.000 0.000 0.000
S_S1 0.980 0.000 0.980
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.000 0.000 0.000
S_S2 0.680 0.000 0.680
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.000 0.000 0.000
S_S3 0.540 0.000 0.540
Based on the CASE assessment results, longitudinal load impact factors were
determined for all three structures. Figure 5-1 shows longitudinal load impact factors
as a function of the normalized weight span of the catenary.
Figure 5-2 shows longitudinal load impact factors for the second structure as a function
of the normalized weight span. Similarly, Figure 5-3 shows longitudinal load impact
factors predicted by the CASE assessment for the third structure from the initial failure.
5-2
Cascading Failure Risk Assessment (CASE)
1.50
1.00
0.50
0.00
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1/2
Normalized Weight-Span Ratio [wL/Ti]
CASE
Figure 5-1
Longitudinal Load Impact Factors at the First Structure from the Failure - CASE
1.50
1.00
0.50
0.00
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1/2
Normalized Weight-Span Ratio [wL/Ti]
CASE
Figure 5-2
Longitudinal Load Impact Factors at the Second Structure from the Failure - CASE
5-3
Cascading Failure Risk Assessment (CASE)
1.50
1.00
0.50
0.00
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Figure 5-3
Longitudinal Load Impact Factors at the Third Structure from the Failure - CASE
5-4
6
COMPARISON OF PREDICTED AND MEASURED
VALUES
Measured impact factors and impact factors predicted using the CASE assessment
method were compared to scale model and full-scale test values published by other
researchers. Figure 6-1 shows a comparison of CASE assessment predictions, full-scale
test results, and published information for the first structure from the initial failure as a
function of the normalized weight span.
1.50 FS Tests
CASE
Thomas
Mozer
1.00 Ferry-Borges
Peyrot
Haro
BPA Lattice
BPA St. Pole
0.50
0.00
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1/2
Normalized Weight-Span Ratio [wL/Ti]
Figure 6-1
Longitudinal Load Impact Factors at the First Structure from the Failure
Based on the data shown in Figure 6-1 it can be concluded that the full-scale test results
and the CASE assessment predictions compare very well at the first structure from the
6-1
Comparison of Predicted and Measured Values
initial failure. Depending on the normalized weight span, average impact factors at the
first structure range from 1.0 to a maximum value of 2.0.
Figure 6-2 shows predicted and measured impact factors in comparison with published
values for the second structure from the initial failure. Again, impact factors from the
full-scale tests, impact factors predicted by the CASE assessment method, and
published values compare very well, even though data appears to be more dispersed
than values measured at the first structure. Average impact factors at the second
structure from the initial failure range from 0.6 for a normalized weight span of 0.3 to
1.0 for a normalized weight span of 0.5. Based on the data, impact factors at the second
structure are approximately 50 percent lower than comparable values at the first
structure.
1.50
FS Tests
CASE
Peyrot
1.00 Haro
BPA Lattice
BPA St. Pole
0.50
0.00
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1/2
Normalized Weight-Span Ratio [wL/Ti ]
Figure 6-2
Longitudinal Load Impact Factors at the Second Structure from the Failure
Figure 6-3 shows predicted and measured impact factors in comparison with published
values for the third structure from the initial failure. Similar to Figure 6-1 and Figure 6-
2, impact factors obtained in the full-scale tests, impact factors predicted by the CASE
assessment method correlate well with published values. As observed in Figure 6-2,
the data appears to be more dispersed than values measured at the first structure from
the initial failure. Average impact factors at the third structure from the initial failure
range from 0.5 for a normalized weight span of 0.3 to 0.7 for a normalized weight span
of 0.5. Based on the data, impact factors at the third structure are approximately 25
percent lower than comparable values at the second structure.
