Sei sulla pagina 1di 1

MATERIAL LIST

ITEM DESCRIPTION QTY


IMC567 1/2"T x 1/2"NPT Male Connector, 316 SS 16
SIT493 1/2" OD x 0.049" WT Tubing, A269 Gr.TP316, Smls, Fully Annealed 160 ft

SEE DETAIL 'A'


FLOW

IMC567 IMC567 IMC567 IMC567 BY PIPING


BY INSTRUMENTS
IMC567 IMC567 IMC567 IMC567

SLOPE DOWN 1" SLOPE DOWN 1" SLOPE DOWN 1" SLOPE DOWN 1"
PER FOOT MIN. PER FOOT MIN. PER FOOT MIN. PER FOOT MIN.
45 o MAX 45 o MAX
SIT493 SIT493 SIT493 SIT493 SIT493 SIT493 SIT493 SIT493

DETAIL 'A'

TIME: 10:07:09
NOTE 4 NOTE 4 NOTE 4 NOTE 4

IMC567 IMC567 IMC567 IMC567 IMC567 IMC567 IMC567 IMC567

GENERATED DATE: 06-Oct-10


H L H L H L H L

CLASS 150, 300 & 600


NOTES
INSTRUMENT INSTALLATION DETAIL
1. SEE INSTRUMENT NOTES AND LEGEND DRAWING #166000-000-DG-IC04-0001.
2. FOR TAGS ASSIGNED TO THIS DETAIL SEE INSTRUMENT INDEX.
3 ISSUED FOR CONSTRUCTION GC DS GN 08-Oct-10 (4) REDUNDANT D/P FLOW TRANSMITTERS

HOOK-UP: FT-STD-009
3. INSTRUMENT TUBING TO BE FIELD ROUTED AND SUPPORTED 2 ISSUED FOR CONSTRUCTION GC DS GN 25-Mar-10 LIQUID BELOW REMOTE MOUNT
AS REQUIRED.
4. MANIFOLD & MOUNTING BRACKET SUPPLIED WITH TRANSMITTER. 1 REVISED AS NOTED KRF PMB COMM 09-Feb-09 CARTAGENA EXPANSION PROJECT
0 ISSUED FOR DESIGN KRF PMB COMM 24-Aug-09
THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION DESCRIBING TECHNOLOGY
OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN CONNECTION WITH WORK PERFORMED BY CB&I.
REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN
PERMISSION OF CB&I. IT IS TO BE SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.
FOR: Refineria de Cartagena S.A.
DRAWN: CK'D: APPD: DATE: SCALE:
NO. REVISION DRAWN CK'D APPD DATE
PMB RSB COMM 18-Aug-08 N/A PROJ NO: 166000 DWG NO: 000-DG-IC04-0011 REV: 3