Sei sulla pagina 1di 14

PT. PUPUK SRIWIDJAJA PALEMBANG PT. WIJAYA KARYA (Persero) Tbk.

PROYEK PEMBANGUNAN PABRIK NPK FUSION II


KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

NPKII-00-N3-DS-401-W

1 IFA 10-Oct-18 WIT AVH THD


0 IFA 9-Mar-18 WIT AVH THD
DIBUAT DIPERIKSA DISETUJUI DIPERIKSA DISETUJUI
REV. STATUS DATE OLEH OLEH OLEH OLEH OLEH
PT.WIJAYA KARYA PT. PUPUK SRIWIDJAJA PALEMBANG
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

NAME & NAME &


NO COMPANY COMMENT CONTRACTOR RESPONSE
TITLE TITLE

1 Page: 3, 5, 7, 9, 11
- Update general requirement cable - Incoporated
2 Page: 4, 6, 8, 10, 12
- Update reference and abbreviation - Incoporated
3 Page: 13, 14
- Add datasheet of earthing cable - Incoporated

NPKII-00-N3-DS-401-W 2 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : As per Electrical Power & Control Cable Schedule
2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : 13.8 kV Medium Voltage Power Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 1. SITE CONDITION
7 Location of Installation Indoor / Outdoor
8 Temperature
o
9 - Max. Ambient Temperature C 40
o
10 - Min. Ambient Temperature C 20
o
11 - Design Ambient Temperature C 35
12 Humidity
13 - Max. Humidity % 100
14 - Min. Humidity % 54
15 - Average Humidity % 85
16 Atsmosphere Corrosive, Dust and Humid Tropical
17 Altitude mm 5500
18
19 2. GENERAL REQUIREMENT
20 Design Code & Standard IEC Standard
21 Manufacturer As per AML 1
22 (Supreme, Kabelindo, KMI, Sumi Indo Kabel)
23 Type of Cables Cu / XLPE / CTS / PVC / SFWA / PVC
24 N2XSEFGbY
25 Rated Voltage of Cable (Uo/U) kV 8.7 / 15
26 Rating Voltage kV 13.8
27 No. of Phases Three (3)
28 Frequency Hz 50
29 Conductor Material Copper
30 Number of Core Nos 3 1
31 Size of Cable mm2 Refer to " NPKII-00-N0-BE-402-W 1
32 Electrical Power & Control Cable Schedule ")
33 Conductor Max. Withstand Temperature for:
o
34 - Continous Rating C VTA 1
o
35 - Overload C VTA 1
o
36 - Short Circuit C VTA 1
37 Rated Current Ampacity
38 - In Air VTA
39 - In Soil VTA
40 Max. DC Conductor Resistance at 20oC Ohm / km VTA
41 Max. DC Conductor Resistance at 90oC Ohm / km VTA
42 Max. Conductor Inductance mH/km VTA
43 Short Circuit kA / 1 sec VTA
44 Special Features N/A
45 Insulating Material XLPE
46 - Minimum Thickness at Any Point IEC 60502-1
47 - Nominal Thickness Appoximately IEC 60502-1
48 - Color Identification Red (R), Black(S), Yellow (T) 1
49 Screen Material Yes/No Yes, Copper Tape Screen
50 Inner Covering Yes/No Yes, PVC
51 Armor Yes/No Yes, Steel Flat Wire Armor
52 - Steel Tape Thickness Approximately IEC 60502-1
53 Outer Protective Sheath PVC
54 - Nominal Thickness Appoximately IEC 60502-1
55 - Minimum Thickness at Any Point IEC 60502-1
56 - Color Red
57 Overall Diameter for Cable mm VTA
58 Standard Length per Reel Cable m VTA
59 Cable Weight Approximate per meter kg VTA
60 Marking & Identification Yes / No Yes, Printed
61 - Manufacturer's Name Required
62 - Year Of Manufacturing Required
63 - Applicable IEC Standard Identification Required
64 - Cable Type, Core Size, Voltage Grade, Number of Cores Required ( every 500 mm)
65 - Purchaser's Type Code Required

