Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
TABULATIONxxxx
OF REVISED PAGES
Page D00 D01 D02 D03 D04 Page D00 D01 D02 D03 D04
1. X X X 35.
2. X X X 36.
3. X X 37.
4. X X 38.
5. X X X 39.
6. X X 40.
7. X X 41.
8. X X 42.
9. X X 43.
10. X X 44.
11. X X X 45.
12. X X X 46.
13. X X 47.
14. X X X 48.
15. X X 49.
16. X X X 50.
17. X X 51.
18. X X 52.
19. X X X 53.
20. X X X 54.
21. X X 55.
22. X X X 56.
23. X X X 57.
24. X X X 58.
25. X X 59.
26. X 60.
27. 61.
28. 62.
29. 63.
30. 64.
31. 65.
32. 66.
33. 67.
34. 68.
Client: Project: Subcontractor:
Azar Oil Field Development
Doc. Title:
NIOC
Electrical Design Criteria
Contract No.: 91014
Document Number Subcontractor Document No :
9018-AZ-EE-CRT-0005
ARFD-GCPFDC-ENEL-DCEL-0005 Page 3 of 26 Rev. D02
xxxx
Table of Content
1. General ..................................................................................................................................................... 5
1.1. Purpose .................................................................................................................................................... 5
1.2. Definition of terms ................................................................................................................................. 5
2. Reference and Standards ....................................................................................................................... 6
2.1. References................................................................................................................................................ 6
2.2. Standards.................................................................................................................................................. 7
2.3. Conflicting requirement ......................................................................................................................... 7
3. Scope of Documentation ...................................................................................................................... 7
4. Units ......................................................................................................................................................... 8
5. Design Condition.................................................................................................................................... 8
6. Design Basis ............................................................................................................................................ 9
6.1. Voltage Levels ......................................................................................................................................... 9
6.2. Types of Enclosure ................................................................................................................................ 9
6.3. Area Classification & Materials Selection ............................................................................................ 9
6.4. Certifications .........................................................................................................................................10
6.5. Minimum system requirement ............................................................................................................11
7. Electrical System Description .............................................................................................................12
7.1. Relay and Metering System .................................................................................................................13
7.2. High Voltage Switchgear (132kV) ......................................................................................................13
7.3. Medium Voltage Switchgear (6, 11kV) ..............................................................................................14
7.4. Low Voltage Switchboard ...................................................................................................................14
7.4.1. General ...................................................................................................................................................14
7.4.2. Power Motor Control Centers ............................................................................................................15
7.4.3. Subsidiary L.V. Switchboards .............................................................................................................15
7.5. Power Transformers ............................................................................................................................16
Client: Project: Subcontractor:
Azar Oil Field Development
Doc. Title:
NIOC
Electrical Design Criteria
Contract No.: 91014
Document Number Subcontractor Document No :
9018-AZ-EE-CRT-0005
ARFD-GCPFDC-ENEL-DCEL-0005 Page 4 of 26 Rev. D02
7.6. xxxx
Diesel generator .................................................................................................................................... 16
7.7. Electric Motors .....................................................................................................................................18
7.8. Lighting System.....................................................................................................................................18
7.9. Grounding System ................................................................................................................................19
7.10. Lightning Protection ............................................................................................................................21
7.11. Cables .....................................................................................................................................................21
7.12. Bus duct .................................................................................................................................................22
7.13. NER sizing ............................................................................................................................................23
7.14. DC Uninterruptible Power Systems...................................................................................................23
7.15. AC Uninterruptible Power Systems ...................................................................................................23
7.16. Power Factor Improvement................................................................................................................24
7.17. Cathodic Protection System ................................................................................................................24
7.18. Miscellaneous ........................................................................................................................................25
7.18.1. Convenience Receptacles ....................................................................................................................25
7.18.2. Welding Receptacles .............................................................................................................................25
7.18.3. Local Control Station ...........................................................................................................................25
7.18.4. Cable Terminations ..............................................................................................................................25
7.18.5. Cable trays and Ladders .......................................................................................................................26
7.18.6. Conduits .................................................................................................................................................26
Client: Project: Subcontractor:
Azar Oil Field Development
Doc. Title:
NIOC
Electrical Design Criteria
Contract No.: 91014
Document Number Subcontractor Document No :
9018-AZ-EE-CRT-0005
ARFD-GCPFDC-ENEL-DCEL-0005 Page 5 of 26 Rev. D02
xxxx
1. GENERAL
1.1. Purpose
This specification covers the basic requirements for the electrical system in project, Azar Oil
Fields Development Project
This specification is not intended to define the scope of supply.