6-2
Comparison of Predicted and Measured Values
1.50
FS Tests
1.00 CASE
Haro
0.50
0.00
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1/2
Normalized Weight-Span Ratio [wL/Ti]
Figure 6-3
Longitudinal Load Impact Factors at the Third Structure from the Failure
Figure 6-4, 6-5, and 6-6 show measured and predicted longitudinal load impact factors
as a function of span/sag ratios. Impact factors predicted using the CASE assessment
method and results from Bonneville Power Administration’s scale model study are
compared to impact factors measured in the full-scale tests. Based on the data shown
in Figure 6-4, 6-5, and 6-6, it can be concluded that the magnitude of the longitudinal
load impact factor is primarily a function of the span/sag ratio. As the span/sag ratio
increases, the longitudinal load impact factors at the first, second, and third structure
decrease. On the contrary, as the span/sag ratio decreases, the impact factors at the
first, second, and third structure increase. Impact factors range from 0.7 to 1.9, 0.4 to
1.5, and 0.2 to 1.3 for the first, second, and third structure from the initial failure,
respectively.
6-3
Comparison of Predicted and Measured Values
1.50
1.00
0.50
0.00
0 10 20 30 40 50 60 70 80 90 100
Span/Sag
FS Tests BPA Lattice BPA St. Pole CASE
Figure 6-4
Longitudinal Load Impact Factors at the First Structure vs. Span/Sag Ratio
1.50
1.00
0.50
0.00
0 10 20 30 40 50 60 70 80 90 100
Span/Sag
FS Tests BPA Lattice BPA St. Pole CASE
Figure 6-5
Longitudinal Load Impact Factors at the Second Structure vs. Span/Sag Ratio
6-4
Comparison of Predicted and Measured Values
1.50
1.00
0.50
0.00
0 10 20 30 40 50 60 70 80 90 100
Span/Sag
FS Tests CASE
Figure 6-6
Longitudinal Load Impact Factors at the Third Structure vs. Span/Sag Ratio
Both, longitudinal load impact factors predicted by the CASE assessment method and
measured values were determined to vary as a function of the span/insulator ratio.
Figures 6-7, 6-8, and 6-9 show longitudinal load impact factors as a function of the
span/insulator ratio. Based on the data, it appears that the average longitudinal load
impact factor increases if the span/insulator ratio decreases and that the impact factor
decreases as the span/insulator ratio increases. Average longitudinal load impact
factors range from 0.9 to 1.2, 0.5 to 0.8, and 0.4 to 0.6 for the first, second, and third
structure, respectively.
Based on the test results and the predictions made by the CASE assessment method,
changes in the span/insulator ratio do not appear to influence the magnitude of the
longitudinal load impact factors as significantly as variations in the span/sag ratio. For
example, the average longitudinal load impact factor at the first structure for a
span/insulator ratio of 100 is approximately 1.1 while the average longitudinal load
impact factor for a span/insulator ratio of 200 equals approximately 1.0. Thus, a
reduction in the length of the insulator by a factor of two decreases the longitudinal
load impact factor by only 10 percent. On the contrary, a reduction in the sag of the
conductor or shield wire by a factor of two decreases the longitudinal load impact
factor by approximately 25 percent. Similar rates of reduction in the average
longitudinal load impact factors have been observed in the data of the first and second
structure at the same span/insulator ratios.
6-5
Comparison of Predicted and Measured Values
1.50
1.00
0.50
0.00
0 50 100 150 200 250 300 350 400 450 500
Span/Insulator
FS Tests CASE
Figure 6-7
Longitudinal Load Impact Factors at the First Structure vs. Span/Insulator Ratio
1.50
1.00
0.50
0.00
0 50 100 150 200 250 300 350 400 450 500
Span/Insulator
FS Tests CASE
Figure 6-8
Longitudinal Load Impact Factors at the Second Structure vs. Span/Insulator Ratio
6-6
Comparison of Predicted and Measured Values
1.50
1.00
0.50
0.00
0 50 100 150 200 250 300 350 400 450 500
Span/Insulator
FS Tests CASE
Figure 6-9
Longitudinal Load Impact Factors at the Third Structure vs. Span/Insulator Ratio
6-7
7
SUMMARY, CONCLUSIONS AND
RECOMMENDATIONS
7.1 Summary
A total of 16 full-scale dynamic tests were performed on a four-span steel pole line
segment for two different phase configurations. The test line consisted of a traditional
twelve-sided steel pole single circuit configuration with three conductors and 1 shield
wire. Failure modes simulated in the tests included broken shield wire or conductor
failure. Load cells were used in each span at each shield wire and conductor location
and at each insulator.