NPKII-00-N3-DS-401-W 3 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : As per Electrical Power & Control Cable Schedule
2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : 13.8 kV Medium Voltage Power Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 3. CONSTRUCTION
7 Cable Arrangement Drawing Required
8 Type of Cable Drum Steel / Wood VTA
9 Max Cable Length On Drum m VTA
10 Total Cable Weight On Drum kg VTA
11
12 4. TESTING AND INSPECTION
13 Routine test Yes / No Yes
14 Type Test Certificate Yes / No Yes
15 Vendor's Documentation Review Requirement Yes / No Yes
16
17 REFERENCE
18 1. NPKII-00-N0-GS-401-W Electrical Design Basis
19 2. NPKII-00-N3-IS-401-W Electrical Specification of Cable and Wire
20 3. NPKII-00-N3-CS-401-W Electrical Calculation of Cable Sizing Calculation
21 4. NPKII-00-N0-BE-402-W Electrical Power & Control Cable Schedule
22
23 ABBREVIATION
24 VTA : Vendor To Advise
25 TBA : To Be Available
26 N/A : Not Applicable
27 AML : Approved Manufacturer List 1
28
29 NOTE
30 1. All these data shall be verified during Technical Bid Evaluation and subject to owner approval
31 2. Cable end shall be sealed with watertight heatsrink seal and shall be firmly fixed to the drum
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
64
65

NPKII-00-N3-DS-401-W 4 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : As per Electrical Power & Control Cable Schedule
2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : 2.4 kV Medium Voltage Power Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 1. SITE CONDITION
7 Location of Installation Indoor / Outdoor
8 Temperature
o
9 - Max. Ambient Temperature C 40
o
10 - Min. Ambient Temperature C 19
o
11 - Design Ambient Temperature C 29
12 Humidity
13 - Max. Humidity % 100
14 - Min. Humidity % 54
15 - Average Humidity % 85
16 Atsmosphere Corrosive, Dust and Humid Tropical
17 Altitude mm 5500
18
19 2. GENERAL REQUIREMENT
20 Design Code & Standard IEC Standard
21 Manufacturer As per AML 1
22 (Supreme, Kabelindo, KMI, Sumi Indo Kabel)
23 Type of Cables Cu / XLPE / CTS / PVC / SFWA / PVC
24 N2XSEFGbY
25 Rated Voltage of Cable (Uo/U) kV 3.6 / 6
26 Rating Voltage kV 2.4
27 No. of Phases Three (3)
28 Frequency Hz 50
29 Conductor Material Copper
30 Number of Core Nos 3 1
31 Size of Cable mm2 Refer to " NPKII-00-N0-BE-402-W 1
32 Electrical Power & Control Cable Schedule ")
33 Conductor Max. Withstand Temperature for:
o
34 - Continous Rating C VTA 1
o
35 - Overload C VTA 1
o
36 - Short Circuit C VTA 1
37 Rated Current Ampacity
38 - In Air VTA
39 - In Soil VTA
40 Max. DC Conductor Resistance at 20oC Ohm / km VTA
41 Max. DC Conductor Resistance at 90oC Ohm / km VTA
42 Max. Conductor Inductance mH/km VTA
43 Short Circuit kA / 1 sec VTA
44 Special Features N/A
45 Insulating Material XLPE
46 - Minimum Thickness at Any Point IEC 60502-1
47 - Nominal Thickness Appoximately IEC 60502-1
48 - Color Identification Red (R), Black(S), Yellow (T) 1
49 Screen Material Yes/No Yes, Copper Tape Screen
50 Inner Covering Yes/No Yes, PVC
51 Armor Yes/No Yes, Steel Flat Wire Armor
52 - Steel Tape Thickness Approximately IEC 60502-1
53 Outer Protective Sheath PVC
54 - Nominal Thickness Appoximately IEC 60502-1
55 - Minimum Thickness at Any Point IEC 60502-1
56 - Color Red
57 Overall Diameter for Cable mm VTA
58 Standard Length per Reel Cable m VTA
59 Cable Weight Approximate per meter kg VTA
60 Marking & Identification Yes / No Yes, Printed
61 - Manufacturer's Name Required
62 - Year Of Manufacturing Required
63 - Applicable IEC Standard Identification Required
64 - Cable Type, Core Size, Voltage Grade, Number of Cores Required ( every 500 mm)
65 - Purchaser's Type Code Required

