General method for cable sizing


From Electrical Installation Guide

Contents
1- Possible methods of installation for different types of conductors or cables
2- Possible methods of installation for different situations:
3- Examples of wiring systems and reference methods of installations
4- Maximum operating temperature:
5- Correction factors
5.1- Ambient temperature
5.2- Soil thermal resistivity
5.3- Grouping of conductors or cables
5.4- Harmonic current
6- Admissible current as a function of nominal cross-sectional area of conductors

Possible methods of installation for different types of conductors or cables


The different admissible methods of installation are listed in Figure G8, in conjonction with the different types of conductors and
cables.

Method of installation
Cable
Cable trunking
ladder,
systems (including Cable
Conductors cables Without Clipped Conduit skirting trunking, On Support
ducting Cable tray,
fixings direct systems insulators wire
systems Cable
flush floor trunking)
rackets

Bare conductors - - - - - - + -
Insulated conductors[b] - - + +[a] + - + -
Sheathed cables Multi-
+ + + + + + 0 +
core
(including
armoured and
Single-
mineral insulated) 0 + + + + + 0 +
core

+ : Permitted.
– : Not Permitted.
0 : Not applicable, or not normally used in practice.
[a] Insulated conductors are admitted if the cable trunking systems provide at least he degree of protection IP4X or IPXXD and if the cover can only be removed by means of a
tool or a deliberate action.
[b] Insulated conductors which are used as protective conductors or protective bonding conductors may use any appropriate method of installation and need not be laid in
conduits, trunking or ducting systems.

Fig. G8: Selection of wiring systems (table A.52.1 of IEC 60364-5-52)

Possible methods of installation for different situations:


Different methods of installation can be implemented in different situations. The possible combinations are presented in Figure G9.

The number given in this table refer to the different wiring systems considered.

www.electrical-installation.org/enwiki/General_method_for_cable_sizing#Soil_thermal_resistivity 1/10
7/12/2019 General method for cable sizing - Electrical Installation Guide

Method of installation
Situations Cable trunking (including Cable Cable ladder,
Without Clipped Conduit On Support
skirting trunking, flush ducting cable tray, cable
fixings direct Systems insulators wire
floor trunking) systems brackets
30, 31, 32, 33,
Accessible 40 33 41, 42 6, 7, 8, 9,12 43, 44 - 0
Building 34
voids Not
40 0 41, 42 0 43 0 0 0
accessible
Cable channel 56 56 54, 55 0 30, 31, 32, 34 - -
Buried in ground 72, 73 0 70, 71 - 70, 71 0 - -
Embedded in 1, 2, 59,
57, 58 3 50, 51, 52, 53 46, 45 0 - -
structure 60
20, 21,
Surface mounted - 22, 23, 4, 5 6, 7, 8, 9, 12 6, 7, 8, 9 30, 31, 32, 34 36 -
33
Overhead/free in air - 33 0 10, 11 10, 11 30, 31, 32, 34 36 35
Window frames 16 0 16 0 0 0 - -
Architrave 15 0 15 0 0 0 - -
Immersed 1 + + + - + 0 - -

– : Not permitted.
0 : Not applicable or not normally used in practice.
+ : Follow manufacturer’s instructions.
Note: The number in each box, e.g. 40, 46, refers to the number of the method of installation in Table A.52.3.

Fig. G9: Erection of wiring systems (table A.52.2 of IEC 60364-5-52)

Examples of wiring systems and reference methods of installations


An illustration of some of the many different wiring systems and methods of installation is provided in Figure G10.

Several reference methods are defined (with code letters A to G), grouping installation methods having the same characteristics
relative to the current-carrying capacities of the wiring systems.

www.electrical-installation.org/enwiki/General_method_for_cable_sizing#Soil_thermal_resistivity 2/10
7/12/2019 General method for cable sizing - Electrical Installation Guide

Methods Reference method of installation to be


Item
of Description used to obtain current-carrying
No.
installation capacity
Insulated conductors or single-core cables in conduit in a thermally
1 Room A1
insulated wall
2 Room Multi-core cables in conduit in a thermally insulated wall A2
Insulated conductors or single-core cables in conduit on a wooden,
4 B1
or masonry wall or spaced less than 0,3 x conduit diameter from it
Multi-core cable in conduit on a wooden, or mansonry wall or
5 B2
spaced less than 0,3 x conduit diameter from it
Single-core or multi-core cables: - fixed on, or sapced less than 0.3
20 C
x cable diameter from a wooden wall
Single-core or multi-core cables:
30 C
On unperforated tray run horizontally or vertically

Single-core or multi-core cables:


31 E or F
On perforated tray run horizontally or vertically

36 Bare or insulated conductors on insulators G


70 Multi-core cables in conduit or in cable ducting in the ground D1
71 Single-core cable in conduit or in cable ducting in the ground D1

Fig. G10: Examples of methods of installation (part of table A.52.3 of IEC 60364-5-52)

Maximum operating temperature:


The current-carrying capacities given in the subsequent tables have been determined so that the maximum insulation temperature is
not exceeded for sustained periods of time.