Data was processed to determine longitudinal load impact factors at the first, second,
and third structure from the initial failure. Impact factors were compared to impact
factors predicted by the advanced CASE assessment method and to scale model and
full-scale test values published by other researchers.
7.2 Conclusions
Unbalanced longitudinal load predictions by the CASE assessment method for the first,
second, and third structure from the initial failure compare well with measured full-
scale test values and values published by other researchers (see also Volume III of the
report). Based on the data, unbalanced longitudinal loads were significantly lower at
the second structure compared to the first structure. Similarly, unbalanced longitudinal
loads were significantly lower at the third structure relative to the second structure and
the first structure.
7-1
Summary, Conclusions and Recommendations
increase while the initial tensions decrease resulting in non-proportional changes of the
unbalanced longitudinal loads.
Impact factors and corresponding unbalanced longitudinal loads at each structure were
determined to vary as a function of the span/insulator ratio. Based on the data,
increases in the span/insulator ratios appear to reduce impact factors and unbalanced
longitudinal loads at each structure while decreasing span/insulator ratios have the
opposite effect (see also Volume III of the report). However, changes in the
span/insulator ratios do not affect the magnitude of the impact factors and
corresponding unbalanced loads as severe as changes in the span/sag ratios.
Finally, it was observed that the flexibility of the structures had an effect on the
magnitudes of the impact factors and corresponding unbalanced longitudinal loads at
each support (see also Volume III of the report). Based on the data, increases in the
structural flexibility cause a reduction of the impact factors and unbalanced
longitudinal loads at each structure while decreases in the structural flexibility cause an
increase in the unbalanced longitudinal loads. However, it was observed that large
changes in the structural flexibility of the support structures cause only relatively small
changes in the impact factors and corresponding unbalanced longitudinal loads at the
first, second, and third structure from the initial failure. Based on the structural
characteristics of most transmission structures, changes in the impact factors and
unbalanced longitudinal loads are less than 10 percent of the value.
Test results show that the CASE assessment method accurately predicts unbalanced
longitudinal loads at the first, second, and third structure from an initial failure such as
a broken shield wire or conductor (also see Volume III). Additionally, the CASE
assessment method correctly predicts the dissipation of energy along the transmission
line in the computation of the unbalanced longitudinal loads. The CASE assessment
method can be used to determine the cascading potential of transmission lines allowing
the engineer to identify the most critical lines within a particular utility’s system.
7.3 Recommendations
While the CASE assessment method allows the engineer to identify the transmission
lines with the highest cascading potential, it does not provide the tools or devices to
mitigate the identified problem. There is a need to develop a variety of cascading
failure mitigation devices such as longitudinal load dampers or load reduction
hardware. Mitigation alternatives need to be developed which can be used to mitigate
the cascading potential on existing line configurations and in limited right-of-way
situations. Naturally, such mitigation alternatives would also facilitate upgrading of
otherwise marginal transmission lines.
7-3
8
REFERENCES
(3) BROKEN WIRE ASSUMPTION, AIEE Committee Report, Paper 60, Power
Apparatus and Systems, June 1960.