NPKII-00-N3-DS-401-W 5 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : As per Electrical Power & Control Cable Schedule
2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : 2.4 kV Medium Voltage Power Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 3. CONSTRUCTION
7 Cable Arrangement Drawing Required
8 Type of Cable Drum Steel / Wood VTA
9 Max Cable Length On Drum m VTA
10 Total Cable Weight On Drum kg VTA
11
12 4. TESTING AND INSPECTION
13 Routine test Yes / No Yes
14 Type Test Certificate Yes / No Yes
15 Vendor's Documentation Review Requirement Yes / No Yes
16
17 REFERENCE
18 1. NPKII-00-N0-GS-401-W Electrical Design Basis
19 2. NPKII-00-N3-IS-401-W Electrical Specification of Cable and Wire
20 3. NPKII-00-N3-CS-401-W Electrical Calculation of Cable Sizing Calculation
21 4. NPKII-00-N0-BE-402-W Electrical Power & Control Cable Schedule
22
23 ABBREVIATION
24 VTA : Vendor To Advise
25 TBA : To Be Available
26 N/A : Not Applicable
27 AML : Approved Manufacturer List 1
28
29 NOTE
30 1. All these data shall be verified during Technical Bid Evaluation and subject to owner approval.
31 2. Cable end shall be sealed with watertight heatsrink seal and shall be firmly fixed to the drum.
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
64
65

NPKII-00-N3-DS-401-W 6 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : As per Electrical Power & Control Cable Schedule
2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : 400V Low Voltage Power Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 1. SITE CONDITION
7 Location of Installation Indoor / Outdoor
8 Temperature
o
9 - Max. Ambient Temperature C 40
o
10 - Min. Ambient Temperature C 19
o
11 - Design Ambient Temperature C 29
12 Humidity
13 - Max. Humidity % 100
14 - Min. Humidity % 54
15 - Average Humidity % 85
16 Atsmosphere Corrosive, Dust and Humid Tropical
17 Altitude mm 5500
18
19 2. GENERAL REQUIREMENT
20 Design Code & Standard IEC Standard
21 Manufacturer As per AML 1
22 (Supreme, Kabelindo, KMI, Sumi Indo Kabel)
23 Type of Cables Cu / PVC / SFWA / PVC
24 NYFGbY
25 Rated Voltage of Cable (Uo/U) kV 0.6 / 1
26 Rating Voltage V 400
27 No. of Phases 3Ph
28 Frequency Hz 50
29 Conductor Material Copper
30 Number of Core and Size Cable Refer to NPKII-00-N0-BE-402-W
31 Electrical Power & Control Cable Schedule
32 Conductor Max. Withstand Temperature for:
o
33 - Continous Rating C VTA 1
o
34 - Overload C VTA 1
o
35 - Short Circuit C VTA 1
36 Rated Current Ampacity
37 - In Air VTA
38 - In Soil VTA
39 Max. DC Conductor Resistance at 20oC Ohm / km VTA
40 Max. DC Conductor Resistance at 90oC Ohm / km VTA
41 Max. Conductor Inductance mH/km VTA
42 Short Circuit kA / 1 sec VTA
43 Special Features N/A
44 Insulating Material PVC
45 - Minimum Thickness at Any Point IEC 60502-1
46 - Nominal Thickness Appoximately IEC 60502-1
47 - Color Identification Red (R), Black(S), Yellow (T), Blue(N) 1
48 Screen Material Yes/No N/A
49 Inner Covering Yes/No Yes, PVC
50 Armor Yes/No Yes, Steel Flat Wire Armor
51 - Steel Tape Thickness Approximately IEC 60502-1
52 Outer Protective Sheath PVC
53 - Nominal Thickness Appoximately IEC 60502-1
54 - Minimum Thickness at Any Point IEC 60502-1
55 - Color Black
56 Overall Diameter for Cable mm VTA
57 Standard Length per Reel Cable m VTA
58 Cable Weight Approximate per meter kg VTA
59 Marking & Identification Yes / No Yes, Printed
60 - Manufacturer's Name Required
61 - Year Of Manufacturing Required
62 - Applicable IEC Standard Identification Required
63 - Cable Type, Core Size, Voltage Grade, Number of Cores Required ( every 500 mm)
64 - Purchaser's Type Code Required
65