2.1. References
The following Iranian Petroleum Standards (latest edition) shall be used for selection of
equipment:
• IPS-E-EL-100 "Engineering Standard for Electrical System Design (Industrial and Non-
Industrial) "
• IPS-E-EL-110 "Engineering Standard for hazardous area"
• IPS-C-EL-115 "Construction Standards for Electrical Installation"
• IPS-M-EL-131(2) "Material and equipment standard for low voltage induction motors"
• IPS-M-EL-132(2) "Material and equipment standard for medium & high voltage induction
motors"
• IPS-M-EL-138 "Material and equipment standard for Synchronous Generators"
• IPS-M-EL-143(2) "Material and equipment standard for Low Voltage Switchgear and
Control gear"
• IPS-M-EL-144(1) "Material and equipment standard for Medium and High Voltage
Switchgear and Control gear"
• IPS-M-EL-152(2) "Material and equipment standard for Oil Immersed Power Transformers"
• IPS-M-EL-155(1) "Material and equipment standard for Transformer Rectifiers for Cathodic
Protection"
• IPS-M-EL-161(1) "Material and equipment standard for General Electrical Items"
• IPS-M-EL-174(2) "Material and equipment standard for Battery & Battery Chargers"
• IPS-M-EL-176(2) "Material and equipment standard for Uninterrupted Power Supply
(UPS)"
• IPS-M-EL-181(2) "Material and equipment standard for Power Factor Improvement
Capacitor"
• IPS-M-EL-190(1) "Material and equipment standard for Electrical Heat Tracing"
• IPS-M-EL-230 "Material and equipment standard for Electrical Lighting Columns"
• IPS-M-EL-240 "Material and equipment standard for Low Voltage Industrial and
Flameproof a.c. Switch Fuse Assembly"
Client: Project: Subcontractor:
Azar Oil Field Development
Doc. Title:
NIOC
Electrical Design Criteria
Contract No.: 91014
Document Number Subcontractor Document No :
9018-AZ-EE-CRT-0005
ARFD-GCPFDC-ENEL-DCEL-0005 Page 7 of 26 Rev. D02
xxxx
• IPS-M-EL-271(1) "Material and equipment standard for Low Voltage Cables and Wires”
2.2. Standards
The electrical system design shall in general comply with the IEC requirements, where other
codes or standards are referenced to, it is understood that equivalent IEC (or BS)
recommendation shall be considered.
List of standards mentioned in this specification:
3. SCOPE OF DOCUMENTATION
The scope of the documentation for electrical equipment is as follows:
Client: Project: Subcontractor:
Azar Oil Field Development
Doc. Title:
NIOC
Electrical Design Criteria
Contract No.: 91014
Document Number Subcontractor Document No :
9018-AZ-EE-CRT-0005
ARFD-GCPFDC-ENEL-DCEL-0005 Page 8 of 26 Rev. D02
xxxx
• Drawing Index
• Specifications
• Key diagrams for protection and metering
• Single Line Diagram
• Main Equipment data sheets (Transformers, Switchgears, Generators, NER)
• Preliminary power and control cable schedules
• Electrical layout (Main cable routing layout; street lighting layout)
• Electrical Equipment Characteristics
4. UNITS
The international system of units (SI) shall be used for all drawings and documents.
5. DESIGN CONDITION
The electrical equipment shall be designed in due consideration of following design conditions,
unless otherwise specified:
6.4. Certifications
All materials to be installed in hazardous area will be certified by recognized Authority.
The marking requirements will include the following:
Electrical system and equipment shall be so designed to have highest reliability and minimum
failure in order to achieve safe, efficient, accurate and easy operation under various operational
requirements with minimum possible maintenance and operation cost.
The electrical system shall be designed based on safety to personnel during operation and
maintenance, reliability of services, ease of maintenance, convenience of operation, maximum
interchangeability of equipment and parts and shall be capable for future expansion of loads. All
major electrical equipments shall be centralized as far as possible and located in safe areas to
make maximum use of industrial type switchgear, motor control center equipment and etc.
Documents including in calculations, drawings, catalogues shall have sufficient and necessary
information for satisfactory operation, maintenance, trouble shooting, calibration, spare part list
and etc.
According to process requirements, some of the electrical information shall be indicated and/or
reported by monitoring and logging system in the plant with DCS and/or conventional control
system with owner’s prior approval.
Control of power sources and switchgears shall be achieved via Power Control
Distribution System (PDCS). For more detail of PDCS requirements refer to “PDCS
system specification (ARFD-GCPFSP-ENEL-SPDI-0019)”.
All guarantee figures shall be measured by sufficient and accurate metering system.
As far as possible designer and supplier shall consider equipment with low variety and high
interchangeability.
General spare parts shall be in the form of individual parts except for capital spares that are in
complete set or main part of vital equipment. Supply of spare part warranty shall be guaranteed
by manufacturer for minimum 10 years.