8-1
References
8-2
B
CASE ASSESSMENT PREDICTIONS -
'VERTICAL' CONFIGURATION
B-1
CASE Assessment Predictions - ‘Vertical’ Configuration
Table B-1
Normalized Tensions - Broken Ground Wire, Long Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.286 0.286
MI_2 0.286 0.286
UI_2 0.286 0.286
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.286 0.286
MI_3 0.286 0.286
UI_3 0.286 0.286
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.286 0.286
MI_4 0.286 0.286
UI_4 0.286 0.286
Table B-2
Normalized Unbalanced Loads - Broken Ground Wire, Long Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 0.000 0.000 0.000
S_S1 0.980 0.000 0.980
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.000 0.000 0.000
S_S2 0.680 0.000 0.680
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.000 0.000 0.000
S_S3 0.540 0.000 0.540
B-2
CASE Assessment Predictions - ‘Vertical’ Configuration
Table B-3
Normalized Tensions - Broken Upper Conductor, Long Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.298 0.298
MI_2 0.298 0.298
UI_2 0.298 0.298
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.298 0.298
MI_3 0.298 0.298
UI_3 0.298 0.298
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.298 0.298
MI_4 0.298 0.298
UI_4 0.298 0.298
Table B-4
Normalized Unbalanced Loads - Broken Upper Conductor, Long Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 1.290 0.000 1.290
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.900 0.000 0.900
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.700 0.000 0.700
S_S3 0.000 0.000 0.000
B-3
CASE Assessment Predictions - ‘Vertical’ Configuration
Table B-5
Normalized Tensions - Broken Ground Wire, Long Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.175 0.175
MI_2 0.175 0.175
UI_2 0.175 0.175
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.175 0.175
MI_3 0.175 0.175
UI_3 0.175 0.175
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.175 0.175
MI_4 0.175 0.175
UI_4 0.175 0.175
Table B-6
Normalized Unbalanced Loads - Broken Ground Wire, Long Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 0.000 0.000 0.000
S_S1 0.770 0.000 0.770
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.000 0.000 0.000
S_S2 0.540 0.000 0.540
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.000 0.000 0.000
S_S3 0.420 0.000 0.420
B-4
CASE Assessment Predictions - ‘Vertical’ Configuration
Table B-7
Normalized Tensions - Broken Upper Conductor, Long Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.184 0.184
MI_2 0.184 0.184
UI_2 0.184 0.184
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.184 0.184
MI_3 0.184 0.184
UI_3 0.184 0.184
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.184 0.184
MI_4 0.184 0.184
UI_4 0.184 0.184
Table B-8
Normalized Unbalanced Loads - Broken Upper Conductor, Long Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 1.010 0.000 1.010
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.710 0.000 0.710
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.550 0.000 0.550
S_S3 0.000 0.000 0.000
B-5
CASE Assessment Predictions - ‘Vertical’ Configuration
Table B-9
Normalized Tensions - Broken Ground Wire, Short Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.183 0.183
MI_2 0.183 0.183
UI_2 0.183 0.183
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.183 0.183
MI_3 0.183 0.183
UI_3 0.183 0.183
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.183 0.183
MI_4 0.183 0.183
UI_4 0.183 0.183
Table B-10
Normalized Unbalanced Loads - Broken Ground Wire, Short Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 0.000 0.000 0.000
S_S1 0.700 0.000 0.700
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.000 0.000 0.000
S_S2 0.490 0.000 0.490
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.000 0.000 0.000
S_S3 0.380 0.000 0.380
B-6
CASE Assessment Predictions - ‘Vertical’ Configuration
Table B-11
Normalized Tensions - Broken Upper Conductor, Short Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.198 0.198
MI_2 0.198 0.198
UI_2 0.198 0.198
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.198 0.198
MI_3 0.198 0.198
UI_3 0.198 0.198
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.198 0.198
MI_4 0.198 0.198
UI_4 0.198 0.198
Table B-12
Normalized Unbalanced Loads - Broken Upper Conductor, Short Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 0.860 0.000 0.860