NPKII-00-N3-DS-401-W 7 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : As per Electrical Power & Control Cable Schedule
2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : 400 V Low Voltage Power Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 3. CONSTRUCTION
7 Cable Arrangement Drawing Required
8 Type of Cable Drum Steel / Wood VTA
9 Max Cable Length On Drum m VTA
10 Total Cable Weight On Drum kg VTA
11
12 4. TESTING AND INSPECTION
13 Routine test Yes / No Yes
14 Type Test Certificate Yes / No Yes
15 Vendor's Documentation Review Requirement Yes / No Yes
16
17 REFERENCE
18 1. NPKII-00-N0-GS-401-W Electrical Design Basis
19 2. NPKII-00-N3-IS-401-W Electrical Specification of Cable and Wire
20 3. NPKII-00-N3-CS-401-W Electrical Calculation of Cable Sizing Calculation
21 4. NPKII-00-N0-BE-402-W Electrical Power & Control Cable Schedule
22
23 ABBREVIATION
24 VTA : Vendor To Advise
25 TBA : To Be Available
26 N/A : Not Applicable
27 AML : Approved Manufacturer List 1
28
29 NOTE
30 1. All these data shall be verified during Technical Bid Evaluation and subject to owner approval.
31 2. Cable end shall be sealed with watertight heatsrink seal and shall be firmly fixed to the drum.
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
64
65