For different type of insulation material, the maximum admissible temperature is given in Figure G11.

Temperature
Type of insulation
limit °C
70 at the
Polyvinyl-chloride (PVC)
conductor
Cross-linked polyethylene (XLPE) and ethylene propylene 90 at the
rubber (EPR) conductor
Mineral (PVC covered or bare exposed to touch) 70 at the sheath
Mineral (bare not exposed to touch and not in contact with
105 at the seath
combustible material)

Fig. G11: Maximum operating temperatures for types of insulation (table 52.1 of IEC 60364-5-52)

Correction factors
In order to take service conditions of the installation into account, correction factors have been introduced.

The cross-sectional area of cables is determined using the current-carrying capacity of the cable IZ, multiplied by correction factors:
I'Z = IZ . k1 . k2 ...

where:

www.electrical-installation.org/enwiki/General_method_for_cable_sizing#Soil_thermal_resistivity 3/10
7/12/2019 General method for cable sizing - Electrical Installation Guide

IZ = current carrying capacity of the cable in the reference installation method


I'Z = "corrected" current carrying capacity of the cable in real installation conditions
k1, k2 ... = corrections factors, detailed in the following paragraphs

The cross sectional area of cables is then chosen in order to ensure that their "corrected" current-carrying capacity I'Z is higher than
the rated load current IB: IB ≤ I'Z

Ambient temperature

The current-carrying capacities of cables in the air are based on an average air temperature equal to 30 °C. For other temperatures,
the correction factor is given in Figure G12 for PVC, EPR and XLPE insulation material.

The related correction factor is here noted k1.

Insulation
Ambient air temperature °C
PVC XLPE and EPR
10 1.22 1.15
15 1.17 1.12
20 1.12 1.08
25 1.06 1.04
30 1 1
35 0.94 0.96
40 0.87 0.91
45 0.79 0.87
50 0.71 0.82
55 0.61 0.76
60 0.50 0.71
65 - 0.65
70 - 0.58
75 - 0.50
80 - 0.41

Fig. G12: Correction factors for ambient air temperatures other than 30 °C to be applied to the current-carrying capacities for cables in the air (from table B.52.14 of IEC
60364-5-52)

The current-carrying capacities of cables in the ground are based on an average ground temperature equal to 20 °C. For other
temperatures, the correction factor is given in Figure G13 for PVC, EPR and XLPE insulation material.

The related correction factor is here noted k2.

www.electrical-installation.org/enwiki/General_method_for_cable_sizing#Soil_thermal_resistivity 4/10
7/12/2019 General method for cable sizing - Electrical Installation Guide

Insulation
Ground temperature °C
PVC XLPE and EPR
10 1.10 1.07
15 1.05 1.04
20 1 1
25 0.95 0.96
30 0.89 0.93
35 0.84 0.89
40 0.77 0.85
45 0.71 0.80
50 0.63 0.76
55 0.55 0.71
60 0.45 0.65
65 - 0.60
70 - 0.53
75 - 0.46
80 - 0.38

Fig. G13: Correction factors for ambient ground temperatures other than 20 °C to be applied to the current-carrying capacities for cables in ducts in the ground (from table
B.52.15 of IEC 60364-5-52)

Soil thermal resistivity

The current-carrying capacities of cables in the ground are based on a ground resistivity equal to 2.5 K•m/W. For other values, the
correction factor is given in Figure G14.

The related correction factor is here noted k3.

Thermal resistivity, K•m/W 0.5 0.7 1 1.5 2 2.5 3


Correction factor for cables in buried ducts 1.28 1.20 1.18 1.1 1.05 1 0.96
Correction factor for direct buried cables 1.88 1.62 1.5 1.28 1.12 1 0.90

Note 1: The correction factors given have been averaged over the range of conductor sizes and types of installation included in Tables B.52.2 to B.52.5. The overall accuracy of
correction factors is within ±5 %.
Note 2: The correction factors are applicable to cables drawn into buried ducts; for cables laid direct in the ground the correction factors for thermal resistivities less than 2.5
K•m/W will be higher. Where more precise values are required they may be calculated by methods given in the IEC 60287 series.
Note 3: The correction factors are applicable to ducts buried at depths of up to 0.8 m.
Note 4: It is assumed that the soil properties are uniform. No allowance had been made for the possibility of moisture migration which can lead to a region of high thermal
resistivity around the cable. If partial drying out of the soil is foreseen, the permissible current rating should be derived by the methods specified in the IEC 60287 series.