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.600 0.000 0.600
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.470 0.000 0.470
S_S3 0.000 0.000 0.000
B-7
CASE Assessment Predictions - ‘Vertical’ Configuration
Table B-13
Normalized Tensions - Broken Ground Wire, Short Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.299 0.299
MI_2 0.299 0.299
UI_2 0.299 0.299
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.299 0.299
MI_3 0.299 0.299
UI_3 0.299 0.299
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.299 0.299
MI_4 0.299 0.299
UI_4 0.299 0.299
Table B-14
Normalized Unbalanced Loads - Broken Ground Wire, Short Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 0.000 0.000 0.000
S_S1 0.950 0.000 0.950
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.000 0.000 0.000
S_S2 0.660 0.000 0.660
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.000 0.000 0.000
S_S3 0.520 0.000 0.520
B-8
CASE Assessment Predictions - ‘Vertical’ Configuration
Table B-15
Normalized Tensions - Broken Upper Conductor, Short Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.311 0.311
MI_2 0.311 0.311
UI_2 0.311 0.311
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.311 0.311
MI_3 0.311 0.311
UI_3 0.311 0.311
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.311 0.311
MI_4 0.311 0.311
UI_4 0.311 0.311
Table B-16
Normalized Unbalanced Loads - Broken Upper Conductor, Short Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 1.250 0.000 1.250
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.870 0.000 0.870
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.680 0.000 0.680
S_S3 0.000 0.000 0.000
B-9
C
FULL-SCALE TEST RESULTS -
'DELTA' CONFIGURATION
C-1
Full-Scale Test Results - ‘Delta’ Configuration
Table C-1
Tension Summary - Broken Middle Conductor, Long Insulator, 15% UTS
Table C-2
Unbalanced Loads - Broken Middle Conductor, Long Insulator, 15% UTS
C-2
Full-Scale Test Results - ‘Delta’ Configuration
Table C-3
Normalized Tensions - Broken Middle Conductor, Long Insulator, 15% UTS
Table C-4
Normalized Loads - Broken Middle Conductor, Long Insulator, 15% UTS
C-3
Full-Scale Test Results - ‘Delta’ Configuration
Table C-5
Tension Summary - Broken Upper Conductor, Long Insulator, 15% UTS
Table C-6
Unbalanced Loads - Broken Upper Conductor, Long Insulator, 15% UTS
C-4
Full-Scale Test Results - ‘Delta’ Configuration
Table C-7
Normalized Tensions - Broken Upper Conductor, Long Insulator, 15% UTS
Table C-8
Normalized Loads - Broken Upper Conductor, Long Insulator, 15% UTS
C-5
Full-Scale Test Results - ‘Delta’ Configuration
Table C-9
Tension Summary - Broken Middle Conductor, Long Insulator, 15% UTS
Table C-10
Unbalanced Loads - Broken Middle Conductor, Long Insulator, 15% UTS
C-6
Full-Scale Test Results - ‘Delta’ Configuration
Table C-11
Normalized Tensions - Broken Middle Conductor, Long Insulator, 15% UTS
Table C-12
Normalized Loads - Broken Middle Conductor, Long Insulator, 15% UTS
C-7
Full-Scale Test Results - ‘Delta’ Configuration
Table C-13
Tension Summary - Broken Upper Conductor, Long Insulator, 15% UTS
Table C-14
Unbalanced Loads - Broken Upper Conductor, Long Insulator, 15% UTS
C-8
Full-Scale Test Results - ‘Delta’ Configuration
Table C-15
Normalized Tensions - Broken Upper Conductor, Long Insulator, 15% UTS
Table C-16
Normalized Loads - Broken Upper Conductor, Long Insulator, 15% UTS
C-9
Full-Scale Test Results - ‘Delta’ Configuration
Table C-17
Tension Summary - Broken Middle Conductor, Long Insulator, 25% UTS
Table C-18
Unbalanced Loads - Broken Middle Conductor, Long Insulator, 25% UTS
C-10
Full-Scale Test Results - ‘Delta’ Configuration
Table C-19
Normalized Tensions - Broken Middle Conductor, Long Insulator, 25% UTS
Table C-20
Normalized Loads - Broken Middle Conductor, Long Insulator, 25% UTS
C-11
Full-Scale Test Results - ‘Delta’ Configuration
Table C-21
Tension Summary - Broken Upper Conductor, Long Insulator, 25% UTS
Table C-22
Unbalanced Loads - Broken Upper Conductor, Long Insulator, 25% UTS
C-12
Full-Scale Test Results - ‘Delta’ Configuration
Table C-23
Normalized Tensions - Broken Upper Conductor, Long Insulator, 25% UTS
Table C-24
Normalized Loads - Broken Upper Conductor, Long Insulator, 25% UTS
C-13
Full-Scale Test Results - ‘Delta’ Configuration
Table C-25
Tension Summary - Broken Outside Insulator, Unguyed, Long Insulator, 25% UTS
Table C-26