NPKII-00-N3-DS-401-W 8 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : As per Electrical Power & Control Cable Schedule
2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : Control Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 1. SITE CONDITION
7 Location of Installation Indoor / Outdoor
8 Temperature
o
9 - Max. Ambient Temperature C 40
o
10 - Min. Ambient Temperature C 19
o
11 - Design Ambient Temperature C 29
12 Humidity
13 - Max. Humidity % 100
14 - Min. Humidity % 54
15 - Average Humidity % 85
16 Atsmosphere Corrosive, Dust and Humid Tropical
17 Altitude mm 5500
18
19 2. GENERAL REQUIREMENT
20 Design Code & Standard IEC Standard
21 Manufacturer As per AML 1
22 (Supreme, Kabelindo, KMI, Sumi Indo Kabel)
23 Type of Cables Cu / PVC / SFWA / PVC
24 NYFGbY
25 Rated Voltage of Cable (Uo/U) kV 0.6 / 1
26 Rating Voltage V 110
27 No. of Phases N/A
28 Frequency Hz N/A
29 Conductor Material Copper
30 Number of Core and Size Cable Nos Refer to " NPKII-00-N0-BE-402-W
31 Electrical Power & Control Cable Schedule ")
32 Conductor Max. Withstand Temperature for:
o
33 - Continous Rating C VTA 1
o
34 - Overload C VTA 1
o
35 - Short Circuit C VTA 1
36 Rated Current Ampacity
37 - In Air VTA
38 - In Soil VTA
39 Max. DC Conductor Resistance at 20oC Ohm / km VTA
40 Max. Conductor Inductance mH/km VTA
41 Short Circuit kA / 1 sec VTA
42 Special Features N/A
43 Insulating Material PVC
44 - Minimum Thickness at Any Point IEC 60502-1
45 - Nominal Thickness Appoximately IEC 60502-1
46 - Color Identification Black 1
47 Screen Material Yes/No No
48 Inner Covering Yes/No No
49 Armor Yes/No Yes
50 - Steel Tape Thickness Approximately IEC 60502-1
51 Outer Protective Sheath PVC
52 - Nominal Thickness Appoximately IEC 60502-1
53 - Minimum Thickness at Any Point IEC 60502-1
54 - Color Black
55 Overall Diameter for Cable mm VTA
56 Standard Length per Reel Cable m VTA
57 Cable Weight Approximate per meter kg VTA
58 Marking & Identification Yes / No Yes, Printed
59 - Manufacturer's Name Required
60 - Year Of Manufacturing Required
61 - Applicable IEC Standard Identification Required
62 - Cable Type, Core Size, Voltage Grade, Number of Cores Required ( every 500 mm)
63 - Purchaser's Type Code Required
64
65

NPKII-00-N3-DS-401-W 9 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : As per Electrical Power & Control Cable Schedule
2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : Control Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 3. CONSTRUCTION
7 Cable Arrangement Drawing Required
8 Type of Cable Drum Steel / Wood VTA
9 Max Cable Length On Drum m VTA
10 Total Cable Weight On Drum kg VTA
11
12 4. TESTING AND INSPECTION
13 Routine test Yes / No Yes
14 Type Test Certificate Yes / No Yes
15 Vendor's Documentation Review Requirement Yes / No Yes
16
17 REFERENCE
18 1. NPKII-00-N0-GS-401-W Electrical Design Basis
19 2. NPKII-00-N3-IS-401-W Electrical Specification of Cable and Wire
20 3. NPKII-00-N3-CS-401-W Electrical Calculation of Cable Sizing Calculation
21 4. NPKII-00-N0-BE-402-W Electrical Power & Control Cable Schedule
22
23 ABBREVIATION
24 VTA : Vendor To Advise
25 TBA : To Be Available
26 N/A : Not Applicable
27 AML : Approved Manufacturer List 1
28
29 NOTE
30 1. All these data shall be verified during Technical Bid Evaluation and subject to owner approval.
31 2. Cable end shall be sealed with watertight heatsrink seal and shall be firmly fixed to the drum.
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
64
65