Fig. G14: Correction factors for cables in buried ducts for soil thermal resistivities other than 2.5 K.m/W to be applied to the current-carrying capacities for reference method
D (table B.52.16 of IEC 60364-5-52)

Based on experience, a relationship exist between the soil nature and resistivity. Then, empiric values of correction factors k3 are
proposed in Figure G15, depending on the nature of soil.

Nature of soil k3
Very wet soil (saturated) 1.21
Wet soil 1.13
Damp soil 1.05
Dry soil 1.00
Very dry soil (sunbaked) 0.86

www.electrical-installation.org/enwiki/General_method_for_cable_sizing#Soil_thermal_resistivity 5/10
7/12/2019 General method for cable sizing - Electrical Installation Guide
Fig. G15: Correction factor k3 depending on the nature of soil

Grouping of conductors or cables

The current-carrying capacities given in the subsequent tables relate to single circuits consisting of the following numbers of loaded
conductors:

Two insulated conductors or two single-core cables, or one twin-core cable (applicable to single-phase circuits);
Three insulated conductors or three single-core cables, or one three-core cable (applicable to three-phase circuits).

Where more insulated conductors or cables are installed in the same group, a group reduction factor (here noted k4) shall be applied.

Examples are given in Figures G16 to G18 for different configurations (installation methods, in free air or in the ground).

Figure G16 gives the values of correction factor k4 for different configurations of unburied cables or conductors, grouping of more
than one circuit or multi-core cables.

Number of circuits or multi-core cables Reference


Arrangement (cables touching)
1 2 3 4 5 6 7 8 9 12 16 20 methods
Bunched in air, on a surface, Methods
1.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.45 0.41 0.38
embedded orenclosed A to F
Single layer on wall, floor or
1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70
unperforated tray
Method C
Single layer fixed directly under
0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.61 No further reduction factor for
a wooden ceiling
more than nine circuits or multi-
Single layer on a perforated
1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72 core cables
horizontal or vertical tray Methods
Single layer on ladder support or E and F
1.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.78
cleats etc.

Fig. G16: Reduction factors for groups of more than one circuit or of more than one multi-core cable (table B.52.17 of IEC 60364-5-52)

Figure G17 gives the values of correction factor k4 for different configurations of unburied cables or conductors, for groups of more
than one circuit of single-core cables in free air.

www.electrical-installation.org/enwiki/General_method_for_cable_sizing#Soil_thermal_resistivity 6/10
7/12/2019 General method for cable sizing - Electrical Installation Guide

Number of three-phase
Number of circuits Use as a multiplier to rating
Method of installation
tray for
1 2 3
1 0.98 0.91 0.87
Three cables in horizontal
Perforated trays 31 Touching 2 0.96 0.87 0.81
formation
3 0.95 0.85 0.78
1 0.96 0.86 Three cables in vertical
Vertical perforated trays 31 Touching
2 0.95 0.84 formation
32 1 1.00 0.97 0.96
Ladder supports, cleats, etc... Three cables in horizontal
33 Touching 2 0.98 0.93 0.89
formation formation
34 3 0.97 0.90 0.86
1 1.00 0.98 0.96
Perforated trays 31 2 0.97 0.93 0.89
3 0.96 0.92 0.86
1 1.00 0.91 0.89
Vertical perforated trays 31 Spaced Three cables in trefoil formation
2 1.00 0.90 0.86
32 1 1.00 1.00 1.00
Ladder supports, cleats, etc... 33 2 0.97 0.95 0.93
34 3 0.96 0.94 0.90

Fig. G17: Reduction factors for groups of more than one circuit of single-core cables to be applied to reference rating for one circuit of single-core cables in free air - Method of
installation F. (table B.52.21 of IEC 60364-5-52)

Figure G18 gives the values of correction factor k4 for different configurations of cables or conductors laid directly in the ground.