Unbalanced Loads - Broken Outside Insulator, Unguyed, Long Insulator, 25% UTS
C-14
Full-Scale Test Results - ‘Delta’ Configuration
Table C-27
Normalized Tensions - Broken Outside Insulator, Unguyed, Long Insulator, 25% UTS
Table C-28
Normalized Loads - Broken Outside Insulator, Unguyed, Long Insulator, 25% UTS
C-15
Full-Scale Test Results - ‘Delta’ Configuration
Table C-29
Tension Summary - Broken Upper Conductor, Short Insulator, 25% UTS
Table C-30
Unbalanced Loads - Broken Upper Conductor, Short Insulator, 25% UTS
C-16
Full-Scale Test Results - ‘Delta’ Configuration
Table C-31
Normalized Tensions - Broken Upper Conductor, Short Insulator, 25% UTS
Table C-32
Normalized Loads - Broken Upper Conductor, Short Insulator, 25% UTS
C-17
D
CASE ASSESSMENT PREDICTIONS -
'DELTA' CONFIGURATION
D-1
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-1
Normalized Tensions - Broken Middle Conductor, Long Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.304 0.304
MI_2 0.304 0.304
UI_2 0.304 0.304
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.304 0.304
MI_3 0.304 0.304
UI_3 0.304 0.304
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.304 0.304
MI_4 0.304 0.304
UI_4 0.304 0.304
Table D-2
Normalized Unbalanced Loads - Broken Middle Conductor, Long Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 1.300 0.000 1.300
UC_S1 0.000 0.000 0.000
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.910 0.000 0.910
UC_S2 0.000 0.000 0.000
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.710 0.000 0.710
UC_S3 0.000 0.000 0.000
S_S3 0.000 0.000 0.000
D-2
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-3
Normalized Tensions - Broken Upper Conductor, Long Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.301 0.301
MI_2 0.301 0.301
UI_2 0.301 0.301
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.301 0.301
MI_3 0.301 0.301
UI_3 0.301 0.301
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.301 0.301
MI_4 0.301 0.301
UI_4 0.301 0.301
Table D-4
Normalized Unbalanced Loads - Broken Upper Conductor, Long Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 1.290 0.000 1.290
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.900 0.000 0.900
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.710 0.000 0.710
S_S3 0.000 0.000 0.000
D-3
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-5
Normalized Tensions - Broken Middle Conductor, Long Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.304 0.304
MI_2 0.304 0.304
UI_2 0.304 0.304
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.304 0.304
MI_3 0.304 0.304
UI_3 0.304 0.304
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.304 0.304
MI_4 0.304 0.304
UI_4 0.304 0.304
Table D-6
Normalized Unbalanced Loads - Broken Middle Conductor, Long Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 1.300 0.000 1.300
UC_S1 0.000 0.000 0.000
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.910 0.000 0.910
UC_S2 0.000 0.000 0.000
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.710 0.000 0.710
UC_S3 0.000 0.000 0.000
S_S3 0.000 0.000 0.000
D-4
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-7
Normalized Tensions - Broken Upper Conductor, Long Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.307 0.307
MI_2 0.307 0.307
UI_2 0.307 0.307
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.307 0.307
MI_3 0.307 0.307
UI_3 0.307 0.307
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.307 0.307
MI_4 0.307 0.307
UI_4 0.307 0.307
Table D-8
Normalized Unbalanced Loads - Broken Upper Conductor, Long Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 1.310 0.000 1.310
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.910 0.000 0.910
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.720 0.000 0.720
S_S3 0.000 0.000 0.000
D-5
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-9
Normalized Tensions - Broken Middle Conductor, Long Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.286 0.286
MI_2 0.286 0.286
UI_2 0.286 0.286
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.286 0.286
MI_3 0.286 0.286
UI_3 0.286 0.286
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.286 0.286
MI_4 0.286 0.286
UI_4 0.286 0.286
Table D-10
Normalized Unbalanced Loads - Broken Middle Conductor, Long Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 1.000 0.000 1.000
UC_S1 0.000 0.000 0.000
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.700 0.000 0.700