NPKII-00-N3-DS-401-W 10 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : -


2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : Lighting Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 1. SITE CONDITION
7 Location of Installation Indoor / Outdoor
8 Temperature
o
9 - Max. Ambient Temperature C 40
o
10 - Min. Ambient Temperature C 19
o
11 - Design Ambient Temperature C 29
12 Humidity
13 - Max. Humidity % 100
14 - Min. Humidity % 54
15 - Average Humidity % 85
16 Atsmosphere Corrosive, Dust and Humid Tropical
17 Altitude mm 5500
18 2. GENERAL REQUIREMENT
19 Design Code & Standard IEC Standard
20 Manufacturer As per AML
21 (Supreme, Kabelindo, KMI, Sumi Indo Kabel)
22 Type of Cables
23 - Indoor NYY ( Cu/PVC/PVC ) 1
24 - Outdoor NYFGbY ( Cu/PVC/SFWA/PVC ) 1
25 Rated Voltage of Cable (Uo/U) kV 0.6 / 1
26 Rating Voltage V 230 1
27 No. of Phases N/A
28 Frequency Hz N/A
29 Conductor Material Copper
30 Number of Core Nos Refer to Panel Schedule
31 Size of Cable mm2 Indoor min. 2.5mm2 & Outdoor min. 4mm2 1
32 Conductor Max. Withstand Temperature for:
o
33 - Continous Rating C VTA 1
o
34 - Overload C VTA 1
o
35 - Short Circuit C VTA 1
36 Rated Current Ampacity
37 - In Air VTA
38 - In Soil VTA
39 Max. DC Conductor Resistance at 20oC Ohm / km VTA
40 Max. DC Conductor Resistance at 90oC Ohm / km VTA
41 Max. Conductor Inductance mH/km VTA
42 Short Circuit kA / 1 sec VTA
43 Special Features N/A
44 Insulating Material PVC
45 - Minimum Thickness at Any Point IEC 60502-1
46 - Nominal Thickness Appoximately IEC 60502-1
47 - Color Identification Red (Ph-1), Black(Ph-2), Blue (N), 1
48 Green with Yellow Stripes (E)
49 Screen Material Yes/No No
50 Inner Covering Yes/No No
51 Armor Yes/No Indoor (No), Outdoor (Yes) 1
52 - Steel Tape Thickness Approximately IEC 60502-1
53 Outer Protective Sheath PVC
54 - Nominal Thickness Appoximately IEC 60502-1
55 - Minimum Thickness at Any Point IEC 60502-1
56 - Color Black
57 Overall Diameter for Cable mm VTA
58 Standard Length per Reel Cable m VTA
59 Cable Weight Approximate per meter kg VTA
60 Marking & Identification Yes / No Yes, Printed
61 - Manufacturer's Name Required
62 - Year Of Manufacturing Required
63 - Applicable IEC Standard Identification Required
64 - Cable Type, Core Size, Voltage Grade, Number of Cores Required ( every 500 mm)
65 - Purchaser's Type Code Required

NPKII-00-N3-DS-401-W 11 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : -


2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : Lighting Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 3. CONSTRUCTION
7 Cable Arrangement Drawing Required
8 Type of Cable Drum Steel / Wood VTA
9 Max Cable Length On Drum m VTA
10 Total Cable Weight On Drum kg VTA
11
12 4. TESTING AND INSPECTION
13 Routine test Yes / No Yes
14 Type Test Certificate Yes / No Yes
15 Vendor's Documentation Review Requirement Yes / No Yes
16
17 REFERENCE
18 1. NPKII-00-N0-GS-401-W Electrical Design Basis
19 2. NPKII-00-N3-IS-401-W Electrical Specification of Cable and Wire
20 3. NPKII-00-N3-CS-401-W Electrical Calculation of Cable Sizing Calculation
21
22 ABBREVIATION
23 VTA : Vendor To Advise
24 TBA : To Be Available
25 N/A : Not Applicable
26 AML : Approved Manufacturer List 1
27
28 NOTE
29 1. All these data shall be verified during Technical Bid Evaluation and subject to owner approval.
30 2. Cable end shall be sealed with watertight heatsrink seal and shall be firmly fixed to the drum.
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65