Necessary spare equipment and space for future expansion to the knowledge and experience of
contractor shall be considered. Owner’s approval shall be necessary for the case where there is no
figure appearing for spare parts in the contract.
Enough bulk materials for contingencies shall be added to the related material take-off lists.
As a whole. Design of the electrical system shall be based on the safety of personnel and
equipment during all expected modes of operation and maintenance, having minimum power
Client: Project: Subcontractor:
Azar Oil Field Development
Doc. Title:
NIOC
Electrical Design Criteria
Contract No.: 91014
Document Number Subcontractor Document No :
9018-AZ-EE-CRT-0005
ARFD-GCPFDC-ENEL-DCEL-0005 Page 12 of 26 Rev. D02
xxxx
losses, mechanical protection of equipment, interchangeability of equipment and parts and being
capable and ready to be expected.
Equipment shall be designed and derated for local working condition.
Specifications of equipment shall be prepared by contractor and submitted to owner for review
and approval.
Throughout these specifications the initial load means the foreseen load of plant at full operation
of the related state.
Electrical drawings, equipment specification and etc of package units shall be included in related
overall plant and equipment specifications.
The switchgears will consist of metalclad air insulated freestanding units, assembles together in
single row, suitable for indoor installation. Switchgears will be arranged for future extension at
both ends.
Units will be equipped with necessary current and potential transformer, relays, instruments and
other ancillary equipment.
Potential transformers will have draw out type primary current limiting fuses. Secondaries will be
rated 110 VAC
Current transformers will have secondary’s rated 1 A for protective relays, local and for remote
indication or metering.
Bus bars system will be insulated copper.
Circuit breakers will be restricted free vacuum type or maintenance free SF6 type with suitable
rupturing capacity.
Motor up to 1000 kW (inclusive) will be electrical operated by a combination of fuses and
vacuum contactor.
7.4.1. General
Low voltage switchboards will include Power Motor Control Centers (PMCC) and subsidiary
switchboards feeding all low voltage users.
The PMCC distribute power to large low voltage users, motors, Lighting Panels, Air Conditioning
units, Welding Receptacles, Heaters and so on. In case of admissible voltage tolerance limitations
in network studies, like motor starting, required bus bar separations for minimizing voltage drop
will be shown in related SLDs.
Unless otherwise indicated the switchboards will be for indoor installation.
L.V. switchboards will be designed with adequate rupturing capacity, the bus bar will be isolated
copper air insulated.
Deleted.
Low voltage switchboards will be equipped with 10 % of outgoing feeders as spare for future
needs plus 10 % spare space.
Client: Project: Subcontractor:
Azar Oil Field Development
Doc. Title:
NIOC
Electrical Design Criteria
Contract No.: 91014
Document Number Subcontractor Document No :
9018-AZ-EE-CRT-0005
ARFD-GCPFDC-ENEL-DCEL-0005 Page 15 of 26 Rev. D02
They will be of self-supporting, metal enclosed structure consisting of vertical sections housing
individual withdrawable motor starters for motors up to 150 KW.
Motor starters will be equipped with Fast Trip Moulded Case Circuit Breaker, air contactor, over
load relay as well as ground fault relay, indicating lamps for motor operation signal (Running,
Stop, Tripped, Draw out) and with reset button for thermal relay.
Equipment coordination will be according to IEC 60947.4.1 type 2.
The direct on line motor starters will be designed of utilization category AC-3.
The bi-metallic overload thermal protection will be 3 poles device, compensated as to operating
temperature, will be provided with protection devices against phase failure and with external
manual reset. Earth fault protection will have an adjustable setting current and adjustable time
setting to assure protective co-ordination requirements.
Starters will be housed in modular compartments and will be interchangeable.
Starters for motors larger than 4 kW will have a current transformer for ammeter installed on
remote control station.
Each PMCC board bus section will have a feeding compartment equipped with an on-load three-
phases disconnecting switch, suitably sized, a 400/110 VAC transformer for control circuits,
voltmeter and ammeter for local measuring as necessary.
20 % spare load capacity to be considered for PMCC.
20 % space capacity to be considered for PMCC extension.
Power Transformers will be oil immersed type, self cooled, suitable for outdoor installation (fully
outdoor type in 132kv substation and outdoor/under shelter in CPF plant). Transformers with
rating up to and including 2500 KVA shall be sealed type.
Transformers will be sized each one for the total power demand in the normal operating
conditions. 20% over sizing will be foreseen for each transformer.
Starting of large motors may require an over sizing of the transformer, for this reason the starting
current of motors and the starting method shall be considered in transformer sizing.
Windings will be copper made; cooling oil will be mineral type.
The following provides a basic list of measuring and protection devices for each type of
transformer. Definitive requirements shall be as specified in the datasheet.