UC_S2 0.000 0.000 0.000
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.550 0.000 0.550
UC_S3 0.000 0.000 0.000
S_S3 0.000 0.000 0.000
D-6
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-11
Normalized Tensions - Broken Upper Conductor, Long Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.286 0.286
MI_2 0.286 0.286
UI_2 0.286 0.286
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.286 0.286
MI_3 0.286 0.286
UI_3 0.286 0.286
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.286 0.286
MI_4 0.286 0.286
UI_4 0.286 0.286
Table D-12
Normalized Unbalanced Loads - Broken Upper Conductor, Long Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 0.960 0.000 0.960
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.670 0.000 0.670
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.530 0.000 0.530
S_S3 0.000 0.000 0.000
D-7
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-13
Normalized Tensions - Broken Middle Conductor, Short Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.286 0.286
MI_2 0.286 0.286
UI_2 0.286 0.286
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.286 0.286
MI_3 0.286 0.286
UI_3 0.286 0.286
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.286 0.286
MI_4 0.286 0.286
UI_4 0.286 0.286
Table D-14
Normalized Unbalanced Loads - Broken Middle Conductor, Short Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.900 0.000 0.900
UC_S1 0.000 0.000 0.000
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.630 0.000 0.630
UC_S2 0.000 0.000 0.000
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.490 0.000 0.490
UC_S3 0.000 0.000 0.000
S_S3 0.000 0.000 0.000
D-8
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-15
Normalized Tensions - Broken Upper Conductor, Short Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.286 0.286
MI_2 0.286 0.286
UI_2 0.286 0.286
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.286 0.286
MI_3 0.286 0.286
UI_3 0.286 0.286
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.286 0.286
MI_4 0.286 0.286
UI_4 0.286 0.286
Table D-16
Normalized Unbalanced Loads - Broken Upper Conductor, Short Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 0.910 0.000 0.910
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.630 0.000 0.630
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.500 0.000 0.500
S_S3 0.000 0.000 0.000
D-9
D
CASE ASSESSMENT PREDICTIONS -
'DELTA' CONFIGURATION
D-1
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-1
Normalized Tensions - Broken Middle Conductor, Long Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.304 0.304
MI_2 0.304 0.304
UI_2 0.304 0.304
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.304 0.304
MI_3 0.304 0.304
UI_3 0.304 0.304
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.304 0.304
MI_4 0.304 0.304
UI_4 0.304 0.304
Table D-2
Normalized Unbalanced Loads - Broken Middle Conductor, Long Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 1.300 0.000 1.300
UC_S1 0.000 0.000 0.000
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.910 0.000 0.910
UC_S2 0.000 0.000 0.000
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.710 0.000 0.710
UC_S3 0.000 0.000 0.000
S_S3 0.000 0.000 0.000
D-2
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-3
Normalized Tensions - Broken Upper Conductor, Long Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.301 0.301
MI_2 0.301 0.301
UI_2 0.301 0.301
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.301 0.301
MI_3 0.301 0.301
UI_3 0.301 0.301
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.301 0.301
MI_4 0.301 0.301
UI_4 0.301 0.301
Table D-4
Normalized Unbalanced Loads - Broken Upper Conductor, Long Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 1.290 0.000 1.290
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.900 0.000 0.900
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.710 0.000 0.710
S_S3 0.000 0.000 0.000
D-3
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-5
Normalized Tensions - Broken Middle Conductor, Long Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.304 0.304
MI_2 0.304 0.304
UI_2 0.304 0.304
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.304 0.304
MI_3 0.304 0.304
UI_3 0.304 0.304
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.304 0.304
MI_4 0.304 0.304
UI_4 0.304 0.304
Table D-6