NPKII-00-N3-DS-401-W 12 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : -


2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : Earthing Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
6 1. SITE CONDITION
7 Location of Installation Indoor / Outdoor
8 Temperature
o
9 - Max. Ambient Temperature C 40
o
10 - Min. Ambient Temperature C 19
o
11 - Design Ambient Temperature C 29
12 Humidity
13 - Max. Humidity % 100
14 - Min. Humidity % 54
15 - Average Humidity % 85
16 Atsmosphere Corrosive, Dust and Humid Tropical
17 Altitude mm 5500
18
19 2. GENERAL REQUIREMENT
20 2.1 Main Earthing Cable
21 Design Code & Standard IEC Standard
22 Manufacturer As per AML 1
23 (Supreme, Kabelindo, KMI, Sumi Indo Kabel)
24 Type of Cable Stranded Bare Copper
25 Number of Core 1
26 Conductor Material Copper
27 Size of Conductor mm2 70
28 Number of Wire VTA
29 Approx. Overall Diameter Cable mm VTA
30 Outer Protective Sheath N/A
31 DC Resistance at 20oC Max. Ohm/km VTA
32 Standard Length per Reel Cable m VTA
33 Cable Weight Approximate per meter kg/m VTA
34 Marking & Identification Yes / No N/A
35 2.2 Bonding Cable
36 Design Code & Standard IEC Standard
37 Manufacturer VTA
38 Type of Cables
39 - Main Earthing Loop Stranded Bare Copper
40 - Bonding Cable NYA (Cu/PVC)
41 Rated Voltage of Cable (Uo/U) kV 0.45 /0.75
42 Conductor Material Copper
43 Number of Core Nos 1
44 Size of Bonding Cable mm2 1C-16
45 mm2 1C-35
46 mm2 1C-50
47 mm2 1C-95
48 Rated Current Ampacity
49 - In Air VTA
50 - In Soil VTA
51 Max. DC Conductor Resistance at 20oC Ohm / km VTA
52 Max. AC Conductor Resistance at 70oC Ohm / km VTA
53 Max. Conductor Inductance mH/km VTA
54 Short Circuit kA / 1 sec VTA
55 Outer Protective Sheath (Bonding Cable) PVC, Green with Yellow Stripe
56 Overall Diameter for Cable mm VTA
57 Standard Length per Reel Cable m VTA
58 Cable Weight Approximate per meter kg VTA
59 Marking & Identification Yes / No Yes, Printed
60 - Manufacturer's Name Required
61 - Year Of Manufacturing Required
62 - Applicable IEC Standard Identification Required
63 - Cable Type, Core Size, Voltage Grade, Number of Cores Required ( every 500 mm)
64 - Purchaser's Type Code Required
65

NPKII-00-N3-DS-401-W 13 of 14 REV.1
PROYEK PEMBANGUNAN PABRIK NPK FUSION II
KAPASITAS 2 X 100,000 MTPY
PT. PUPUK SRIWIDJAJA PALEMBANG

ELECTRICAL DATASHEET OF CABLE AND WIRE

1 Client : PT. PUPUK SRIWIDJAJA PALEMBANG Tag Number : -


2 Project : PROYEK PEMBANGUNAN PABRIK NPK FUSION II Service : Earthing Cable

Revision
3 KAPASITAS 2 X 100,000 MTPY PT. PUPUK SRIWIDJAJA PALEMBANG
4 Location : PALEMBANG, SOUTH SUMATRA
5 PARTICULAR OF EQUIPMENT UNITS CONTRACTOR'S REQUIREMENT VENDOR'S RESPONSE
64 3. CONSTRUCTION
65 Cable Arrangement Drawing Required
60 Type of Cable Drum Steel / Wood VTA
61 Max Cable Length On Drum m VTA
62 Total Cable Weight On Drum kg VTA
63
17 REFERENCE
18 1. NPKII-00-N0-GS-401-W Electrical Design Basis
19 2. NPKII-00-N3-IS-401-W Electrical Specification of Cable and Wire
20 3. NPKII-00-N5-IS-401-W Electrical Specification of Electrical Earthing, Bonding & Lightning Protection System
4. NPKII-00-N5-DW-406-W Electrical Earthing System
22
23 ABBREVIATION
24 VTA : Vendor To Advise
25 TBA : To Be Available
26 N/A : Not Applicable
27 AML : Approved Manufacturer List
28
29 NOTE
30 1. All these data shall be verified during Technical Bid Evaluation and subject to owner approval.
31 2. Cable end shall be sealed with watertight heatsrink seal and shall be firmly fixed to the drum.
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
64
65

NPKII-00-N3-DS-401-W 14 of 14 REV.1