Oil Immersed Power and Distribution Transformers
• Buchholz Relay (conservator type transformers only)
• Winding Temperature Indicator
• Oil Temperature and Level Indicator
• Pressure Relief Device
• Low Oil Level Alarm Device
Cast Resin Distribution Transformers
• Winding Temperature Device
Provision for installing of cooling fans in future shall be considered.
An off-load tap changer, manually operated, shall be provided on primary side, with at least five
taps, two above and two below the rated primary voltage ( ± 2 x 2.5%Vn).
Generally neutral of transformers will be solidly earthed and just for medium voltage
transformers that feed MV motors neutral earthing resistor will be used.
MV and LV motors will be asynchronous, squirrel-cage type, suitable for direct-on-line starting
unless otherwise specified. Motors will be according to IEC-60034.
Insulation class of motors will be “F“with temperature rise class “B”. The motors shall be totally
enclosed fan cooled (TEFC).
Low voltage motors should be selected in the range of the IEC series.
Anti-condensation heater/s is not required for low voltage motors unless otherwise specified.
Medium voltage motors shall be equipped with space heaters to prevent condensation inside
motors when they are not in operation. The voltage of the anti-condensation heaters shall be 230
volt single phase for heaters of up to 3 kW. For heaters above 3 kW, 400 volt three phase and
neutral shall be used. Anti-condensation heaters will be supplied by one power cable for each
motor.
MV motors will be equipped with main terminal box (for power cables) and with separated
terminal boxes for anti condensation heater, winding and bearing temperature detectors.
Winding temperature detectors will be provided for MV motors. Two resistance type temperature
detectors (PT100) for each phase will be wired in a separated auxiliary terminal box.
Motors larger than 1000 kW will be provided with current transformers for differential protection
installed in a separate terminal box.
Maximum noise level will be 85 db at 1 (one) meter.
Inside each terminal box an earthing stud of adequate dimensions will be fitted for connection of
earthing conductor. In addition all motors will be provided with an external earthing screw of at
least 8 mm diameter, metric thread, tapped into frame foot for equipment earthing, located at the
box side of the motor, at the opposite end to drive shaft
• normal
• emergency
• vital
Client: Project: Subcontractor:
Azar Oil Field Development
Doc. Title:
NIOC
Electrical Design Criteria
Contract No.: 91014
Document Number Subcontractor Document No :
9018-AZ-EE-CRT-0005
ARFD-GCPFDC-ENEL-DCEL-0005 Page 19 of 26 Rev. D02
xxxx and adequate light distribution in all working
The normal lighting system will provide an uniform
areas, the average illumination levels will be as per IPS-E-EL-100 Appendix “G”.
The main lighting feeders and the outlet feeders will be three phases, four wires plus neutral,
controlled by means of four poles automatic circuit breakers having an adequate breaking
capacity. The lighting branch circuits will be single phase, three wires and controlled by automatic
circuit breakers having an adequate breaking capacity and earth leakage protection. 25% spare
circuit capacity will be provided in all lighting panels.
External lighting will be automatically controlled by twilight photo-electric cell and a bypass for
manual operation.
The emergency lighting feed from the emergency system and shall be supplied at least the
following percentage of total lighting fixtures:
7.11. Cables
Cables will be according to IEC 60502 and IEC 60840.
MV cables will be stranded copper conductor, XLPE insulated, screened, single core and multi-
core, steel or aluminum single wire armored, lead sheated (if required), PVC outer jacket.
LV cables will be stranded copper conductor, XLPE insulated, single core and multicore, steel or
aluminum single wire armored, lead sheated (if required), PVC outer jacket.
The PVC outer jacket will be flame retardant type as per IEC 60332-3 Cat. C.
The cables voltage level will be:
• Continuous duty
• Ambient temperature (air or soil temperature)
• For buried cables depth and soil thermal resistivity
• Grouping derating factor and pass through conduits
• Rated current of users
• Voltage drops.
The short circuit of consumer side of outgoing LV cables will be considered in cable
sizing and maximum short circuit only will be considered for MV and main LV incoming
cables. The period of short circuit remaining in cable sizing will be 0.25 second.
• Fully automatic dual static battery charger with all associated parts.
• Distribution panel, with outgoing feeders by automatic circuit breakers.
• Vented Ni-Cd type batteries.
• Back up time 4 hours (including 2 sets of battery racks, each of them can supply total loads
for 2 hours).
Unless otherwise specified, power supply of charger shall be considered as 400V, 3ph, 50Hz.
Batteries shall be installed within separate room located near to DC UPS unit.
Cable trays /ladders shall be hot dip galvanized steel, but in corrosive areas, corrosion resistant
material such as stainless steel shall be considered.
7.18.6. Conduits
Where necessary above grade conduits shall be rigid hot dipped galvanized steel.