Normalized Unbalanced Loads - Broken Middle Conductor, Long Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 1.300 0.000 1.300
UC_S1 0.000 0.000 0.000
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.910 0.000 0.910
UC_S2 0.000 0.000 0.000
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.710 0.000 0.710
UC_S3 0.000 0.000 0.000
S_S3 0.000 0.000 0.000
D-4
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-7
Normalized Tensions - Broken Upper Conductor, Long Insulator, 15% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.307 0.307
MI_2 0.307 0.307
UI_2 0.307 0.307
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.307 0.307
MI_3 0.307 0.307
UI_3 0.307 0.307
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.307 0.307
MI_4 0.307 0.307
UI_4 0.307 0.307
Table D-8
Normalized Unbalanced Loads - Broken Upper Conductor, Long Insulator, 15% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 1.310 0.000 1.310
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.910 0.000 0.910
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.720 0.000 0.720
S_S3 0.000 0.000 0.000
D-5
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-9
Normalized Tensions - Broken Middle Conductor, Long Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.286 0.286
MI_2 0.286 0.286
UI_2 0.286 0.286
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.286 0.286
MI_3 0.286 0.286
UI_3 0.286 0.286
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.286 0.286
MI_4 0.286 0.286
UI_4 0.286 0.286
Table D-10
Normalized Unbalanced Loads - Broken Middle Conductor, Long Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 1.000 0.000 1.000
UC_S1 0.000 0.000 0.000
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.700 0.000 0.700
UC_S2 0.000 0.000 0.000
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.550 0.000 0.550
UC_S3 0.000 0.000 0.000
S_S3 0.000 0.000 0.000
D-6
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-11
Normalized Tensions - Broken Upper Conductor, Long Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.286 0.286
MI_2 0.286 0.286
UI_2 0.286 0.286
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.286 0.286
MI_3 0.286 0.286
UI_3 0.286 0.286
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.286 0.286
MI_4 0.286 0.286
UI_4 0.286 0.286
Table D-12
Normalized Unbalanced Loads - Broken Upper Conductor, Long Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 0.960 0.000 0.960
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.670 0.000 0.670
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.530 0.000 0.530
S_S3 0.000 0.000 0.000
D-7
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-13
Normalized Tensions - Broken Middle Conductor, Short Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.286 0.286
MI_2 0.286 0.286
UI_2 0.286 0.286
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.286 0.286
MI_3 0.286 0.286
UI_3 0.286 0.286
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.286 0.286
MI_4 0.286 0.286
UI_4 0.286 0.286
Table D-14
Normalized Unbalanced Loads - Broken Middle Conductor, Short Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.900 0.000 0.900
UC_S1 0.000 0.000 0.000
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.630 0.000 0.630
UC_S2 0.000 0.000 0.000
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.490 0.000 0.490
UC_S3 0.000 0.000 0.000
S_S3 0.000 0.000 0.000
D-8
CASE Assessment Predictions - ‘Delta’ Configuration
Table D-15
Normalized Tensions - Broken Upper Conductor, Short Insulator, 25% UTS
Normalized Normalized
Maximum Minimum
Value Value
LC_1 1.000 1.000
MC_1 1.000 1.000
UC_1 1.000 1.000
S_1 1.000 1.000
LC_2 1.000 1.000
MC_2 1.000 1.000
UC_2 1.000 1.000
S_2 1.000 1.000
LI_2 0.286 0.286
MI_2 0.286 0.286
UI_2 0.286 0.286
LC_3 1.000 1.000
MC_3 1.000 1.000
UC_3 1.000 1.000
S_3 1.000 1.000
LI_3 0.286 0.286
MI_3 0.286 0.286
UI_3 0.286 0.286
LC_4 1.000 1.000
MC_4 1.000 1.000
UC_4 1.000 1.000
S_4 1.000 1.000
LI_4 0.286 0.286
MI_4 0.286 0.286
UI_4 0.286 0.286
Table D-16
Normalized Unbalanced Loads - Broken Upper Conductor, Short Insulator, 25% UTS
Net
Maximum Minimum Unbalanced
Value Value Load
LC_S1 0.000 0.000 0.000
MC_S1 0.000 0.000 0.000
UC_S1 0.910 0.000 0.910
S_S1 0.000 0.000 0.000
LC_S2 0.000 0.000 0.000
MC_S2 0.000 0.000 0.000
UC_S2 0.630 0.000 0.630
S_S2 0.000 0.000 0.000
LC_S3 0.000 0.000 0.000
MC_S3 0.000 0.000 0.000
UC_S3 0.500 0.000 0.500
S_S3 0.000 0.000 0.000
D-9