Cable to cable clearance(a)


Number of circuits Nil (cables One cable 0.125 0.25 0.5
touching) diameter m m m
2 0.75 0.80 0.85 0.90 0.90
3 0.65 0.70 0.75 0.80 0.85
4 0.60 0.60 0.70 0.75 0.80
5 0.55 0.55 0.65 0.70 0.80
6 0.50 0.55 0.60 0.70 0.80
7 0.45 0.51 0.59 0.67 0.76
8 0.43 0.48 0.57 0.65 0.75
9 0.41 0.46 0.55 0.63 0.74
12 0.36 0.42 0.51 0.59 0.71
16 0.32 0.38 0.47 0.56 0.38
20 0.29 0.35 0.44 0.53 0.66
(a) for Multi-core
cables
(a) for Single-core
cables

Fig. G18: Reduction factors for more than one circuit, single-core or multi-core cables laid directly in the ground. Installation method D. (table B.52.18 of IEC 60364-5-52)

Harmonic current

The current-carrying capacity of three-phase, 4-core or 5-core cables is based on the assumption that only 3 conductors are fully
loaded.
www.electrical-installation.org/enwiki/General_method_for_cable_sizing#Soil_thermal_resistivity 7/10
7/12/2019 General method for cable sizing - Electrical Installation Guide

However, when harmonic currents are circulating, the neutral current can be significant, and even higher than the phase currents.
This is due to the fact that the 3rd harmonic currents of the three phases do not cancel each other, and sum up in the neutral
conductor.

This of course affects the current-carrying capacity of the cable, and a correction factor noted here k5 shall be applied.

In addition, if the 3rd harmonic percentage h3 is greater than 33%, the neutral current is greater than the phase current and the cable
size selection is based on the neutral current. The heating effect of harmonic currents in the phase conductors has also to be taken
into account.

The values of k5 depending on the 3rd harmonic content are given in Figure G19.

Correction factor
Third harmonic content
of phase current % Size selection is based Size selection is based
on phase current on neutral current
0 - 15 1.0
15 - 33
33 - 45 0.86 0.86
> 45 1.0[a]

[a] If the neutral current is more than 135 % of the phase current and the cable size is selected on the basis of the neutral current then the three phase conductors will not be fully
loaded. The reduction in heat generated by the phase conductors offsets the heat generated by the neutral conductor to the extent that it is not necessary to apply any reduction
factor to the current carrying capacity for three loaded conductors.

Fig. G19: Correction factors for harmonic currents in four-core and five-core cables (table E.52.1 of IEC 60364-5-52)

Admissible current as a function of nominal cross-sectional area of conductors


IEC standard 60364-5-52 proposes extensive information in the form of tables giving the admissible currents as a function of cross-
sectional area of cables. Many parameters are taken into account, such as the method of installation, type of insulation material, type
of conductor material, number of loaded conductors.

As an example, Figure G20 gives the current-carrying capacities for different methods of installation of PVC insulation, three
loaded copper or almunium conductors, free air or in ground.

www.electrical-installation.org/enwiki/General_method_for_cable_sizing#Soil_thermal_resistivity 8/10
7/12/2019 General method for cable sizing - Electrical Installation Guide

Installation methods of Table B.52.1


Nominal cross-sectional area of conductors(mm2)
A1 A2 B1 B2 C D1 D2

1 2 3 4 5 6 7 8
Copper
1.5 13.5 13 15.5 15 17.5 18 19
2.5 18 17.5 21 20 24 24 24
4 24 23 28 27 32 30 33
6 31 29 36 34 41 38 41
10 42 39 50 46 57 50 54
16 56 52 68 62 76 64 70
25 73 68 89 80 96 82 92
35 89 83 110 99 119 98 110
50 108 99 134 118 144 116 130
70 136 125 171 149 184 143 162
95 164 150 207 179 223 169 193
120 188 172 239 206 259 192 220
150 216 196 262 225 299 217 246
185 245 223 296 255 341 243 278
240 286 261 346 297 403 280 320
300 328 298 394 339 464 316 359
Aluminium
2.5 14 13.5 16.5 15.5 18.5 18.5
4 18.5 17.5 22 21 25 24
6 24 23 28 27 32 30
10 32 31 39 36 44 39
16 43 41 53 48 59 50 53
25 57 53 70 62 73 64 69
35 70 65 86 77 90 77 83
50 84 78 104 92 110 91 99
70 107 98 133 116 140 112 122
95 129 118 161 139 170 132 148
120 149 135 186 160 197 150 169
150 170 155 204 176 227 169 189
185 194 176 230 199 259 190 214
240 227 207 269 232 305 218 250
300 261 237 306 265 351 247 282

Note: In columns 3, 5, 6, 7 and 8, circular conductors are assumed for sizes up to and including 16 mm2. Values for larger sizes relate to shaped conductors and may safely be
applied to circular conductors.

Fig. G20: Current-carrying capacities in amperes for different methods of installation, PVC insulation, three loaded conductors, copper or aluminium, conductor temperature:
70 °C, ambient temperature: 30 °C in air, 20 °C in ground (table B.52.4 of IEC 60364-5-52)

Retrieved from "http://www.electrical-installation.org/enw/index.php?title=General_method_for_cable_sizing&oldid=24180"


Category: Chapter - Sizing and protection of conductors

This page was last modified on 2 November 2018, at 21:21.